Fire Alarm Permit
Permit No: FA160038
Job Address: 6195 EL CAMINO REAL
Permit Type: FALARM
Parcel No: 2131001800
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 7/13/2016
Approved: 7/13/2016
Issued: 7/13/2016
Inspector:
Project Title: SAFC 6195 EXPANSION PHASE 2 PROVIDE AND INSTALL NEW
DEISGO FC2005 (50-POINT) ADDRESSABLE FIRE ALARM CONTROL
PANEL. -PROVIDE AND INSTALL NEW NOTIFICATION DEVICES, MULTI
CANDELLA HORN/STROBES, FOR THE RENOVATED AREA PER NEW
CEILING AND WALL LAYOUT IN ALL COMMONLY OCCUPIED SPACES
AND OFFICES WITH MORE THAN 2 WORKSTATIONS. -PROVIDE AND
INSTALL NEW SPOT TYPE SMOKE DETECTOR IN ELECTRICAL ROOM
(123) FOR FACP PROTECTION. -PROVIDE AND INSTALL NEW
MANUAL PULL STATION IN ELECTRICAL ROOM (123) AT FACP. -
PROVIDE AND INSTALL ADDRESSABLE MONITOR MODULES FOR
FIRE SPRINKLER WATERFLOW AND TAMPER SWITCH SUPERVISION.
Fees ($) Add'I Fees ($) j Total ($) Balance ($)
497 0 497 0
Siemens Building Technologies, Inc.
FIS Fire I Life Safety Division
10100 Willow Creek Rd
San Diego, California 92123
(858) 693-8711
Equipment Submittal
FIRE ALARM SYSTEM
NEW INSTALLATION
For:
SAFC 6195 EXPANSION
6195 EL CAMINO REAL
CARLSBAD, CA 92009
440P-186988
01/15/2016
FAI 60038
6195 EL CAMINO REAL
M
[FIRE ALARM CONTROL PANEL AND ACCESSORIES]
SIEMENS Data Sheet
Fire Safety Products
Desigo® Fire Safety System
50-Point Addressable Fire Alarm Control Panel
Model FC2005
HITECT AND ENGINEER SPECIFICATION
Fire alarm control panel (FACP) for up to 50 addressable points
that is comprised of the following three (3) system components:
Main board (Model FCM901-U2)
6.5 Amps (170-Watt) power supply (Model FP2011-Ui)
System enclosure (Model FH901-U2 /R2)
System features:
Supports 50 addressable devices on one (1) 'Class A' or two (2) 'Class B' circuits
Includes one (1) 'Class A', or two (2) 'Class B' notification appliance circuits (NACs)
Supports Carbon Monoxide (CO) detection
Built-in digital alarm communication transmitter (DACT)
Built-in RS-485 connection for remote annunciators
Supervised remote printer via Desigo's Model FCA2018-Ui
Downloads, prints system-event history & detector sensitivity
Resettable and non-resettable 24VDC auxiliary power
Optional connectivity to a leased-line/city-tie module • Alphanui
Off-normal warning message prior to reset • for manudi LUIlIIUIøLIUII
Fast and easy set-up with custom-configuration tool
Supports a 182-character display • ®UL 864 9th Edition Listed;
Programmable function keys FM, CSFM & NYC Fire Department Approved
Product Overview
Model FC2005 is an addressable FACP that provides
a cost-effective solution for simple fire-alarm-system
applications.
Small and compact in design, Model FC2005 is ideal
for small fire-protection applications using less than
50 addressable devices:
retail outlets I strip malls • doctors' offices
dry-cleaner shops - restaurants, etc
With its built-in DACT and two (2) NACs, Model
FC2005 is powerful enough to economically meet the
needs of these applications. Each 50-point FACP is
FM (43010); CSFM (47165-0067:0259) and FDNY
(#61 04) Approved.
Specifications
The Model FC2005 FACP consists of a main board
(Model FCM901 -U2); a 170-Watt power supply
(Model FP201 1-Ui), and a Model FH901 -U2 I R2
system enclosure. The programming software for
Model FC2005 is held in flash electrically erasable
programmable read-only memory (EEPROM).
Main Board
The Model FCM901 -U2 main board provides system
display and control, as well as connections for system
field wiring, via removable terminal blocks.
The 3.5-inch (8.9 centimeters) by 1.5" (3.8
centimeters) liquid-crystal display (LCD) screen shows
all system messages and event status. Each screen
supports 182 characters: seven (7) lines with 26
characters per line. Each event may have a custom
message up to 40 characters that describes the
event's location.
The backlit LCD screen illuminates on any system
event or manual key press. New, 'unacknowledged'
events are indicated by a flashing exclamation point
(!). Once 'acknowledged,' the exclamation point
changes to a check mark ('f'). A system-status line
shows the quantity of events presently active.
The main board supports system-status light-emitting
diodes (LEDs), based upon the following conditions I
events of Model FC2005:
Power • Alarm
Trouble • Supervisory
Ground-Fault
Desigo 50-Point Addressable FACP 681 3
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
There are also LEDs to indicate when audible circuits
are 'active' or 'silenced.' The main board supports
four (4) system-control buttons, including:
Acknowledge; Alarm Silence; Unsilence, and Reset.
The system offers an off-normal warning feature,
alerting users when active devices are not ready fcr
reset. These active devices may include manual
stations that have not been reset; smoke detectors
with smoke remaining in the optical chamber, etc.
Additionally, the main board supports an
alphanumeric keypad, as well as navigation keys,
which are used for scrolling maintenance functions
and system configuration.
The main board supports connection for up to 50
addressable devices, via one (1) 'Class A', or two (2)
'Class B' circuits. The loop supports all FDnet devices,
including the Desigo Fire Safety and Model 'H'-series
devices. The main board also supports one (1) 'Class
A' or two (2) 'Class B' NACs.
Each NAC supports a maximum 2.5 Amps—with 2.5
Amps, max., allowed between both NACs. Each NAC
can be set to a synchronized strobe, for horn-strobe
devices, or for audible devices. Audible devices can
be set for:
'STEADY
'ANSITemporaI3'
'March Time 30 / 60 /120 Codes'
The main board supports four (4) 'Form C relays for
Alarm, Trouble, Supervisory and user-programmable
events. Each relay is rated at 2 Amps at 30VDC
maximum, resistive. The main board supports two
(2) auxiliary 24VDC connections. Upon system reset,
one (1) connection interrupts the power for five
seconds for use with (4) four-wire conventional
detectors. Each auxiliary-power output is 24VDC,
nominal - rated at 0.75 Amps.
The main board contains a built-in DAd (Model
FCA201 5-Ui), which provides communication
between Model FC2005 and with the central or
remote monitoring station. The built-in DACT
supports two (2) separate programmable accounts,
as well as two (2) connections to the public-switched
telephone network. The connections support RJ31 X
male connectors.
(For compatibility with each Model FC2005 FAc?, see
the Central Station Receiver Compatibility Table
on the last page of this data-sheet document.)
The main board contains a battery-charging circuit,
providing connection to lead-acid batteries rated at
24VDC, nominal. The main board can charge up to
i 8AH batteries.
SIEMENS Industry, Inc.
Building Technologies Division
The main board contains a universal serial bus (USB)
connector that supports connection for system
configuration and module firmware upload, via the
custom-configuration tool.
Model FC2005 can be configured using the custom-
configuration tool or manually from the
alphanumeric keypad on the main board. An auto-
configuration feature creates a basic system
configuration of all connected devices to accelerate
initial system commissioning.
50-Point Power Supply
The Model FCM901 -U2 main board also supports
connection to the system power supply. The 6.5
Amps (170-Watt) power supply, Model FP2011-U1,
incorporates a 4.OA, non-resettable slow-blow fuse
on the primary input. It also includes a built-in AC-
line filter for surge and noise suppression. Model
FP201 1-U1 mounts in a standard Siemens - Fire
Safety enclosure, and there are no serviceable
Siemens - Fire Safety parts to be maintained.
