CUT SHEETS FOR:
ANSUL, R-102, FIRE SUPPRESSION SYSTEM
FOR A RESTAURANT KITCHEN HOOD & DUCT
PROJECT INFO:
St. Michael's By-the-Sea Episcopal Church
2775 Carlsbad Blvd.
Carlsbad, CA 92008
Job No. 11 MJJ2569F
DESIGN BY:
Luis C. Gonzalez
(System Designer)
858-495-2364
ANSUL DESIGN
INSTALLATION
RECHARGE AND
MAINTENANCE
MANUAL
R-102 RESTAURANT
FIRE SUPPRESSION
SYSTEM
(Standard UL 300 Listed)
S
'a
REVISION INDEX
UL EX3470 ULC EX3470 Page 6
REV. 0 7-1-09
DATE PAGE REV. NO. DATE PAGE REV. NO.
7-1-09 6-1 3
7-1-09 6-2 3
7-1-09 6-3 4
7-1-09 7-2 6
7-1-09 7-3 5
7-1-09 7-4 3
7-1-09 8-1 8
7-1-09 8-2 4
7-1-09 8-3 5
7-1-09 8-4 6
7-1-09 8-5 5
7-1-09 8-6 5
7-1-09 8-7 5
7-1-09 8-8 2
7-1-09 8-9 New
7-1-09 8-10 New
7-1-09 9-1 6
7-1-09 9-5 6
7-1-09 9-6 7
7-1-09 9-6.1 5
7-1-09 9-6.2 3
7-1-09 9-7 4
7-1-09 9-10.1 4
7-1-09 9-12 4
7-1-09 9-13 New
7-1-09 9-14 New
--7 F-
Indicates revised information.
Indicates change in page sequence.
SECTION II - SYSTEM DESCRIPTION
UL EX3470 ULC EX3470 Page 2-1
7-1-09 REV.4
TOTAL SYSTEM
There are four types of R-102 Restaurant Fire Suppression
Systems:
Single-tank System
Double-tank System
Three-tank System (1 Cartridge)
Multiple Tank System (Three Tanks or More - Multiple
Cartridges)
The type of system required for the particular installation will be
determined through the guidelines covered in "System Design."
Additional equipment which may be required to complete the sys-
tem design is explained in the "System Components" section.
Additional devices covered are: remote manual pull stations,
mechanical and electrical gas shut-off valves, electrical switches,
and pressure switches.
Single-Tank System
The R-102 single-tank system is available with a stainless steel
enclosure and consists of:
ANSUL AUTOMAN Regulated Release Assembly (Electrical
or Mechanical)
Nitrogen Cartridge and/or Carbon Dioxide Cartridge
ANSULEX Low pH Liquid Fire Suppressant
Discharge Nozzles
Detection Components
Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank hookup,
and enclosure knockouts to facilitate installing detection system
and additional equipment. Refer to "System Components" section
for individual component descriptions.
FIGURE 1
000133
Double-Tank System
o. The R-1 02 double-tank system is available with stainless steel
enclosures and consists of:
ANSUL AUTOMAN Regulated Release Assembly (Electrical
or Mechanical)
Nitrogen Cartridge and/or Carbon Dioxide Cartridge
ANSULEX Low pH Liquid Fire Suppressant
Enclosure or Bracket Assembly
Discharge Nozzles
Detection Components
Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank hookup,
and enclosure knockouts to facilitate installing expellant piping,
detection system, and additional equipment.
The enclosure or bracket assembly is mounted separately but
within the guidelines of the regulated release assembly expellant
gas piping requirements to ensure simultaneous actuation of the
system. Refer to "System Components" section for individual com-
ponent descriptions.
0.
FIGURE 2
8321
NOTE: AGENT TANK MUST BE
ORDERED SEPARATELY
OR SEE PAGE 3-4
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-1
7-1-09 REV. 6
EXTINGUISHING AGENT
ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon - Part No.
79694 or 3.0 gallon - Part No. 79372) is a potassium-based solu-
tion designed for fast knock-down and suppression of grease-
related fires. The agent is shipped in plastic containers which pro-
vide one complete tank charge. (Refer to Section V, Page 5-2.1, for
maximum agent fill capacity.) Agent storage life expectancy is
twelve years and can be stored at a temperature of —40 OF to 130
OF (-40 °C to 54°C). Note: When installing agent in R-102 sys-
tem, temperature range is 32 OF (0 °C) to 130 OF (54 °C). The
distributor must record the batch numbers and date of shipment
receipt to be filed with each installation record.
ANSULEX" LOW pH LIQUID FIRE SUPPRESSANT
3.0 GALLON 1.5 GALLON
SHIPPING WT 35 LB (16 kg) SHIPPING WT. 19 LB (9 kg)
000136 000137
FIGURE 1
REGULATED RELEASE ASSEMBLY (MECHANICAL)
The ANSUL AUTOMAN Regulated Mechanical Release Assembly
(Part No. 429853) contains the regulated release mechanism,
expellant gas hose for agent tank hookup, and enclosure knock-
outs to facilitate installing actuation piping; expellant piping; detec-
tion system; and additional equipment. This regulated release
assembly is used in single, double, and multiple-tank systems and
must be mounted to a rigid surface. The release mechanism can
be used to interconnect both the actuation and expellant gas lines
as required per system design. The regulator is designed to allow
a constant flow of gas into the tank at 110 psi (7.6 bar) when the
system is actuated. The agent tank must be ordered separately.
In single, double, and multiple-tank systems, the provided expel-
lant gas hose connects the agent tank to the bottom outlet of the
regulator. In double and multiple-tank system configurations, the
back outlet of the regulator is used as an expellant gas feed for
one additional tank-enclosure or tank-bracket hookup. The enclo-
sure contains the required knockouts to facilitate this connection.
If a pressure switch is to be attached to the regulator, additional fit-
tings are required.
The tank is mounted within the enclosure. The tank contains an
adaptor/tube assembly with a burst disc union. The burst disc
helps prevent siphoning of the agent up the pipe due to significant
temperature fluctuations in the area where the tank is located. The
tank is stainless steel and, under normal conditions, requires
hydrostatic testing every twelve years.
The detection and additional equipment required per system
design are connected to the release mechanism. The enclosure
contains knockouts to facilitate detection and additional hookups.
The system can be actuated automatically or manually. Automatic
actuation occurs when a fusible link within the detection system
separates in a fire condition. Manual actuation of the system
occurs when personnel pull on the remote manual pull station
pull ring.
"ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY
(MECHANICAL)
FIGURE 2
000138
REGULATED RELEASE ASSEMBLY (ELECTRICAL)
The ANSUL AUTOMAN Regulated Electrical Release Assembly
(Part No. 429856) is identical to the mechanical version except it
also contains a factory installed 120 VAC solenoid and electrical
switch.
The solenoid is used to provide electrical actuation of the release
mechanism. The electric switch is used to protect the solenoid by
opening the circuit to the solenoid once the system is fired.
Additional electrical switches can be added as required for auto-
matic equipment and gas shut-off accessories, as well as initiating
audible and visual alarms.
"ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY
(ELECTRICAL)-
NOTE: AGENT TANK MUST
ORDERED
SEPARATELY
OR SEE PAGE 3-4
REGULATOR
SWITCH
SOLENOID
0%
SHIPPING WT. 34 LB (15 kg)
FIGURE 3
000139
* NOTE: ANSUL AUTOMAN Regulated Electrical Release, Part No. 429856, is not
intended to be used with electric detection.
MOUNTING
BRACKET
SHIPPING WT. 7 LB (3 kg)
FIGURE 6
980141
REGULATED ACTUATOR ASSEMBLY
The Regulated Actuator Assembly (Part No. 429850) contains the
regulator, pneumatic actuator, expellant gas hose for agent tank
hookup, and enclosure knockouts to facilitate installing expellant pip-
ing. This assembly is used in multiple-tank systems and must be
mounted to a rigid surface.
The regulator contains two outlets 1350 apart. One outlet is used
to interconnect the expellant gas hose to the enclosed agent tank.
The other outlet connects an expellant gas line to an additional
enclosure or bracket assembly. The regulator is designed to allow
a constant flow of nitrogen into each agent tank connected (two
o. tanks maximum) at 110 psi (7.6 bar).
The pneumatic actuator is designed to puncture the expellant gas
cartridge seal upon receiving pressure from the regulated release
assembly actuation piping. The enclosure contains a knockout to
facilitate distribution piping hookup.
REGULATED ACTUATOR ASSEMBLY
NOTE: AGENT TANK
MUST BE
ORDERED
SEPARATELY
OR SEE PAGE 3-4
PNEUMATIC
ACTUATOR
ASSEMBLY
REGULATOR
ING WE
1(9 kg)
FIGURE 7
000143
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-2
REV. 6 7-1-09
REMOTE MECHANICAL RELEASE
The Remote Mechanical Release, Part No. 433485, is used to
actuate up to five (5) R-102 regulated actuators. The remote
mechanical release utilizes a 101-10 carbon dioxide cartridge as
the actuation pressure to operate the regulated actuators. The
release is housed in a stainless steel enclosure.
RELEASE
MECHANISM
10
SHIPPING WEIGHT: I
20 LB (9.1 kg)
0
FIGURE 4
007498
SINGLE TANK ENCLOSURE ASSEMBLY
The Single Tank Enclosure Assembly (Part No. 429870) is used in
double and multiple-tank systems and must be mounted to a rigid
surface near the regulated release or regulated actuator assembly
its expellent gas line will be connected to.
