HomeMy WebLinkAbout3172 LIONSHEAD AVE; 100; FPC2018-0289; PermitPERMIT REPORT
tCity of
Carlsbad
Print Date: 02/17/2022 Permit No: FPC2018-0289
Job Address: 3172 LIONSHEAD AVE, # 100, CARLSBAD, CA 92010-4707 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: Track #: Applied: 08/30/2018
Valuation: $0.00 Lot #: Issued: 09/13/2018
Occupancy Group: Project #: Finaled Close Out: 02/01/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: TACO TRUCK TI -SPRINKLER (21 HEADS)
Applicant: FPContractor:
EPIC FIRE PROTECTION INC EPIC FIRE PROTECTION INC
ADAM BOISVERT 765 TURTLE POINT WAY
765 TURTLE POINT WAY ' SAN MARCOS, CA 92069-8126
SAN MARCOS, CA 92069-8126 (760) 310-6122
(760) 310-6122
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
Fft2ot _07
hIATERIAL DATA SUBI**--1177AL
TACO TRUCK Ti.
CARLSBAD, CA
EPIC FIRE PROTECTION, INC.
75 TURTLE POINT WAY
SAN N1ARCOS, CA 9209
(7roO)310-0122 FAX(7O)78-055
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT• PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosertsitive element This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable standards.
It offers the additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick QUICK RESPONSE
Response Sprinklers should be used advisedly and under the UPRIGHT CONVENTIONAL
direction of approving authorities having jurisdiction.
The heart of Globes GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used. QUICK ESPONSE
TECHNICAL DATA PENDENT VERTICAL
See reverse side for Approvals and Specifications.
-Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C) MOM
-Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
Frame - bronze • Deflector - brass • Screw - brass HORIZONTAL LPC!CE
Lodgement wire - stainless steel • SIDEWALL HORIZONTAL
SIDEWALL Bulb seat - copper • Spring - nickel alloy • Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
SPRINKLER TEMPERATURE RATiNG/CLASSIFICATiON and COLOR CODING
I AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION TEMPERATURES BU LB COLOR CEILING TEMPERATURE
ORDINARY 135°F155°F STC/69°C ORANGE/RED 100°F ' 32°C
INTERMEDIATE 175 F1200 F 79 C/93 C YELLOW/GREEN '150!F 661C
HIGH 28rF 141'C BLUE 225°F 107 C
4077AIRPARKDRWE, STANDISH, MICHIGAN 48658 989544583 • FAX989-846-9231
JULY 2012 A-20 BULLETIN GL5615, REV. #9
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT. PENDENT. VERTICAL SIDEWALL
HORIZONTAL SIDEWALL. CONVENTIONAL (OLD STYLE)
SPECIFICATiONS
NOMINAL K" FACTOR THREAD SLM LENGTH' FINISHES
2.8 (39 metric) 112" NPT 2 1/4" (5.7cm)
4.2 (59 metric) 1/2' NPT 2 1/4" (5.7cm) Factory Bronze
5.6 (80 metric) 112" NPT 2 1/4' (5.7cm)
chrome
IM,Ite Polyester 7.8 (111 metric) 1/2" NPT 2 1/4" (5.7cm)
8.1 (118 metric) 314" NPT 2 7/16" (6.2cm) Black Polyester"
METRIC C0WER510N5 ARE APPRONMATE.
'HOREONTAI, SIDEWALL IS 2 9116'.
'FINISHES AVAILABLE ON SPECIAL ORDER.
AVAILABLE AS sUL,w LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE SIN K HAMD, 135-F IS6'F 175-F 207F 28EF we C . re -C
VYC-DOB
MODEL FACTOR src MEC 79C 'C I4?C MEA 10182.8
G12815 26 LII X X X X X S - - - S
GL8215 4.2 UI X S X X S S - - - S
UPRIGHT 015615 EN Ll-VOH S S S X S S X S X S
018115 7.6' LWOH S X S X S S - - - S
018116 6,1 LWOH S S X X S S S X X S
GLI 28 UI X X S X X S - - - X
0L4331 4.2 LII X X S X S X - - - S
PENDENT GLSIRI 5.8 LWOH S X S X S X X S S S
GL810I 7.6' LWOH S X X S S X S - - S
01.8156 8.1 LIUIOH S S S 5 5 X X S X X
VERTICAL. G1 8.6 LII X S - - -
SISEWALLT 018133 El UI X - - - -
G128561 2.8 LII 5 S - - - 5
HORIZONTAL GL4DOt 42 UI X S S - - - X
SIDEWALL GL56WI 5.6 LWOH 5 5
MXX
X X - - S
01.56278 5.6 LWOH - -' X S -
0181271 8.1 LIYOH S - - - -
001411EN110114L GL5624 5.6 LIIIOH .- - S S -
(OLD STYLE) GLSI33 El LIttON
ISPRINKLERS SHALL BE LASTED AS PER THE REQUIREMENTS OF NFPAI3 AND ANY OTHER RELATED DOCUMENTS, -
§IIORIZONTAL SIDEWALL 551119 LISTED FOR DEFLECTOR 6' TO 12' BELOW THE CEILING, FM APPROVED 6' TO N' BELOW THE CEILING.
INSTALL IN ACCORDANCE TO 8S5306 AND ANY OTHER RELATED DOCUMENTS.
