Series TY-FRB - 28,42,56, and 80 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 2.8, 4.2, 5.6,
and 8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TY-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following,
A two-piece Style 10 (1/2 inch NPT)
or Style 40 (3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a
A two-piece Style 20 (1/2 inch NPT)
or Style 30 (3/4 inch NPT) Recessed
Escutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 10
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level of the Series TY-
FRB Pendent Sprinklers is detailed
in Technical Data Sheet TFP356, and
Sprinkler Guards are detailed in Tech-
nical Data Sheet TFP780.
NOTICE
The Series TY-FRB Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The
installing contractor or sprinkler manu-
facturer should be contacted with any
questions.
JULY 2010
Model/Sprinkler
Identification
Number (SIN)
TY1131: Upright 2.8K, 1/2- NPT
TY1231: Pendent 2.8K, 1/2" NPT
TY2131: Upright 4.2K, lIZ NPT
TY2231: Pendent 4.21K, 1/2- NPT
TY3131: Upright 5.6K, 1I2 NPT
1Y3231: Pendent 5.6K, 1/2" NPT
TY4131: Upright 8.0K, 3/4" NPT
TY4231: Pendent 8.0K, 3/4" NPT
TY4831: Upright* 8.0K, 1/2" NPT
TY4931: Pendent* 8.0K, 1/2" NPT
'Eastern Hemisphere Sales Only
TFPI7I
TFPI7I
Page 2 of 10
7/16 (11,1 mm) ESCUTCHEON
NOMINAL PLATE SEATING SSU*
DEFLECTOR MAKE-IN NPT SURFACE
6*
7/16
:
4 (11,1 mm)
NOMINAL (57,2 mm)
WRENCH
hi_ _
MAKE-IN
9/16" 3 2-3/16"
(55,6 mm)
FLATS
(39,7 mm)
t 1/2" NPT SSP DEFLECTOR*
STYLE 10 or 20
RECESSED
ESCUTCHEON
2-7/8' (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector
Assembly Temperature rating is indicated on deflector or adjacent to
2 - Button 5 - Compression 7 - Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
7/16" (11,1 mm) ESCUTCHEON
SSU* NOMINAL 1/2" PLATE SEATING
DEFLECTOR MAKE- IN NPT SURFACE
6*
(11,1 mm) 2316"
5 7/16
I NOMINAL
I MAKE IN
1/2" T
(55
2-3/16"
WRENC (3
(55,6 mm)
,6 mm) -
FLATS
mm)
1/2" NPT SSP DEFLECTOR*
STYLE 10 or 20
RECESSED
ESCUTCHEON
2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3-Sealing 4-Bulb 6- Deflector
Assembly * Temperature rating is indicated on deflector or adjacent to
2 - Button 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
TFPI7I
Page 3 of 10
ESCUTCHEON
PLATE SEATING
SURFACE
_2-16'
(55,6 mm)
I 1-1/2
(38,1 mm)
SSP DEFLECTOR *
7/16(11,1 mm)
ssu NOMINAL 1/2
DEFLECTOR MAKE-IN NPT
4 NOMINAL
T/~M/ (55,6 mm) WRENCH 3 FLATS
1/2 NPT
STYLE 10 or 20
RECESSED
ESCUTCHEON
11i: 2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3-Sealing 4-Bulb 6 - Deflector * Assembly Temperature rating is indicated on deflector or adjacent to
5 - Compression orifice seat on frame. 2 - Button Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
1/2(12,7mm) ESCUTCHEON STYLE 300r40
SSU * NOMINAL 3/4fl PLATE SEATING RECESSED
DEFLECTOR MAKE- IN NPT SURFACE ESCUTCHEON
6*
5 1 1/2
2i16' (12,7 mm)
NOMINAL (58,7 mm)
MAKE-IN
2 -1/4 I L ll -9/16
' j57,2mm (319 ,7 mm)
3/4 NPT SSP DEFLECTOR* I- 2-7/8' (73,0 mm) DIA. -i
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector
Assembly Temperature rating is indicated on deflector or adjacent to
5 - Compression orifice seat on frame. 2 - Button Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4 131) AND PENDENT (TV4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
TFPI7I
Page 4 of 10
7/16 (11,1 mm)
SSU NOMINAL
DEFLECTOR MAKE-IN 1/2"
NPT
6
5 7/16"
(11,1mm) 2-1/4"
4 NOMINAL (57,2 mm)
MAKE-IN
2 -3/16" 1-9/16'
Vj WRENC (39,7 mm) 5,6 mm) (5 I _______ _______ FLATS
SSP*_-.,
1/2" NPT DEFLECTOR CROSS
SECTION UPRIGHT PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector
Assembly Temperature rating is indicated on deflector or adjacent to
2 - Button - Compression orifice seat on frame. Screw
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and NYC Approved
Refer to Table A and B for complete
approval information including
corrosion-resistant status.
