HomeMy WebLinkAbout5541 FERMI CT; ; FS140005; PermitCity of Carlsbad Fixed Systems Permit Permit No: FS140005 Job Address: 5541 FERMI CT Status: ISSUED Permit Type: FIXSYS Applied 1/30/2014 Parcel No: 2121305000 Approved: 3/4/2014 Lot #: 0 Reference No.: Issued: 3/4/2014 PC #: Inspector: Project Title: VERIZON-TAYLORMADE INSTALLATION OF A MINIMAX, MS-200 (FM-200) CLEAN AGENT FIRE SUPPRESSION SYSTEM IN THE VERIZON ROOM. THE MX-200 SYSTEM WILL UTILIZE A MS- 2002 AGENT RELEASE CONTROL PANEL FOR THE DETECTION AND CONTROL FUNCTIONS. Applicant: BRADSHAW ENGINEERING CORP 8645 ARGENT ST SANTEE CA 619-448-4300 Owner: FERMI COURT L P 1800 THIBODO RD #320 VISTA CA Fees ($) Add'I Fees ($) I Total ($) Balance ($) 229 0 229 0 Bradshaw Eng- ine e-ring Corp. Fire Protection Engineers and Contractors 8654 Argent Street Santee, CA. 92071 . Phone. (619)-44874800, Fax .(6.19)448-O535 ----Project info: -. 5541 Fermi Ct. . . . Carlsbad; CA. 92008 . . •.. . : ...........................'Scope ofWork. .•.... .. •.. . Installation of a MINIMAX, MX-200 (FM-200), Clean Agent Fire - RbôTThMX2OO të ilF utilize aMX-2002, agent release control panel for the detection and control functions. 44 ..................................................•o FS140005 Calculating the System Current Draw Power Supply Calculations Table 5.3 contains three columns for calculating current draws. For maximum output current avail- able per circuit and per panel, refer to Section 1. 2, "Specifications ", on page 14. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 108. Calculation Column I Calculation Column 2 Calculation Column 3 Device Type Primary, Non-Fire Alarm Current Secondary, Fire Alarm Current Secondary, Non-Fire Alarm Current (amps) (amps) (amps) Qty X[current draw]= Total Qty X [current draw] = Total Qty X[current draw]= Total Main Circuit Board 1 X[O.095]= 0.095 1 XFo.22111 2 0.221 1 X[O.095] 0.095 N-CAC-5X [ ] X[0.001]= F ] X[0.001]= [ ] X[0.001]= 4XTM [ ] X0.0051= F I X[0.011]1 I I X[0.005]= (1 max.) ANN-SEC Card j X[0.003]= F I X[O.003] I ] X[O.003]= (1 max.) (1 max.) (1 max.) N-ANN-80(C) F ] X[0.037]= F I XI0.0401= I I X[O.037]= N-ANN-I/O F I X[0.035]= F ] X[0.200]= F I X[O.035]= ANN-RLY F I X[0.015]= F I X[0.075]= F ] X[O.015]= ANN-(R)LED F I X[0.028]= F I X[0.068]= F X[0.028]= N-ANN.S/PG [] X0.045]= F I X[0.045]= F I X[0.045]= 2-wire Detector [ I XF 13= F j4 X[0.040] F I X[ ]3 Heads 4-wire Detector F I XF 13= F 14 X[0.040]= [ ] X[ ]3= Heads Power Supervision F I XIO.0251= F I X[0.025]= F ] X[O.025]= Relays5 I NAC #1 F I X[ 1= NAC #2 11jJ11111111111111111116 F I XF 1= NAC #3 NAC #4 F 1= F 1= F 1= Current Draw from TB9 (nonalarm) Sum each column6 Primary Non-Alarm = Secondary Alarm = Secondary Non-Alarm = for totals Table 5.3 System Current Draw Calculations I If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps. 2 The current shown represents one zone (lDC) on the main circuit board in alarm. One zone consumes 0.04C amps. 3 Refer to the Device Compatibility Document for standby current. 4 Enter the number of IDCs used minus one. 5 Must use compatible listed Power Supervision Relay. 6 Total current draw listed above cannot exceed 7.2 amps MX-2002 Series Instruction Manual - P/N 54508:Al 3/2/2011 107 Hydraulic Flow CaIcs for the Minimax, MX-200 System n 0 MX DesicinManacier - System MX200/HFC Mx DesignManager - MX200 V.1.0 / MX DesignManager 1.3.2 UL: EX 5248 - MX 1230/MX 200 FM: 3035914-MX 1230 I 30359: Project Parameters !Custorne..Bradshaw Engineering Corp Project Name Verizon Date 2014-01-27 Address User . .........................dmeyers No. 'Protected Area -Equip Room Installation MX Type of System .MX 200 Discharge .Time [s] 10 Height above Sea Level [ft] . 0 Guideline/Standard NFPA Project Info Container Pipe System Starting Node 0 2 3 4 Agent in PiDe System Nominal Diameter Ending Node [in] 1 11/4" 2 1" 3 1" 4 5 6.5 lb MX DesicinManaaer - System MX200/HFC Mx DesignManager - MX200 V.1.0 I MX DesignManager 1.3.2 UL: EX 5248- MX 1230/MX 200 FM: 3035914-MX 1230 I 30359: Quantity Calculation Enclosure Sect o Length Width ion Height Vv Vg Vr Av Ab Ar Ca Tr [ft] [ft] [ft] [ft 3] 1ft31 [ft3] [ft2] [ft2] [ft2J 1%] ["F] Equip Room 0 0 0 2062 0 2062 0 1 0 0 7 0 70 2062 0 2062 0 0 0 e Number Pressure Filling Quantity Filling Portion Filling Temp. Storage [psi] [lb] [lb/1] ["F] [°F I .360 71 . 1.37 70 Length Elevation Change Component * Flow Rate Starting Pressure Final Pressur Iii]....................................... ................. [if] .[j ]............................................[psil .[p•s.ii.................... 0 0 B 7.1 0 240.67 0.5 0.5 SV 7.1 240.67 233.51 4.5 . ......L 7.1 233.51 .226.36 . 6 0 E 7.1 226.36 220.35 0.5 -0.5 E 7.1 220.35 . 220.05 tainer = B Manifold = M, Container Valve = SV, Bull-Tee = BT, Side-T = ST, Thru-T = TT, Elbow = E, Zone Valve = ZV, Zone Manifold Outlet = ZMO, Zone Manifold Thru = ZMT Nozzles Discharge set Starting. Discharge Nominal Spray Angle Orifice Quantity Pressure i Discharge Rui Value Node act value Description Art No Diameter [] [in] of Orifices [psi] Time actual ac [0/] [lb] [in] . Es] I 5 100 71 CDNPTO53 889036 1/2 180 0189 3 22005 100 C Pressure Relief Vent Guideline Max. allowed pos. enclosure Enclosure volume Pressure relief vent area calc.Concentration oressure Fosil lft31 . lin21 1%1 ..................I:........fiT..................T LU fl.................................................................................................................................I. ...J...................................................................................................... 0 2062 MX DesignManager - System MX200/HFC Mx DesignManager- MX200 V.1.0 / MX DesignManager 1.3.2 UL: EX 5248- MX 1230/MX 200 FM: 3035914-MX 1230 I 30359 Bill of Material Quantity. Unit Part No Description lease select PCs. 826758 Limit switch pneumatically actuated 1.00 PCs. Order .Release Device MX 200/1230 electrical ............7.1..OP..b .887745 ..X200 (HFC 227ea) 1.00: PCs. Order Form Contact Pressure Gauge MX200/1230 - ................1..P0........p•c...889Q9.8 .Container 52 . psi, Valve B0482-ADN3.3 ................1.00.pçs .887450 Adapter ho.Se DN.40 !.SO-.NPT 1.001.. . PCs. ....P. for 25/50/801 extinguishing agent cylinder MX 200/MX 12.9........ ................1.59•ft 'bider Form .Pipe Sch.40A-53B ..W1"x............................................................................................................ Dlease select PCs. .887647 .Hose DN 40 MX 200/MX 1230 . -... :'lease select pcs. . 888052 .Connection piece DN 40 MX 200/MX 1230 ................2.09 PCs. bider .....wi..NPTANS.. 1.00 . PCs. . .889036 Nozzle CD 180° MX 200 NPT 1/2 °brass, 3 bores . .. Minimmax, MX-200 CLEAN AGENT SYSTEM DATA SHEETS I 0 IN THE EVENT OF A FIRE AND SYSTEM DISCHARGE, CAUTION MUST BE TAKEN TO AVOID EXPOSURE TO PRODUCTS OF COMBUSTION. DO NOT ENTER WITHOUT AN APPROVED SELF-CONTAINED BREATHING APPARATUS OR UNTIL AREA IS THOROUGHLY VENTILATED. MX-200 FIRE SUPPRESSION SYSTEM C Page 1 Caution Labels Two caution labels are available for indicating the presence of a Minimax MX-200 suppression system. Each caution label is made of aluminum. Label must be located in areas visible to the personnel located within or near the protected areas. Technical Data Material.......Aluminum Thickness.. ..0.039 in. Finish.........Red Weight........0.26 lb. Dimensions 9 in. x 8 in. Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 . FM Approved.. ..File No. 3035914 Shipping Assembly Part No. Description 17493 CAUTION! Do NOT re-enter until area is thoroughly ventilated 17493-S Spanish Version 17494 CAUTION! This area is protected by a MX 200 Fire Suppression system 17494-S Spanish Version ACAUTION THIS AREA IS PROTECTED BY AN MX-200 FIRE SUPPRESSION SYSTEM. WHEN THE FIRE ALARM SOUNDS, OR IN THE EVENT OF A FIRE, AND SYSTEM DISCHARGE, EVACUATE HAZARD AREA IMMEDIATELY AND DO NOT RE-ENTER UNTIL AREA IS THOROUGHLY VENTILATED. SYSTEM MANUEATURER MIN IMAX USA LLC I ii I It. 4055 E CORNICE OR. SUITE 112 10 MESA, AZ BUStS SYSTEM MANUFACTURER MU4IRIEX USA LLC r I I I I I i II BOTO S. CORNICE OR, EERIE 152 MESS AZ 852i Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 ... hftp://www.minimaxfp.com C 14.2 MX-200 FIRE SUPPRESSION SYSTEM C::3 Page Agent Tanks (Pressurized at 360 psi (25 bar)) The agent tank assemblies are manufactured in accordance with DOT 4BW500 and includes the finished tank, shipping cap, valve assembly, and siphon tube and Pressure Gauge/Low Pressure Switch. A nameplate is adhered to the finished tank displaying the agent weight and gross weight of the complete charged assembly. Tanks are superpressurized with dry nitrogen at 360 psi (25 bar) at 70 OF (21 °C). When ordering charged tank assemblies, the quantity of agent must be ordered with tank part number hyphen agent quantity in lbs. i.e. 88 9098 - 57, quantity is in 1 lb. increments. Nominal Volume Shipping Part No. "A" "B" Dia. Mm. Fill (lb) Max. Fill (lb) Empty Weight (Ib) 55 lb 914146 40.8 in. 23.2 in. 10 in. 25 lb 55 lb 88 lb 130 lb 889098 65.4 in. 47.8 in. 10 in. 57 lb 130 lb 108 lb 2701b 889100 61.4 in. 40.9 in. 16 in. 116 lb 2661b 1901b 370 lb 889103 74.5 in. 54.0 in. 16 in. 162 lb 369 lb 229 lb 450 lb 91 0508 82.0 in. 61.5 in. 16 in. 199 lb 452 lb 313 lb With Liquid Level Indicator 270 lb 914148 61.4 in. 40.9 in. 16 in. 116 lb 266 lb 210 lb 370 lb 914149 74.5 in. 54.0 in. 16 in. 162 lb 369 lb 251 lb 450 lb 91 4150 82.0 in. 61.5 in. 16 in. 199 lb 452 lb 286 lb Technical Data Tank Material......Steel Tank Finish.......Red Nameplate.......PVC foil self adhesive Valve.......Brass Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved... .File No. 3035914 Shipping Assembly See chart above Minimax Fire Products.. .4030 East Quenton Dr.. .Suite 112... