HomeMy WebLinkAbout2628 GATEWAY RD; 120; FPC2019-0135; PermitPERMIT REPORT
(_City of
Carlsbad
Print Date: 03/21/2022 Permit No: FPC2019-0135
Job Address: 2628 GATEWAY RD, # 120, CARLSBAD, CA 92009 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2132621900 Track #: Applied: 06/12/2019
Valuation: $101,473.45 Lot #: Issued: 07/01/2019
Occupancy Group: Project #: Finaled Close Out: 05/25/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: BANTAMS ROOST -REVISED PLANS SPRINKLER TI (16 HEADS)
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
FIRE Plan Review Per Hour - Office Hours $136.00
Total Fees: $689.00 Total Payments To Date: $689.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
Sully Fire Protection
1975 Spanish Oak Way
Vista, California
Cl6 701590
HYDRAULIC CALCULATIONS
FOR
Exterior Dining Area
Bantam's Roost
2628 Gateway Road, Suite 120
Carlsbad, California 92009
FILE NAME: Bantam's Roost 2.sdf
DATE: August 1, 2019
-Design Data-
OCCUPANCY CLASSIFICATION: Light Hazard
DENSITY: 0.10 gpm/ft2
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS FLOWING:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose):
FLOW AND PRESSURE REQUIRED BOR:
PRESSURE AVAILABLE AT BOR:
SPRINKLER ORIFICE SIZE:
Notes:
All sprinklers
LB = 225 ft2 maximum
4 sprinklers
131.8 gpm
231.8 gpm
131.8 gum @51.7 psi
61.8 psi
Restaurant seating area meets the definition of a light hazard occupancy, per NFPA 13, §5.2,
A.5.2.2 (14).
Extended coverage horizontal sidewall sprinklers provided, meeting minimum flow and
pressure requirements of 32.0 gum @ 32.7 psi for each flowing sprinkler, per manufacturer's
data sheet for coverage area of 18' x 18', with sprinkler deflector 4" - 12" below ceiling.
Available pressure and flow based on hydraulic calculation sign for existing system, designed
for Ordinary Hazard Group 2, 0.20 gpm/ft2 , remote area 1,500 W. Sign shows flow and
pressure required at base of riser is 423.78 gum @ 61.773 psi. This was used to establish
supply data.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 8/1/2019 C:\HASS FILES\BANTAM'S ROOST 2.SDF
JOB TITLE: Exterior Dining Area
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
BRE 62.0 61.3 423.0 61.8 231.8 51.7
Available pressure is 10.0 psi (16%) greater than required pressure.
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 231.8 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 131.8 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 11.5 K= 5.60 32.7 32.0
2 11.5 K= 5.60 35.0 33.1
21A 11.5 - - - - 44.9 - - -
3 11.5 K= 5.60 35.4 33.3
4 11.5 K= 5.60 35.2 33.2
2A 11.0 - - - - 45.0 - - -
3A 11.0 - - - - 45.0
4A 11.0 - - - - 45.0 - - -
16 11.0 - - - - 46.0 - - -
21 11.0 - - - - 46.0 - - -
22 11.0 - - - - 46.2 - - -
B2 11.0 - - - - 46.1 - - -
B1 11.0 - - - - 46.1 - - -
TRE 11.0 - - - - 46.9
BRE 0.0 SOURCE 51.7 131.8
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 8/1/2019 C:\HASS FILES\BANTAM'S ROOST 2.SDF
JOB TITLE: Exterior Dining Area
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -32.0 1.049 PL 22.00 PF 12.1
1 11.5 5.6 32.7 32.0 11.9 120 FTG 6ET PH 0.2
2A 11.0 0.0 45.0 0.0 0.311 TL 39.00 PV
Pipe: 2 -33.1 1.049 PL 16.75 PF 9.8
2 11.5 5.6 35.0 33.1 12.3 120 FTG 4ET PE 0.0
21A 11.5 0.0 44.9 0.0 0.331 TL 29.75 PV
Pipe: 3 -33.3 1.049 PL 12.83 PF 9.3
3 11.5 5.6 35.4 33.3 12.4 120 FTG 5ET PE 0.2
3A 11.0 0.0 45.0 0.0 0.335 TL 27.83 PV
Pipe: 4 -33.2 1.049 PL 13.99 PF 9.6
4 11.5 5.6 35.2 33.2 12.3 120 FTG SET PH 0.2
4A 11.0 0.0 45.0 0.0 0.333 TL 28.99 PV
Pipe: 6 -32.0 1.740 PL 28.00 PF 1.0
2A 11.0 0.0 45.0 0.0 4.3 120 FTG T PE 0.0