The enclosure is designed for mounting either a 1.5 gallon (Part
No. 429864) or a 3.0 gallon tank (Part No. 429862) in a minimum
amount of space.
ENCLOSURE ASSEMBLY
NOTE: AGENT TANK MUST
BE ORDERED
SEPARATELY
OR SEE PAGE 3-4
MOUNTING
ENCLOSURE
I3LB(6k9) EEI SHIPPING WT.
FIGURE 5
000142
RED PAINTED BRACKET ASSEMBLY
The Bracket Assembly (Part No. 429878) is used in double and
multiple-tank systems and must be mounted to a rigid surface near
the regulated release assembly or regulated actuator assembly
that its expellant gas line will be connected to.
The tank bracket is constructed of mild steel and painted red. It is
designed for mounting the tank in a minimum amount of space.
The Bracket Assembly can only be utilized with 3.0 gallon tanks
(Part No. 429862).
BRACKET ASSEMBLY
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-3
4-1-06 REV.8
AGENT TANK ASSEMBLY
The agent tank shipping assembly (3-Gallon, Part No. 429862,
and 1.5 Gallon, Part No. 429864) consists of a stainless steel tank
and an adaptor/tube assembly. The adaptor/tube assembly con-
tains a burst disc. The burst disc prevents agent leakage due to
significant temperature fluctuations in the area where the tank is
located. Under normal conditions, the tank requires hydrostatic
testing every twelve years. The date of manufacture is stamped on
the tank nameplate.
The tank is shipped uncharged and must be filled with only
ANSULEX Low pH Liquid Fire Suppressant during installation.
(ADAPTOR/
ASSEMBLY
3 GALLON
SHIPPING WT.
7 LB (3 kg)
1.5 GALLON
SHIPPING WT.
5 LB (2 kg)
AGENT
TANK
FIGURE 8
000140
OEM RELEASE/BRACKET ASSEMBLY
(FOR OEM IN-CABINET USE ONLY)
The OEM Regulated Mechanical Release/Bracket Assembly, Part
No. 79493, contains the same regulated release mechanism as
the standard ANSUL AUTOMAN Regulated Release Assembly.
The OEM Regulated Electrical Release/Bracket Assembly, Part
No. 418054*, is identical to the mechanical version except it con-
tains a factory installed 120 VAC solenoid and electrical switch.
These release/bracket assemblies must be installed in a suitable
equipment enclosure either horizontally or vertically. They contain
all the necessary mounting and conduit holes needed to fully
install the assembly. The agent tank is installed separately and
need not be bracketed once it is piped and filled. Note: OEM
Release/Bracket Assembly must be installed high enough in cabi-
net so that there is sufficient room to install and remove cartridge.
*Note: OEM Regulated Electrical Release/Bracket Assembly, Part No. 418054, is
not intended to be used with electric detection.
RELEASE
MECHANIS
REGULAT
FIGURE 9
000144
OEM REGULATED ACTUATOR ASSEMBLY
The OEM Regulated Actuator Assembly, Part No. 418691,
includes the regulator, pneumatic actuator, expellant gas hose and
OEM bracket. Also available is an OEM Regulated Actuator
Assembly with all the above mentioned components except for the
bracket. This assembly is Part No. 418522.
SHIPPING WT. 4 LB (2 kg)
FIGURE 10
002225
TWO TANK ENCLOSURE ASSEMBLY
The Two Tank Enclosure Assembly, Part No. 429872, consists of
two expellant gas hoses, two grommets, and the mounting enclo-
sure. The assembly is used in 9 gallon systems. It can be coupled
with a 3-gallon regulated release assembly or a 3-gallon regulated
actuator assembly to give a total of 9 gallons of agent. Agent tanks
must be ordered separately.
The tank enclosure is designed to mount in a minimum amount of
space.
SHIPPING WE
26 LBS (12 kg)
FIGURE 11
002277
MOUNTING
BRACKET
;HIPPING WT.
10 LB (5 kg)
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-4
REV. 7 4-1-06
24 VDC REGULATED RELEASE ASSEMBLY (ULC APPROVED
ONLY)
The 24 VDC Regulated Release Assembly, Part No. 429859, is
used where electric, thermostat detection is required via the use of
a releasing control unit. This assembly consists of a 24 VDC
ANSUL AUTOMAN Il-C regulated release mechanism, expellant
gas hose, and enclosure knockouts to facilitate installing actuation
piping, expellant piping, detection system, and additional equip-
ment. Agent tank must be ordered separately.
The system can be actuated automatically or manually. Automatic
actuation occurs when the control panel receives a signal from the
detection circuit. The panel then sends an electrical signal to the
24 VDC regulated release, causing it to actuate. When actuation
occurs, the gas cartridge is punctured, pressurizing the agent tank
and discharging the agent through the distribution piping. Manual
actuation of the system occurs when personnel pull on the remote
manual pull station pull ring.
ADDITIONAL SHIPPING ASSEMBLIES
Several complete shipping assemblies are available containing
both the release or actuator mechanism and the agent tank. When
ordering a complete shipping assembly, order the following part
numbers:
Shipping Wt.
Part No. Description lb (kg)
430299 3.0 Gallon Mechanical Release 33 (15)
Shipping Assembly including:
429853 Mechanical Regulated
Release Assembly
429862 3.0 Gallon Tank Assembly
430300 1.5 Gallon Mechanical Release 30 (14)
Shipping Assembly including:
429853 Mechanical Regulated
Release Assembly
429864 1.5 Gallon Tank Assembly
430324 6.0 Gallon Stainless Steel Enclosure 40 (18)
Shipping Assembly including:
429872 Two Tank Mounting Box
Assembly
429862 3.0 Gallon Tank Assembly (2)
430332 3.0 Gallon Mounting Bracket Shipping 20 (9)
Assembly including:
429878 3.0 Gallon Mounting Bracket
Assembly
429862 3.0 Gallon Tank Assembly
NOTE: AGENT TANK MUST BE ORDERED SEPARATELY 430309 3.0 Gallon Regulated Actuator 36 (16)
Shipping Assembly including:
SHIPPING WT. 429850 Regulated Actuator Assembly
34 LB (15 kg) 429862 3.0 Gallon Tank Assembly
430316 1.5 Gallon Stainless Steel Enclosure 18 (8)
Shipping Assembly including:
429870 Single Tank Mounting Box
Assembly
429864 1.5 Gallon Tank Assembly
418511 Hose Assembly
430317 3.0 Gallon Stainless Steel Enclosure 20 (9)
FIGURE Shipping Assembly including:
002279 429870 Single Tank Mounting Box
Assembly
429862 3.0 Gallon Tank Assembly
418511 Hose Assembly
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-5
7-1-09 REV. 8
GAS CARTRIDGES
The R-1 02 system uses gas cartridges to store nitrogen or carbon
dioxide expellant gases under pressure until the system is actuat-
ed, at which time the cartridge seal is punctured and the released
gas expels liquid agent from one or more tanks through the dis-
charge piping and out the discharge nozzles.
Four nitrogen gas cartridges and three carbon dioxide gas car-
tridges are available as shown in Figure 13.
Cartridges noted as TO/DOT are both Transport Canada (TO) and
Department of Transportation (DOT) approved. Cartridges noted
as DOT are Department of Transportation approved only.
Cartridge selection options are provided in Section IV under Tank
and Cartridge Requirements.
NITROGEN GAS CARTRIDGES
17 1/4f
' f11 tJ 121/4 11 5/8 (43.8 cm)
7 7/8 IN (29.5 c
(20 cm (31.1 Cm)
21/2IN. 21/2IN. 43/161N. 39/16IN.
(6.4 cm) (6.4 Cm) (10.6 cm) (9 cm)
LT-20-R LT-30-R DOUBLE-TANK LT-A-101-30
CARTRIDGE CARTRIDGE CARTRIDGE CARTRIDGE p 000145 000146 000147 000145
CARBON DIOXIDE CARTRIDGES
115/f
7 7/8 IN. (29.5 cm gIN. )
(22.9 cm) (20 cm)
-
21N. 21/21N. 21/21N.
(5.1 cm) (6.4 cm) (6.4 cm)
101-10 CARTRIDGE 101-20 CARTRIDGE 101-30 CARTRIDGE p 000149 000150 000151
FIGURE 13
Additional cartridge shipping assemblies are available for
European and Australian requirements.
Cartridge European Australian TO/DOT
Description Part No. Part No. Part No.
LT-20-R 428440 428948 423429
LT-30-R 428441 426553 423435
Double Tank 428446 426563 423493
LT-A-101-30 428442 426555 423491
101-10-002 428443 N/A 423439
101-20 - 002 428445 N/A 423441
101-30 - 002 428444 N/A 423443
I. Note: For 101-10 cartridge, Part No. 15850 is DOT only
NOZZLES
There are 11 types of discharge nozzles each designed to distrib-
ute the liquid agent in a uniform pattern throughout the hazard
area:
1W Nozzle 7. 245 Nozzle
1 Nozzle 8. 260 Nozzle
1/2N Nozzle 9. 290 Nozzle
3N Nozzle 10. 2120 Nozzle
2W Nozzle 11. 1 F Nozzle
230 Nozzle
Although these nozzles are similar in appearance and have
certain common parts, the tip of each nozzle is designed for a
specific application and must only be used in those areas. See
Nozzle Application Chart in Section IV - System Design, for
individual nozzle usage.