'PENDENT VERTICAL SIDEWALL CULL. LISTED FORE MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL oUL,. LISTED FOR N' MIN. SPACING.
OH ORDINARY HAZARD
Lft LIGHT HAZARD
117 NPT
GLOBES PRODUCT WARRANTY
Globe agrees to repair or replace any of its ore, manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
GLAINUP E
FIRE SPRINKLER CORPORATION
JUNE2012
CIA; BE
FIRE SPRINKLER CORPORATION
ORDERING INFORMATION SPECIFY Quantity Model Number Style
-Orifice • Thread Sizes • Temperature
Finishes desired
-Quantity - Wrenches - P/N 325350 (1/2°);
P/N 312366 (L.O.)
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248.0278 www.globesprinkler.com
PRINTED U.S.A. BULLETIN GL5615, REV. #9
Components: "Temperature rating is 00 Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Seallog Screw ESCUTCHEON PLATE 1/2' 7/16' 111,1 nnml RECESSED
Assembly 6 - Deflector" DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
I
7/16' (11,1 mm)
I NOMINAL E MAKE-IN iso
I
2
150.8 rnml I (34,9 antI WRENC FLATS
1 N 0 DEFLECTOR 2-7/8' 3,O mml Dl
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE I
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
The TYCO Series TY-FRB, 5.6 K-factor, tighten the sprinkler Into the sprinkler
WRENCH NCH RECESS Upright (TY313) and Pendent (TY323) fittIng.
USE ONLY Sprinklers must be Installed in accor- Step 3, Tighten the sprinkler Into the
END 'A) dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench (Figure 2). With ref-
FIGURE 2 Do not Install any bulb-type sprinkler erenco to Figure 1, apply the W-Type 6
W6 -TYPE It the bulb Is cracked or there Is a loss Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH of liquid from the bulb. With the sprin- Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
Mar held horizontally, a small air bubble 19,0 Nm).
TFPI72
Page 2of4
General FIMM
Description The TYCO Series TYIcRB Sprinklers
described herein must be installed and maintained in compliance with
The TYCO Series TY-FRB, 5.6 K-factor, this document, as well as with the
Upright (TY313) and Pendent (TY323) applicable standards of the National
Sprinklers described in this data sheet Fire Protection Association, in addition
are quick response, standard coverage, to the standards of any other autho.'i-
decorative 3 m glass bulb-type spray ties having jurisdiction. Failure to do so
sprinklers designed for use in light or may impair the performance of these
ordinary hazard, commercial occupan- devices. cies such as banks, hotels, and shop- The owner is responsible for main- ping malls. taming their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrec-
applicable, is intended for use In areas for or product manufacturer with any
with a finished ceiling. This recessed questions.
pendant sprinkler uses one of the
following: Sprinkler A two-piece Style 15 Recessed Identification Escutcheon with recessed adjust- ment up to 5/8 Inch (15,9 mm) from
the flush pendant position. Number (SIN)
A two-piece Style 20 Recessed Upright 5.6K, 1/2-NPT Escutcheon with recessed adjust- .........Pendent 5.6K, 1/2-NPT ment up to 1/2 inch (12,7 mm) from
the flush pendent position. Technical The adjustment provided by the Data Recessed Escutcheon reduces the
azrzrrz'am, to which the fixed aloe drops
WRENCH
RECESS
6
t
PUSH WRENCH
INTO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
to the sprinklers must be cut.
Intermediate level versions of Series TY-FRB Sprinklers are described In
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
In Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions
with respect to handling and instal-
lation of sprinklersystems and com-ponents. Improper handling and Installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate ma fire situation or cause It to operate prematurely.
Page 1 of 4
Approvals Refer to Table A
Maximum Working Pressure
175 psi 112.1 ban 250 psi 117.2 bar)'
- The maximum working praxaum cf 26 psI 17.2 bar) only applies to the hating by Under_ Labanato. rite, Inc.(UL).
Discharge Coefficient
K=5.6 OPM/pai5 (80.6 LPM/bar5i
Temperature Rating Refer to Table A
Finishee Sprinkler: Refer to Table B
Recessed escutcheon: White Coated,
Black Coated, Chrome Rated, or Brass Plated
Physical Characteristics Frame .............................Bronze Button. .......................0cc/Copper
5esSsg Assembly ... Stainless Steal w/TEFLON
Bulb .. .............. ... ... .. ..... ..Glass Compression Screw ................. aronzo Deflector .........................Bronze
FEBRUARY 2018
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the
fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Uptight (TY313) and Pendant (TY323)
Sprinklers are Intended for fire protec-
tion systems designed In accordance with the standard installation rules recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval Is based on the requirements of FM's Loss Prevention Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is tube used
for recessed pendent Installations.
TFPI72
should be present. The diameter of the air bubble Is approximately 1/16 Inch (1,6 mm) for the 135°F (57°C) and 3/32
Inch (2,4 mm) for the 286°F (141°C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 t 14 ft.-Ibs, (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or Impairment
of the sprinkler.
Do not attempt to compensate for Insufficient adjustment In the Escutch-eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendant Sprinklers must be Installed In accordance with the following
Instructions.
Step 1. Install Pendant sprinklers in the pendent position. Install upright sprin-klers In the upright position.
Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor-dance with the following Instructions.
Step A. After installing the Style 15 or Style 20 Mounting Plate over the sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler Into the sprinkler fitting.
Step B. Tighten the sprinkler Into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft-lbs. (9,5 to 19,0
Nm).
Step C. After ceiling Installation and finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until Its flange comes In contact with the ceiling.
ti,ca Worldwide www.tyco-fire.com Contacts
Series TY.FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313( and Pendant (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that It controls, obtain permission to shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation In afire situation.
The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced If they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing It with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa-tion Section.)
The owner Is responsible for the
inspection, testing, and maintenance of their fire protection system and devices In compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-ommended to be Inspected, tested,
and maintained by a qualified inspec-
tion Service in accordance with local
requirements and/or national codes.
111 Limited
Warranty
For warranty terms and conditions, visit www.tyco-flre.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, Indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB Upright or Pendent (specify) Sprinkler, SIN
(specify), K,a5.6, Quick Response.
(specify) temperature rating, (specify) finish, P/N (specify, refer to Table A).
Recessed Escutcheon Specify: Style 15 Recessed Escutch- eon with (specify") finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-eon with (specify") finish, P/N (specify")
"Refer to Technical Data Sheet TFP770
Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001
2-7/8" 015.
mwi
2-1/4' DIA 2 mm) FACE OF SPRINKLER
FITTING 5/8'(15,9 mm)
FLUSH
3/8±5/
(9,5.7,9 mm) 7
\ MOUNTING (3,2 mar) SURFACE
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4'(19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON
2-7/8" DIP..
(73,0 mm)
FACE OF SPRINKLER 2-1/4" DIP..
FITTING (572 mm(
5/16u1/4" 1/2" (12,7 mm) )7.9e,4 mm) FLUSH
/8" MOUNTING///
7
1!
(3,2 mm) SURFACE
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm(
Vt'.FRB PLATE 7/8" (22,2 mm)
FIGURES
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72 TFPI72
Page 3 of 4 Page 4 of 4
SPRINKLER FINISH (5cc Note 7)
TYPE TEMPERATURE BULB LIQUID NATURAL CHROME
COLOR POLYESTER- FACTOR
135"P (57°C) Orange
UPRIGHT 155°F (88°C) Red
175°F (795C) Yellow and 1,2,3,4,5, e
- PENDENT (TY323) 200 F (93-C) Green
285°F (1415C) Blue 1/2'°NPT _______________ 135(57°C) Orange RECESSED 155 P168 C) Red PENDENT
175F)79"Ci Yellow (TY323) Fogures 4 and 5b
200F (93C) Green
N hand I. Usred by Underwriters Laboratettes. Inc.. lULl as Quick Response Spyrkiere.
Listed by Underwriters Laboratories, inc.. for use in Canada (0-SIlas Quick Response Sprinklers. Appnavod by Fetruiy Mutual ResearchCurporailon (FM) as Quick Response Sprinklers.
'PP rocedbyttreCliyotNeoc York ardsrMEU3S4-Oi-C. ydbflppr000d Fa, derails, ccntact TYCO Fire Proieciive Products, Enschede, Netherlands, 1.1.31.53.426-4444/Fax 31-54-420-33774
S. approved by the Loss Pmssaniion Csrtlllcesur 000W 110CR P57.50. oaualnol as Quick R.epoose Sprb,klsr5. 7. Where Pobestar Costed 0prtnklen. are nored Sc SOUL and C-al USied. crc apnirkions are UL and C-UL Listed as Conoeion-yeeisrant SprInklers.
a. installed with Style IS )t/2• NPfl 5/6 Total Adjustment Recessed Escutcheon, so applicable.
S. Installed ,ilfl Otyto 200/2" NPTi 1/2" 70151 Udlu.ttnent Recessed bscutohson, as applicable.
c, Fremeavnd 00000ton only. Ustings and sppr000i. apply locator (Special Order(.
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Ne 77 - X(X -
1 IN SPRINKLER
I S FINISH
370 5.6K UPRIGHT (1/2" NPr) TY313
371 5.6K PENDENT (1/2 NPT) TY323
Nets.: Us.. "i" 10, ISO 7-1 c000lsdilOn: Ian .u.,nlpie, 77-370-4-175-I
TEMPERATURE RATINGS
135°F (57°C)
155°F )e8°C)
175F )79C)
200°F (93°C)
286F (141°C)
1 NATURAL BRASS
- PURE WHITE (RAL9010)° POLYESTER
- SIGNAL WHITE (RAL9003) POLYESTER
JET BLACK (RAL8005) POLYESTER
9 CHROME PLATED
a. Eesram Hsmlophore seals only
TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
- -- - PART NUMBER SELECTION
eaRn P.5054005 Parkway. Lassdale. PA 194,4411 lst.aheos o1-20staU-O7O0
00 Johnson
Scw00eeaarwoeasa,*w4reeenaxt5aOec Controls
TFPI8I
Page 2 of 6
Technical
Data
Sprinkler Approvals Approvals apply only to the service conditions indicated in the Design Cri-
teria section.
TY3531 (3-mm Bulb) is IlL Listed,
C-UL Listed, LPCB Approved (Ref. No. 094a/10), VdS Approved (Cer-
tificate No. S 4090007), and NYC
Approved (MEA 353-01-E) as Quick Response.