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K=2.8 GPM/psi112 (40,3 LPM/barll2)
K=4.2 GPM/psi112 (60,5 LPM/bar112)
K=5.6 GPM/psi112 (80,6 LPM/bart/2)
K=8.0 GPM/psi112 (115,2 LPM/bar1'2)
Temperature Rating
Refer to Table A and B.
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame ...................Bronze
Button..............Brass/Copper
Sealing Assembly.........Beryllium
Nickel w/Teflont
Bulb ......................Glass
Compression Screw........Bronze
Deflector...........Copper/Bronze
Bushing (K=2.8) ...........Bronze
t Registered Trademark of Dupont
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB Pendent
and Upright Sprinklers are intended
for fire protection systems designed in
accordance with the standard installa-
tion rules recognized by the applicable
Listing or Approval agency (such as, UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based on
the requirements of FM's Loss Preven-
tion Data Sheets). Only the Style 10,
20, 30, or 40 Recessed Escutcheon, as
applicable, is to be used for recessed
pendent installations.
Installation
The TYCO Series TY-FRB Sprinklers
must be installed in accordance with
the following instructions.
NOTICE
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 135°F/57°C and
3/32 inch (2,4 mm) for the 286°F/141°C
temperature ratings.
Obtain a leak-tight 1/2 inch NPT sprin-
kler joint by applying a minimum to
maximum torque of 7 to 14 ft.Ibs. (9,5
to 19,0 Nm). Higher levels of torque
can distort the sprinkler Inlet with con-
sequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
The Series TY-FRB Pendent and
Upright Sprinklers must be installed
in accordance with the following
instructions.
Install Pendent sprinklers in the
pendent position. Install upright
sprinklers in the upright position.
With pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 6
Sprinkler Wrench (Figure 14). With
reference to Figures 1 through
5, apply the W-Type 6 Sprinkler
Wrench to the sprinkler wrench
flats.