3/8-18 NPT
FEMALE THREAD
INTERNAL CUP
STRAINER
INSIDE
RECESS FOR
VENDOR CAP LOOP
BLOW OFF
CODE
NOZZLE (IF PRESENT)
STAMPING
FIGURE 14
000000
Nozzle Identification Chart
p Note: See Component Index for nozzle package shipping aSsem-
p bly part numbers.
Nozzle
Nozzle Nozzle Nozzle* Flow
p!= Part No. Stamping tQ. Nozzle Material
p 1W Nozzle 419336 1W** 1 Chrome-Plated Body
p 1 N Nozzle 419335 1 N** 1 Chrome-Plated Body
1/2N Nozzle 419334 1/2N 1/2 Chrome-Plated Body
3N Nozzle 419338 3N 3 Chrome-Plated Body
2W Nozzle 419337 2W 2 Chrome-Plated Body
230 Nozzle 419339 230 2 Chrome-Plated Body
245 Nozzle 419340 245 2 Chrome-Plated Body
260 Nozzle 419341 260 2 Chrome-Plated Body
290 Nozzle 419342 290 2 Chrome-Plated Body
2120 Nozzle 419343 2120 2 Chrome-Plated Body
1 F Nozzle 419333 1 F 1 Chrome-Plated Body
* Nozzle stamping may Contain an additional letter indicating a vendors Code.
p **Stainless steel versions are available in the 1W nozzle (Part No. 432527) and
p the 1 N nozzle (Part No. 435672).
SILICONE LUBRICANT
Dow Corning Compound 111, Part No. 78112, is available in a
5.3-ounce tube. Compound has excellent qualities for sealing and
lubricating system components.
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-6
REV. 7 7-1-09
SWIVEL ADAPTOR
m. The Swivel Adaptor Assembly consists of a swivel nut, swivel body
and swivel ball. All are chrome-plated. The swivel adaptor allows
any nozzle to be rotated approximately 30° in all directons. Swivel
Adaptors must be ordered as a Swivel Adaptor Shipping
m. Assembly, Part No. 423572, which contains 25 Swivel Adaptors or
Part No. 419385, which contains 9 Swivel Adaptors.
3/8-18 NPT
FEMALE THREAD
PT
READ
30
RO
FIGURE 15
000003
RUBBER BLOW-OFF CAPS
v. The Rubber Blow-Off Cap helps keep the orifice of the nozzle free
of grease or other substances that could interfere with agent dis-
tribution. A retaining strap attaches the blow-off cap to the nozzle.
Rubber Blow-Off Caps must be ordered as a Shipping Assembly,
Part No. 77695, which contains 50 blow-off caps, or Part No.
77411, which contains 12 blow-off caps.
FIGURE 16
000009
CB METAL BLOW-OFF CAP
The CB Metal Blow-off Cap Package, Part No. 433208, is used for
all high temperature environments. The metal blow-off cap con-
tains a special 0-ring placed inside the cap which integrates with
the nozzle to create a seal and to help hold the blow-off cap in
position.
The CB Metal Blow-Off Cap Package, Part No. 433208, contains
10 blow-off caps.
Also available is a 10 pack of CB Stainless Steel Blow-Off Caps,
Part No. 434707.
A 10 pack of Metal Blow-Off Cap 0-rings, Part No. 551530, is also
available.
STAINLESS
STEEL WIRE
METAL CAP
FIGURE 17
007633
CONDUIT OFFSET ASSEMBLY
The conduit offset assembly, Part No. 435961, is used to change
direction of the wire rope on detection, mechanical gas valve, and
remote pull station lines. The conduit offset assembly can only be
used in the area where the conduit attaches to the regulated
release assembly. When using the conduit offset assembly, the
maximum number of pulley elbows is still allowed. The Conduit
Offset Shipping Assembly, Part No. 436063, consists of 6 conduit
offsets.
CONDUIT
COUPLING
CONDUIT
OFFSET
CONDUIT
CONNECT
FIGURE 18
000153
"QUIK-SEAL" ADAPTOR
The "Quik-Seal" adaptor is a listed mechanical bulkhead fitting that
produces a liquid-tight seal around both distribution piping and
detection conduit which runs through restaurant hoods and ducts.
The "Quik-Seal" adaptor accepts threaded pipe or conduit. The
adaptor is available for 1/4 in. (Part No. 78196), 3/8 in. (Part No.
77285), 1/2 in. (Part No. 77287), or 3/4 in. (Part No. 77289) pipe or
conduit sizes. When using with EMT conduit, a conduit connector
must be installed in each end of the adaptor. The "Quik-Seal"
Adaptor Shipping Assembly must be ordered as stated below:
Shipping
Assembly Hole Size
Size Part No. Qty. Required
1/4 in. 78196 24 3/4 in.
3/8 in. 77285 24 1 1/8 in.
1/2 in. 77287 24 11/Bin.
3/4 in. 77289 24 1 3/8 in.
ADAPTOR
cc__t orn' GASKET
LOCKWASHER
NUT
FIGURE 19
000154
COCKING LEVER/LOCK BAR
The cocking lever is a component required to cock (arm) both the
mechanical/electrical ANSUL AUTOMAN release and the mech-
anical gas valve. After the ANSUL AUTOMAN is cocked (armed),
the lock bar must be inserted to eliminate the accidental firing of
the release mechanism. These components are available as either
an individual shipping assembly or a shipping assembly containing
both. Listed below are the various shipping assembly part num-
bers.
Part No. Description
435603 Short Handle Cocking Lever only
(Mechanical/Electrical ANSUL AUTOMAN)
435790 Short Handle Cocking Lever with Lock Bar
(Mechanical/Electrical ANSUL AUTOMAN)
14995 Long Handle Cocking Lever only
(Mechanical/Electrical ANSUL AUTOMAN)
15618 Long Handle Cocking Lever with Lock Bar
(Mechanical/Electrical ANSUL AUTOMAN)
26310 Cocking Lever only (ANSUL AUTOMAN II-C)
416018 Cocking Lever only (Mechanical Gas Valve)
14985 Lock Bar
Short Handle Cocking Lever
Requires a crescent wrench or open end/box wrench
Long Handle Cocking Lever
Lock Bar
FIGURE 23
008325
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-7
7-1-09 REV. 6
"COMPRESSION-SEAL" ADAPTOR
This adaptor is a mechanical bulkhead fitting that produces a
liquid-tight seal around pipe and conduit when installing distribu-
tion piping and detection conduit through restaurant hoods and
ducts. The "Compression-Seal" adaptor is a straight-through
design requiring no cutting or threading of conduit or pipe. The
m. adaptor is available for pipe sizes of 1/4 in. (Part No. 79149), 3/8 in.
(Part No. 79151), 1/2 in. (Part No. 79147), and EMT conduit size of
m. 1/2 in. (Part No. 79153). Each "Compression-Seal" Adaptor
Shipping Assembly must be ordered as stated below:
Shipping
Assembly Hole Size
Se Part No. Qty. Required
1/4 in. Pipe / 1/2 in. tube 79149 24 3/4 in.
3/8 in. Pipe / 5/8 in. tube 79151 24 1 1/8 in.
1/2 in. Pipe 79147 24 11/8 in.
1/2 in. EMT Conduit 79153 24 11/8 in.
COMPRESSION NUT
ADAPTOR BODY
LOCK WASHER
FIGURE 20
000155
"HOOD SEAL" ADAPTOR ASSEMBLY
This adaptor is a mechanical bulkhead fitting that produces a liq-
uid-tight seal around 1/2 in. EMT conduit when installing the detec-
tion line through restaurant hoods and duct. The adaptor accepts
a high temperature pulley elbow and, when used, correctly posi-
tions the elbow or conduit in line with the conduit adaptor hole in
the detector bracket. The "Hood Seal" eliminates the need for mul-
tiple elbows when penetrating the top of a hood when installing the
detection line. "Hood Seal" Adaptors are available in quantities of
6 as Shipping Assembly Part No. 423253.
SEAL NUT
SEAL 111 11191 WASHER
ADAPTOR
BODY
I\ GASKET
PULLEY
ELBOW
(NOT PART
OF ASSEMBLY)
USE ONLY PULLEY ELBOW, PART NO. 423250 FIGURE 21
000156
REDUCING COUPLING
The reducing coupling, Part No. 436228, is made of stainless steel
material with 3/8 in. x 1/2 in. NPT inlet threads. If necessary, the
reducing coupling can be utilized when installing the Agent
Distribution Hose Line Kit, Part No. 435982. Two couplings are
required per Agent Distribution Hose.
1/4 IN. I
(3.3 cm)
-TI 1 3/16 IN.
(3.0 cm)
I
FIGURE 22
008324
GASKET
NUT
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-8
REV.8 7-1-09
DETECTORS
The detector consists of three basic components: the bracket, link-
age, and fusible link. (Fusible links are not included and must be
ordered separately.) The bracket holds the entire assembly to the
mounting surface. The linkage is used to support the fusible link.
The fusible link is designed to separate at a specific temperature
and release the wire rope, thereby actuating the regulated release
mechanism.
The scissor style detector allows the wire rope to be strung com-
pletely through the detection system conduit and brackets first and
the detector linkage assemblies are then clipped on later.