50-Point System Enclosure
The Model FH901 -U2 I R2 enclosure for the Model
FC2005 FACP is available in either black or red, and
supports all system modules. The enclosure also
supports 1 2A batteries.
Note: For systems requiring larger than 12AH batteries,
use a ®UL Listed battery box.
The Model FH901-U2 I R2 enclosure for the 50-point
panel is comprised of a dual-mounting setup that
allows the main board to be partially mounted in a
lower-to-upper position. When temporarily installed
in the lower position, technicians are allowed more
space to install field wiring at the time of system set-
up. When field-wiring installation is complete, the
main board shall be moved to the upper position for
standard mounting prior to applying power to the
system.
Additionally, the enclosure supports an optional
battery bracket (Model FHA90i-U1)that can be used
to secure batteries up to i 2AH. Model FHA901 -Ui is
required to comply with seismic certification,
pursuant to ASC I SEI 7-05, Section 13.2.2.
A flush-mount trim kit (Model FHA902-Ui I Ri) is also
available for use when flush mounting Model FH901 -
U2 I R2.
Specifications - (continued)
Optional Accessories
The Model FC2005 FACP has the capability of
operating an optional leased-line, city-tie module
(Model FC12020-Ul) that provides a local-energy
output for municipal call-box connection. The leased-
line, city-tie module is installed on the back of the
Model FC2005 FACP's main board, and all field wiring
is connected to the main board.
Model FC2005 contains a built-in RS-485 connection
on the main board, thus eliminating the need for an
additional communication module. The fire-system
displays (FSD901 -U2 / 112) are remote LED / LCD units
that show the existing status of the Model FC2005
FACP.
The Model FSD901 -U2 I R2 optional display supports
the following LEDs for system-status conditions:
Power
Alarm
Trouble
Supervisory
Ground-Fault
There are also LEDs to indicate when audible circuits
are 'active' or 'silenced.' The main board supports
four (4) system-control buttons, including:
Acknowledge; Alarm Silence; Unsilence, and Reset.
For Model FSD901 -U2 I R2, a LED will illuminate for
any given Alarm, Supervisory and Trouble Desigo-
system event. A 3.5-inch (8.9 centimeters) by 1.5"
(3.8 centimeters) LCD screen will give details of the
event in alphanumeric form. The display screen can
be scrolled to reveal additional events. Optional
remote-system-control capabilities are also available.
The Remote Peripheral Module (FCA201 8-Ui)
provides a means of connecting a Model FC2005
Desigo FACP to a parallel printer for creating a hard
copy of system-status events.
This supervised, intelligent module contains built-in-
transient protection and plain-decimal addressing.
When Model PAL-1 is used with the remote
peripheral module, Model FCA201 8-Ui supervises
the printer for On I Off Line, Power On, Paper Out,
Paper Jam, and wiring-fault conditions, as required
by UL for NFPA 72 proprietary systems.
The dimensions (based upon connection to a one-
height-unit enclosure) for Model FC2005 are as
follows:
Approximate size: 16.25" (41.3 cm.) [H];
18" (46 cm.) [W];
5" (41.3 cm.) [D]
The weight (without operating unit or batteries)
is approximately 9 Lbs [4082 g].
SIEMENS Industry, Inc.
Building Technologies Division
Temperature and Humidity Range
Model FC2005 is ®UL 864 9th Edition Listed for indoor
dry locations within a temperature range of
120+1-3°F (49+/-2°C) to 3 2+1-3°F (0+/-2°C) and a
relative humidity of 9342% at a temperature of
90+/-3°F (32+/-2°C).
Related Documentation
Product Data Sheet Number
Model FP2011-U1 Power Supply 6806
Leased-Line I City-Tie Module 6810
Remote Peripheral Module 6811
50-Point Remote Annunciator 6817
Details for Ordering
Model Part Description
Number
FCM901-U2 S54433-B100-A1 Desigo Main Board
{for_ the _50-point_FACP}
FH901-U2 554433-B103-A1 System Enclosure, Black
{for the _SO-point_FACP}
FH901-R2 554433-B103-A2 System Enclosure, Red
(for _the _50-point_FACP}
FP2011-U1 500-450222 170-Watt Power Supply
Optional Accessories
Model Part
Number Description
FCA2018-U1 554400-A65-A1 Remote Peripheral Module
FC12020-U1 554400-A57-A1 Leased-Line / City-Tie Module
FHA901-U1 554433-B107-A1 Battery Bracket
FHA902-U1 554433-B1 06-Al Flush-Mount Trim Kit, Black
FHA902-R1 S54433-Bi 06-A2 Flush-Mount Trim Kit, Red
FSD901-U2 S54433-Cl 02-A4 System Display, Black
{for the 50-point FACP}
F5D901-R2 554433-C102-A3 System Display, Red
{for the SO-point FACP}
Electronics Package
Model Part
Number Description
Desigo Fire Safety Kit for the
50-Point Addressable FACP
170W power supply,
Model FP2011-U1
FC2005-U2 S54433C103A1 (Qty. 1)
Includes: System main board,
Model FcM901-u2
(Qty. 1)
Central Station Receiver Compatibility Table
The following table S:10WS a list of central station receivers that are
compatible with the Desigo Fire Safety 50-point addressable system,
Model FC2005 -
0
o o
-4 D -
D>
- D1 1 0 0
o o o E E u° • uO
Protocol x oo (' o'ø
-
51A8 V V V V V V V
SIA2O V V V V V I V
Ademco Contact lD V V V V V
4/2 V V V
3/1 V/ V/
Note: Multiple central station receivers are compatible with the Desigo Fre Safety
50-point FAcP, Model FC2005.
Although the table above illustrates central station receivers that have been
verified by Siemens with the Model FC2005 FAcP, additional receiters and
formats can also be used with each 50-point addressable system.
After completing the installation, communication between the Dig tal Alarm
Communication Transmitter (Model DACT) and central Station Receiver must
be tested and verified.
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario February 2015
Building Technologies Division Tel: (973) 593-2600 (sll-fs) L6H 0H6 I Canada Supersedes sheet dated 5/14
FAX: (908) 547-6877 Printed inU.S.A. Tel: [905] 465-8000 (Rev. 11)
uRL: www.USA.Siemens.coml0eslgo-Fire-Safety URL: www.Siemens.cA-
CELLULAR ALARM
TG=7FS COMMUNICATOR
P/N:TG7GFSO4 FOR 3G/4G NETWORKS
t COMMERCIAL FIRE
PRODUCT FEATURES
Meets UL 864 requirements for sole, primary or backup path
communications.
E- Provides RMR protection by leveraging technology that operates
on 3G/4G networks.
I- Supports listen-in, two-way voice verification over cellular.
- Minimizes false alarms by providing dual paths for self-tests.
I Falls back to 2G (GSM) if a 3G/4G network isn't available.
TELGUARD
The Telguard TG-7FS is the ideal cellular alarm communications solution
for commercial fire systems. The TG-7FS transmits alarm signals from
the fire panel over the digital cellular network to the designated
monitoring station.
Compliant with the 2013 Edition of NFPA 72, the TG-7FS can serve as
the sole communications path for the fire alarm system. It replaces
all of the landlines currently dedicated to the master control unit. On
average, cellular monitoring costs the end user significantly less than
a dedicated landline. For each landline replaced with a TG-7FS, the
monthly communications bill decreases.
By being able to signal failures to the central station within sixty
minutes of an outage, the TG-7FS can be installed as the sole path for
commercial fire installations. For existing installations, all landlines
can be swapped for a single TG-7FS because of the new sixty minute
supervision mode.