TFPI7I
Page 5 of 10
SPRINKLER FINISH (See Note 5)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
FCHROME
ATED
I WHITE***
POLYESTER
2.8
1/2" NPT
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135°F/57°C Orange
1, 2, 3, 4
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286F/141C Blue
RECESSED
PENDENT (TY1231)*
Figure 6
135°F/57C Orange
1,2, 4
155°F/68°C Red
175F/79°C Yellow
200°F193°C Green
RECESSED
PENDENT (TY1231)**
Figure 7
135°F/57C Orange
- 155°F/68C Red
175F/79°C Yellow
200°F!93°C Green
4.2
1/2" NPT
PENDENT
(TY2231)
and
UPRIGHT
(1Y2131)
135°F/57°C Orange
1,2
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
RECESSED
PENDENT (TY2231)*
Figure 8
135°F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT (TY2231)**
Figure 9
135F/57°C Orange
155°F/68°C Red
175°F!79°C Yellow
200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40(3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 AND 4.2 K-FACTOR SPRINKLERS
TFPI7I
Page 6 of 10
SPRINKLER FINISH (See Note 8)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED
I WHITE***
POLYESTER
LEAD
COATED
5.6
1/2" NPT
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57C Orange
1, 2, 3, 4, 5, 6, 7
Blue
1, 2, 3, 5
155°F/68C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C
RECESSED
PENDENT
(TY3231)*
Figure 10
135°F/57°C Orange
1, 2, 4, 5
Blue
N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C
RECESSED
PENDENT (TY3231)**
Figure 11
135F/57°C Orange
1, 2, 3, 4, 5
Blue
N/A
155F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C
8.0
3/4" NPT
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C Orange
1, 2, 3, 4, 5, 6, 7
Blue
1, 2, 5
155F/68°C Red
175°F/79C Yellow
2O0F/93°C Green
286F/141C
RECESSED
PENDENT
(TY4231)
Figure 12
135°F/57°C Orange
1, 2. 5
Blue
N/A
155F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141C
RECESSED
PENDENT (TY4231)**
Figure 13
135F/57°C Orange
1, 2, 3, 5
Blue
N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C
8.0
1/2" NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135°F/57°C Orange
1, 2, 4, 5, 6
Blue
1, 2, 5
155°F/68°C Red
175°F/79C Yellow
200°F/93°C Green
286°F/141°C
NOTES: Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax
31-53-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved
as a Corrosion-Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I
Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD
FACTOR BRASS PLATED POLYESTER COATED
PENDENT (TY1231)
and
2.8
UPRIGHT (TY1131)
1/2" NPT 75 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY1231)
PENDENT (TY2231)
and
4.2
UPRIGHT (TY2131)
1/2" NPT 175 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY2231)
PENDENT (TY3231) 175 PSI
5.6
and
UPRIGHT (TY3131) 250 PSI (17,2 BAR) (12,1 BAR)
1/2" NPT OR 175 PSI (12,1 BAR)
RECESSED (SEE NOTE 1)
N/A PENDENT (TY3231)
PENDENT (TY4231) 175 PSI and
UPRIGHT (TY4131)
(12,1 BAR)
8.0
3/4" NPT 175 PSI (12,1 BAR)
RECESSED N/A PENDENT (TY4231)
8.0 PENDENT (TY4931) 175 PSI
1/2" NPT and
UPRIGHT (TY4831)
175 PSI (12,1 BAR) (12,1 BAR)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL): and, the Approval by the City of New York.
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
After installing the Style 10, 20, 30,
or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and
with pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Fig-
ure 15). With reference to Figures 1
to 4, apply the W-Type 7 Recessed
Sprinkler Wrench to the sprinkler
wrench flats.
After ceiling installation and finish-
ing, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TABLE C
MAXIMUM WORKING PRESSURE
Care and
Maintenance
The TYCO Series TY-FRB must be
maintained and serviced in accordance
with the following instructions.
MUM
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
Exercise care to avoid damage to
sprinklers before, during, and after
installation. Never paint, plate, coat,
or otherwise alter automatic sprinklers
after they leave the factory.
Replace sprinklers that:
were modified or over-heated.
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
are leaking or exhibiting visible signs
of corrosion.
were exposed to corrosive products
of combustion but have not oper-
ated, if you cannot easily remove
combustion by-products with a cloth.
have a cracked bulb or have lost liq-
uid from the bulb. Refer to the Instal-
lation section in this data sheet.