The detector consists of two types of assemblies:
The Terminal Detector (Part No. 435546) includes a test link and
is placed last in a series of detectors. This detector is sometimes
referred to as the end-of-line detector and is thus named because
it is at the point at which the wire rope "terminates," or is anchored
at the detector bracket. Only one terminal detector is required per
detection system.
The Series Detector (Part No. 435547) is any detector located in-
line between the regulated release assembly and the terminal
detector.
When using Part No. 435546 and 435547 detectors, a total of 15
detectors can be in one detection system: 14 series detectors, Part
No. 435547 and 1 terminal detector, Part No. 435546.
'Note: Series Detector, Part No. 435547, is also available as Part
No. 435548, 25/Pkg.
SCISSOR STYLE - PART NO. 435546 AND 435547
PULLEY TEE
The Pulley Tee (Part No. 427929) is used to change the direction
of two wire ropes by 90°. It must be used in areas where the tem-
peratures are within the range of 32 IF to 130 OF (0 °C to 54 °C).
Pulley tees can be used in mechanical gas valve actuation lines
and remote manual pull station lines. Pulley tees cannot be used
within a detection line.
FIGURE 26
000447
STAINLESS STEEL CABLE
The 1/16 in. stainless steel cable is run from the terminal detector,
through conduit, all series detectors and pulley elbows, and into
the regulated release mechanism trip lever. When any fusible link
separates, the tension on the cable is relaxed, and the trip lever
actuates the regulated release mechanism. The cable can also be
used for mechanical gas valves and remote manual pull stations.
The cable is available in 50 ft (15 m) (Part No. 15821) and 500 ft
(152.4 m) (Part No. 79653) lengths.
BRACKET
/
FIGURE 24
000159
PULLEY ELBOWS
There are two types of pulley elbows used to change the direction
of the wire rope by 90°. ANSUL recommends for temperatures not
in excess of 700 IF (371 °C). Part No. 415670 has socket ends
with set screws for 1/2 in. conduit, and Part No. 423250 has com-
pression ring ends also for 1/2 in. conduit. Pulley elbows must be
ordered in quantities of 50 as Shipping Assembly Part No. 415671
(socket end type) and Part No. 423251 (compression end type).
PART NO. 415670 PART NO. 423250
000160 000161
FIGURE 25
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-9
7-1-09 REV.5
REMOTE MANUAL PULL STATION
The remote manual pull station (Part No. 434618 or 435960) is
made out of a molded red composite material. The red color
makes the pull station more readily identifiable as the manual
means for fire suppression system operation. The pull station is
compatible with the ANSUL Flexible Conduit. The molded manual
pull station should be mounted at a point of egress and positioned
at a height determined by the authority having jurisdiction. Trim
Rings, Part No. 427074 (pack of 10), are available.
Part No. 434618 (Without Wire Rope)
Part No. 435960 (With 50 ft (15.2 m) of Wire Rope)
FIGURE 27 008326
FLEXIBLE CONDUIT
Flexible conduit allows for quicker installations and the conve-
nience of being able to route the cable over, under and around
obstacles. Flexible conduit can be used as a substitute for stan-
dard EMT conduit or can be used with EMT conduit. Flexible con-
duit can be used only with the Molded Manual Pull Station, Part
No. 434618, and mechanical gas valve installations. The Flexible
Conduit comes in a 500 ft (152.4 m) length, Part No. 434525, or
together with 500 ft (152.4 m) of wire rope, Part No. 435959.
Also available is a Flexible Conduit Strain Relief (50-pack), Part
No. 435979.
A 50-pack of Flexible Conduit Inserts, Part No. 434347, is also
available.
'. Note: Flexible conduit cannot be used in detection systems.
MECHANICAL GAS VALVES
The mechanical gas valves are designed to shut off the flow of gas
to the appliances upon actuation of the regulated release assem-
bly. The valves are available in sizes of 3/4 in., 1 in., 1 1/4 in., 1 1/2
in., and 2 in. ANSUL style; and 2 1/2 in. and 3 in. ASCO style. The
valves are rated for natural and LP gas. Both styles are UL Listed
and includes the air cylinder, tubing, and fittings, Part No. 15733,
for connection to the release mechanism.
Maximum
Part Operating
No. Description Pressure
55598 3/4 in. Gas Valve (ANSUL) 10 psi (0.69 bar)
55601 1 in. Gas Valve (ANSUL) 10 psi (0.69 bar)
55604 1 1/4 in. Gas Valve (ANSUL) 10 psi (0.69 bar)
55607 1 1/2 in. Gas Valve (ANSUL) 10 psi (0.69 bar)
55610 2 in. Gas Valve (ANSUL) 10 psi (0.69 bar)
25937 2 1/2 in. Gas Valve (ASCO) 5 psi (0.35 bar)
25938 3 in. Gas Valve (ASCO) 5 psi (0.35 bar)
Flow Capacity BTUIHR, at 1 in. P.D.
(CFH) 0.64 SP GR
Pipe Size P.D. 1 in. WC 1000 BTU/ft3
(inches) 0.64 SP GR Natural Gas
3/4 751 751,000
1 1288 1,288,000
11/4 1718 1,718,000
1 1/2 2630 2,630,000
2 4616 4,616,000
21/2 5700 5,800,000
3 7100 7,300,000
To calculate gas flow for other than 1 inch p.d.:
New cfh = (cfh at 1 inch) x J new p.d
To calculate gas flow for other than 0.64 SP GR
New cfh = (cfh at 0.64) x ' 0.64
New SP GR
A B C
Valve Size in. (mm) in. (mm) in. (mm)
3/4 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7)
1 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7)
1 1/4 in. 47/8 (123.8) 73/8 (187.3) 63/8 (161.9)
11/2 in. 47/8 (123.8) 73/8 (187.3) 63/8 (161.9)
2in. 57/8 (149.2) 77/8 (200.0) 611/16 (169.9)
2 1/2 in. 713/16 (198.4) 91/16 (230.2)
3 in. 725/32 (197.6) 91/16 (230.2)
3/4 IN. THRU 2 IN.
004208
2 1/2 IN. THRU 3 IN.
004209
FIGURE 28
FIGURE 31
001812
N.O. COM
Valve A B
Size in. (mm) in. (mm)
3/4 in. 35/16 (81.0) 35/8 (92.1)
1 in. 5 (127.0) 627/32 (173.8)
11/4 in. 713/16 (198.4) 729/32 (200.8)
11/2in. 5 (127.0) 519/32 (142.1)
2in. 63/32 (78.6) 515/16 (150.8)
21/2in. 713/16 (198.4) 729/32 (200.8)
3 in. 713/16 (198.4) 729/32 (200.8)
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-10
REV.4 7-1-09
ELECTRICAL GAS VALVES
The electrical gas valves are designed to shut off the flow of either
natural or LP gas to the appliances upon actuation of the regulat-
ed release assembly. The valves are available in sizes of 3/4 in.,
1 in.,1 1/4in.,1 1/2 in., 2 in., 2 1/2 in., and 3 in. The valve is held
open by an energized solenoid and upon system actuation, the
switch contacts in the regulated release assembly open, thus de-
energizing the circuit to the gas valve solenoid, causing the valve
to close. Valves are available in 120 VAC and are UL Listed.
Part Max. Operating
No. Description Pressure
13707 3/4 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar)
13708 1 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar)
550360 1 1/4 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar)
13709 1 1/2 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar)
13710 2 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar)
550363 2 1/2 in. Solenoid Gas Valve (ASCO) 5 psi (0.35 bar)
17643 3 in. Solenoid Gas Valve (ASCO) 5 psi (0.35 bar)
Flow Capacity BTU/HR, at 1 in. RD
(CFH) 0.64 SP GR
Pipe Size P.D. 1 in. WC 1000 BTU/ft3
(inches) 0.64 SP GR Natural Gas
3/4 264.96 247,500
1 1091.01 1,119,000
11/4 1662.49 1,730,000
1 1/2 1818.35 1,900,000
2 3117.18 3,251,000
21/2 6078.49 5,821,000
3 7169.51 7,430,000
To calculate gas flow for other than 1 inch p.d.:
New cfh = (cfh at 1 inch) x
To calculate gas flow for other than 0.64 SP GR:
New cfh = (cfh at 0.64) x / 0.64
New SPGR
MANUAL RESET RELAY
The Manual Reset Relay, Part No. 426151, is required when using
an electrical gas valve shut-off system. After the electric gas valve
has closed, either due to system actuation or power failure, the
valve cannot be re-opened, allowing gas to flow, until the reset
relay button is manually pressed, re-energizing the circuit. The
reset relay is available 120 VAC. The manual reset relay is also
recommended for electrical shut down.
FIGURE 30
000087
ELECTRICAL SWITCHES
The electrical switches are intended for use with electric gas
valves, alarms, contactors, lights, contractor supplied electric
power shut-off devices and other electrical devices that are
designed to shut off or turn on when the system is actuated.
Switches are available in kits: One Switch Kit, Part No. 423878,
Two Switch Kit, Part No. 423879, Three Switch Kit, Part No.
423880, and Four Switch Kit, Part No. 423881. Mounting hardware
and 12 in. (305 mm) long wire leads are provided with each kit.