The TG-7FS can also be installed as a backup path and upgraded to sole
path at a later date.
,TA 1
VOLY
TELG UARD
TG=7FS
P/N: TG7GFS04
CELLULAR ALARM
COMMUNICATOR
FOR 3G/4G NETWORKS
Ica
Telguard technology allows full data reporting for unlimited
point-to-point signal details and maximum transmitting power for
superior in-building penetration.
Telguard products are easy to install, economical, and UL Listed.
Accessories
ACD 12, ACD 35, ACD 50, ACD 100:
12/35/50/100 feet of low loss, high performance cable.
HGD-0: High gain directional antenna.
EXD-0: External antenna.
UL Listings
Commercial Fire
864 • Control units &
accessories for fire
alarm systems
Commercial Burglary
365 • Police Station
connected burglar
alarm units and
systems
1610 • Central station burglar
alarm units;
Line security servcies
Residential
985 • Household fire
warning systems
For the most current product specifications and UL Listings visit www.Telguard.com.
() C]ELECTRONIC
I ICTCfl NFPA LISTED U INTERNATIONAL
Telguard, a Division of Telular Corporation Cumberland Center IV 3225 Cumberland Blvd Suite 300 Atlanta, GA 30339 USA
800-229-2326, Option 5 www.Telguard.com Copyright c 2012 Telular Corporation All Rights Reserved
SIEMENS Data Sheet
Fire Safety Products
Accessories
System Battery Sets
Models 13P-61; BT-series and BTX-series
ARCHITECT AND ENGINEER SPECIFICATIONS
24 VDC, nominal for ancillary power of fire n Irm
control panels (FACPs)
7AH, 10AH, 15AH, 31AH, 55AH & 100AH
(Amp-hour) battery sets
Sealed, lead-acid and rechargeable types
Mounts in a system enclosure, or in
Models 1313-55, BB-55R battery boxes
Detector-component compatibility
Product Overview
Siemens - Fire Safety battery sets are
manufactured by major suppliers of batteries,
such as: Werker, Johnson Controls, Yuasa
Batteries, Inc. and EaglePicher Technologies,
LLC.
As the manufacturers improve the design of
their batteries, the amp-hour rating will
increase. However, the dimensions of the
batteries will remain the same to ensure
proper fit in the system enclosures, as
specified.
If the system enclosure does not house the
required battery set, use the Model BB-55
battery box: [data-sheet number, 3326.]
Model BB-55 can house any of the available
battery sets.
Details for Ordering
Model Part
Number Description
BT-33 175-387141 7-Amp-Hour Battery Set
BT-34 175-387140 10-Amp-Hour Battery Set
BP-61 175-387194 15-Amp-Hour Battery Set
BTX-1 175-083897 31-Amp-Hour Battery Set
BTX-2 175-083898 55-Amp-Hour Battery Set
BTX-3 599-034220 100-Amp-Hour Battery Set
Notes:
The amp-hours stated above are minimum ratings.
The actual batteries installed may exceed the indicated rating.
SXL® is listed with BT-33, BT-34 and BP-61 only.
System Battery Sets 3361
SIEMENS Industry, Inc.
Building Technologies Division
Dimensions
BT-33
(pL.t) r I— n
I2V7AH
5Lbs.
I..------
(+)
BT-34
(+) _) (1 pt)
r •I fl
GVIOAH cc
4.6 Lbs.
J-----5.95 "-----11
BP-61
(1prt)
r 171
24V16AH
27.5 Lbs. 46
r----------------- 13.42 -------------------
BTX-1 Set)
(+) (-)
I2V3IAH
26.6 Lbs.
-7.78 ---------e'
BTX-2
(+) (-.)
'
(Lper i)_____ri __
I
12V 5SAH
40 Lbs.
110.26M----------
BTX-3
-r
I
¶ I __I '1
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety
8 Fern-wood Road
SIEMENS Industry, Inc. Florharn Park, NJ 07932 November 2014
Building Technologies Division Tel: (973) 593-2600 sll-Fsi Supersedes sheet dated 6/2012
FAX: (908) 547-6877 Printed in U.S.A. (Rev. 3)
URL: www.usa.Siemens.com/Fire
SIEMENS Data Sheet
Fire Safety & Security Products
Des ig OTM Fire Safety System
Remote Annunciator for the 50-Point Addressable System
Model FSD901-U2, FSD901-R2
ARCHITECT AND ENGINEER SPECIFICATIONS
Displays the existing status of the 50-point
addressable fire alarm control panel (FACP)
Liquid-crystal display (LCD) screen shows
the same event message display as the
main FACP display
Includes light-emitting diodes
(LEDs) for system status
Supports 'Acknowledge'; 'Alarm Silence';
'Unsilence,' and 'Reset' controls
Keyswitch prevents unauthorized access
Product Overview
The Desigo Fire Safety Model FSD901 -U2 I R2 are
separate LED I LCD remote annunciators that show
the existing status of the 50-point addressable FACP
(Model FC2005). Each remote annunciator
connects to the Desigo 50-point FACP through a
built-in RS-485 connection on the main board.
A 3.5-inch (8.9 centimeters) by 1.5" (3.8
centimeters) LCD screen will give details of the
event in alphanumeric form. The display screen
can be scrolled to reveal additional events. Each
screen supports 182 characters: seven (7) lines
with 26 characters per line.
Optional remote-system-control capabilities are also
available. A keyswitch is also provided to prevent
unauthorized access to the control operations.
Additionally, Model FSD901-U2 IR2 contains
navigation keys that are used for scrolling through
the list of FACP events. The programming software
is held in flash electrically erasable programmable
read-only memory (EEPROM).
Each remote annunciator is FM (43010); FDNY
(#61 04) and CSFM (17165-0067:0259) Approved.
®UL 864 9th Edition Listed;
FM, CSFM and NYC Fire Department Approved
Each Model FSD901 -U2 I R2 Remote Annunciator
supports the following LEDs for system-status
conditions: Power; Alarm; Trouble; Supervisory,
and Ground-Fault.
Note: Each remote annunciator can have its own 'Normal'
system message. Further, Model FSD901-U2 IR2 can be
configured to display any aforesaid system command, or
any combination of FACP events.
There are also LEDs to indicate when audible
circuits are 'active' or 'silenced.' Each remote
annunciator supports four (4) system-control
buttons, including: 'Acknowledge'; 'Alarm Silence';
'Unsilence', and 'Reset'.
The dimensions for each Model FSD901 - U2 I R2
remote annunciator are as follows:
Approximate size: 8.5" (21.6 cm.) [H];
11.25" (28.8 cm.) [W];
2.5" (6.4 cm.) [D]
Note: Up to eight (8) remote annunciators are supported for
each 50-point addressable FACP.
The weight of each remote annunciator is
approximately 4 Lbs [1814 g.].
Remote Annunciator for the 50-Point Fire Alarm Control Panel 6817
SIEMENS Industry, Inc.
Building Technologies Division
Temperature and Humidity Range Related Documentation
Each Model FSD901-U2 /R2 Remote Annunciator
is oUL 864 9th Edition Listed for indoor dry
locations within a temperature range of
1 20+/-3°F (49+/-2°C) to 3 2+/-3°F (0+I2DC) and a
relative humidity of 93+/-2% at a temperature of
90+/-3°F (32+/-2'C).