TFPI7I
Page 8 of 10
2-7/8 DIA. -
5/8±1/4
(7310 mm) 3/4" (19,1 mm)
2-1/4 DIA. 1/4' (6.4 mm) I (15,9±6,4 mm)
(572 mm) -H FACE OF MOUNTING I
SPRINKLER PLATE
FITTING
1/8
4/mm)
MOUNTING /
SURFACE
,,
/"
CLOSURE SERIES 1-5/16' (33,3 mm)l
TY-FRB 13/16 (20,6 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
(73,0 mm) 3/4" (19,1 mm) 5/8±1/4" r (15,9±6,4 mm) 2-1/4" DIA. 1/4' (6,4 mm) I
FACE OF (572 mm) MOUNTING I
SPRINKLER PLATE
FITTING
MOUNTING /
SURFACE/ SERIES
1-1/4(31,8 mm)1 CLOSURE TY-FRB 3/4" (19,1 mm)
FIGURE 8
SERIES TV-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -I (73,0 mm)
1/2±1/8" 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) I -
(572mm) I FACE OF I MOUNTING I SPRINKLER PLATE
FITTING I
MOUNTING /
SURFACE///
CLOSURE SERIES 1-5/16" (33,3 mm)1
TY-FRB 1-1/16" (27,0 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
1/2±1/8"
(73,0 mm) 1/2"(127 mm) r (12,7±3,2 mm) 2-1/4" DIA
-
1/4 (6,4 mm)
FACE OF MOUNTING
SPRINKLER PLATE
FITTING
17771 7,
MOUNTING
SURFACE
SERIES 1-1/4(31,8 mm) 1 CLOSURE TYFRB 1" (25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
Responsibility lies with the owner for
the inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any other authorities having jurisdic-
tion. Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
TFPI7I
Page 9 of 10
CLOSURE SER
2-7/8 DIA. - (73,0 mm) 3/4" (19,1 mm)
2-1/4 DIA. 1/4 (6,4 mm)
(57,2 mm) MOUNTING f -
1-1/4" (31,8 mm)
3/4' (19,1 mm)
2-7/8" DIA.
(73,0 mm) 1/2" (12,7 mm)
2-1/4" DIA . —1 1/4" (6,4 mm)
(57,2 mm)
t PI
MOUNTING
ATF
1/8"
(3,2 mm)
CLOSURE SERIES 1-1/4" (31,8 mm)
1" (25,4 mm)
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
(3,2 mm)
T__7_ -
MOUNTING
MOUNTING SURFACE
SURFACE
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
/
2-7/8" DIA.
(73,0 mm) 3/4'(19,1 mm)
2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm)
I
MOUNTING
01 A=
1/8"
(3,2 mm)
2-7/8" DIA.
(73,0 mm) - 1/2" (12,7 mm)
2-1/4' DIA. 1/4" (6,4 mm)
(57,2 mm) MOUNTING
DI ATr-
(3,2 mm)
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB
1-5/16" (33,3 mm)
13/16" (20,6 mm)
t \ -
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W- TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
PUSH WRENCH IN TO
ENSURE ENGAGEMENT WITH
SPRINKLER WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI7I
Page 10 of 10
P/N 57- XXX- X- XXX
I L
MODEL/SIN
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2"NPT) TY2231
370 5.6K UPRIGHT (1/2"NPT) TY3131
371 5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (3/4"NPT) TY4131
391 8.0K PENDENT (3/4"NPT) TY4231
360 8.OK UPRIGHT (1/2"NPT) TY4831°
361 8.0K PENDENT (1/2"NPT) TY4931*
SPRINKLER TEMPERATURE
L FINISH ___
RATINGS
1 NATURAL BRASS 135 135-F (57-C)
4 WHITE POLYESTER 155 155°F (68°C)
3 WHITE (RAL9010)' 175 175°F (79°C)
9 CHROME PLATED 200 200°F (93°C)
7 I LEAD COATED I I 286 1 286°F (141°C)
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation in
connection with the sale of products or
parts of products. TFSBP shall not be
responsible for sprinkler system design
errors or inaccurate or incomplete infor-
mation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and fitness for a particular
purpose.
This limited warranty sets forth the
exclusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim is
made in contract, tort, strict liability or
any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*).
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Refer to Technical Data Sheet TFP770.