Each switch has a set of single-pole, double-throw contacts rated
at:
UL/cULJCSA Rating ENEC Rating
250 VAC, 21A Resistive lE4T105p Approved
250 VAC, 2 HP 250V, 21A Resistive
125 VAC, 1 HP 8A Motor Load
FIGURE 29
004210
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-11
7-1-09 REV. 1
ALARM INITIATING SWITCH
The Alarm Initiating Switch Kit, Part No. 428311, can be field
mounted within the ANSUL AUTOMAN release. This switch must
be used to close a supervised alarm circuit to the building main fire
alarm panel when the ANSUL AUTOMAN release actuates. This
action will signal the fire alarm panel that there was a system actu-
ation in the kitchen area. The switch kit contains all necessary
mounting components along with a mounting instruction sheet.
The switch is rated 50 mA, 28 VDC.
SPACER
TOWARD ANSUL WHEN SPACER AND AUTOMAN SWITCH ARE PROPERLY
MOUNTED, THIS DIVIDER
MUST BE BETWEEN THE / N.C. AND N.C. TERMINALS
N.
COM
r, - N.O.
N.C.
ALARM INITIATING
SWITCH
FIGURE 32
004890
U1i1t41i
The Test Kit Assembly (Shipping Part No. 56972) is required to test
the regulator setting and nitrogen flow during 12-year maintenance
examinations. This will ensure that the regulator is functioning
properly.
FIGURE 33
000169
FUSIBLE LINK
Select correct UL Listed fusible link(s) for installation in detector(s)
according to the temperature condition chart below:
K STYLE Fusible Link To Be Used
Fusible Shipping Where
Link Assembly Temperature Temperature
Part No. Part No. Rating Does Not Exceed
415739(1) 415739(1) 165°F (74°C) 100°F (38°C)
415740(1) 415740(1) 212°F(100°C) 150°F (66°C)
415741 (1) 415744 (25) 280 °F (138 °C) 225°F (107 °C)
415742(l) 415745 (25) 360 °F (182 °C) 290 °F (143 °C)
415743(l) 415746 (25) 450 °F (232 °C) 360 °F (182 °C)
ML STYLE Fusible Link To Be Used
Fusible Shipping Where
Link Assembly Temperature Temperature
aLLNQ. Part No. Rating Does Not Exceed
550368(1) 551522(10) 165°F (74°C) 100°F (38°C)
550365(1) 551523(10) 212°F(100°C) 150°F (66°C)
550366(l) 551524 (10) 280 °F (138 °C) 225 °F (107 °C)
550009(l) 551525 (10) 360 °F (182 °C) 290 °F (143 °C)
550367(1) 551526(10) 450 °F (232 °C) 360 °F (182 °C)
56816(1) 551527(10) 500 °F (260 °C) 400 °F (204 °C)
56816(l) 73867 (25) 500 °F (260 °C) 400 °F (204 °C)
I I I &:~ZD
II
I°'•, I TEMPERATURE
I I RATING STAMPED ON
FUSIBLE LINK BODY
K STYLE ML STYLE
000170 000171
FIGURE 34
MAXIMUM REGISTERING THERMOMETER
The Maximum Registering Thermometer, Part No. 15240, may be
used to indicate the highest normal temperature for the protected
area. Once this is established, the correct rated fusible link can be
chosen. Other methods for determining maximum temperatures
. may be used.
HOSE/GROMMET PACKAGE
The Hose/Grommet Package, Part No. 418511, consists of a 24 in.
rubber hose and 2 (two) grommets. This package is required when
expellant gas hose is routed outside the ANSUL AUTOMAN
Regulated Release, Regulated Actuator, and/or tank enclosure
assemblies.
SECTION III - SYSTEM COMPONENTS
UL EX3470 ULC EX3470 Page 3-12
REV. 1 7-1-09
.IN-LINE BURST DISC ASSEMBLY (MANIFOLDED SYSTEMS
ONLY)
The in-line burst disc assembly is required to eliminate the siphon-
ing of the agent up the pipe during extreme temperature variations.
In addition to eliminating the siphoning effect, the common in-line
burst disc assembly eliminates the possibility of one or more indi-
vidual discs located in the tank adaptor from failing to burst. The
assembly consists of a stainless steel body which houses the
burst disc. When utilizing this assembly in a manifolded system, it
is necessary to modify (remove) the burst disc located in all of the
R-102 tank adaptors in the system. The in-line burst disc assem-
bly is to be mounted as close to the tank outlet as possible. After
system discharge, the assembly must be disassemblec and a new
burst disc installed.
Part No. Description
416970 In-Line Burst Disc Assembly
417911 Burst Disc (Pack of 10)
RED SIDE OF BIJ
DISC TO BE --
ADAPTOR, PART NO.
417707 FIGURE 35
008383
1/4 IN. CHECK VALVE
The 1/4 in. check valve, Part No. 25627, blocks the flow of actua-
tion gas from the actuator that was actuated to the actuator(s) that
was not actuated. This prevents actuation gas from escaping from
an open actuator which may have had the cartridge removed.
CHECK VALVE PART NO. 25627
0"'~ N
1/4 IN. NPT
2 IN. (0.6 cm)
(5.1 cm)
FIGURE 36
000899
NOZZLE AIMING DEVICE
The Nozzle Aiming Device, Part No. 431992, is available to prop-
erly aim each nozzle to the correct aiming point. The device
clamps to the nozzle and emits a small laser light that reflects on
the surface that it is aiming at. The nozzle can then be rotated to
point at a predetermined aiming point and then tightened to hold
that angle. The aiming device adaptor attaches to the nozzle. The
shipping assembly consists of the aiming device and the adaptor.
0\\
ADAPTOR
NOZZLE
AIMING __
DEVICE
FIGURE 37
006520
STAINLESS STEEL BRAIDED ACTUATION HOSE
The Stainless Steel Actuation Hose is used to connect the actua-
tion line compression tees between each pneumatic actuator. The
hose has the same thread, 7/16-20, as the fittings. The actuation
hose allows flexibility between the AUTOMAN and each regulated
actuator.
Hose Part No. Length Couplings
31809 16 in. (41 cm) 7/16-20 x 7/16-20 Females
32335 20 in. (51 cm) 7/16-20 x 7/16-20 Females
32336 24 in. (61 cm) 7/16-20 x 7/16-20 Females
430815 42 in. (107 cm) 7/16-20 Female x 1/4 in. NPT
Fitting
Part No. Description
31810 Male Elbow (7/16-20 x 1/4 in. NPT)
31811 Male Tee (7/16-20 x 7/16-20 x 1/4 in. NPT)
415371 Tee (7/16-20 x 1/8 in. Male NPT x 1/8 in. Female NPT)
32338 Male Straight Connector (7/16-20 x 1/4 in. NPT)
25627 1/4 in. Check Valve
7/16-20 7/16-20
FIGURE 38
000433
AGENT DISTRIBUTION HOSE AND RESTRAINING CABLE KIT
The Agent Distribution Hose and Restraining Cable Kit, Part No.
435982, consists of a 5 ft (1.5 m) long Agent Distribution Hose, a
3 ft (0.9 m) long Restraining Cable, and a Restraining Cable
Hardware Package. The Agent Distribution Hose can be utilized
with castered cooking appliances with castered supports found in
commercial kitchens. The hose allows for movement of the appli-
ance for cleaning without having to disconnect any fire suppres-
sion system discharge piping.
Note: The Agent Distribution Hose is authorized for use with only
UL Listed ANSUL Wet Chemical Restaurant Fire Suppression
Systems.
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-1
7-1-09 REV.8
SYSTEM DESIGN
The ANSUL R-102 Restaurant Fire Suppression System may be
used on a number of different types of restaurant cooking appli-
ances and hood and duct configurations. The design information
listed in this section deals with the limitations and parameters of
this pre-engineered system. Those individuals responsible for the
design of the R-102 system must be trained and hold a current
ANSUL certificate in an R-102 training program.
The R-102 and the PIRANHA systems use compatible agents and
components, therefore, they may be used together for cooking
appliance, hood, and duct protection. The primary ANSUL
AUTOMAN Release can be either an R-102 or a PIRANHA
ANSUL AUTOMAN Release and can actuate up to two additional
R-102 or PIRANHA Regulated Actuators. In systems utilizing a
101 remote release, any combination of the maximum number of
regulated actuators can be used.
Both systems must actuate simultaneously.
Each system must be designed and installed per its appropri-
ate manual.
Adjacent appliances requiring protection must be protected
with the same type of system, either R-102 or PIRANHA,
unless the center-to-center spacing between the adjacent
R-1 02 and PIRANHA nozzles is no less than 36 in. (91.4 cm).
When appliances are protected with R-102 nozzles, the hood
and connecting duct above those appliances cannot be pro-
tected with PIRANHA nozzles.
Mixing systems in a common plenum is not allowed.
One of the key elements for restaurant fire protection is a correct
system design. This section is divided into ten sub-sections: Noz-
zle Placement Requirements, Tank Quantity Requirements, Actu-
ation and Expellant Gas Line Requirements, Distribution Piping
Requirements, Detection System Requirements, Manual Pull Sta-
tion Requirements, Mechanical Gas Valve Requirements, Electri-
cal Gas Valve Requirements, Electrical Switch Requirements, and
Pressure Switch Requirements. Each of these sections must be
completed before attempting any installation. System design
sketches should be made of all aspects of design for reference
during installation.
NOZZLE PLACEMENT REQUIREMENTS
This section gives guidelines for nozzle type, positioning, and
quantity for duct, plenum, and individual appliance protection. This
section must be completed before determining tank quantity and
piping requirements.