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 . . . hftp://www.minimaxfp.com I MX-200 FIRE SUPPRESSION SYSTEM Page 4 Mounting Bracket The mounting bracket is required to properly and safely secure the agent tank assemblies to a rigid vertical mounting surface. Brackets are available for 360 psi (25 bar) and 725 psi (50 bar) agent tanks. Each size tank requires only one bracket. Size Tank Used On Shipping Assembly Part No. Radius (R) "B" Weight 130 lb..........360 psi 887628 5.3 in. 4.72 in. 3.2 lb 270 lb..........360 psi 370 lb..........360 psi 887639 8.1 in. 7.87 in. 4.6 lb 200 lb..........725 psi 350 lb..........725 psi 450 lb .........725 psi Technical Data Material.......Steel Finish .......... Matt-finish or powder-coated, graphite black Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved.... File No. 3035914 Shipping Assembly See chart above I - —T— +11 ---T+]2.3€" Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670.. .Fax: 480-553-5701 ... http://www.minimaxfp.com E 14.2 MX-200 FIRE SUPPRESSION SYSTEM Page 5 Nozzles The Minimax MX-200 Fire Suppression System offers several sizes of both 1800 and 3600 agent discharge nozzles. All nozzles are manufactured in brass and are available with NPT threads. A wide range of drilled orifice sizes are available to meet any discharge rate requirement. Nozzle bores are drilled per MX DesignManager calculations. 1800 Nozzle Size Shipping Assy Part No. Orifice Diameter Mm Max. "A" "B" 1/2 in. NPT 889036 0.118 in.......0.236 in. 2.2 in. 1.1 in. 1 in. NPT 889040 0.118 in.......0.433 in. 2.6 in. 1.6 in. 1 % in. NPT 1 889044 0.118 in.......0.709 in. 1 3.4 in. 2.2 in. 360° Nozzle Size Shipping Assy Part No. Orifice Diameter Mm Max. "A" "B" 1/2 in. NPT 889037 0.118in ...... 0.197in. 2.2 in. 1.1 in. 1 in. NPT 889041 0.118 in......0.394 in. 2.6 in. 1.6 in. 1 1/2 in. NPT 1889045 0.118 in......0.630 in. 1 3.4 in. 12.2 in. Technical Data Material.......Brass Finish..........Brass Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved. ...File No. 3035914 Shipping Assembly See chart above A Ordering Information Order nozzle part no. - orifice code (i.e. 88 9045-0.118) Minimax Fire Products ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 ... http://www. minimaxfp.com 0 B MX-200 FIRE SUPPRESSION SYSTEM Page 9 Manual Release The manual release assembly contains a hand lever which can be used to manually actuate the tank valve. When the ring pin is pulled from the lever, the lever can be pushed down, moving the internal pin down, which will cause the tank valve to actuate. The release is not spring loaded, therefore it must be reset manually after actuation. Manual reset requires pushing the pin up, back into the body of the release. Technical Data Body........Brass Handle......Stainless Steel Spring......Stainless Steel Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved.... File No. 3035914 0 Shipping Assembly Part No. Description 887668 Manual release H 3.03" Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701... hftp://www.minimaxfp.com MX-200 FIRE SUPPRESSION SYSTEM Page 11 Electric Release The 24V electric release can be used to electrically actuate the agent tank valve. An electric signal is required from the detection panel. This signal operates an internal solenoid which actuates the release mechanism. The release mechanism then opens tank valve. Only one electric release is required on multiple tank system. The remaining tank valves are opened by agent pressure through the pilot line. Technical Data Nominal Voltage..........24VDC Nominal Current......... 0,5i" lP Code .................... P65 Max. Permitted Test Current. . .20 mA Electrical Inlet........1/2 in. NPT Weight...........5.5 lb Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved.... File No. 3035914 Shipping Assembly Part No. Description 889323 Release without diode 887645 Electric release screw reset tool 5.51" Note: Polarity must be observed when wiring the release to control panel. The release will not operate if installed with reverse polarity. Note: To reset the electric release, the reset tool Must be threaded into the base of the release until it stops. Remove the reset tool and visually inspect the pin inside the release. If the red marking on the pin is not visual, the release has been correctly reset. Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670.. .Fax: 480-553-5701 ... http://www.minimaxfp.com 14.2 MX-200 FIRE SUPPRESSION SYSTEM Page 19-01 2013 Swivel Adaptor (Tank to Pipe) The swivel adaptor is used to connect the agent tank valve outlet with the NPT piping network. Two sizes are available, 1 1/2 in. and 2 in. outlet size. Technical Data Material.......Galvanized Steel Weight ........ 11/2 in. size 2.2 lb 2 in. size 2.9 lb Listings/Approvals UL Listed ......... EX-5248 ULC Listed ....... EX-5248 FM Approved... .File No. 3035914 Shipping Assembly Part No. Description 17562 1 7/8"-12 UN. Valve Connection (G2) to I 1/2' NPT Pipe Connection (Gi) A=3" 17563 2 "-12 UN. Valve Connection (G2) to 2" NPT Pipe Connection (GI) A=3 1/2" A Minimax Fire Products.. .4030 East Quenton Dr.. Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 ... http://www.minimaxfp.com 14.2 MX-200 FIRE SUPPRESSION SYSTEM Page 20 (Pneumatic Limit/Pressure Switch The pneumatic operated limit/pressure switch can be mounted in the agent distribution piping. Upon system discharge, the agent pressure in the piping network will actuate the switch, causing the internal electrical contacts to either open or close. This action can be used to signal alarms, turn on warning lights, cause door closures to operate, etc. Technical Data Material.........Alloy Die-cast Metal IP Rating ....... 1P65 Nominal Isolation Voltage... .500V Permanent Current .... 16A Nominal Operation Current... .6A, 400 VAC Weight..................3.3 lb. Listi ngsIApprovals UL Listed ......... EX-5248 • ULC Listed ....... EX-5248 FM Approved... .File No. 3035914 Shipping Assembly Part No. Description 826758 Pneumatic Limit/Pressure Switch 724420 US 432y-M20-2352 Replacement Limit Switch (2 Contact) 224831 US 434y-M20-2352 Replacement Limit Switch (4 Contact) Minimax Fire Products.. .4030 East Quenton Dr. Suite 112. ..Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 . . . http://www.minimaxfp.com Minimax. MX-2002 AGENT RELEASE CONTROL PANEL DATA SHEETS 1] 40 MIN-60680:A1 MX-2002(E) Agent Release Control Panel minimnX 0 General The MX-2002 is a six-zone FACP for single and dual hazard agent releasing applications. The MX-2002 provides reliable fire detection, signaling and protection for commercial, indus- trial and institutional buildings requiring agent-based releasing. The MX-2002 is compatible with System Sensor's i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory freeze' signal when the ambient temperature falls below the detector rating of approximately 45°F (7.22°C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Minimax Device Compatibility Document for a complete listing of compatible devices. Four outputs are programmable as NACs (Notification Appli- ance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The MX-2002 supervises all wiring, AC voltage, battery charger and battery level. Activation of a compatible smoke detector or any normally- open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm infor- mation on the panel's LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function. The F offers the same features as the MX-2002 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 110/120 VAC and 220/240 VAC versions of the panels. Features Listed to UL Standard 864, 9th edition. FM Approved. Designed for agent releasing standards NFPA 12, 12A, 12B, and 2001. Disable/Enable control per input zone and output zone. Extensive transient protection. Dual hazard operation. Adjustable pre-discharge, discharge and waterflow delay timers. Cross-zone (double-interlock) capability. Six programmable Style B (Class B) lDCs (Initiating Device Circuit). System Sensor i3 series detector compatible. Four programmable Style Y (Class B) output circuits - (spe- cial application power). Strobe synchronization: - System Sensor - Wheelock - Gentex - Faraday - Amseco Three programmable Form-C relays. 