TY3531 (3-mm Bulb) is FM Ap-proved as Standard Response.
Factory Mutual does not approve any concealed sprinklers for quick
response.
TY3551 (5-mm Bulb) is UL Listed.
C-UL Listed, FM Approved, 12GB Approved (Ref. No. 094a/9), and
NYC Approved (MEA 353-01-B) as
Standard Response.
Approvals for Air and Dust Seal
UL and C-UL Listed for use with the
RFll Standard Response Concealed
Sprinkler (TY3551).
Maximum Working Pressure
Maximum 250 psi (17.3 bar) by UL,
C-IlL and NYC
Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB
Temperature Rating
155"F/68"C Sprinkler with
139"F/59"C Plate
200"F/93"C Sprinkler with
165"F/74"C Rate
Discharge Coefficient
K= 5.6 GPM/psi"2 (80,6 LPM/bar"2)
Adjustment
1/2 inch (12,7 mm)
Finishes
Seethe Ordering Procedure section.
Physical Characteristics
Frame ...................Bronze
Support Cup... Chrome Plated Steel Guide Pins .........Stainless Steel
Deflector.................Bronze
Compression Screw.........Brass
Bulb ......................Glass
Cap.............Bronze or Copper
Sealing Assembly.........Beryllium
Nickel wl Teflon'
Cover Plate................Brass
Retainer ..................Brass Ejection Spring......Stainless Steel
rDuponl Registered Trademark
Design
Criteria
The Tyco5 Series RFil Concealed Pen-dent Sprinklers are intended for fire protection systems designed in ac-cordance with the standard instal-
lation rules recognized by the appli-cable Listing or Approval agency; for
example, IlL Listing is based on NFPA
13 and VdS Approval is based on the
CEA 4001.
For more information on LPCB and
VdS Approvals, contact Tyco Fire Sup-
pression & Building Products at the
following office:
Enschede, Netherlands Telephone: 31-53-428-4444
Fax: 31-53-428-3377
The Series RFil Concealed Pendent
Sprinklers are only listed and approved with the Series RFll Concealed Cover
Plates having a factory applied finish.
1/2' NPT
ASSEMBLY
FRAME CAP
SUPPORT WITH BULB ROLL FORMED THREADS
coMPREssrce SCREW GUIDE PINS (2)
I DEFLECTOR (DROPPED DEFLECTOR iLJLj-
posmote
sPRINKLZRFsupVORT cup ASSEMBLY
THREAD INTO II RETAiNER SUPPORT CUP ii WITHTHREAO UN11LMOUNT1NG 'h DIMPLES SURFACES FLUSH WITH H EJECTION cEluNc 1 SPRING
SOWER TABS 131 COVER PLATE/RETAINER PLATE ASSEMBLY
FIGURE 1
MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
Do not use the Series RH! in applica-
tions where the air pressure above the
ceiling is greater than that below Down
drafts through the Sprinkler/Support Cup Assembly can delay sprinkler op-
eration in a fire situation.
Fire Suppression I
& Building Products I
I Technical Seices: TeL (800) 381-9312/ Fax (800) 791-5500
Entail: techserc@tycofp.com
I
Series AFil - 5.6 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Description Protective Cap Cap is temporarily removed
installation and replaced to help
The TycowSeries RFII Quick Response protect the sprinkler during ceiling in-
(3-mm bulb) and Standard Response statation or finish. The tip of the Pro-
(5-mm bulb), 5.6 K-Factor, "Royal tective Cap can be used to mark the
Flush It" Concealed Pendent Sprin- center of the ceiling hole into plaster
kters are decorative sprinklers featur- board or ceiling tiles by gently push-
ing a flat cover plate designed to con- ung the ceiling product against the Pro-
ceal the sprinkler. These sprinklers are tective Cap. When ceiling installation
optimal for architecturally sensitive ar- is complete, Protective
eas such as hotel lobbies, office build- ings, churches, and restaurants.
an a ''' ner Assembly is installed. Sprinkler Each sprinkler includes a Cover Plate/
Retainer Assembly and a Sprinkler/
As an option, the Series RFll Standard
Response (5-mm bulb) "Royal Hush 11" Identification Support Cup Assembly. The sepera- ble, two-piece assembly design pro-
Concealed Pendent Sprinklers can be fitted with a silicone Air and Dust Seal. Number (SIN) vides the following benefits: (Refer to Figure 5.) The Air and Dust Seal is intended for sensitive areas TY3531 - 3 mm bulb Allows installation of the sprinklers where it is desirable to prevent air and TY3551 - 5 mm bulb and pressure testing of the fire pro- dust from the area above the ceiling to faction system prior to Installation pass through the cover plate. of a suspended ceiling or applica- tion of the finish coating to a fixed ________ ceiling. The Series RH! Concealed Pendant Permits the removal of suspended Sprinklers described herein must be ceiling panels for access to building installed and maintained in compliance service equipment without having with this document and with the app/i- to first shut down the fire protection cable standards of the National Fire system and remove sprinklers. Protection Association, in addition to
Provides for 1/2 inch (12.7 mm) of the standards of any authorities having
vertical adjustment to allow a men- jurisdiction. Failure to do so may impair
sure of flexibility in determining the the performance of these devices.
length of fixed piping to cut for the The owner is responsible for maintain- sprinkler drops. ing their fire protection system and de-
vices in proper operating condition. The installing contractor or sprinkler
manufacturer should be contacted
IMPORTANT with any questions.