16 11.0 0.0 46.0 0.0 0.026 TL 37.80 PV
Pipe: 7 -33.3 1.740 PL 28.00 PF 1.1
3A 11.0 0.0 45.0 0.0 4.5 120 FTG T PH 0.0
Hi 11.0 0.0 46.1 0.0 0.028 TL 37.80 PV
Pipe: 8 -33.2 1.740 PL 26.00 PF 1.0
4A 11.0 0.0 45.0 0.0 4.5 120 FTG T PH 0.0
B2 11.0 0.0 46.1 0.0 0.028 TL 35.80 PV
Pipe: 9A -33.1 1.740 PL 25.00 PF 1.0
21A 11.5 0.0 44.9 0.0 4.5 120 FTG T PE 0.2
21 11.0 0.0 46.0 0.0 0.028 TL 34.80 PV
Pipe: 10 -32.0 3.316 PL 10.00 PF 0.0
16 11.0 0.0 46.0 0.0 1.2 120 FTG ---- PE 0.0
21 11.0 0.0 46.0 0.0 0.001 TL 10.00 PV
Pipe: bA -65.2 3.316 PL 5.00 PF 0.1
21 11.0 0.0 46.0 0.0 2.4 120 FTG T PH 0.0
22 11.0 0.0 46.2 0.0 0.004 TL 24.70 PV
Pipe: 11 66.6 3.316 PL 1.00 PF 0.1
22 11.0 0.0 46.2 0.0 2.5 120 FTG T PE 0.0
BI 11.0 0.0 46.1 0.0 0.004 TL 20.70 PV
Pipe: 12 33.2 3.316 PL 9.50 PF 0.0
Bi 11.0 0.0 46.1 0.0 1.2 120 FTG ---- PH 0.0
B2 11.0 0.0 46.1 0.0 0.001 TL 9.50 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 8/1/2019 C:\HASS FILES\BANTAM'S ROOST 2.SDF
JOB TITLE: Exterior Dining Area
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 131.7 3.316 PL 33.00 PF 0.8
TRE 11.0 0.0 46.9 0.0 4.9 120 FTG 2E PE 0.0
22 11.0 0.0 46.2 0.0 0.016 TL 48.00 PV
Pipe: 14 131.8 4.316 PL 15.00 PF 0.1
BRE 0.0 SRCE 51.7 (N/A) 2.9 120 FTG ---- PE -4.8
TRE 11.0 0.0 46.9 0.0 0.004 TL 15.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2016)
under license no. 50110279 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.032 gpm and a maximum
imbalance at any node of 0.453 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.4 ft/sec at pipe 3.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node BRE under full flow conditions is
61.73 psi with a flow of 245.23 gpm.
PIPE FITTINGS TABLE
User Pipe Table Name: KEN CUSTOM.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 8/1/2019 C:\HASS FILES\BANTAM'S ROOST 2.SDF
JOB TITLE: Exterior Dining Area
PAGE: A MATERIAL: 40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli T LngEil ChkViv BfyViv GatViv AimChk DPVlv BlHdTe --------------------------------------------------------
R K
TeeRun TeeRun
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00
2.00 2.00
PAGE: Y MATERIAL: Mega-Flow HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee 45 Check BtrFly GateVi
1.740 3.90 9.80 0.00 0.00 0.00 0.00 0.00 0.00
3.316 7.50 19.70 0.00 0.00 0.00 0.00 0.00 0.00
4.316 9.60 22.70 0.00 0.00 0.00 0.00 0.00 0.00
P
R
E
S
S
U
R
E
80.0
70.0
G
A
u 60.0 A
G
E
50.0
40.0
30.0
20.0
10.0
P
0.0
p
S
I
WATER SUPPLY ANALYSIS
Static: 62.00 psi Resid: 61.27 psi Flow: 423.0 gpm
-14.7
Note: (1) Dashed Lines indicate extrapolated values from Test Results
(2) On Site pressures are based on hose stream deduction at the source
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 8/1/2019 C:\HASS FILES\BANTAM'S ROOST 2.SDF
JOB TITLE: Exterior Dining Area
WATER SUPPLY CURVE
72+
66+
*\\\Q\\\\\\\\* <-61.3 psi @ 423 gpm
60+ Flow Test Point
54+
X
P 48+
R I
E I
S I
S 42+
U
R I
E I
36+
P I
S
I 30+
24+
18+
12+ LEGEND
'p
I X = Required Water Supply
I 51.74 psi 8 231.8 gpm
6+
I 0 = Available Water Supply
61.76 psi 8 231.8 gpm
-------+------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
17
SERIES GL-QRIECLH!SW
EXTENDED COVERAGE
RECESSED
HORIZONTAL SIDEWALL
QUICK RESPONSE
EXTENDED COVERAGE
LIGHT HAZARD
A U TOMA TiC SPRiNKLERS
GL5628
HORIZONTAL SIDEWALL
RECESSED HORIZONTAL SIDEWALL
DESCRIPTION AND OPERATION
The Globe Quick Response GL5628 Extended Coverage Hori-
zontal Sidewall Sprinkler is a low profile yet durable design which
utilizes a 3m frangible glass ampule as the thermosensitive element.