7.0 amps total 24 VDC output current. Resettable and non-resettable output power. Built-in Programmer. ANN-BUS connector for communication with optional devices (up to 8 total of any of the following): - N-ANN-80 Remote LCD Annunciator - N-ANN-I/O LED Driver - N-ANN-S/PG Printer Module - N-ANN-RLY Relay Module - N-ANN-LED Annunciator Module 80-character LCD display (backlit). Real-time clock/calendar with daylight savings time control. History log with 256 event storage. Piezo sounder for alarm, trouble and supervisory. 24 volt operation. Low AC voltage sense. Outputs Programmable for: - Releasing Circuits or NACS NACs programmable for: - Silence Inhibit - Auto-Silence - Strobe Synchronization - Selective Silence (horn-strobe mute) - Temporal or Steady Signal - Silenceable or Non-silenceable - Release Stage Sounder Automatic battery charger with charger supervision. Optional Dress Panel DP-51050 (red). MIN-60680:A1 .06/14/2011 —Page lot 4 I 40 Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet. Optional N-CAC-5X Class A Converter Module for Outputs and lDCs. Optional 4XTM Municipal Box Transmitter Module. Optional Digital Alarm Communicators (411, 411 UD, 411 UDAC). Optional ANN-SEC card for a secondary ANN-BUS. PROGRAMMING AND SOFTWARE: Custom English labels (per point) may be manually entered or selected from an internal library file. Programmable Abort operation. Three programmable Form-C relay outputs. Pre-programmed and custom application templates. Continuous fire protection during online programming at the front panel. Program Check automatically catches common errors not linked to any zone or input point. USER INTERFACE: Integral 80-character LCD display with backlighting. Real-time clock/calendar with automatic daylight savings adjustments. ANN-Bus for connection to remote annunciators. Audible or silent walk test capabilities. Piezo sounder for alarm, trouble, and supervisory. Controls and Indicators LED INDICATORS FIRE ALARM (red). SUPERVISORY (yellow). TROUBLE (yellow). AC POWER (green). ALARM SILENCED (yellow). DISCHARGED (red). PRE-DISCHARGE (red indicator). ABORT (yellow indicator). CONTROL BUTTONS ACKNOWLEDGE. ALARM SILENCE. SYSTEM RESET (lamp test). DRILL. AC Power - TB MX-2002:120 VAC, 60 Hz, 3.66 amps. MX-2002E: 240 VAC, 50 Hz, 2.085 amps. Wire size: minimum #14 AWG (2.0 mm 2) with 600V insula- tion. Supervised, nonpower-limited. Battery (sealed lead acid only) - J12: Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC © 1.4 amp. Supervised, nonpower-limited. Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or NFS-LBBR). Minimum Battery Size: 7 Amp Hour. Initiating Device Circuits - TB4 and TB6 Zones 1 - 5 on TB4. Zone 6onTB6. Supervised and power-limited circuitry. Style B (Class B) wiring with Style D (Class A) option. Normal Operating Voltage: Nominal 20 VDC. Alarm Current: 15 mA minimum. Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 Ohms. End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252). Standby Current: 4 mA. Refer to the Minimax Device Compatibility Document for listed compatible devices. Notification Appliance and Releasing Circuit(s) - TB5 and TB7 Four Output Circuits. Style Y (Class B) or Style Z (Class A) with optional con- verter module. Special Application power. Supervised and power-limited circuitry. Normal Operating Voltage: Nominal 24 VDC. Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC). End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252). Max. Wiring Voltage Drop: 2 VDC. Refer to the Minimax Device Compatibility Document for com- patible listed devices. Form-C Relays - Programmable - TB8 Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: - 2 amps © 30 VDC (resistive) - 0.5 amps © 30 VAC (resistive) Auxiliary Trouble Input - J6 The Auxiliary Trouble Input is an open collector circuit which can be used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector cir- cuits. Special Application Resettable Power - TB9 Operating Voltage: Nominal 24 VDC. Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note). Power-limited Circuitry. Refer to the Minimax Device Compatibility Document for com- patible listed devices. NOTE: Total current for resettable power, nonresettable power and Output Circuits must not exceed 7.0 amps. Special Application Resettable or Nonresettable Power - TB9 Operating Voltage: Nominal 24 VDC. Maximum Available Current: 500 mA (see note 1). Power-limited Circuitry. Jumper selectable by JP31 for resettable or nonresettable power. Refer to the Minimax Device Compatibility Document for com- patible listed devices. Page 2 of 4— MIN-60680:A1 • 06/14/2011 Product Line Information MX-2002: Six-zone, 24 volt Agent Release Control Panel (includes backbox, power supply, technical manual, and a frame & post operating instruction sheet) for single and dual hazard agent releasing applications. MX-2002E: Same as above but allows connection to 220/240 VAC. N-CAC-5X: Class A Converter Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). NOTE: Two Class A Converter modules are required to convert all four Output Circuits and six Initiating Device Circuits. 4XTM: Transmitter Module provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. N-ANN-80(-W): LCD Annunciator is a remote LCD annuncia- tor that mimics the information displayed on the FACP LCD display. Recommended wire type is un-shielded. (Basic model is black; order -w version for white; N-ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. Ships with N-ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. N-ANN-RLY (16911): Relay Module, which can be mounted inside the cabinet, provides 10 programmable Form-C relays. N-AN N-SIPG: Serial/Parallel Printer Gateway module pro- vides a connection for a serial or parallel printer. N-ANN-I/O: LED Driver Module provides connections to a user supplied graphic annunciator. ANN-SEC: Optional card for a secondary ANN-BUS. See 53944. DP-51050: Dress panel (red) is available as an option. The dress panel restricts access to the system wiring while allow- ing access to the membrane switch panel. TR-CE: Trim-ring (red) is available as an option. The trim-ring allows semi-flushing mounting of the cabinet. BB-26: Battery box, holds up to two 26 Amp Hour batteries and CHG-75. NFS-LBBR: Battery box, houses two 55 Amp Hour batteries, red. BAT Series Batteries: Refer to DN-6933. PRN-6: UL-listed compatible event printer. Dot-matrix, tractor- fed paper, 120 VAC. PRT-PK-CABLE: Programming cable. Used to update the FACP's flash firmware. (Also requires an R5485 to RS232 converter). MIN-60680:A1 • 06/14/2011 - Page 3 of 4 C SYSTEM SPECIFICATIONS System Capacity useful life of the system's standby batteries and the electronic components may be adversely affected by extreme tempera- Annunciators ......................................................................8 ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment Electrical Specifications with a normal room temperature of 15— 270C/60 - 80°F MX-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps MX-2002E (FLPS-7 Power Supply): 240 VAC, 50 Hz, 2.085 amps Wire size: minimum 14 AWG (2.0 mm2) with 600 V insula- tion, supervised, nonpower-limited Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82° (42.73 cm.) wide x 0.72° (1.82 cm.) deep. Backbox: 19.00° (48.26 cm.) high x 16.65° (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR- CE): 22.00° (55.88 cm.) high x 19.65° (49.91 cm.) wide. Shipping Specifications Dimensions: - Height 20.00° (50.80cm) —Width 22.50" (57.15cm) - Depth 8.50° (21.59cm) Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 - 49°C/32 - 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 30F). However, the NFPA Standards The MX-2002(E) complies with the following NFPA 72 Fire Alarm Systems requirements: - NFPA 12 CO2 Extinguishing Systems - NFPA 12A Halon 1301 Extinguishing Systems - NFPA 12B Halon 1211 Extinguishing Systems - NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module) - NFPA 2001 Clean Agent Fire Extinguishing Systems Agency Listings and Approvals The listings and approvals below apply to the basic MX- 2002(E) control panels. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. FM approved NOTE: For ULC-listed model, see MIN-60681. 02011 All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I Iso 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. I I I ENGINEERING & MNOMCThRING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Minimax, 4030 East Quenton Drive, Suite 112, Mesa AZ 85215 Page 4 of 4— MIN-60680:A1 • 06/14/2011 N-ANN-RLY Relay Module General The N-ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP (Fire Alarm Control Panel). The N-ANN-RLY module may be mounted inside the FACP main circuit board chassis or in the battery area of the enclosure using optional mounting bracket P/N: ANN-MBRLY. Reference Installation Instructions document #. The N-ANN-RLY and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication for- mat. An additional two wires are used for 24-volt DC power. A single four-conductor unshielded cable may be used for both power and data communications. Up to eight ANN-BUS devices may be connected to the ANN- BUS of each FACP. Features N-ANN-RLY connects to the ANN-BUS terminal on the FACP and requires minimal programming. Provides 10 programmable Form-C relays. Ten Form-C relays can be programmed for various func- tions; Alarm, Trouble, Supervisory, AC Loss, Waterflow Delay, Input Zones and Silenceable Alarm. Compatible with the ,, and. May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC). Up to eight ANN-BUS devices may be connected to the ANN-BUS of each FACP. Listed to UL Standard 864, 9th Edition. Specifications Maximum ANN-BUS Voltage: 24 VDC Maximum Current: - Alarm: 75 mA Standby: 15 mA Ambient Temperature: 32F to 1202F (0C to 49C) Relative Humidity: 93% ± 2% RH (noncondensing) at 32C ± 2C (909F ± 32F) For use indoors in a dry location Connections to FACP are power-limited and supervised. Relay Contact Ratings: 2 Amps @ 30VDC (Resistive) 0.5 Amps © 30VAC (Resistive) Agency Listings and Approvals The listings and approvals below apply to the N-ANN-RLY. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S635 FM Approved CSFM: 7165-0028:0245; 7165-0028:0246 DN-7107:A1 • K-20 NOTIFIER® by Honeywell The ANN-BUS POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY ANN-BUS devices can be powered by an auxiliary power sup- ply when available panel power is exceeded. See FACP man- ual for information. ANN-BUS DEVICE ADDRESSING Each ANN-BUS device requires a unique address (ID Num- ber) in order to communicate with the FACP. A maximum of eight devices can be connected to the FACP ANN-BUS com- munication circuit. See the FACP manual for more information. WIRE REQUIREMENTS The N-ANN-RLY connects to the FACP ANN-BUS communica- tions circuit. To determine the type of wire and the maximum wiring distance, calculate the total worst case current draw for all modules on a single 4-conductor bus. Use the table on the following page to determine the maximum distance the mod- ules can be located from the FACP. In general, the wire length is limited by resistance, but for heavier wire gauges, capaci- tance is the limiting factor. These cases are marked in the chart with an asterisk (*)• Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. Refer to the appropriate FACP manual for wiring details. Ordering Information ANN-RLY: Relay Module provides 10 programmable Form C relays. ANN-MBRLY: Optional mounting bracket. ROME: Relay Option Module Enclosure, includes one ANN-RLY Relay module and one ANN-MBRLY bracket installed. DN-7107:A1 .9/21/10—Page 1 0f2 0 Communication Pair Wiring Distance: FACP to last ANN-BUS Module Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1,852 ft. (565 m) 4,688 ft. (1,429 m) * 6,000 ft. (1,829m) * 6,000 ft. (1,829 m) 0.200 926 ft. (282 m) 2,344 ft. (715 m) 3,731 ft. (1,137 m) 5,906 ft. (1,800 m) 0.300 617 ft. (188 m) 1,563 ft. (476 m) 2,488 ft. (758 m) 3,937 ft. (1,200 m) 0.400 463 ft. (141 m) 1,172 ft. (357m) 1,866 ft. (569 m) 2,953 ft. (900 m) 0.500 370 ft. (113 m) 938 ft. (286 m) 1,493 ft. (455 m) 2,362 ft. (720 m) 0.600 309 ft. (94 m) 781 ft. (238 m) 1,244 ft. (379 m) 1,969 ft. (600 m) 0.700 265 ft. (81 m) 670 ft. (204 m) 1,066 ft. (325 m) 1,687 ft. (514 m) 0.800 231 ft. (70 m) 586 ft. (179 m) 933 ft. (284 m) 1,476 ft. (450 m) 0.900 206 ft. (63 m) 521 ft. (159 m) 829 ft. (253 m) 1,312 ft. (400 m) 1.000 (max.) 185 ft. (56 m) 469 ft. (143 m) 746 ft. (227 m) 1,181 ft. (360 m) TB6 ANN-BUS 0 -+AB OTBI B (ANN-B1Jj1 Connect to FACP ANN-BUS A (ANN_Bu.sfand/or next device + (24 VD)l_Connect to FACP or UL listed Power Supply for - (ON D) J Fire Protective Signaling and/or next device N-ANN-RLY Relay Module 02010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. b dl I -J We cannot cover all specific applications or anticipate all requirements. ENGINEERING I IIIIIIIINUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2of2—DN-7107:A1 .9/21/10 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-2078:0101 Page 1 of 1 CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Minimax USA, LLC4030 E Quenton Drive, Suite 112, Mesa, AZ 85215 Contact: Bill Freeman (480) 553-5670 Fax (480) 553-5701 Email: bfreemanminimaxfp.com DESIGN: Model MX-2002 conventional fire alarm control unit. Each unit employs six programmable input circuits, four programmable output circuits, and three relay contact outputs for alarm, trouble, and supervisory signals. These units do not contain an integral digital alarm communicator transmitter (DACT). Model is intended for agent release control. FLPS-7 Power Supply module 4XTMF Transmitter module CAC-5X Converter module ANN-80 LCD Annunciator ANN-1 /0 LED Driver module ANN-LED Annunciator module ANN-RLY Relay module ANN-S I PG Serial/Parallel printer module DP-51050 Dress panel DP-5105OLED Dress panel INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product designation, electrical rating and UL label. APPROVAL: Listed as a fire alarm control unit suitable for use as agent releasing panel. Unit also provides fire detection, signaling and protection features. Refer to manufacturer's Installation Manual for details.This control unit meets the requirements of UL-864, 9th Edition Standards. XLF: 7165-0075:0216 10-04-2011 mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not , an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division 11 Ll i3 Series Photoelectric Smoke Detectors General System Sensor's i3TM Series photoelectric and photoelectric/ thermal smoke detectors represent a significant advancement in conventional detection, incorporating three key features: installation ease, intelligence, and instant inspection. Installation ease. The P Series redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire-entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of backbox mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i Series heads plug into the base with a simple Stop-Drop 'N LocklM action. Intelligence. P Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensa- tion and smoothing algorithms, to minimize nuisance alarms, are standard in the P Series. When connected to the 2W-MOD loop test/maintenance module, an SFP-2402/-2404 panel, SFP-5UD/10UD, or RP-2001/2002 two-wire i3 detectors are capable of generating a remote maintenance signal when they need cleaning. This signal is indicated by LEDs located at the module and at the panel. To read the sensitivity of i3 detectors, the SENS-RDR is a wireless device that displays sensitivity in terms of percent-per-foot obscuration. Instant inspection. The 3 Series provides wide-angle red and green LED indicators for instant inspection of detector condi- tion. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The "EZ Walk" loop test feature is available on two-wire l Series detectors when con- nected to the 2W-MOD loop test/maintenance module. The "EZ Walk" feature verifies the initiating loop wiring by providing LED status indication at each detector. Features Plug-in detector line - mounting base included Large wire-entry port. In-line terminals with SEMS screws. Mounts to octagonal and single-gang backboxes, 4° (101.6 mm) square backboxes, or directly to ceiling. Stop-Drop 'N Lock attachment to base. Removable detector cover and chamber for easy cleaning. Built-in remote maintenance signaling. Drift compensation and smoothing algorithms. Simplified sensitivity measurement. Wide-angle, dual-color LED indication. Loop testing via "EZ Walk" feature. Built-in test switch. Specifications PHYSICAL SPECIFICATIONS Operating Temperature Range: For models 2W-B and 4W- B: 32°F to 120°F (0°C to 49°C); for thermal models 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.80C). Operating Humidity Range: 0% - 95% RH, non-condens- ing. DN-6885:A2 • 1-80 NOTIFIER® by Honeywell Thermal Sensor: 135°F (57.2°C) fixed (models 2WT-B, 4WT-B). Freeze Trouble: 41°F (5°C) (models 2WT-B and 4WT-B). Sensitivity: 2.5%/foot (0.762%/meter) nominal. Input Terminals: Utilize 14 to 22 AWG wire. Dimensions (including base): 5.3° (134.62 mm) diameter, 2.0" inches (50.8 mm) high. Weight: 6.3 oz. (178.6 grams). Mounting Options: 3.5° (88.9 mm) octagonal backbox; 4" (101.6 mm) octagonal backbox; single-gang backbox; 4" (101.6 mm) square backbox with a plaster ring; or direct mount to ceiling. ELECTRICAL SPECIFICATIONS Operating Voltage: 12/24 V non-polarized nominal; 8.5 V minimum; 35 V maximum. Maximum Alarm Current: For two-wire models: 130 mA lim- ited by control panel; For four-wire models: 20 mA © 12 V, 23 mA © 24 V. Alarm Contact Ratings: For four-wire models: 0.5 A © 30 VACNDC; not applicable for two-wire models. Architectural/Engineering Specifications Smoke detector shall be a System Sensor i3 Series model number , Listed to Underwriters Laboratories UL 268 Fire Protection Signaling Systems. The detector shall be a photoelectric type (models 2W-B, 4W-B) or a combination pho- toelectric/thermal (models 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3.5° (88.9 mm) and 4" (101.6 mm) octag- onal, single-gang, and 4" (101.6 mm) square backboxes with a plaster ring, or directly mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5%/foot (0.762%/meter) as measured in the UL smoke box. The detector shall be capable of auto- matically adjusting its sensitivity by means of drift compensa- tion and smoothing algorithms. The detector shall provide dual-color LED indication which blinks to indicate power-up, normal standby, out-of-sensitivity, alarm, and freeze trouble DN-6885:A2 • 11/17/09 - Page 1 of 2 (models 2WT-B, 4WT-B) conditions. When used in conjunction Product Line Information with the 2W-MOD module, two-wire models shall include a maintenance signal to indicate the need for maintenance at 2W-B: Two-wire photoelectric smoke detector. the alarm control panel, and shall provide a loop testing capa- . C2W-BA: Same as 2W-B, ULC listing. bility to verify the circuit without testing each detector individu- 2WT-B: Two-wire photoelectric smoke detector with 135°F ally. (57.2°C) fixed thermal sensor. Agency Listings and Approvals C2WT-BA: Same as 2WT-B, ULC listing. 4W-B: Four-wire photoelectric smoke detector. In some cases, certain modules may not be listed by certain NW-BA: Same as 4W-B, ULC listing. approval agencies, or listing may be in process. Consult fac- 4WT-B: Four-wire photoelectric smoke detector with 135°F tory for latest listing status. (57.2°C) fixed thermal sensor. UL/ULC Listed: S911 C4WT-BA: Same as 4WT-B, ULC listing. FM Approved CSFM: 7272-1653:152 ACCESSORIES: MEA:290-01-E 2W-MOD2: Two-wire loop test/maintenance module. Maryland State Fire Marshal: Permit # 2093 SENS-RDR: Sensitivity reader. A77-AB2: Retrofit adapter bracket, 6.6" (167.7cm) diameter. LED Modes Green LED Red LED Power Up Blink every 10 Blink every 10 seconds seconds Normal (Standby) Blink every 5 OFF seconds Out of Sensitivity OFF Blink every 5 seconds Freeze Trouble OFF Blink every 10 seconds Alarm OFF Solid ON Power Up Sequence for LED Indication Condition Duration Initial LED Status Indication 80 Seconds P'4 and Stop-Drop 'N LockTm are trademarks of Honeywell International Inc. 02009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. iso 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEENNG & 1111IUIFAC1UN All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161 FAX: (203) 484-7118. www.notifier.com Page 2 of 2 - DN-6885:A2 • 11/17/09 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION ....... OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-1653:0152 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Models 2W-B, 2W1-B, 4W-B and 4W1-B photoelectric type smoke detectors. Models 2W-B and 2W1-B are 2-wire and model 4W-B and 4W1-B are 4-wire detectors. Models 2W1-B and 4W1-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental to the detector and is not intended for use as a required heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 8.5 - 35 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling mount. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mm. NOTE: Formerly 7272-1209:210 06-20-05 This sting is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division NOTI Fill ER® by Honeywell Dual Action NBG-12LR SYSTEM SYSTEM NORMAL ACTIVATED 0 0 0 0 TO ABORT - HOLD IN dn-6840:a NBG-12LR and NBG- 12LRA Dual-Action Agent Release Stations General The NBG-12LR and NBG-12LRA are Agent Release Stations designed for use with NOTIFIER Fire Alarm Control Panels with releasing capabilities and RP Series Releasing Systems. Features Non-coded, dual-action operation. Made with durable polycarbonate. Optional surface backbox. NBG-12LRA INCLUDES: Abort switch. Power-on indication. Released indication. Manual release (dual-action). NBG-12LR INCLUDES: Dual-action release only. Applications The NBG-12LRA and NBG-12LR are ideal for areas such as clean rooms and computer rooms where a chemical agent is used to extinguish a fire. Product Line Information NBG-12LRA: Agent release station with abort switch, Release LED, Normal LED. NBG-12LR: Dual-action agent release station. SBA-10: Surface backbox for NBG-12LRA, metal. Dimensions 4.5" (11.43 cm) W x 8.188" (20.8 cm) Lx 1.375" (3.49 cm) D. SB-10: Surface backbox for NBG-12LR, metal. Dimensions 4.125" (10.48 cm) W x 5.5" (13.97 cm) Lx 1.375" (3.49 cm) D. SB-I/O: Surface backbox for NBG-1 2LR, plastic. BG12TR: Optional trim ring for semi-flush mounting. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in progress. Consult fac- tory for latest listing status. UL/ULC Listed: S692 MEA Listed: 67-20-E FM Approved CSFM: 7150-0028:0199 U.S. Coast Guard: 161.002/23/3 (AFP-200: NBG-12LRA), 161.002/42/1 (NFS-640: NBG-12LRA), 161.002/27/3 (AFP1 010/AM2020). FDNY: #6058 (NFS2-3030), #6038 (NFS2-640) Dual Action NBG-12LR (shown activated) dn-6840:a • 3/4/1C - Page 1 of 2 Wiring ------------ 24 VDC: I N.O.: ------------- Release Relay C B System Operated LED (Red) I 10K 1/4W System Normal LED (Green) 10K 1/4W N.O. Abort Switch D TO Abort 10K,114W Circuit E Resistors (+) 2 To Manual Release (-) I * Circuit 4 10K,1/4W Resistors Mount End-of-Line Resistor on the last unit. Mount 4.7K ELR on the last unit when abort switch and manual release switch are connected to control panel circuits. Mount 47K resis- tor on last unit when abort switch and manual release switch are connected to monitor module or control module. Refer to control panel manual for the listed ELR. Refer to the product installation documentation for connection to the control panel A BiT Notifier® and FlashScan® are a registered trademark of Honeywell International Inc. Bayblend® is a registered trademark of Bayer Corp. 02010 by Honeywell International Inc. All rights reserved. Unauthorized use NBG-I2LRA (Rear view) Agent Release Pull Station of this document is strictly prohibited. iso 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. g We cannot cover all specific applications or anticipate all requirements. GlNffRlNC & IIIINFACENNI All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203)484-7161, FAX: (203)484-7118. www.notifier.com Page 2 of 2 - dn.6840:a • 8/4/10 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION ....-...... OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-0028:0199 Page 1 of 1 CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com DESIGN: Models NBG-12, NBG-125, NBG-I2LR, NBG-12LRA, NBG-12LAO, NBG-12LAOB, NBG-12-LO, NBG-I2LOB, NBG-12W, NBG-12LW, NBG-12NC, NBG-12WP, NBG-12LWP, NBG-12L, NBG-I2LX, NBG-12LA, NBG-12P5, NBG-12LSP, NBG-12LPS, NBG-12LPSP, NBG-12SP, NOT-BGI2LX, NBG-I2LXSP, NBG-12LXBL and NBG-12LXP fire alarm pull boxes. All units except Model NBG-12S are dual action pull stations. Models NBG-12LR and NBG-I2LRA are intended for agent releasing device. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Models NBG-I2WP, NBG-I2LW, NBG-12W, NBG-12LWP, NBG-12LAO, NBG-12LO, NBG-12LAOB and NBG-12LOB are intended for outdoor use when installed with Models WBB, . SB-I/O, or WP-1 0 back box. Refer to listee's Installation Instruction Manual for details. These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and California amendments which the controls and operating mechanisms required to be operable at no more than 51bs. force with one hand and shall not require tight grasping, pinching, or twisting of the wrist. *corrected 10-08-12 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not S an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Page 21 MX-1230 FIRE SUPPRESSION SYSTEM July 2011 Abort Switch The abort switch is designed to be wired to the abort terminals of a listed releasing panel. The switch consists of a stainless steel faceplate and a modular switch assembly. It is designed to mount on a standard double gang electrical enclosure. The switch is designed for indoor use only. Technical Data Material.........Stainless steel faceplate Dimensions.. ..4 1/2 in. W x 4 1/2 in. H x 2 in. Deep Contact Rating.. ..One N.O. momentary contact rated at 2.5 amps @ 24 VDC (5 mA minimum) Listings/Approvals UL Listed ULC Listed fo FM Approved Shipping Assembly Part No. Description 17120 Abort Switch Assembly L-1 0~'~> ~ \EOLR FROM RELEASING PANEL DWG, #1136-I Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 . http://www.minimaxfp.com MX-200 FIRE SUPPRESSION SYSTEM Page 22 Releasing Circuit Disable Switch (RCDS-1) The Release Circuit Disable Switch (RCDS-1) consists of a stainless steel faceplate, green LED, amber LED, and switch assembly. It is designed to mount on a standard single gang electrical enclosure. The switch is designed for indoor use only. The connection for the supervisory circuit has 4 wires: 2 yellow and 2 gray. " The 2 yellow wires are for connection to the supervisory circuit. The 2 gray wires are for connection to additional supervisory devices or the EOLR for the supervisory zone. I Technical Data Material.........Stainless steel faceplate Dimensions.. ..2 % in. W x 4 1/2 in. H x 2 in. Deep Contact Rating.. ..1 AMP @ 40 VDC Power Requirements.. ..24 VDC, 10 mA Temperature Range.....-22 OF to 140 OF (-30 °C to 60 °C) Listings/Approvals UL Listed ULC Listed Shipping Assembly Part No. Description 17121 Releasing Circuit Disable Switch Assy Application The RCDS-1 complies with NFPA 72: - Specifying a physical switch to disconnect the release circuit in place of a software controlled disconnect. - Creating a supervisory condition on the associated release panel. Installation Connect the red and black leads to the 24 VDC auxiliary power terminals on the panel. Be certain to observe polarity. Connect the yellow wires to the supervisory zone on the panel. 21 VDC SUPERVISORY RELEASING ZONE CIRCUIT Operation 0 RED o I LED 'S BLACK The green LED indicates the RCDS YELLOW is in the normal condition and the \ YELLOW release circuit is enabled. The amber k, ju BLUE LED indicates that the release circuit KEY 3NNITCH is disabled. BLUE BLACK \\ GRAY DIODE -GRAY ASSY DWG=2 14-i Minimax USA LLC ... 4030 East Quenton Dr ... Suite 112 ... Mesa, AZ 85215 Ph: 480-553-5670... Fax: 480-553-5701 . . . http://www.minimaxfp.com RELEASING SOLENOID SYSTEM SENSOR Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrA lert@ Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. Features Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela Field-selectable candela settings on wall units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and three volume selections Universal mounting plate for wall units Mounting plate shorting spring checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert devices Compatible with MDL sync module Listed for ceiling or wall mounting SPECTRAert The SpectrAlert Advance series ofrers the mst versatile and easy-to-use line of horns, strobes, and h:n strobes n the industry. With white and red plastic housings, wal and ceiling mounting options, and plain and FIRE-printed devices, SpecfrAlert Advance can meet virtually any application requirement. Like th3 entire SpectrAlert Advance product line, wal-rnount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifyig installa:icn. All devices feature plug-in designs with minimal intrLsion into te back box, makinç installations fast and foolproof wh:ie virtually eliminating costly and time-consuming ground faults.. To furtt-er simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal m.'n7ing plate with an onboard shorting spring, so instaers can tes: w!ing continuity before the device is installed. lnstalle-s can also easily adapt devices tc a suit a v' c-a range of application requirements using field-selectable can :ea settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horr tones with three volume selectiors. Agency Listings SIGNALING ZMEA LISTED approved PP 7125-1653.166 (indoor strobes) APPROVED 7126-1653:168 (trots strobes. S4011 (ctsmes. horn strobes. horns) 3023572 MEM52-05-E chime strobes) S5512 (strobes) 7135-1653:169 (horns, chirrres) SpectrAlert Advance Specifications General SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync.Circuit° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns Is on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also control two Style V (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications; —f1Jk Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17,5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6" L x 4.7"W x 25" D (142 mm L x 119 mm W x 64 mm 0) Horn Dimensions 5.6"L x 4.7"W x 1.3"D (142 mm Lx 119 mm W x 33 mm D) Wall-Mount Back Box Skirt Dimensions (BBS-2, BBSW-2) 5.9'L x 5.0'W x 2.2'D (151 mm Lx 128 mm W x 56 mm 0) Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS,TRW- 5.7"L x 4.8"W x 0.35"D (145 mm Lx 122 mm W x 9 m D) HS) Notes: Full Wave Rectified (F\NR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. P. 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. S AVOSCXJ1O UL Current Draw Data 8-17.5 Volts 16-33 Volts 8-17.5 Volts 18-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA DC Input RMS), 2-Wire 8-17.5 Volts 15 Horn 15/75 Strobe, Standard 16-33 Volts 15 Candela Range (15-115 15/75 30 cd) 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low UL max. current Draw (mA DC Input 132 RMS), 2-Wini: 16-33 Volts 135 150 154 Horn Strobe, 177 80 High Candela 185 90 105 Range (135486 cd) FWR Input 161 184 16-33 Volts 135 150 202 177 211 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temooral Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output (dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 2 3 Temporal Temporal Temporal High Medium Low 78 74 71 78 74 73 84 80 76 84 80 76 88 86 83 88 86 80 99 96 94 98 96 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 7T Coded High 82 82 88 88 93 92 101 101 81 Coded Medium 78 78 85 85 90 90 97 98 91 Coded Low 75 75 81 81 88 85 96 92 tSettings 7, 8, and 9 are not available on 2-wire horn strobes. AVDSOO6OI SpectrAlert Advance Dimensions n 5.05" r 2.23'1' .11 Wall-mount horn strobes Wall back box skirt SpectrAlert Advance Ordering Information Wall Horn Strobes Horns P2Rwt 2-Wire Horn Strobe, Standard cd, Red HR Horn, Red P2RH* 2-Wire Horn Strobe, High cd, Red HW Horn, White P2W* 2-Wire Horn Strobe, Standard cd, White Accessories P2WH* 2-Wire Horn Strobe, High cd, White BBS-2 Back Box Skirt, Wall, Red P4R* 4-Wire Horn Strobe, Standard cd, Red BBSW-2 Back Box Skirt, Wall, White P4RH 4-Wire Horn Strobe, High cd, Red TR-HS Trim Ring, Wall, Red P4W 4-Wire Horn Strobe, Standard cd, White TRW-HS Trim Ring, Walt White Wall Strobes SR*i Strobe, Standard cd, Red SRH*t Strobe, High cd, Red SW* Strobe, Standard cd, White SWH* Strobe, High cd, White Notes: * Add "-P' to model number for plain housing (no "FIRE" marking on cover), e.g.. P2R-P. t Add "-SF' to model number for "FUEGO" marking on cover, e.g., P2R-SP. "Standard cd" refers to strobes that include 15. 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd" refers to strobes that include 135, 150, 177, and 185 candela settings. "\ S)'STEII7 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to ch g vithoutnOU(.e.ViSits~,.qtemsen=.com ©2012 System Sensor. SENSOR' Phone 800-SENSOR2 • Fax: 630-377-6495 fO( current product intormaon, inctuding ee Iatestversion o thisdata sheet AVDS0 0 601 • 3/12 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1653:0186 Page 1 of 1 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Synchronous type strobe lights, Models SR, SRH, SW, SW-CLR-ALERT, SWH, SCR, SCRH, SCW, SCW-CLR-ALERT and SCWH followed by the suffix -P, -SP, -PG, or none. Intended for indoor use mounted on the wall or the ceiling. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 8-17.5 or 16-33 VDC/FWR Candela: 15, 15/75, 30, 75, 95, 110, 115, *135, *150, *177 *185cd INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as strobe lights suitable for hearing impaired application when used with separately listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted. 4W Refer to listee's Installation Instruction Manual for details. *Rev. 03-11-10fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not . an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM to LISTING SERVICE LISTING No. 7125-1653:0188 Page 1 of 1 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Models CHSR and CHSW Chime/Strobes. Models P2R, P2W, P2RH and P2WH Horn/Strobes two-wire type, rectangular enclosure. Models PC2R, PC2W, PC2RH and PC2WH Horn/Strobes two-wire type, round enclosure Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure. Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure. All models are intended for indoor use only unless other wise indicated. Models may be followed by the suffix "K" indicating indoor or outdoor use, or may be followed by suffix "P' for plain housing with no lettering. "K" suffix models are suitable for outdoor applications at temperatures from -40°F to +151°F (-40°C to +66°C) and are rated NEMA 4X when used with the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall), SA-WBBC (Ceiling) and *SA.IBCW (Ceiling). Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Standard Horn/Strobes and Chime/Strobes 8- 17.5 or 16-33 VDC/FWR Hi CD Horn/Strobes 16-33 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling appliances and equipment for the hearing impaired applications when used with separately listed compatible fire alarm control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall mount. Chime section is suitable for private mode and indoor use only. Horn/Strobes or chime/strobes* can generate the distinctive three- pulse audible Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2010 Edition. Refer to listee's Installation Instruction Manual for details. "Corrected 12-15-11 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division SYSTEM $ SENSOR Audible Visible Accessories System Sensor offers a wide range of Audible Visible (A V) accessories to enable you to meet a variety of application requirements. Features MP120K Mounting Plate Designed for both indoor and outdoor use Plug-in design eliminates ground faults Power supply that converts 120 VAC to nominal 24 V FWR Compatible with all two-wire SpectrAlert Advance® devices Color Lens Attachments Easily turns any device into a strobe for ECS, severe weather, sprinkler activation and more Outdoor rated from —35°F to 151°F Wall- or ceiling-mount lenses available UL 1638 listed WTP Weatherproof Plates Enables flush mounting of outdoor devices to brick, ceramic tile, concrete, and masonry brick Weatherproof per NEMA 3R For use in both indoor and outdoor applications For use with all K series (outdoor) products replacement -R models Universal mounting plate easily attaches to the weatherproof plate Agency Listings ®!!J MEA LISTED U approved 54011 7300-1653:195 582-06-E 83593 7300-1653:204 The MPI 20K Mount ing Plate is designed to use 120 VAC to power SpectrAlert Adsnce horns, strobes, horn strobes, chimes, and chime strobes. Color Lens Attachments install easily on any indoor or outdoor SpectrAlert Advance slrobe devices to provide distinctive visual signaling. WTP Series Weatherproof Plates enable installers to flush mount outdoor horns, strobes, horn strobes, speakers, and speaker strobes to a variety ot wall surfaces, including brick, ceramic tile, concrete, and masorsry brick. These NEMA 3R-rated plates come in red and white to 5L ! aesthetic and functional requirements. They may be used indoors r outdoors (with outdoor devices), as required by conditions. They Essily attach to the SpectrAlert Advance universal mounting p ste. Trim Rings for spea'kers and speaker strobes allow for additional space within the bac'- box. Trim rings for horns, strobes, and horn strobes allow 4-wire cevices to mount to a single-gang back box. SpectrAlert Advar.ce Outdoor Back Boxes ensure a NEMA 4X watertight listing for AV devices. In locations where a SpectrAlert Advance device is sijface mounted, Back Box Skirts are the best solution to mask the back box. Retrofit Plates cover paint outlines on the wall when replacing legacy SpectrAlert Advance products. SpectrAlert Advance DECALS are for use on our non-pad printed wall- and ce:1g-mount devices. Each decal comes with AGENT, EVAC, ALER, or FIRE label options. The Sync-Circuit Module synchronizes SpectrAlert Advance strobes at 1 Hz and horns and chimes at iomporal 3 over a single pair of wires. Patented module technology also allows the silencing of horns or chimes on horn strobe and chime strobe models over a pair of wires. See Datasheet A05-1007-905 for more information. Specifications 120 VAC mounting plate model MP12OK shall be listed to UL 464 for fire protective signaling systems. The mounting plate shall power a two-wire SpectrAtert® Advance horn, strobe, horn strobe, chime or chime strobe from a 120 VAC supply converted to nominal 24 V FWR. For indoor applications, the mounting plate shall be installed in a 4x4x21/8 -inch junction box. For outdoor applications, the mounting plate shall be installed using the proper SpectrAlert Advance outdoor weatherproof back box and outdoor listed notification appliance. Compatibility MP120K may be used with any of the following products at all horn and strobe settings: P2R, P2RH, P2RK, P2RHK, P2W, P2WH. SR, SRH, SRK, SRHK, SW, SWH, FUR, PC2RH, PC2RK, PC2RHK, P02W, PC2WH, SCR, SCRH, SCRK, SCRHK, SOW, SCWH, HR, HRK, F-lW, SR-F, SW- F, SRH-P, SWH-P, P2R-P, P2W-F, P2RH- P2WH-P, SCR-P, SOW-F, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P, SR-SF, SRH-SP, P2R-SP, P2RH-SP, SOW-SF, SCWH-SF, P02W-SF, PC2WH-SP, CHA, CHW, CHSR, CHSW. -PhysicaMperating Specifications Standard Operating Temperature -40°F to 151°F (-40°C to 66°C) Humidity Range 10 to 93% non-condensing (indoor products) Nominal Voltage Regulated 120 VAC Operating Voltage Range 96-132 VAC Current Draw From AC Line 150 mA max. i Weatherproof R(* The SpectrAlert Advance weatherproof plate for horns, strobes, and horn strobes shall mount to 4x4x11/4-inch and 2x4x11/2-inch back boxes. The weatherproof plate for speakers and speaker strobes shall mount to 4421/8-inch back boxes. The weatherproof plate may be installed on brick, concrete, ceramic tile, and masonry brick and must be used with System Sensor "K" series outdoor replacement models (-R). Outdoor SpectrAlert Advance products shall operate between -40°F and 151°F. -Physical Specifications Speaker Strobe 7.25" L x 6.26" W x 3.00" 0 (including speaker and lens) Speaker 7.25" L x 6.26" W x 1.30" 0 (including speaker) Horn Strobe 6.90" Lx 5.90" W x 2.80" D (including strobe lens) Horn 6.90" L x 5.90" W x 1.60" D (including horn) Note: WTP and WTPW are compatible with 4x4x1 1/4-inch and 2x4x1 1/2-inch back boxes. (Compatible with outdoor horns, horn strobes and . strobes) WTP-SF and WTF-SFW are compatible with 4421/8-inch back boxes. (Compatible with outdoor speakers and speaker strobes) lModels 1l1t r Use withWatertight WTPIWTPW HRK-R WTP/WTPW SRK-R, SRHK-R, SWK-R, SWHK-R WTP/WTPW P2RK-R, P2RHK-R, P4RK-R, P2WK-R, P2WHK-R WTP-SP SFRK-R, SPWK-R WTP-SPW SPSRK-R Note: -R models ship without the outdoor back box. The weatherproof mounting plates are designed to be used only with -R replacement models. AVDSW4O I Specifications .0 The System Sensor SpectrAlert Advance color lens attachments shall be approved for fire protective service as listed in UL 1638. The lens attachments shall only be used with non-FIRE-printed System Sensor strobe devices. The lens shall mount to any wall- or ceiling-mount strobes and shall be rated from —35°F to 151°F. Color lens attachments may be used with the following System Sensor plain (non-FIRE-printed) indoor or outdoor strobe models: SR-P, SRH-P, SW-F, SWH-P, 1`213-P. P2W-F, P2WH-P, P2RK-F, P2RHK-P, SOW-F, PC2R-P, P02W-F, PC2WH-P, SPSW-F, SPSR-P, SPSWH-F, SPSRH-F, SPSWV-F, SPSRV-P, SPSCW-P, SPSCWH-P, SPSCWV-P, SPSCWVH-P, SRK-P, SRHK-P, SWK-P, SWHK-F, P2WK-P, P2WHK-P, SPSWK-P, SPSRK-F, SW-CLR-ALERT, SCW-CLR-ALERT, SFSCW-CLRALERT. Color Lens Installation Installation to Wall-Mount Strobe Installation to Ceiling-Mount Strobe Candela Rating for UL 1638 Light output of color lenses is measured per UL 1638, on axis, and is = derated. Candela Switch Setting On-Axis Candela Rating (1JL1638)—All Colors 15 15 15/75* NA 30 30 75 75 95 95 110 110 115 115 135 135 150 150 177 177 185 185 * 15/75 Candela setting not to be used with color lenses AVDSQ(i4O1 Ordering Information 0 Metal Weatherproof Backboxes Colored Colored Lenses LENS-13 LENS-A Wall-mount, blue Wall-mount, red MWBBW white, wall-mount, compatible with: SPWK-R, LENS-C Wall-mount, green SPWK, SPSWK-R, SPSWK-P, SPSWK LENS-A Wall-mount, amber MWBB red, wall-mount, compatible with: SPRK-R, LENS-BC Ceiling-mount, blue SPAK LENS-AC Ceiling-mount, red MWBBCW white, ceiling-mount, compatible with: SPCWK, LENS-GC Ceiling-mount, green SPSCWK,SPCWK-A, SPSCWK, SPSCWK-R, LENS-AC Ceiling-mount, amber SPSCWHK, SPSCWHK-A Decals SA-WBBW white, wall-mount, compatible with: P2WK, DECAL-A red, used for non-pad-printed wall-mount P2WHK, P2WHK-P, P2WK-P, SWK, SWK- devices. (10 total decals per box for 5 