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
Won of sprinkler systems and com-ponents. Improper handling and in-
stallation can permanently damage a sprinkler system or its components and cause the Sprinkler to fail to
operate in a fire situation or cause it
to Operate ptnmalu,efy.
Page 1 of 6 OCTOBER 2009 TFP181
FACE OF CLEARANCE HOLE SPRINKLER DIAMETER FITTING L OMENS ION C
SPRINKLER
SUPPORT CUP
ASSEMBLY
112 (12.7 —)
THREAOED
U ADJUSTMENT
FACE OF CEILING,
RETAINING RING MOUNTING
SURFACE 77
W,16'to 11116' MANUFACTURER DEFLECTOR COVER PLATE (4.610 IN DROPPED RETAINER POSITION ASSEMBLY I REFERENCE 3/32 (2,4 mm)
COVER PLATE L COVER PLATE PROFILE DEPTH DIAMETER
DIMENSION 8 DIMENSION A
A 3414 inches (82,6 mm) C: 2-3/8 to 2-5/8 Inches (60.3 to 66,7 mm)
B: 3/16 inches (4.8 mm) 0:1-3/4 to 2.114 inches (44,51a57,2 mm)
FIGURE 2
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS
TFPI8I TFPIBI
Page 3 of 6 Page 4 of 6
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector—supported by the
Guide Pins—then drops down to its
operational position.
The glass Bulb contains a fluid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Installation
The Tyco0 Series RFii must be in-
stalled in accordance with the follow-
ing instructions.
Em
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-ble should be present. The diameter
of the air bubble is approximately 1/16 inch (1.6 mm) for the 155"F/68"C and 3/32 inch (2,4 mm) for the 200"F/931C temperature ratfIngs.
Obtain a 1/2 inch NPT sprinkler joint
by applying a minimum to maximum
torque of 7 to 14 ft.-lbs. (9,5 to 19.0
Nm). Higher levels of torque can dis-
tort the sprinkler Inlet with consequent leakage orimpairrnent of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
by under- or over-tightening the Sprin-
kler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to
suit.
Step 1. Install the sprinkler only in the pendant position with the center-line
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench-tighten the sprinkler using only the RFii Sprinkler Wrench.
(Refer to Figure 3.) Apply the RFil
Sprinkler Wrench to the Sprinkler as
shown in Figure 3.
Step S. Replace the Protective Cap
by pushing it upwards until it bottoms out against the Support Cup. (Refer
to Figure 4.) The Protective Cap helps
prevent damage to the Deflector and
Arms during ceiling installation and/or
finish. You can also use the Protective
Cap to locate the center of the clear-
ance hole by gently pushing the ceiling material up against the center point of
the Protective Cap.
As long as the Protective Cap remains in place, the system Is considered
"Out of Service".
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63.5 mm) diameter clearance hole and in prepa-
ration for installing the Cover Plate/Re-
tainer Assembly, remove and discard
the Protective Cap. Verify that the De-
flector moves up and down freely.
If the Sprinkler is damaged and the
Deflector does not move up and down
freely, replace the entire Sprinkler.
Do not attempt to modify or repair a
damaged sprinkler.
Step 7. When installing an Air and Dust
Seal, refer to Figure 5; otherwise, pro-
ceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and Dust
Seal is engaged.
Step 8. Screw on the Cover Plate/
Retainer Assembly until the Retainer
(shown In Figure 2) or the Air and Dust
Seal (shown in Figure 5) contacts the ceiling. Do not continue to screw on
the Cover Plate/Retainer Assembly
so that it lifts a ceiling panel out of Its normal position. It you cannot engage
the Cover Plate/Retainer Assembly with the Support Cup or you cannot
engage the Cover Plate/Retainer As-
sembly sufficiently to contact the ceil-
ing, you must reposition the Sprinkler Fitting,
Care and
Maintenance
The Tyco8 Series RFII must be
maintained and serviced in accordance
with the following instructions.
Before closing a fire protection sys-tem main control valve for maintenance
work on the fire Protection system that it controls, obtain permission to shut down the affected fire protection sys-
tem from the proper authorities and no-
lily, all personnel who may be affected by this action.
Absence of the Cover Plate/Retainer Assembly can delay sprinkler opera-
tion In a fire situation.
When properly installed, there is a
nominal 3/32 inch (2.4 mm) air gap be-
tween the lip of the Cover Plate and the
ceiling, as shown in Figure 2.
This air gap Is necessary for proper
operation of the sprinkler. It the ceil-
ing requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap
Do not pull the Cover Plate relative to the Enclosure. Separation may result.
Replace sprinklers that:
are leaking or exhibiting visible signs
of corrosion.
were modified or over-heated.
Never paint, plate, coat, or otherwise
alter automatic sprinklers after they leave the factory. Never repaint facto-
ry-painted Cover Plates. If necessary, replace them with factory-painted units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of afire.