Product I Data Sheet Number
Desigo Fire Safety 50-point 6813 Addressable System
Details for Ordering
Model Part Description Number Number
FSD901 -R2 554433-Cl 02-A3 Remote Annunciator, Red
{for the 50-point addressable system}
FSD901-U2 S54433-Cl 02-A4 Remote Annunciator, Black
{for the 50-point addressable system)
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario June 2013 Building Technologies Division Tel: (973) 593-2600 5(1-Is) L6T 5E4 / Canada Supersedes sheet dated 2/13 FAX: (908) 547-6677 Printed in U.S.A. Tel (905) 7999937 (Rev. 3)
uRL: www.usa Siemens.com/Fire FAX: (905) 799-9858
[INITIATING DEVICES]
SIEMENS Data Sheet
Fire Safety Products
Intelligent Detection Devices
Intelligent FirePrintTM Multi-Criteria Detector
[For use with FireFinder® XLS and FS-250 Panels]
Model HFP-1 I
ARCHITECT AND ENGINEER SPECIFICATIONS
Most sophisticated 'detector intelligence' available
Easily programmed to match specific hazard profiles from the fire alarm control panel (FACP)
FirePrinP technology to differentiate between deceptive phenomena and an actual fire
Supports software-based automatic environmental compensation
System logic activation based on any of three (3) inputs
from the detector (smoke, heat or neural network)
Remote sensitivity-measurement capability
Pre-alarm reporting based on fire-profile selection
Polarity insensitive utilizing Sure Wire technology
Multi-color detector status light-emitting diode (LED)
Compatible with Model DPU (device programmer! tester unit)
Field-cleanable chamber with replaceable chamber parts available
Multi-criteria fire detection for the price of a photoelectric detector
Optional fully programmable relay base, audible base and duct housing
Detectors are self-testing:
complete diagnostics every four seconds • ®UL and ®ULC Listed;
Two-wire operation FM, CSFM & NYC Fire Department Approved
Product Overview
Model HFP-1 1 utilizes advanced detection technology
that allows each detector to distinguish non-
threatening deceptive phenomena —such as cigarette
smoke, from actual fire hazards, while optimizing
detection for the area it is intended to detect. Model
HFP-1 1 uses state-of-the-art microprocessor circuitry
with error check, detector self-diagnostics and
supervision programs.
Model HFP-1 1 is compatible with the Siemens—Fire
Safety field device program /test unit (Model DPU),
which is a compact, portable, menu-driven accessory
for electronically programming and testing detectors,
easily and reliably.
Model DPU eliminates the need for cumbersome,
unreliable mechanical programming methods—such
as dials or switches, and reduces installation and
service costs by electronically programming and
testing the detector prior to installation. Model HFP-1 1
is compatible with FS-250 and Fire Finder XLS FACPs.
Specifications
Model H FP-1 1 is a plug-in, two-wire and multi-sensor detector
(with both photoelectric and thermal inputs) that is compatible
with FireFinder XLS and FS-250 series of FACPs.
Each detector consists of a dust-resistant, field-cleanable and
photoelectric chamber; a solid state, non-mechanical thermal
sensor, and microprocessor-based electronics with a low-profile
plastic housing. Model HFP-1 1 utilizes state-of-the-artASIC
circuitry and surface-mount technology for maximum reliability.
Every Model HFP-1 1 fire detector is shipped with a protective
dust cover. Model HFP-1 1 utilizes an infrared light emitting
diode (IRLED), and light-sensing photodiode. Under normal
conditions, light transmitted by the LED is directed away from
the photodiode and scattered through the smoke chamber in a
controlled pattern.
Model H FP-1 1 is ®Underwriters' Laboratory and Underwriters'
Laboratory of Canada Listed.
FirePrintTM Multi-Criteria Detector 6301
SlEMENsIndustry, Inc.
Building Technologies Division
Specifications - (continued)
The smoke chamber is designed to manage light
dissipation and extraneous reflections from dust particles
or other non-smoke, airborne contaminants in such a way
as to maintain stable, consistent detector operation.
When smoke enters the detector chamber, light emitted
from the IRLED is scattered by the smoke particles, and is
received by the photodiode.
Model HFP-1 1 also utilizes a modern, accurate and
shock-resistant thermistor to sense temperature
changes. The'on-board'FirePrintrm technology allows
the detector to first gather smoke and thermal data, and
then analyze this information in the detector's 'neural
network.' By comparing data received with the
common characteristics of fires or fire fingerprints,
Model HFP-1 1 can compare these 'fire prints' to those of
deceptive phenomena that cause other detectors to
false alarm.
FirePrint
The advanced FirePrint technology allows Model HFP-11
to accurately determine a true fire hazard from
unthreatening, deceptive phenomena. Further, the
advanced FirePrint technology will not require a need to
use alarm-delaying verification and confirmation
techniques, which can increase the probability of tosses
due to fire. Model H FR-i 1 provides the highest level of
detector intelligence available today with a detector I
control panel link that allows the user to program the
detector for the specific hazard profile, using a simple
software menu selection.
Model HFP-1 l's FirePrint application monitors input
from both the photo chamber and the thermal sensor,
evaluating this information with sophisticated
mathematical formulas or algorithms, comparing this
input to characteristics of both threatening fires and
deceptive phenomena that would mislead any ordinary
detector.
Detectors are optimized by selecting one (1) of the
following 11 applications:
Office I Retail
Lobby
Computer room
Dormitory
Healthcare
Parking garage
Utility / Transformer room
Hostile environment
Precious storage
Air Duct
Warehouse I Light Manufacturing
The control panel programs Model HFP-1 1 detector for
the protected area without hassle and without confirmatioi
delays. Once optimized for the hazards in the protected
area, Model H FR-i 1 provides the best detection. Should
the operator or installer forget to program the de:ector,
Model HFP-i 1 will revert to a default setting, allowing
operation as an office-environment detector.
SIEMENS Industry, Inc.
Building Technologies Division
The FirePrint technology was developed over years of research
and reviewing the results of over 20 years of fire test data in one
of the world's most advanced fire-research centers.
The results of this research are the mathematical models that
form the algorithms used in FirePrint. No other fire detector
has this level of intelligence or this amount of research and
development supporting its design. The microprocessor's
software can identify and disregard false input caused by radio
frequency (RFI) and electromagnetic (EMI) interference, while
validating all Trouble conditions before annunciating or
reporting to the FACP.
Model HFP-11
The Model HFP-i 1 detector's microprocessor uses an essential
electronically erasable programmable read-only memory
(EEPROM) to store the detector's address and other critical
operating parameters, including the assigned program values
for Alarm and Trouble thresholds.
Communication within the detector, as well as between Model
HER-i 1 and the control panel, or with Model DRU (field device
programmer! test unit), are supervised and safe-guarded
against disruption by reliable, microprocessor-based error
checking routines.
Additionally, the micro-processor supervises all EEPROM
memory locations, and provides a high degree of EEPROM-
failure fault tolerance. Model HER-il determines its operating
status to be Normal in Alarm or in Trouble modes, depending
on the difference between the alarm threshold values stored in
the detector's memory and the detector's latest analog
measurement.
The detector then communicates changes in its status to the
control panel. In addition, the FireFinder XLS control panel
will sample the value of the analog signal for Model H FR-i 1 over
a period of time, in order to determine if those values indicate
excessive buildup in the photo chamber. If such is the case, the
FireFinder XLS control panel will indicate the particular
detector requires maintenance.
Model HER-i 1 is listed as a self-testing device. The visible light
emitting diode (LED) for Model HFP-ii flashes green every four
(4) seconds to indicate it is communicating with the control
panel, as well as to indicate it has passed its internal self-test.
Should the detector sense a fault or failure within its systems,
the LED will flash amber, and the detector will transmit that data
to the control panel.
A quick visual inspection is enough to indicate the condition of
the detector at anytime. If more detailed information is
required, a printed report can be provided from the FireFinder
XLS FACP, indicating the status and settings assigned to each
individual detector. When Model HFP-i 1 moves to the Alarm
mode, it will flash red, and will continue flashing until the
system is reset at the FACP. Simultaneously, any user-defined,
system-alarm functions programmed into the system are
activated.