devices)* P,P2WHK-A, P2WK-R, SWHK-R DECAL-AC red, used for non-pad-printed ceiling-mount SA-WBB red wall-mount, compatible with: P2RK, P2RK-P, devices. (15 total decals per box for 5 devices)* P2RK-A, SAK, SAK-P, SAK-R P2RHK, P4AK, P4RHK, SRHK, HAK, P2AHK-A, P2AK-A, DECAL-W white, used for non-pad-printed wall-mount HRK-A, P4AHK-R, P4AK-R, SAHK-R devices. (10 total decals per box) for 5 devices* SA-WBBCW white, ceiling-mount DECAL-WC white, used for non-pad-printed ceiling-mount compatible with: PC2WK, SCWK devices. (15 total decals per box for 5 devices) SA-WBBW white, wall-mount, compatible with: P2WK, *All Decals include Labels: "AGENT, EVAC, ALERT & FIRE" P2WHK, P2WHK-P, P2WK-P, SWK, SWK- Retrofit Plates (For use with horn strobe & speaker strobe P,P2WHK-R, P2WK-A, SWHK-A devices) Back Box Skirts RFPW 9.5" x 7" white BBS-2 red, wall-mount, compatible with: P2R, SR, HA, RFP 9.5" x 7" red CHSR, CHR, P2RH, P4R, P4RH, SRH, P2R-P, P2RH-P, P4R-P, P4RH-P, SR-P, SRH-P, SR-SF, Mounting Plate SRH-SP, P2R-SP, P2RH-SP MP120K 120 VAC Adapter Mounting Plate BBSC-2 red, ceiling-mount, compatible with: PC2R, Sync Modules SCR, PC2RH, PC4R, PC2RHP, SCRH, PC2RP, MDL3W white, 12/24 volt Sync-Circuit module. SCR-P, SCRH-P MDL3A red 12/24 volt Sync-Circuit module BBSW-2 white, wall-mount, compatible with: P2W, SW, HW, CHSW, CHW, P2WH, P4W, P4WH, SWH, Trim Rings SW-ALERT, SWH-ALERT, SW-CLR-ALERT, SW- TA red, wall-mount for use with speaker devices P, SWH-P TRC red, ceiling-mount for use with speaker devices BBSCW-2 white, ceiling-mount, compatible with: PC2W, TRC-HS red, ceiling-mount for use with horn strobe SOW, PC4W, PC4WH, SCWH, SCW-SP, SCWH- devices SF, PC2W-SP, PC2WH-SP, PC2W-P, PC2WH-P, SCWH-P, SOW-F, SCWH TRCW white, ceiling-mount for use with speaker devices BBS-SP201W Surface-mount back-box skirt for the PF24V TACW-HS red, ceiling-mount for use with horn strobe (ExitPointiM Directional Sounder with Voice devices Messaging) TR-HS red, wall-mount for use with horn strobes devices SPBBS red, wall-mount, compatible with: SPA, SPSR, TRW white, wall-mount for use with speaker devices SPA V, SPSR-P, SPSRH , SPSR H-P TRW-HS white, wall-mount for use with horn strobe devices SPBBSC red, ceiling-mount, compatible with: SPCR, SPSCR Watertight Plates SPBBSW white, wall-mount, compatible with: SPW, SPSW, WTPW white, for use with horn, strobes & horn strobe SPWV, SPSW-CLR-ALERT, SPSW-ALERT, SPSWH, SPSWH-P, SPSWV, SPSWV-P devices SPBBSCW white, ceiling-mount, compatible with: SPCW, WTP red, for use with horn, strobes & horn strobe SPSCW, SPCWV, SPSCW-CLA-ALERT, devices SPSCW-P, SPSCWH, SPSCWH-P, SPSCWJ, WTP-SPW white, for use with speaker devices SPSCVWP, SPSCWVH, SPSCWVHP WTP-SP red, for use with speaker devices I SYSTEM 3825 02012 System Sensor. Ohio Avenue • St. Charles, IL 60174 4 SENSOR"Phone: po(Juctspecificarions subject to change wihinat notice. hio,tss'stemsenoOr.cn for current product information, including the latest version of this data sheet. 800-SENSOR2 • Fax 630-377-6495 AVDS0401 • 3112 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1653:0204 Page 1 of 1 CATEGORY: 7300-- FIRE ALARM CONTROL UNITACCESSORIES/MISC. DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Intl Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Models LENS-B, LENS-R, LENS-G, LENS-A, LENS-BC, LENS-RC, LENS-GC, and LENS-AC retrofit colored strobe lenses for non-fire applications with all System Sensor SpectrAlert Advance models having "-P' or "K-P' suffixes. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: LENS-B: blue rectangular lens LENS-R: red rectangular lens LENS-G: green rectangular lens LENS-A: amber rectangular lens LENS-BC: blue circular lens LENS-RC: red circular lens LENS-GC: green circular lens LENS-AC: amber circular lens INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, and UL label. APPROVAL: Listed as retrofit colored strobe lenses for use with listee's separately listed and compatible strobe lights for non-fire applications. For indoor or outdoor use. Refer to listee's Installation Instruction Manual for details. NOTE: Not approved for use as fire signaling devices for the hearing impaired. 10-17-08 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not . an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division DN-6910:A1 •J-200 SSM Series 0 Alarm Bells NOTIFIER® by Honeywell General System Sensor's SSM Series alarm bells are low-current, high-decibel notification appliances for use in fire and burglary systems or other signaling applications. They come pre-wired to reduce installation time, and also incorporate a polarized electrical design for use with supervision circuitry. With reliable performance, SSM Series alarm bells provide loud, resonant tones. They operate on 24 VDC and are motor- driven. SSM Series alarm bells offer simplified installation. For indoor use, SSM Series alarm bells mount to a standard 4" (10.16 cm) square electrical box. For outdoor applications, a WBB weatherproof backbox is used. Model shall be a SSM Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bell shall be no smaller than nominal 6" (15.24 cm), 8' (20.32 cm), or 10' (25.40 cm) (specify size) with an operating voltage of 24 VDC. Bells shall be suitable for surface or semi- flush mounting. Outdoor surface-mounted installations shall be weatherproof (using optional WBB weatherproof backbox); otherwise, bells shall mount to a standard 4' (10.16 cm) square electrical box having a minimum projection of 2.5" (6.35 cm). Bells shall be located as shown on the installation drawings or as determined by the Authority Having Jurisdic- tion. Bells shall be Listed for indoor/outdoor use by Underwrit- ers Laboratories, ULC (Canada), and the California State Fire Marshal, and approved by Factory Mutual and MEA. pg Agency Listings and Approvals These listings and approvals app to the modules specified in this document. In some :ases, certain modules or applications may not be listed by certain appwval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S4011 ULC Listed: C5549 MEA Listed: 331 -01-E FM Approved CSFM: 7135-1653:125 Ordering Information SSM24-6: 6" (15.24 cm) bell, 24 VDC, polarized, 82 dBA. SSM24-8: 8' (20.32 cm) bell, 24 VDC, polarized, 80 dBA. 55M24-8A: Canadian model of 3' bell above. SSM24-10: 10" (25.40 cm) bell, 24 VDC, polarized, 81 dBA. WBB: Weatherproof backbox. Features Approved for indoor or outdoor (with WBB backbox) use. Low current draw. High dB output. Three sizes available: 6" (15.24 cm), 8" (20.32 cm), and 10" (25.40 cm) diameter. 24 VDC models; polarized for use with supervision circuitry. Bells mount directly to standard 4" (10.16 cm) square elec- trical box. S Specifications Regulated voltage: 24 VDC. Operating voltage range: 116 to 33 VDC. Maximum Current: DC 31.1 mNFWR -53.5 mA. Operating temperature range: —31°F (-35°C) to +150°F (+66°C). Termination: provided with two sets of leads for in/out wiring. Service use: Fire Alarm, General Signaling, Burglar Alarm. Engineering and Architectural Specifications DN-6910:A1 .2/9/10—Page 1 0f2 02010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I is ISO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. I ENGINEEMNS awtitirnciurn All specifications are subject to change without notice. I QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 —DN-6910:A1 • 2/9/10 1~ CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7135-1653:0217 Page 1 of 1 CATEGORY: 7135--AUDIBLE DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Models SSM24-6, -8, -10 and 55V120-6, -8, -10 audible signal devices. Models are AC or DC powered and available in 6", 8" and 10" bells. Refer to listee's data sheet for detailed product description and operational considerations.The units may be employed outdoors when used with NEMA 3R weather resistant back box Model WBB. RATING: SSM24-6 Sound output: 82 dBA SSM24-8 Sound output: 80 dBA SSM24-10 Sound output: 81 dBA 55V120-6 Sound output: 85 dBA SSV120-8 Sound output: 82 dBA SSV120-10 Sound output: 82 dBA SSM Series Voltage Range: 16-33 VDC SSV Series Voltage Range: 96-132 VAC Temperature Range: -31°F to 150° F (-35°C to 66°C) S INSTALLATION: In accordance with listee's printed installation instruction, applicable codes & ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as audible devices for use with separately listed compatible fire alarm control units. If this appliance is required to produce a distinctive three- pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition, the appliance must be used with a fire alarm control unit that can generate the temporal pattern signal. Refer to manufacturer's Installation Manual for details. 07-30-10 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division