Exercise care to avoid damage to
sprinklers before, during, and after in-
stallation. Replace sprinklers damaged
by dropping, striking, wrench twisting,
wrench slipping, or the like. Also. re-
place any sprinkler that has a cracked bulb or that has lost liquid from its
bulb. (Refer to the Installation section.)
If you must remove a sprinkler, do not reinstall it or a replacement Without re- -
instating the Cover Plate/Retainer As-
sembly. It a Cover Rate/Retainer As-
sembly becomes dislodged during service, replace it immediately.
Responsibility lies with sprinkler own-
ers for the inspection, testing, and
maintenance of their fire protection
system and devices in compliance with
this document, as well as with the ap-
plicable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any other authorities having jurisdic-
tion. Contact the installing contractor
or sprinkler manufacturer regarding
any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a qualified Inspection Service in accor-
dance with local requirements and/or
national code.
SUPPORT FA
CE -,
CUP CEIUNG -FNENT SEAL -'EVEL AS
co SHOWN .~~VEIIFI
ASSEMBLY
CLEAN R. SEAL
RETAINER PLATE
FIGURES
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551)
TFP181 TFP181
Page 5 of 6 Page 6 of 6
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against defects in material and workmanship
when paid for -and properly installed
and maintained under normal use and service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-sion, or which have not been installed,
maintained, modified or repaired In ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation In connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system design errors or inaccurate or incom-
plete information supplied by Buyer or Buyer's representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount equal to the sales price.
The foreaoina warranty is made in live
of any and all other warranties, ex-press or implied. includino warranties
of merclsantabilitv and fitness for a particular ouroose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-tent permitted by law. The Invalidity,
in whale or part, of any portion of this
warranty Will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: (SIN), (temperature rating
from below) Series tEll Concealed
Pendent Sprinkler, P/N (specify).
155'F/65'c 200F193'C TY2531 51-792.1.155 51.792-1.200
TY3551 51-790-1-155 51.790-1.200
Separately Ordered Cover Plate!
Retainer Assembly:
Specify (temperature rating from be-
low) Series RFll Concealed Cover Plate
with (finish), P/N (specify).
939-FI59'clal 166'F,74c1b1 Brass. ......... 56.792.1.135 56-792.1-165
Ch re, ron .......56.792.9.135 56-792.9.165
Signal White IRAL 903l 56-792.4.135 56-792-4.165
Grey White RAt, 9002) 56-792-0-135 5792.0.165
Pore white (n) (PAL 9010).. 56.792.3-135 56-792.3.165
Cuotonr ........56-792.3-135 56-792-5-165
(a) For use with 155'F/68'C sprin1de.
frI For use with 200'F193'C sprinklers.
101 Eastern Hemisphere 0605 only.
Sprinkler Wrench
Specify: REll Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 58-908-1-001.
02008 - 2009TYCO ARE SUPPRESSION & eull.olNG PRODUCTS, 451 North Cannon Avenue, Lartodalo, Pennsylvania 19446
As the Leading supplier of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You
need products of enduring quality and exceptional strength—pLus reliable service. VOL need Bull Moose.
Bull Moose Fire Sprinkler Pipe Product Information
T' 1-1 4"
CM
NM~ifiafoip-e'siii(inc~eO
IIIffii
1• IIIUD ________
CM tL 1111 WYAL
water
I- •1iIJ1I1i
= ory M-1
________________ w
Weight Lift
___
EDDYTHREAD 40 ADVANTAGES:
UL listed (US& Canada) and FM approved
ASTM A135 and A795 Type E, Grade .A Certified
Complies with NFPA-13, 13R and 14
industry-leading hydraulic characteristics
CRR of 1.0 and greater
All pipe NDT weld tested
OTHER BENEFITS/SERVICES:
We have the most stocking locations in the industry,
for best delivery and availability
Plain end or roll groove
Eddy Guard II' bacterial-resistant internal coating
Custom length options
Hot dipped galvanization
Reddi-Pipe® red or black pipe eliminates field painting
Compatible for use in wet, dry, preaction and deluge
sprinkler systems
The only maker with EPDs (to help earn LEED points).
c®us LISTED 4 ONFSA
NI [HI. 'S LU rlrr'M
r
Fig. 200 - "Trimline" Adjustable Band Hanger
Size Range - 1/2" thru 8" pipe
Material - Carbon Steel, Mil. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/2' thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily A
installed around pipe.
(2'/i" thru 8" Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed (1/2"
thru 8") in the USA (UL) and Canada (cUL) for steel l.'7tHR? NCH PiPF
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8"). Conforms to Federal
Specifications WW-H-1 71 E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature - 650F
Finish - Mil, Galvanized For Stainless Steel materi-
als, order TOLCOTM Fig. 200WON.