Specifications - (continued)
Detector sensitivity, calibration and identification are
dynamically supervised at the respective FACP.
Detector sensitivity and pre-alarm levels are a
function of the application chosen at the control
panel, and are controlled by the panel. If an
alternate, non-FirePrint mode is selected, then the
sensitivity can be changed from the control panel.
All Model HFP-1 1 detectors use a surface mounting
base, Model DB-1 1, which mounts on a 4-inch
octagonal, square or single gang electrical box. The
base utilizes screw-clamp contacts for electrical
connections and self-wiping contacts for increased
reliability. Model DB-1 1 can be used with the optional
Model LK-1 1 detector locking kit, which contains 50
detector locks and an installation tool to prevent
unauthorized removal of the detector head. Model
DB-1 1 has integral decorative plugs to cover the outer
mounting screw holes.
Model HFP-1 1 may be installed on the same
initiating circuit with Model HMS-series manual
stations; Model HTRI-series interfaces; Model HCP
output-control devices, or Model HZM series of
addressable, conventional zone modules. All Model
HFP-1 1 detectors can be cleaned in the field - when
required - via easily removing the detector cover and
unsnapping the photo chamber. There is also the
option of cleaning the interior of the detector with a
clean, soft cloth or brush - or by replacing the
labyrinth and bug screen included in the detector
maintenance kit, Model DMK-1 1.
All Model HFP-1 1 detectors are approved for operation
within the ®UL-specified temperature range
of 32 to 100°F (0 to 38°C).
Model DPU
The Device Program I Test Unit accessory is used to
program and verify the address of the detector. The
technician selects the accessory's program mode,
and enters the desired address. Model DPU
automatically sets and verifies the address and tests
the detector.
Model DPU operates on AC power or rechargeable
batteries, providing flexibility and convenience in
programming and testing equipment from practically
any location.
When in 'test' mode, Model DPU will perform a series
of diagnostic tests without altering the address or
other stored data, allowing technicians to determine
if the detector is operating properly.
SIEMENS Industry, Inc.
Building Technologies Division
Application Data
Installation of the Model HFP-1 1 series of fire detectors
requires a two-wire circuit. In many retrofit cases,
existing wiring may be used. T-tapping' is permitted only
for Style 4 (Class B) wiring. Model HFP-1 1 is polarity
insensitive, which can greatly reduce installation and
debugging time. Model HFP-1 1 fire detectors can be
applied within the maximum 30 foot center spacing (900
sq. ft. areas,) as referenced in NFPA 72. This application
guideline is based on ideal conditions, specifically,
smooth ceiling surfaces, minimal air movement, and no
physical obstructions between potential fire sources and
the actual detector. Do not mount detectors in close
proximity to ventilation or heating and air conditioning
outlets. Exposed joints or beamed ceilings may also
affect safe spacing limitations for detectors.
Should questions arise regarding detector placement,
observe NFPA 72 guidelines. Good fire-protection system
engineering and common sense dictate how and when
fire detectors are installed and used. Contact your local
Siemens - Fire Safety distributor or sales office whenever
you need assistance applying FirePrint in unusual
applications. Be sure to follow NFPA guidelines and @UL
Listed / €ULC Listed installation instructions -included
with every Siemens - Fire Safety detector — and local
codes as for all fire protection equipment.
Technical Data
Operating Temperatures: +32°F (0°C) to
100°F (38°C),
per ®UL 268 I 268A
Relative Humidity: 0-93%
Non-condensing
Maximum Spacing: 30-foot Centers
(900 Square Feet),
per NFPA 72 Chapter 5
and €ULC-5524
Current Draw: 1 mA in Alarm or
Supervisory mode
Mounting Diagram Details for Ordering
Part
Model Number Description
HFP-1 1 500-033290 FirePrint Multi-Criteria Fire Detector
DB-1 1 500-094131 Detector Mounting Base for Series 11
DB-1 1 E 500-094151 F- Detector Base {small}
AD2-P 500-649706 Air-Duct Housing
AD2-XHR 500-649708 Air-Duct Housing (with relay}
DB-HR 500-033220 Relay Base for
H-Series Intelligent Detectors
ADBH-1 1 500-033210 Audible Base
RL-HC 500-033230 Remote Alarm Indicator:
4" octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator:
Single-gang box mount, red
LK-1 1 500-695350 Base Locking Kit for Series 11
Detectors
Series 11 Maintenance Kit
DMK-1 1 500-695338 {replacement labyrinth and
bug screen}
In Canada, order
Model Part Description Number
DB-1 1 C 500-095687 Detector Mounting Base
for Series 11 Detectors (ULC)
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593-2600 [511-ES] L6T5E4/Canada June 2015
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 7999937 Supersedes sheet dated 9/13
(Rev. 5)
uRL: www.usa.Siemens.com/Fire FAX: (905) 799-9858
SIEMENS Data Sheet
Fire Safety Products
Intelligent Initiating Devices
HMS-Series
Models HMS-D, HMS-S
ARCHITECT AND ENGINEER SPECIFICATIONS
Durable design
. Shock-and-vibration resistant
Pull-down lever is down, until manually reset
Reset with Allen Key
No break rods necessary
Custom microcomputer-chip technology
Dynamic supervision to the fire-alarm control
panel (FACP)
Polarity insensitive via Sure WireTM technology
Two-wire operation
Surface or semi-flush installation
Model DPU programs and verifies address and
tests functionality of each device
Electronic-address programming is easier, more
efficient and more dependable
Comes in single-action (Model HMS-S) and
double-action (Model HMS-D) stations
Product Overview
The Siemens intelligent manual fire-alarm boxes
(Models HMS-S and HMS-D) provide the most
advanced method of address programming and
supervision. Each Model HMS-series manual box
achieves the state of an 'intelligent-initiating device'
by incorporating custom microcomputer-chip
technology with sophisticated, bi-directional
communication capabilities with the FACP.
Specifications
Models HMS-S and HMS-D are constructed of
durable, molded polycarbonate material that is matte
finished in red with raised white lettering. The
housing accommodates a 'pull-down' lever, which -
when operated - locks into position; indicating the
manual fire-alarm box has been activated.
The pull down lever remains down I in the 'locked'
position, until the fire-alarm box is manually reset.
The manual fire alarm box can only be reset by
opening the hinged housing cover with an Allen key;
followed by closing and locking the cover.
Model HMS-D Model H MS-S
Dual-Action Station Single-Action Station
®UL Listed;
FM (#3015946 & 3052621), CSFM ('7150-0067:0036)
& NYC Fire Dept. (#20212E, Vol. 1) Approved
Models HMS-S and HMS-D operate with Siemens -
Fire Safety FACPs. The microcomputer chip to the
manual fire-alarm box has the capacity of storing - in
memory -identification information as well as
important operating-status data.
Innovative technology from Siemens - Fire Safety
also allows all Model HMS-series intelligent manual
fire-alarm boxes to be programmed via the Device
Programmer I Test Unit (Model DPU). Model DPU is a
compact, portable and menu-driven accessory that
makes programming and testing of a manual fire-
alarm box device faster, easier and more dependable
than previous methods.
The programmer I tester eliminates the need for
mechanical-addressing mechanisms of a device
because Model DPU electronically sets the address of
the manual fire-alarm box into its microcomputer
chip, non-volatile memory. Hence, vibration,
corrosion and other conditions that can compromise
or even deteriorate mechanical-addressing
mechanisms are no longer a cause for concern.
HMS Series Intelligent Initiating Devices 6306
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
Models H MS-S and HMS-D are fitted with screw
terminals for connection to an addressable circuit,
and can be either surface or semi-flush mounted.
The Model HMS-series manual fire-alarm boxes
derive their power, communicate information and
receive commands over a single pair of wires.