Duct Protection - Single Nozzle
All duct protection is UL listed without limitation of maximum duct
length (unlimited length). This includes all varieties of ductworks
both horizontal and vertical including ducts that run at angles to
the horizontal and ducts with directional bends.
The R-102 system uses different duct nozzles depending on the
size of duct being protected.
GENERAL INFORMATION
1. Nozzles must be located 2-8 in. (5-20 cm) into the center of the
duct opening, discharging up. See Figure 1.
2-8 IN.
(5-20 cm)
FIGURE 1
000173
In installations where a UL listed damper assembly is
employed, the duct nozzle can be installed beyond the 8 in.
(20 cm) maximum, to a point just beyond the damper assem-
bly that will not interfere with the damper. Exceeding the maxi-
mum of 8 in. (20 cm) in this way will not void the UL listing of
the system.
Previously listed 3 flow number and 5 flow number duct pro-
tection detailed in earlier published manual, Part No. 418087-
06, can also still by utilized.
DUCT SIZES UP TO 50 IN. (127 cm)
PERIMETER! 16 IN. (41 cm) DIAMETER
One 1W nozzle (Part No. 419336) = one flow number
50 in. (127 cm) perimeter maximum
16 in. (41 cm) diameter maximum
DUCT SIZES UP TO 100 IN. (254 cm)
PERIMETER! 32 IN. (81.3 cm) DIAMETER
One 2W Nozzle (Part No. 419337) = two flow numbers
100 in. (254 cm) perimeter maximum
32 in. (81.3 cm) diameter maximum
The chart below shows the maximum protection available from
each duct nozzle.
Part 3.0 Gallon 1.5 Gallon
Description No. System System
2W Nozzle 419337 Maximum Maximum
100 in. (254 cm) 100 in. (254 cm)
Perimeter Perimeter
1W Nozzle 419336 Maximum Maximum
50 in. (127 cm) 50 in. (127 cm)
Perimeter Perimeter
30 FT (9.1 m)
10FT(3.1 m)
MAXIMUM
1W NOZZLE
10 FT (3.1 m)
MAXIMUM
10 FT (3.1 m)
MAXIMUM
10 FT (3.1 m)
MAXIMUM
FIGURE 12
000206
FIGURE 10
006524
10 FT (3.1 m)
MAXIMUM
10 FT (3.1 m)
MAXIMUM
30 FT (9.1 m)
TWO (2) 1 NOZZLES - PART NO. 419335 - "V' BANK PRO-
TECTION
Two 1 nozzles will protect 10 linear feet (3.1 m) by 4 ft(1.2 m)
wide of "V' bank plenum. The nozzles must be mounted in the
plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered
between the filter height dimension, and aimed down the length.
The nozzle must be positioned 0-6 in. (0-15 cm) from the end of the
hood to the tip of the nozzle. See Figure 11.
2
(I
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-6
REV. 7 7-1-09
Plenum Protection (Continued)
HORIZONTAL PROTECTION - OPTION 2
1W NOZZLE - PART NO. 419336— "V" BANK PROTECTION
One 1W nozzle will protect 6 linear feet (1.8 m) of 'V' bank plenum.
The nozzle must be mounted horizontally, positioned 1/3 the filter
height down from the top of the filter. Nozzles can be located at 6 It
(1.8 m) spacings on longer plenums. The nozzle must be positioned
0-6 in. (0-15 cm) from the end of the hood to the tip of the nozzle.
See Figure 10.
For a plenum, either single or "V' bank, with a linear extension
longer than 10 ft (3.1 m), each bank may be protected using one
iN nozzle every 10 ft (3.1 m) or less depending on the overall
length of the plenum. See Figure 12. The nozzles may point in the
opposite directions as long as the entire plenum area is protected,
and the 10 ft (3.1 m) limitation is not exceeded. See Figure 13. The
nozzle positioning shown in Figure 14 is not an acceptable method
of protection because the plenum area directly under the tee is not
within the discharge pattern of either nozzle.
FIGURE 11
FIGURE 13
000207
FIGURE 14
000206
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-16
REV. 7 7-1-09
Range Protection 1 N (1-Flow) Nozzle - Low Proximity
I Application
15 in. to 20 in. (38.1 cm to 50.8 cm) above the cooking surface.
Range Protection Two (2) 290 (2-Flow) Nozzles - Low
Proximity Application
15 in. to 20 in. (38 cm to 51 cm) above the cooking surface.
The low proximity 1-flow nozzle application for the protection of The low proximity 2-flow application requires the use of two (2) 290
ranges requires the 1 N nozzle, Part No. 419335. nozzles, Part No. 419342.
The nozzle tip is stamped with 1 N indicating that it is a one-flow
nozzle and must be counted as one (1) flow number,
When using the 1 N nozzle for low proximity range protection with
or without obstruction, the maximum length of the burner grates
being protected must not be exceed 24 in. (61.0 cm) length, aimed
along a centerline to a point 20 in. (50.8 cm) from the end of the
length, protecting a maximum width of 18 in. (45.7 cm).
When protecting a range, the 1N nozzle must be located a maxi-
mum of 9 in. (22.9 cm) from each burner grate centerline and must
be positioned above the edge of the hazard area to be protected.
The 1 nozzle tip must be positioned at or below the obstruction,
if present. The protected area begins at the point straight down
from the nozzle tip. The nozzle can be placed at the side of the
range aimed either left or right, or can be placed in the front or
back of the range. See Figures 33 and 34 for nozzle location
details.
I N
15-201N.
(38_5l cm) 1
I 201N.
(51 cm)
PROTECTED AREA
gIN. (23 cm)
18 IN. (46 cm)
20 IN. (51 cm)
24 IN.
- (61 cm)
FIGURE 34
Both nozzle tips are stamped with 290 indicating they are two flow
nozzles and must be counted together for a total of four (4) flow
numbers.
Two (2) 290 nozzles will protect a cooking area of 1008 in.2
P. (6503 cm2) with a maximum dimension of 36 in. (91 cm).
When using two of these nozzles for low proximity range protec-
tion, the nozzles must be positioned along the cooking surface
perimeter to 1.5 in. (3.8 cm) inside the perimeter, and aimed at a
450 angle along the longitudinal centerline of the range. See
P. Figures 35 and 36.
290 NOZZLE TIP
-
r
LOCATION O-1.5IN.
(0-3.8 cm)
t
IN FROM EDGE OF
COOKING SURFACE
15 INTO 20 IN. I I i 15 INTO 20 IN.
(38 to 51 cm) I (38 to 51 cm)
MAXIMUM I MAXIMUM
__ _
_000000l
FIGURE 35 000276
LONGITUDINAL
CENTERLINE
/1
COOKING
AREA
290 NOZZLE TIP
LOCATION CENTER OF
COOKING SURFACE
± 2 IN. (5 cm)
290 NOZZLE TIP LOCATION
0— 1.5 IN. (3.8 cm) IN FROM EDGE 000239
OF COOKING SURFACE
COOKING
AREA
000240
COOKING
AREA
AIM POINT
007924
FIGURE 33
COOKING
AREA
290 NOZZLE TIP LOCATION
0-1.5 IN. (3.8 cm) IN FROM EDGE
OF COOKING SURFACE
I 290 NOZZLE TIP
- Fe- LOCATION CENTER OF
COOKING SURFACE
± 2 IN. (5 cm)
FIGURE 36
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-17
7-1-09 REV. 6
Range Protection (With or Without Back Shelf/Obstruction
m. When this type of hazard is equipped with a back shelf or other
P. similarly sized obstruction located above the range top, two pro-
tection options are available: One requires a 1 F nozzle, Part No.
419333, and the other option requires a 260 nozzle, Part No.
419341.
Range Protection 1F(1-Flow) Nozzle (With or Without Back
Shelf/Obstruction)
Single and multiple burner ranges can be protected using a 1 F
nozzle, Part No. 419333. The nozzle tip is stamped with 1 F indi-
cating that it is a one-flow nozzle and must be counted as one flow
number.
When using the 1 F nozzle for range protection with or without back
shelf or other similarly sized obstruction, the maximum length of
the burner grates being protected must not exceed 28 in. (71 cm)
and the maximum area of the burner grates must not exceed
336 in.2 (2168 cm2). See Figure 37 for nozzle location details.
1 NOZZLE
SHELF OR OTHER SIMILARLY SIZED
OBSTRUCTION CAN OVERHANG BURNER(S)
BY A MAXIMUM OF 11 IN. (28 Cm)
20 It. AIM (51 Cm) POINT MINIMUM (102.122cm)
40-48 IN.
12 IN. MAXIMUM
(35.6 Cm) (30.5 Cm) FRONT T ) REAR MAXIMUM AXIMUM CENTERLINE
IF NOZZLE LOCATED OVER FRONT EDGE OF BURNER GRATE AND ORIENTED
SO NOZZLE TIP FLATS ARE PARALLEL WITH BURNER GRATE FRONT TO REAR
CENTERLINE AND SHALL BE AIMED AT THE CENTER OF THE COOKING SURFACE.
FIGURE 37
000238
Range Protection 260 (2-Flow) Nozzle (With or Without Back
Shelf/Obstruction)
Single and multiple burner ranges can be protected using a 260
nozzle, Part No. 419341. The nozzle tip is stamped with 260 indi-
cating that it is a two-flow nozzle and must be counted as two flow
numbers.