Order By - Figure number and pipe size
2 ;2 iHRJ 8 iNCH Pipz
Dimensions 'Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. Length
1/2 3/8 8mm or 10mm 31/ 2 /8 400 11
3/4 3/8 8mm or 10mm 31/8 21/2 400 11
3/8 8mm or 10mm 33/s 21/8 400 12
7177 3/8 8mm or 10mm 33/4 21/a 400 13
11/2 3/8 8mm or 10mm 3 /8 2% 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21/2 3/8 10mm 55/s 41/ 600 27
3 3/8 10mm 57/8 4 600 29
31/2 3/8 10mm 7 /8 51/4 600 34
4 3/8 10mm 73/s 5 1000 35
5 1/2 12mm 91/3 61/4 1250 66
6 1/2 12mm 10/8 6/4 1250 73
8 1/2 12mm 13'/ 8I4 1250 136
Main Office/Manufacturing Facility 13/i S3Ip;I1 Na, • (I1ij3 Oil 929/0 • P11 909 /3/ /I99 Fax 909./3/ 0330
Customer Ser'jice . 90/ /00 '290
1 0 wwwtolco.com
Fig. 98 - Rod Stiffener
Size Range - Secures 3/8' thru 7/8" hanger rod
Material - Carbon Steel
Function - Secures channel to hanger rod for vertical seismic bracing.
Finish - Electro Galvanized
Note - Available in HDG finish or Stainless Steel materials.
Order By - Figure number
Fig. 99 - Ali Thread Rod Cut to Length
res 3/8" thru 7/8' rod in
1" incrTTTnts
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter, rod
length and finish
Dimensions 'Weights
Rod Max. Rec. Load Lbs.
Size For Service Temps
650°F 750°F
610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
Fig. 100 - All Thread Rod Full Lengths
Size Range - Secures 3/8" thru 7/8" rod in
10' lengths
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electra-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter
and finish
Dimensions Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650°F 750°F wt./100
1/4 240 215 12
3/8 610 540 29
1/2 1130 1010 53
5/8 1810 1610 84
3/4 2710 2420 123
7/8 3770 3360 169
1 4960 4420 222
114 8000 7140 360
11/'11630 10370 510
Main 011icelManufaclurincj Facility. 13/9 Srp;ii Avc Coi'ji. 01 1)22/9 • Ph 909 /3/ • ra 909:3/0330
S. Customer Service • 2X3 /90 926/
wwWtO!co,Com
APPROVED !
8007957 GST 10 X CPVC 1-1/2 300 1.5
8020957 SWG 10 X CPVC 1-1/2 300 1.5
p8008957 GST 20 X 2-1/2 850 1.5
8068925 GST20SS X 2-1/2 850 1.5
8010957 GST 30 X 4 1500 1.5
-8009925 GST 25-380 X 4 1500 1.5
8022925 SWG 25-380 X 3-1/2 - 4 1500 1.5
—8021957 SWG 20 X 2-1/2 3** 1250 1.5
8073925 SWG 20 SS X 2-1/2 1250 1.5
8139957 SH GST 2O X 3 1050 1.5
8141957 SH GST 3O X 4 1500 1.5
8140957 SH GST 20 SS X 3 1050 1.5
8142957 SH GST 3OSS X 4 1500 1,5
X 4 175 1.5
X 4 1475 1.5
X 4 1475 1.5
X 4 1475 1.5
X 4 1'75 1.5
X 4 1'75 1.5
8038957 DSTR 1 X 4 1500 0.035 X 4 1475 0.1050
8037957 DSTR 1-1/2 X 4 1500 0.035 X 4 1475 0.1050
8039957 DSTR 516 X 4 1500 0.037 X 4 1475 0.1050
8045957 DST 516 X 4 1500 0.188 X 4 1475 0.1875
8046957 TEK50 X 4 1500 0.250 X 4 1475 0.1875
8055957 SWDR 1 X 4 1500 0.037 X 4 1475 0.0600
8056957 SWDR 516 X 4 1500 0.037 X 4 1475 0.0600
8054957 SWDR 1-1/2 X 4 1500 0.037 X 4 1475 0.0600
8137957 SH DSTR I X 4 1500 0.035 X 4 1475 0.1050
8150922 XP 20 X 2 750 0.027 X 4 1475 0.1050
8153922 XP 35 X 3-1/2 1250 0.043 X 4 1475 0.1050
8059957 CST 20 X 4 14.75 3000 PSI
8061957 SWC2O X 4 1475 3000 PSI
* SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2
SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4"
** SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2-1/2"
** SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 3"
UL and FM tests were performed in compliance with NFPA-13 Standards.
Fastening requirement: 5 times weight of water filled schedule 40 pipe plus 250 pounds
IT! wBuildex
www.itwbuildex.com
800-284-5339
SSS26
1 of 3
*1 iI[Ifl'7W MODELV-723 SADDLE LET Gu S ®
HOLE CUT SYSTEM
MECHANICAL TEE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
DESCRIP110N
VGSO Model V-723 Saddle Let small mechanical tees are available in sizes 1-1/4'
through 2-1/7. The Models V.723 mechanical tees provide an easy lake-out of a
branch outlet without the need for welding. VGS° Mechanical Tees are manufac-
tured at ($09001 certified facilities an am designed to conform toASTM and other
standards where applicable. Threads are NPT per ANSI B1.20.1.
LISTINGS AND APPROVALS
c®us Guide No. V1ZM
Class 1920
TECHNICAL DATA
Specifications:
Maximum working pressure: 300 psi (21 bar)
Ductile iron conforming to ASTM A536
Grade 65-45-12
Standard black finish
Hot dipped Zinc galvanized versions are available (conforming to ASTM A153);
when ordering, add a "G' suffix to the Model number.
Rubber compound EPOM Grade E conforming to ASTM D2000. A)N(NA C606,
NSF 61 and tAPM0.