The Model HMS-series is compatible on the same
circuit with all Model 'H'-series detectors, interfaces
or addressable, conventional zone modules.
Electrical Ratings
Current Draw (Active or Standby) - 1 .4mA
Details for Ordering
Part Shipping Model Description Number Weight
HMS-D 500-033400 Addressable Manual Fire 2.5 Lbs. 11.13 Oz. Alarm Box, Dual Action
HMS-S 500-033200 Addressable Manual Fire 2.0 Lbs. 0.9 Oz. Alarm Box, Single Action
LTP 500-620490 Reset Tool Package 0.5 Lb. 0.23 Oz. _____________ [contains two (2) tools]
SB-SR 310-019860 Surface-Mounting Box 11.5 Lbs. 10.7 Oz.
HOUSING
HINGED TO
BACKPLATE
1446 i•
Mounting Diagram
SURFACE MOUNTING ENCLOSURE
4 in
NAMEPLATE 'C .... SB-5R
'\
BACKPLATE I
I
I
I
L0 #'
HOUSING LOCKING
SCREW
0 0
0
0
3-1h in DEEP
SWITCH BOX
SEA SUPPLIED)
Notice: This marketing data shee: is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road E.
SIEMENS Industry, Inc. Florham Park, Ni 07932 Oakville, Ontario March 2015 Building Technologies Division Tel: (973) 593-2600 (Sll-FS) 1_61-1 01-16 I Canada Supersedes sheet dated 9/2013
FAX: (908) 547-6877 Printed inU.SA. Tel: [905] 465-8000 (Rev. 5)
uRL: www.usa.S)emens.comlFire URL: www.Siemens.cA
[INTELLIGENT MODULES]
IN
SIEMENS Data Sheet
Fire Safety Products
HTRI-Series Interface Modules
Models HTRI-D, HTRI-R and HTRI-S
ARCHITECT AND ENGINEER SPECIFICATIONS
Interfacing and supervising normally open (N.0) or normally
closed (N.C) contacts
Integral single-pole, double-throw (SPD1) relay on Model HTRI-R
(up to 4 amps)
Dual input on Model HTRJ-D, using a single address
Polarity insensitive with Sure WireM technology
Dynamic supervision
Two-wire operation
Multi-color light-emitting diode (LED) indicates system status:
GREEN/AMBER/RED
Mounts in a 4-inch (10.2 cm.) square, 2_1/4" (5.7 cm.)—deep
single-gang or double-gang back box
Easy front access to programming port and wiring terminals
Comes with 5"-x- 5" (12.7 -x- 12.7 cm.) faceplate
Electronic address programming is easy and dependable
Device Programmer /Tester programs and verifies address • ®UL Listed & @ULC Listed;
of the device and tests for proper functionality FM, CSFM and NYC Fire Dept. Approved
Product Overview
The Siemens - Fire Safety HTRJ-series Intelligent
interface modules are designed to provide the means
of interfacing direct shorting devices to the fire-alarm
control panel (FACP) loop circuit.
The HTRI-series modules provide the most advanced
method of address programming and supervision on
the market -combined with sophisticated control
panel communication. Each HTRI-series interface
module incorporates a microcomputer chip, and each
interface module achieves the state of an 'intelligent
device' through its microcomputer-chip technology,
combined with its sophisticated, bi-directional
communication capabilities with the FACP.
Specifications
The Siemens Mode HTRI-series intelligent interface
modules are available in three (3) types: Model HTRI-
D, as well as Models HTRI-S and HTRT-R, which are both
designed to monitor a (N.0) or (N.C) dry contact.
The interface module reports the status of the (N.0) or
(N.C) contact to the control panel.
Model HTRI-S can only monitor and report the status
of the contact, while Model HTRI-R incorporates an
addressable 'Form C' relay.
The Model HTRI-R relay and contact device input are
controlled at the same address. For the FACP, the
relay and input contact can be controlled as a
separate function. The relay is typically used where
control or shunting of external equipment is required.
The Model HTRI-D is a dual-input module that is
designed to supervise and monitor two (2) sets of
dry contacts. Model HTRI-D only requires one (1)
address, but responds independently to each input.
Model HTRI-D is ideal for monitoring a water-flow
switch and its respective valve tamper switch.
Model HTRI-D flashes twice - once for each
address, and Model HTRI-R LED indicates a change
of state in the relay. The device's microcomputer
chip has the capacity of storing, in memory,
identification information; as well as important
operating-status data.
HTRI Series Interlace Modules 6304
SIEMENS Industry, Inc.
Building Technologies Division
Specifications (continued)
Each Model HTRI device has a multi-color LED that
flashes GREEN when operating in Normal; AMBER if
unit is in Trouble condition, and RED to indicate a
change of state.
Siemens - Fire Safety innovative technology allows
HTRI-series intelligent interface modules to be
programmed via the Device Programming I Test Unit:
a compact, portable and menu-driven accessory that
makes programming and testing an interface device
faster, easier and more dependable than previous
methods.
The programmer / tester eliminates the need for
mechanical addressing mechanisms, such as:
program jumpers, DIP switches or rotary dials, since
Model DPU electronically sets the HTRI-series
interface address into the non-volatile memory of the
interface microcomputer-chip.
Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are
no longer a cause for concern.
The HTRI-series is fitted with screw terminals for
connection to an addressable circuit, and is fully
compatible on the same Siemens FACPs with
Siemens Model 'H'-series intelligent detectors; Model
'HMS'-series addressable manual stations, or any
other addressable intelligent modules (e.g. - Model
HZM or Model HCP).
Temperature and Humidity Range
Model HTRI-series intelligent interface modules are
®UL Listed. Environmental operating conditions for
HTRI-D, HTRI-R and HTRI-S modules are 32°F (0°C) to
1 20°F (49°C) with a relative humidity of no greater
than 93%, non-condensing.
Electrical Ratings
Current Draw 1.3mA (Active _or_Standby)
Relay Ratings, Model HTRI-R
Resistive:
________________
4 Amps, 125 VAC
4Amps, 30 VDC
Electrical Ratings
Relay Ratings, Model HTRI-R - (cont.'d)
3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6P.F.)
Inductive: 2.OA, 120 VAC(0.4P.F.)
2.OA, 120 VAC (0.35P.F.)
2.OA, 30 VDC (0.35P.F.)
Mounting Diagram
Models HTRI-S, HTRI-D and HTRI-R mount directly
into a 4-inch (10.2 cm.) square, 2 1/4" (5.7 cm.)—deep
box back box, or to a user-supplied double-gang back
box. A 5" (12.7 cm.) square, off-white faceplate is
included with each HTRI-series module.
Note: For Marine installations, a faceplate (Model USCG-HPLATE)
is available separately. The faceplate must be used to
protect Siemens HTRI-series interface modules from
receiving radio-frequency interference (RFI).