I When using the 260 nozzle for range protection with or without
'back shelf or other similarly sized obstruction, the maximum length
of burner grates being protected must not exceed 32 in. (81 cm)
and the maximum area of the burner grates must not exceed
384 in.2 (2477 cm2). Nozzle must be located on the front edge of
the burner grates and aimed at a point 10 in. (25 cm) from the back
edge of the burner grates. Nozzle must be mounted 30 to 40 in.
'(76 to 102 cm) above the hazard surface. See Figure 38.
260 NOZZLE
SHELF OR OTHER SIMILARLY SIZED
OBSTRUCTION CAN OVERHANG BURNER(S)
BY A MAXIMUM OF 11 IN. (28 cm)
30-40 IN.
(76-102 Cm)
10 IN.
(25 cm) FROM
BACK OF
BURNER
GRATES
FIGURE 38
OOO238
EDG.
COOKING SURFACE
I MINIMUM
- 1EIGHT
IF 2120
OZZLE TIP
000243
'Griddle Protection 2W (2-Flow) Nozzle - Low Proximity I Application
Option 2c - Nozzle Perimeter Located (Continued)
10 in. to 20 in. (25 cm to 51 cm) above the cooking surface.
The low proximity application uses the 2W nozzle, Part No.
419337.
The nozzle tip is stamped with 2W indicating this is a two-flow noz-
zle and must be counted as two flow numbers.
One 2W nozzle will protect a maximum cooking area of 1080 in.2
(6967.7 cm2) with a maximum dimension of 36 in. (91.4 cm).
When using this nozzle for griddle protection, the nozzle must be
positioned along the perimeter to 9 in. (22.9 cm) inside perimeter,
and aimed at the center of the cooking surface. See Figure 49 and
50.
OVERHEAD VIEW
I .. 36 IN. (91.4 cm) MAX ------------
2W NOZZLE AIM POINT 0-3 IN. (0-7.6 con) TO REAR OF COOKING SURFACE CENTER
NE WHEN 2W NOZZLE IS SITIONED AT OR TO THE
REAR OF CENTER LINE
AIM POINT IN. (0-7.6 con) FORWARD jF
2NOZZLE
COOKING SURFACE CEN-
TER LINE WHEN 2W NOZZLE
IS POSITIONED AT OR FOR-
WARD OF COOKING SURFACE CENTER LINE
—J
4 0- 10 IN. >0.25.4 cm) FROM CENTERLINE MA
f 0- 101N. (0- 25.4 con) FROM CENTERLINE MAX.
i—i
I
30 IN.
cm>
MAX.
008149
FRONT VIEW
0.3 IN (76.2 cm)
20 IN. (50.8 cm) MAX.
10 IN.
(25.4 cm)
MIN.
NOTE: A 2W NOZZLE CAN PROTECT A GRIDDLE
WITH A MAXIMUM COCKING SURFACE
OF 30 IN X 36 IN. (76.2 cm X 91.4 con). AT A
HEIGHT OF 10-20 IN. (25.4. 50.8 con).
THE 2W NOZZLE CAN BE POSITIONED A
MAXIMUM OF ± 10 IN. (25.4 cm) FOR-
WARD OR BEHIND COOKING SURFACE
CENTER LINE AND A MAXIMUM OF 3 IN.
(7.6 cm) AWAY FROM EITHER SIDE OF
THE COOKING SURFACE, AIMED IN 9 IN.
(22.9 cm) TO A POINT 0-3 IN. (0- 22.0 con). FORWARD OR TO THE REAR OF THE COOKING SURFACE CENTER LINE.
SECTION IV - SYSTEM DESIGN
U UL EX3470 ULC EX3470 Page 4-20
REV. 5 7-1-09
'Griddle Protection 2120 (2-Flow) Nozzle - Low Proximity
Application
Option 2b - Nozzle Perimeter Located (Continued)
10 in. to 20 in. (25 cm to 51 cm) above the cooking surface.
The low proximity application uses the 2120 nozzle, Part No.
419343.
The nozzle tip is stamped with 2120 indicating this is a two-flow
nozzle and must be counted as two flow numbers.
One 2120 nozzle will protect a maximum cooking area of 1440 in.2
(9290 cm2) with a maximum dimension of 48 in. (122 cm).
When using this nozzle for griddle protection, the nozzle must
be positioned along the perimeter to 2 in. (5.1 cm) inside perime-
ter, and aimed at the center of the cooking surface. See Figure
47 and 48.
NOZZLE LOCATION
I 0-2 IN. (0-Scm)
INSIDE PERIMETER 20 IN . ._ .p..I L, OF COOKING SURFACE I I (51 CM) I MAXIMUM
I /11 HEIGHT I OF 2120
II NOZZLE TIP
I / 10 IN. (25cm) I
FIGURE 47 I P1
000243 AIM POINT 9 IN. (22.9 cm)
FROM EITHER SIDE OF
COOKING AREA COOKING SURFACE FIGURE 49
I IEf;~TER0i
h
COOKING
COOKING SURFACE p
AREA
r-1-J l— AIM POINT II IL________±J
2120 NOZZLE LOCATED ALONG COOKING SURFACE EDGE
ANY SIDE OF GRIDDLE SURFACE
WITHIN 0-2 IN. (0-5cm) OF
COOKING SURFACE EDGE. NOZZLE
MUST BE AIMED AT CENTER OF
COOKING SURFACE.
FIGURE 48
000241 (22.9 cm) FROM
EITHER SIDE OF
COOKING SURFACE
008100
FIGURE 50
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-28
REV. 6 7-1-09
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct, plenum,
or appliance.
NOTICE
This chart is for general reference only. See
complete details for each type of hazard.
Minimum
Maximum Hazard Nozzle
Hazard Dimensions Quantity
Duct or Transition Length - Unlimited 1
(Single Nozzle) Perimeter —50 in. (127 cm)
Diameter— 16 in. (40.6 cm)
Duct or Transition Length - Unlimited 1
(Single Nozzle) Perimeter - 100 in. (254 cm)
Diameter - 31 7/8 in. (81 cm)
Duct or Transition Length - Unlimited 2
(Dual Nozzle) Perimeter - 150 in. (381 cm)
Diameter —48 in. (122 cm)
Electrostatic Precipitator Individual Cell 1
(At Base of Duct)
Plenum Length - 10 ft (3.1 m) 1
(Horizontal Protection)
Plenum Length —6 ft (1.8 m) 1
(Horizontal Protection) Width - 4 ft (1.2 m) 1
Plenum Length —4 ft (1.2 m) 1
(Vertical Protection) Width - 4 ft (1.2 m)
Fryer (Split or Maximum Size
Non-Split Vat) (without drip board)
14 in. (36 cm) x
15 in. (38 cm) 1
Low Proximity
Fryer (Split or Maximum Size
Non-Split Vat) (without drip board)
14 1/2 in. (37 cm) x
14 in. (36 cm) 1
Medium Proximity
Fryer (Split or Maximum Size
Non-Split Vat)* (without drip board)
15 in. (38 cm) x
14 in. (36 cm)
High Proximity 1
Medium Proximity 1
Fryer (Non-Split Vat Only) Maximum Size
(without drip board)
19 1/2 in. (49.5 cm) x
19 in. (48.2 cm)
High Proximity 1
Low Proximity 1
Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 in. (45.7 cm)
High Proximity 1
For multiple nozzle protection of single fryers, see detailed information on Pages 4-10 and 4-11.
Nozzle Tip
Nozzle Nozzle Stamping -
Heights P&rLN Flow No.-
- 430912 1W
- 419337 2W
- 419337 2W
- 419334 1/2N
- 419335 1
- 430192 1W
- 419336 1W
- 419336 1W
13—l6in. 419342 290
(33-41 cm)
16-27in. 419342 290
(41 - 69 cm)
27-47in. 419339 230
20-27in. 419340 245
21-34 in. 419338 3N
13—l6in. 419342 290
25-35in. 419338 3N
(64-89 cm)
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-29
7-1-09 REV.6
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights EarLNo. Flow No._
Fryer (Non-Split Maximum Size
Vat Only)* (with drip board)
21 in. (53 cm) x
14 in. (36 cm)
(Fry Pot must not exceed
15 in. x 14 in.
(38 cm x 36 cm))
High Proximity 1 27 —47 in. 419339 230
Medium Proximity 1 20 —27 in. 419340 245
Maximum Size
(with drip board)
25 3/8 in. (64.4 cm)
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2 cm)
High Proximity 1 21 —34 in. 419338 3N
Low Proximity 1 13-16 in. 419342 290
Maximum Size
(with drip board)
18 in. (45.7 cm)
x 27 3/4 in. (70.5 cm)
High Proximity 1 25 —35 in. 419338 3N
(64-89 cm)
Fryer (Split or Maximum Size
Non-Split Vat) (with drip board)
14 in. (36 cm) x
21 in. (53 cm) 1 13-16 in. 419342 290
Low Proximity (33 —41 cm)
Fryer (Split or Maximum Size
Non-Split Vat) (with drip board)
14 1/2 in. (37 cm) x
26 1/2 in. (67 cm) 1 16-27 in. 419342 290
Medium Proximity (41 - 69 cm)
Range Longest Side (High Proximity) 1 30 —40 in. 419335 1 N
32 in. (81 cm) (76— 102 cm)
Area —384 sq. in.