'ULO ar,u OU"b. CHiC FIHWU, Laruun clear conforming lOAOiMfllO3 Grade I
(UI-IC nuts and bolts are a silver clrromate color and ISO am gold chromate color)
lr.sai.
c rq
- ..........in F_5 ' , r - Lb-Ftlftrn("-
1.25 x 0.5 1 le 1, a 22 1.61 u-suit 20-fl 09 (320 15) 1301 (48) 1001 1561 (42) (3/ee) (27 301 10.41) 1.250 0.75 1.10 1.87 35 22 1.63 U-Sot 20-22 1.0 1320 201 (30( (46) 1091 (56) 13/eel 127-301 (0.45)
1,25x1 1.18 2,04 3.5 2.2 1.73 U-8e1t 20-20 1.0 1320251 (30) (52) 1091 (56) 1441 (3/8a) (27-30) (0.45)
1.5 00.5 1.10 2.04 3.5 2.2 1.70 U-Box 20-22 0.9 140x 15) (30) 1521 (00) (56) 1481 13/8al (27-30) 10.411 1.5 00.75 1.18 2.04 2.5 2.2 1.79 U-BoO 20-22 0.9 )40x30) (30) (52) 1891 56) (46) (3/9a) 127-301 10.411
1,5e 1 - 1.18 2.04 3.5 2.2 1.69 U-BoO 20-fl 5.9 (40x25) (30) (52) (69) (56) (3/8a) 127-301 10.411 200.5 (to. 15)
1.18 2.30 3.86 2.2 2.07 U-Bn6 20-22 0.9 (30) (59) (59) 1561 (53) (3/8e) (27-301 (0.41) 2e0.75 1.19 2.30 3.88 22 2.07 u-Ben 20.22 5.0 (50020) 1 1001 (59) 1981 1561 (3/00) (27-30) (5.41)
201 1.10 2.30 3.08 2.2 1.97 U-Boll 20-22 1.0 (500251 (30) (59) (90) (56) )50) (3/8o) (27-30) (0.45) 2,000.5 1.18 2.46 4.37 2,2 2.22 U-Son 20-22 1,0 (65n 15) (30) (63) (111) 1561 (57) (3/to) (27-30) (0.45)
2.5n0.75 1.10 2.46 4.37 2.2 2.22 11900 211.22 1.0 (65020) (30) (03) (111) 56) (57) (3/8e) 127-301 (0.45)
2.5o 1 1.18 2.46 4.37 2.2 2.13 "
oft
20-22 1.0 (65025) (30) (63) (111) (56) )3/8e) (27-30) (0.45)
'Hole dbrnelein are suggested hole saw diarnetern. ''l Take-out (Center of roe to end of pipe to be engaged)
2 of 3
NGSO HOLE CUT SYSTEM
1000 MODEL V-723 SADDLE LET
MECHANICAL TEE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
HOLE CUTTING
The hole-cut method of pipe preparation is required when using mechanical lees, mechanical crosses, and saddle-lets. The method
of pipe preparation requires the cutting or drilling of a specified hole size on the centerline of the pipe. Always use the correct hole saw size as shown this data sheet and never use a torch for cutting a hole. After the hole has been cut all rough edges must be
removed and the area within 5/8 (16 mm) of the hole should be inspected to assure a dean smooth surface, free of any indenta-
tions or projections that could affect proper gasket sealing. The area within the 'A dimension should also be inspected and must be free for dirt, scale or any imperfection that could affect proper sealing or assembly of the fitting.
Table 2: Hole Sizes for Mechanical Tees
Model V-723
.c sons ' llafl)crti To", H6 1. Sal 00)
1" 10.3/4.1 ' 1.3/16 - 1.114 - 3/112 - 115.20,25) (30) 1321 (80)
INSTALLATION
NOTES:
Use a wrench to hold the threaded
outlet in place when installing the Table 3: K-factor of Saddle Lets
Tighten the nuts evenly. ___nt
Lt
K-factorof Saddle-Lets 412 415 415
Do not install sprinkler directly into Saddle-Let with V outlet.
U-Bolt
Hole
Gasket - -
Threaded
oufle icy
:t
Sprinkler
Figure 1: V.723 Saddle-Let Installation
The latest VOS Technical Data
can be acessed at
trttp:/lwww.nlkinygroupine.cem.
Scan to visit our Mobile weboite:
10.f)fii!i.ifa I /tl'tliilirtl I Iqt1;i;4
'-I -
Form No. F_110515 16.12.08 Rev 16.1 Replaces Form No. F_110515 Rev 15.1 Form No. F_110515 16.12.08 Rev 16.1
(Added K-factor limit table and flow data)
3 of 3
HOLE CUT SYSTEM
i'l II[i7f MODELV-723 SADDLE LET 'FIttkJ Ei S MECHANICAL TEE
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
6. FLOW DATA
Flow test data has shown that the total Formulas for Cv Values:
head loss between point A and B for p = u Where: fittings can be expressed in terms
of the pressure difference across P CV, a = Flaw (GPM)
the inlet and branch. The pressure OP Pressure Drop (psi)
difference can be obtained from the
relationship below. B—o1ib Q_ x C,Flow Coefficient
Form No. F_110515 16.12.08 Rev 16.1 Replaces Form No. F_110515 Rev 15.1