Details for Ordering
Model Part Description Number
HTRI-R 500-033300 Single Input Module with Relay
HTRI-D 1 500-033360 Dual Input Module
HTRI-S 500-033370 Single Input Module
USCG- Cover metal plate for
HPLATE S54319-F22-Al HTRI Series Interface Modules*
*denotes for required use with Marine-only
Notice: This marketing data sheet is not intended to be used for system design or installations I applications
installation purposes. For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario June 2015
Building Technologies Division Tel: (973) 593-2600 (smFs) L6H 0H6 / Canada Supersedes sheet dated 3/2015
FAX: (908) 547-6877 Printed in USA. Tel: [905] 465-8000 (Rev. 4)
U RL: www.USA.siemens.com/FIRE URL: www.siemens.cA
[NOTIFICATION DEVICES]
SIEMENS Data Sheet
Fire Safety Products
Notification Appliances_________
ZH & ZR - Strobes, Horns, & Horn I Strobes I Application: Indoor
J [-1
rZR
Series
IlI
ZR & ZIII:1iI
(for mounting) ZH Series
Product Overview
- Strobes can be synchronized using the Siemens DSC sync modules, the Siemens 50-point, 252-point
and 504-point addressable fire alarm control panels (FACPs), as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4TM NAC Extenders with built-in sync protocol
- Selectable Continuous Horn or Temporal (Code-3) Tones with 90 or 95 dBA
selectable setting (Series 'ZH')
- Ceiling-mount models feature field-selectable Candela settings of 1 5130/75/95cd and 11 5/1 77cd
- Wall-mount models feature field-selectable Candela settings of 15130/75/11Ocd and 135/185cd
- Base plate is protected by a disposable cover, and the appliances can quickly snap onto the base
after the walls are painted
- Strobes produce one (1) flash per second
- "Special Applications" listed with Siemens panels
- EZ Mount Universal Mounting Plate (Model ZB Series) - uses single plate
for ceiling and wall mount installations
- EZ Mount design - with separate base plate - provides ability to pre-wire the base
and test the circuit wiring before the walls are covered
- ®UL Listed & OULC Listed;
CSFM Approved (Series 'ZH': #712500670248 -> Fire Alarm Devices ForThe Hearing Impaired)
CSFM Approved (Series 'ZR': #7125-0067:0252> Fire Alarm Devices For The Hearing Impaired)
- ADA I NFPA compliant
Specifications
General
- Audible/Visual notification appliances are listed for indoor use only
- Appliances are listed under ®UL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired) and ®UL Standard 464 (Fire Protective Signaling)
- Appliances use a universal back plate, which allows mounting to a
single-gang, double-gang, 4-inch-square (10.2 cm.), 4"-octal (10.2 cm.), or a 3-1/2" (8.9 cm.) octal backbox
- Two-wire configurations allows capability for directly connecting appliances to the mounting back plate
- Continuity check will occur for entire NAC circuit prior to attaching any audible / visual-notification appliances
- A cover fits over the mounting plate for protection to dust and other outside elements
Cover is easily removed when the appliance is installed over the back plate
- Removal of an appliance will result in a Trouble condition by the Siemens Fire Alarm Control Panel (FACP)
'Z' Series Notification Appliances 2584
SlEMENSIndustry, Inc.
Building Technologies Division
Specifications - (continued)
Strobes and Audible Strobe Combinations
- Strobe appliances produce a minimum flash rate of 60 flashes per minute
(one [1] flash per second) over the Regulated Input Voltage Range, and incorporate
a Xenon flashtube enclosed in a rugged Lexan® lens
- Strobes are available with two (2) or four (4) field-selectable settirgs in one (1) unit,
and are rated - per®UL 1971 —for up to:
15/30/75/110cd for wall mounted
135/185cd for wall mounted
1 5130175195cd for ceiling mounted
115/177cd for ceiling mounted
- Strobes operate over an extended temperature range of 32°F to 1 20°F (0°C to 4°C),
and be listed for maximum humidity of 95% RH
- Strobe inputs are polarized for compatibility with standard reverse-polarity
supervision of circuit wiring by a Siemens FACP
Audible and Audible I Strobe Combinations
- Horns and horn I strobes are listed for Indoor use under ®UL Starcard 464
- Horns are able to produce continuous synchronized output or a
Temporal Code-3 synchronized output
- Horns have at least two (2) sound-level settings of 90 and 95 dBA
Synchronization Modules
- The strobe portion, when synchronization is required, is compatible with the
Siemens DSC sync modules; the Siemens 50-point, 252-point and 504-point
addressable FACPs, as well as with:
Fire Finder® XLS and MXL® FACPs
PAD-3 or PAD-4TM NAC Extenders with built-in sync protocol
- The strobes will not drift out of synchronization at any time during operation
- Audibles and strobes are able to synchronize on a two-wire circuit with the capability
to silence the audible, if required
- Strobes revert to a non-synchronized flash-rate, if the sync module or
power supply should fail to operate (i.e. - contacts remain closed)
- All notification appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over their
"Regulated Input Voltage 'Range"
> Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per seconc, and ADA Gu delines
specify a flash rate of 1-to-3 flashes per second
All candela ratings represent minimum-effective Strobe intensity, based on®U_Standard 1971
Series ZH Strobe products are listed under ®UL Standards 197 4 and 464 for incoor use
with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%)
Series ZH horns are listed under ®IJL Standard 464 for audible signal appliances (Indoor use only)
Mounting Diagram
. (Shown In Inches) SIEMENS Industry, Inc
Building Technologies Division
Mounting Diagram
1.) With the provided pan head screws, install mounting
plate to a:
-
- double-gang;
-4' (1S2 cm.) aquare;
4 - (t t.2 cm.) octagon backbox
2.> Connect the fieldwlring.
Address wires back into backbox.
Place dust cover over mounting plate to protect the
terminals white performing the wiring-continuity, check.
Remove dust cover before snapping or
installing the appliance onto the mounting plate
Technical Data
jepinn1: Device only has one (1) mounting
orientation. Match the top of the base to the
top 01 the device.
If it is desired to further secure the device to the
base, then use the two (2) optional screws which
are provided in the shipment. To Install, punch
out the screw holes located at the top and
bottom of the device.
To remove the appliance, push a small, flat-bladed
screwdriver into the side opening. The screwdriver
most clear the snap release opening by 114"( 0.64cm.),
in order for the appliance's snap to disengage.
)p2rtaj5: Do not pry off the housing with the screw driver.
Apply pressure with the screw driver inserted
in either side opening.
ZH Horn: Wall and Ceiling Mount
Operating Voltage (Special Application)
Per ®UL 464
Input Voltage Low* High*
DC 1 16.0-33.OVDC 0.018 0.044
FWR 1 16.0 - 33.OVRMS 0.045 0.075
* Current draw is the same for the Continuous Horn, Code 3
Horn, and March Time settings
ZH Horn I Strobe Series: Wall Mount ZH Horn I Strobe Series: Ceiling Mount
Current Ratings (AMPs)
MAXIMUM RMS Current- with LL1Li dBA Setting
Input Voltage 1 15cd l 30cd 75cd 110c4135cd 185cd
DC 16.0-33.OVDC
1
0.113 0.195 0.25910.371 0.506
FWR 16.0-33.0VRMS0.141 0.200 0.302 0.40610.521 0.722
Current Ratings (AMPS)
MAxrMuMRMS Current- with /,.QyjdBA Setting
Input Voltage 15cd I30cd I 75cd I 95cd I 135cd I 185cd
DC 16.0-33.OVDC 0.070 0.107 10.18810.24610.324 10.455
FWR 16.0 - 33. OVRMS 0.123 10.179 10.29010.39110.497 10.699
ZR Strobe Series: Wall Mount
Current Ratings (AMPS)
Strobe Setting -(cd)
Input Voltage 15ccl 30cd 75cd 110cciJ:135cd 185cd
DC 16.0-33.OVDC 0.064 0.098 0.175 0.23310.318 0.445
FWR 1 16.0-33.0VRM13 0.108 0.164 0.268 0.36810.482 0.684
ZR Strobe Series: Ceiling Mount
Current Ratings (AMPS)
Strobe Setting - (Cd)
Input Voltage 15cd I 30cd I 75cd I 95cd I 11 5c 177cd
DC 16.0-33.OVDC 0.069 10.11110.20010.26410.3118 0.445
FWR 116.0-33.OVRMS 10.117 10.180 10.29710.39810.489 0.684
€ULC Directional Characteristics
-3 dBA 35 degrees left; 40 degrees right
-6 dBA 55 degrees left; 65 degrees right
SlEMENSIndustry, Inc.