(2477 sq cm)
Longest Side (Low Proximity) 1 15 - 20 in. 419335 1 N
24 in. (61 cm) (38 —51 cm)
Area —432 in.2
(2787 cm2)
Longest Side 40 —48 in. 419333 1 F
28 in. (71 cm) (102-122 cm)
Area - 336 sq in. (With Backshelf)
(2168 sq cm)
Longest Side (High Proximity) 1 40-50 in. 419340 245
28 in. (71 cm) (102— 127 cm)
Area - 672 sq in.
(4335 sq cm)
Longest Side
(Medium Proximity) 1 30 —40 in. 419341 260
32 in. (81 cm) (76 - 102 cm)
Area —768sq in.
(4955 sq cm)
P.• For multiple nozzle protection of single fryers, see detailed information on Pages 4-10 and 4-11.
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-30
REV.4 7-1-09
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights Part No. Flow No.
Range (Continued) Longest Side (Low Proximity) 2 15-20 in. 419342 290
36 in. (91 cm) (38 —51 cm)
Area —1008 sq in.
(6503 sq cm)
Griddle Longest Side (High Proximity) 1 30 —50 in. 419341 260
48 in. (122cm) (76-127cm)
Area - 1440 sq in. (perimeter
(9290 sq cm) located)
Longest Side (High Proximity) 1 30-50 in. 419342 290
30 in. (76 cm) (76 - 127 cm)
Area - 720 sq in. (center located)
(4645 sq cm)
Longest Side (High Proximity) 1 35 - 40 in. 419335/435672 1 N/i NSS
36 in. (91 cm) (89— 102 cm)
Area - 1080 sq in. (perimeter located)
(6968 sq cm)
Longest Side 1 20 —30 in. 419342 290
(Medium Proximity) (51 - 76 cm)
48 in. (122 cm) (perimeter
Area - 1440 sq in. located)
(9290 sq cm)
Longest Side (Low Proximity) 1 15-20 in. 4193336 1W
26 in. (66 cm) (38 - 51 cm)
Area - 533 in.2 (center located)
(3439 cm2)
Longest Side (Low Proximity) 1 10 —20 in. 419337 2W
36 in. (91 cm) (25 - 51 cm)
Area - 1080 in.2 (perimeter located)
(6968 cm2)
Longest Side (Low Proximity) 1 10-20 in. 419343 2120
48 in. (122 cm) (25-51 cm)
Area - 1440 sq in. (perimeter
(9290 sq cm) located)
Chain Broiler* Longest Side —34 in. (86 cm) 2 10-26 in. 419336/432527 1W/1 WSS
(Overhead Protection) Area - 1088 sq in. (25-66 cm)
(7019 sq cm)
Chain Broiler Length - 43 in. (109 cm) 2 1 - 3 in. 419335/435672 1 N/l NSS
(Horizontal Protection) Width - 31 in. (79 cm) (3 - 8 cm)
Gas-Radiant Char-Broiler Longest Side - 36 in. (91 cm) 1 15 —40 in. 419335/435672 1 N/i NSS
Area - 864 sq in. (38 - 102 cm)
(5574 sq cm)
Electric Char-Broiler Longest Side —34 in. (86 cm) 1 20 - 50 in. 419335/435672 1 N/l NSS
Area —680 sq in. (51 - 127 cm)
(4388 sq cm)
Lava-Rock Broiler Longest Side - 24 in. (61 cm) 1 18 —35 in. 419335/435672 1 N/l NSS
Area — 312 sq in. (46-89cm)
(2013 sq cm)
Natural Charcoal Broiler Longest Side —24 in. (61 cm) 1 18 —40 in. 419335/435672 1 N/l NSS
Area —288 sq in. (46— 102 cm)
(1858 sq cm)
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-31
7-1-09 REV. 7
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights Part No. Flow No.
Lava-Rock or Natural Longest Side —30 in. (76 cm) 1 14 - 40 in. 419338 3N
Charcoal Char-Broiler Area —720 sq in. (36 - 102 cm)
(4645 sq cm)
Wood Fueled Char-Broiler Longest Side —30 in. (76 cm) 1 14 —40 in. 419338 3N
Area —720 sq in. (36— 102 cm)
(4645 sq cm)
Upright Broiler Length —32.5 in. (82.5 cm) 2 - 419334 1/2N
Width - 30 in. (76 cm)
Salamander Length —29 in. (74 cm) 1 - 419335 1
Broiler Width - 16 in. (41 cm)
Length —31 in. (79 cm) 1 - 419333 1 F
Width - 15 in. (38 cm)
Length —31 in. (79 cm) 1 - 419335 1 N
Width —l5 in. (38cm)
Wok l4 in. —30 in. (36-76cm) 1 35-45in. 419341 260
Diameter (89 —114 cm)
3.75 - 8.0 in. (9.5 —20 cm)
Deep
11 in. — 24 in. (28 — 61 cm) 30-40in. 419335/435672 1N/1NSS
Diameter (76— 102 cm)
3.0-6.0 in. (8— 15.2 cm)
Deep
Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x31 cm), and not less than 60% of internal broiler size.
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-52
REV. 4 7-1-09
DISTRIBUTION PIPING REQUIREMENTS (Continued) START OF LAST
Distribution Piping Requirements —1.5 Gallon System BRANCH LINE
START OF FIRST
DUCT, PLENUM, AND APPLIANCE PROTECTION BRANCH LINE
This option allows for duct protection, plenum protection,
appliance protection, or any combination. However, only one SUP PLY (1) duct nozzle may be used, either a 1W or a 2W, nozzle. I LINE TEE LENGTH \ All distribution piping, supply and branch, must be 3/8 in.
Schedule 40 black iron, chrome-plated, or stainless steel.
I _---
TOTAL
MUST NOT
EXCEED 8 FT
Each 1.5 gallon tank allows a maximum of five flow numbers.*
The pipe length between the start of the first branch line and
the start of the last branch line must not exceed 8 ft (2.4 m).
f1 When the supply line is split, the combined length of both
legs of the supply line (start of first branch line to start of last ST
START OF LAST
BRANCH LINE
branch line) must not exceed 8 ft (2.4 m). See Figure 111. STARIR5T T OF L.J__.- BRANCH LINE
The combined length of all branch lines must not exceed 22 ft FIGURE 111
(6.7 m). See Figure 112. 000784
The requirements of the following table must not be exceeded: 1W NOZZLE
(BRANCH LINES IN BOLD) COMBINED LENGTH MUST
NOT EXCEED 22 FT (6.7 m)
FIGURE 112 000785
Duct Plenum Appliance
Requirements Supply Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft 6 ft 4 ft loft
(12.2 m) (1.8 m) (1.2 m) (3m)
Maximum Rise 6 ft 4 ft 2 ft 2 ft
(1.8 m) (1.2 m) (0.6 m) (0.6 m)
Maximum 90° Elbow 9 4 4 6
Maximum Tees 1 El FE 3
Maximum Flow Numbers 5* 2 2 3
Exceptions:
Six (6) flow numbers are allowed when a duct branch line Is the last branch line on the piping network and no 1 N nozzles are used to protect woks or griddles.
Six (6) flow numbers are allowed when six (6) IN nozzles are used and none of the nozzles are used to protect woks, griddles, ranges, and salamanders.
NOTE: Only live (5) flow numbers are allowed it a 1 N nozzle is used tor wok, griddle, range, or salamander protection.
Six (6) flow numbers are allowed when only two (2) 3N nozzles are used.
U
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements - 3.0 Gallon System
The maximum length between the start of the first branch line
and the start of the last branch line must not exceed 24 ft
(7.3 m). When the supply line is split, the combined total of
both legs of the supply line (from the start of the first branch
line to the start of the last branch line) must not exceed 24 ft
(7.3 m). See Figure 113.
The total length of all branch lines must not exceed 36 ft
(10.9 m). See Figure 113.
Use a 3/8 in. union to connect the tank adaptor to the 3/8 in.
supply line.
A maximum of two nozzles are allowed per duct branch line.
The requirements of the following table must not be exceeded:
SECTION IV - SYSTEM DESIGN
UL EX3470 ULC EX3470 Page 4-53
7-1-09 REV. 4
SUPPLY
TEE
UJ COMBINED LENGTH OF
BOTH LEGS OF SUPPLY
LINE MUST NOT 3 BRANCH LINES
EXCEED 24 Fr (7.3 m)
2W NOZZLE iN NOZZLE
230
NOZZLE
jJ r 245 NOZZLE 112N NOZZLE
(BRANCH LINE IN BOLD) wO5Q2 COMBINED LENGTH MUST
NOT EXCEED 36 FT (10.9 m)
FIGURE 113
C
Duct Plenum Appliance
Requirements Supply Line Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft 8 ft 4 it 12 ft
(12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft 4 ft 2 ft 2 ft
(1.8 m) (1.2 m) (0.6 m) (0.6 m)
Maximum 90° 9 4 4 6
Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11° 4 2 4
Numbers
Exceptlons:
Twelve (12) flow numbers are allowed in any one tank for duct and plenum protection only.
Twelve (12) flow numbers are allowed with any one tank using only two-flow appliance nozzles.
Twelve (12) flow numbers are allowed with any one tank using only three-flow appliance nozzles.
Special Instructions:
P. 1. Twelve (12) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32. The discharge piping must
be as shown in Figure 67 on Page 4-32.
2. For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 112N electrostatic precipitator nozzle,
one (1) iN plenum nozzle, and four (4) two-flow appliance nozzles. Contact ANSUL Applications Engineering Department for additional information.