This provides sprinkler operation approximately six times faster than
ordinary sprinklers. While these Quick Response Sprinklers provide
an aesthetically pleasing appearance, they can be installed wherever
standard extended coverage horizontal sprinklers are specified; but
offer the additional feature of greatly increased safety to life. Quick
Response Sprinklers should be used advisedly and under the direc-
tion of approving authorities having jurisdiction, in accordance with
their listings and in accordance with NFPA 13.
The heart of Globe's Series GL-QR sprinkler proven actuating as-
sembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At
the prescribed temperature the internal pressure within the ampule
exceeds the strength of the glass causing the glass to shatter. This
results in water discharge which is distributed in an approved pattern.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C)
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze • Deflector - brass • Screw - brass
Bulb seat - copper • Spring - nickel alloy 'Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
Escutcheon Assembly - steel
SERIES GL-QRIECLH/SW
EXTENDED COVERAGE
HORIZONTAL SIDEWALL
*SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
A CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR I N.F.P.A. MAXIMUM CEILING
TEMPERATURES TEMPERATURE
ORDINARY 1351th5F 7°CI68° ORANGE/RED r 100F 38C
INTERMEDIATE V 175Fi2r r 7CIJ3'C YELLOW/GREEN 150T
MAR 2019 GFS-220 (Formerly A-44)
ADJ. RECESSED ESCUTCHEON PART NUMBERS
FRICTION FIT THREADED
WHITE CHROME WHITE CHROME
325426-W 325422 329308-W 329306
RJ
12' MX
2' MIN. DIA
ORDERING INFORMATION
SPECIFY
° Quantity o SIN Style o Orifice
° Thread Size 'Temperature • Finishes desired
° Quantity - Wrenches - P/N 325390
Quantity - Recessed Escutcheons
Quantity - Recessed Wrenches - P/N 325391
Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
MAR 2019
QuicK RESPONSE
EXTENDED COVERAGE LIGHT HAZARD
AUTOMATIC SPRINKLERS GL5628
HORIZONTAL SIDEWALL ° RECESSED HORIZONTAL SIDEWALL
SPECIFICATIONS AND APPROVALS
SIN NOMINAL NOMINAL THREAD SIZE LENGTH FINISHES cULus
Factory Bronze
GL5628 5.6 (80 metric) 1/2°NPT
(15mm)
2 1/2"
(6.4cm)
Chrome
White Polyester'
Black Polyester' .2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'FINISHES AVAILABLE ON SPECIAL ORDER.
2AVAILABLE AS cULus LISTED AS CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
cULus LISTING DESIGN - USE REQUIREMENTS FOR LIGHT HAZARDS ONLY
SIN STYLE
TEMPERATURE MAX. AREA OF
COVERAGE
WIDTH x LENGTH
Feet (Meters)
MIN.
PRESSURE
PSI (bars)
MIN.
FLOW
G.PM.
(Umin.)
DEFLECTOR
TO CEILING
DISTANCE
inches (mm)
MIN. DISTANCE
BETWEEN
SPRINKLERS
Feet (Meters)
135°F
(57°C)
155°F
(68°C)
175°F
(79°C)
200°F
(93°C)
GL5628
HORIZONTAL
SIDEWALL
X X X X 16(4.9) x 16(4.9) 21.6(l.49) 26(98)
4 (102)
to
12(305)
32 (125)
8(2.4)
x X X X ° 16(4.9) x 18(5.5) 26.8(l.85) 29(110)
x - X - 16 (4.9) x 20 (6.1) 32.7 (2.25) 32 (125)
X X I X X** 18(5.5) x 18 (5.5) 32.7(2.25) 32 (125)
RECESSED-
HORIZONTAL
SIDEWALL
X - X - X
-
X 16(4.9) x 16(4.9) 21.6 (1.49) 26(98)
X X X X'" 16(4.9) x 18(5.5) 26.8 (1.85) 29(110)
X - - - 16(4.9) x 20 (6.1) 32.7 (2.25) 32 (125)
X X X X° 18 (5.5) x 18 (5.5) 32.7 (2.25)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM FLOW FOR
THE NEXT HIGHEST COVERAGE AREA FOR WHICH DESIGN CRITERIAARE STATED.
**200F (93" C) LISTED AT 4" (102) TO 6" (152) CROSS SECTION DEFLECTOR DISTANCE FROM CEILING
Ir
RETAINER
118' MIN. 1"MIN. 118' MX. 13/4' MAX
(314") ADJUSTMENT RECESSED
HORIZONTAL SIDEWALL
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U.S.A. GFS-220 (Formerly A-44)