Building Technologies Division
Current Ratings (AMPs)
MAXIMUM RMS Current- with fljgj dBA Setting
Input Voltage 15cd I 30cd I 75cd I 95cd 111 5c I 177cd
DC 16.0-33.OVDC 0.087 0.131 0.222 0.292 0.371 0.506
FWR 16.0-33.OVRMS 0.149 0.216 0.331 0.436 0.521 I 0.722
Current Ratings (AMPs)
MAXIMUM RMS Current- with Low dBA Setting
Input Voltage 1 5c 30cd 75cd 95cd 111 5c 177cd
DC I 16.0-33.OVDC 0.075 10.121 1 0.213 10.27710.324 0.455
FWR 116.0-33.OVRMS 0.131 0.195 10.31910.42110.497 10.699
ZH and ZH-MC Series: Wall and Ceiling Mount
dBA Sound Output
Description Volume Reverberant Per ,UL 464
16.0 VDC 24.0 VDC 33.0 VDC
Continuous
Horn
Low 77 81 83
High 83 87 90
Code 3 Horn
(or March Time)*
Low 72 76
1
79
High 79 82 86
dBA Sound Output
Description Volume Reverberant Per ULC-S525-99
20.0 VDC 24.0 VDC 31.0 VDC
Continuous
Horn
Low 88 90 91
High 93 95 96
Code 3 Horn
(or March Time)*1
I Low 88 90 91
High 93 95 96
** Available only in sync mode.
Technical Data - (continued)
Notes: 1. Strobes will produce 1 flash per second over the Input Voltage range.
These horn/strobe models are UL Listed to operate over a Voltage Range Limit from 16.OVDC to 33.OVDC
for 24VDC applications using filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage.
All models are (,UL Listed for indoor ceiling use with a temperature range of +011C to +49°C
(+32°F to +1200F) and maximum humidity of 93% +/- 2% RH.
The effect of shipping and storage temperatures will not adversely affect the performance of the appliance
when stored in original cartons, and is not subjected to either misuse or improper handling of shipment.
Details for Ordering - (Including Mounting Options & Agency Approvals)
A!euILy A1 ovaL
Model Part Number Description Mounting UL ULC CSFM
ZH-R 500-636159 Z Horn: Red B,D,E,F,X V V V
ZH-W 500-636160 Z Horn: White B,D,E,F,X V V V
ZH-MC-R 500-636161 Z Horn: Multi Candela (Wall), Red B,D,E,F,X
ZH-MC-W 500-636162 Z Horn: Multi Candela (Wall), White B,D,E,F,X V V V
ZH-HMC-R 500-636163 Z Horn: Hi Multi Candela (Wall), Red B,D,E,F,X V V V
ZH-HMC-W 500-636164 Z Horn: Hi Multi Candela (Wall), White B,D,E,F,X V V V
ZH-MC-CR 500-636165 Z Horn: Multi Candela (Ceiling), Red B,D,E,F,X V V V
ZH-MC-CW 500-636166 Z Horn: Multi Candela (Ceiling), White B,D,E,F,X V V V
ZH-HMC-CR 500-636167 Z Horn: Hi Multi Candela (Ceiling), Red B,D,E,F,X V V V
ZH-HMC-CW 500-636168 Z Horn: Hi Multi Candela (Ceiling), White B,D,E,F,X V V V
ZR-MC-R 500-636169 Z Strobe: Multi Candela (Wall), Red B,D,E,F,X V V V
ZR-MC-W 500-636170 Z Strobe: Multi Candela (Wall), White B,D,E,F,X V V V
ZR-HMC-R 500-636171 Z Strobe: Hi Multi-Candela (Wall), Red B,D,E,F,X V V V
ZR-HMC-W 500-636172 Z Strobe: Hi Multi-Candela (Wall), White B,D,E,F,X V V V
ZR-MC-CR 500-636173 Z Strobe: Multi Candela (Ceiling), Red B,D,E,F,X V V V
ZR-MC-CW 500-636174 Z Strobe: Multi Candela (Ceiling), White B,D,E,F,X V V V
ZR-HMC-CR 500-636175 Z Strobe: Hi Multi Candela (Ceiling), Red B,D,E,F,X V V V
ZR-HMC-CW 500-636176 Z Strobe: Hi Multi Candela (Ceiling), White B,D,E,F,X V V V
ZB-R 500-636193 Accessory - (Includes base, dust cover, mounting screws and installation sheet)
ZB-W 500-636194 Accessory - (Includes base, dust cover, mounting screws and installation sheet)
V = Listed / Approved
* = Refer to data sheet #: 2585
for detailed mounting options
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SlEMENSIndustry, Inc. Florham Park, ft 07932 East Oakville, Ontario June 2015
Building Technologies Division Tel: (973) 593-2500 (sll) L6H 0H6 I Canada Supersedes sheet dated 612012
FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000 v 4)
URL: www.usa.Siemens.com/Fire URL: www.Siemens.cA
[CSFM LISTINGS]
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
-
LISTING SERVICE
LISTING No. 7165-0067:0259 Page 1 of 2
CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: peter.pawchak@siemens.com
DESIGN: Models Desigo FC2005-U2,-R2 and Cerberus Pro FC90I-U3,-R3 Fire Alarm Control Units.
Non-coded; local, auxiliary, remote, proprietary and central station service; automatic or
manual waterfiow, and sprinkler supervisory service when used as a remote station
(protected premise) unit, proprietary or central station fire receiving unit. Refer to listee's data
sheet for additional detailed product description and operational considerations.
Basic components:
FH90I-U2; Desigo Enclosure (Black)
FH901-R2; Desigo Enclosure (Red)
FH90I-U3; Cerberus Pro Enclosure (Black)
FH901-R3; Cerberus Enclosure (Red)
FHA90I-U1; Battery Brackets, left/right
FCM901-U2; Desigo Main Board
FCM901-U3; Cerberus Main Board
FC12020-UI; City Tie Board (optional)
FP20II-UI; Power Supply Unit
FSD90I-U2; Desigo Remote Annunciator (Black)
FSD90I-R2; Desigo Remote Annunciator (Red)
FSD901-U3; Cerberus Remote Annunciator (Black)
FSD90I-R3; Cerberus Remote Annunciator (Red)
*FDCI0422; Input/Output Module
RATING: 120V 60hz 2A
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as fire alarm control units for use with separately listed compatible initiating and
indicating devices. Refer to manufacturer's Installation Manual for details.
These control units can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
This control unit meets the requirements of UL-864, 9th Edition Standard.
NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
*Rev 03-22-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
IfVt' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
L:stng No. 7165-0067:0259
Page 2 of 2
Retard/Reset/Restart period shEll not exceed 30 seconds
*Rev 03-22-12 gt
This listing is based upon tec.inicai cata submi:ted by the applcant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an iidepedent verificat on of any claims. This lis:ing is not
an endorsement or recommendation of the item listed. This 'isting shcLld not be used to verfy correct
operational requirements or installation criteria. R&er to listee's data sheet installaticr nstructions and/or other
Date Issued: July 01, 2015 Listing Expres June 30, 2016
Authorized By: JAMES PARSEGIAN, Program ocrdnator
Fire Engineering Civision
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
k --.: I : _
LISTING SERVICE
LISTING No. 7272-0067:0203 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models FP-11, HFP-11, and *HFPO..11 analog and FPO-11 photoelectric type smoke
detectors. Models FP-1, and HFP-11 also have a supplemental 1350F heat sensor. Model
DGH-11 detector guard housing suitable for use with Models HFP-11, *HFPO..11 and FP-11
smoke detectors. Refer to listee's data sheet for additional detailed product description and
operational considerations.
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. These detectors are intended
for installation on a vertical wall surface or the ceiling. They are also acceptable for duct
application with an air velocity of 0-4000 ft/mm. when used with Models DB- 11, DB-HR or
DB-X1IRS bases.
MARKING: Listees name, model number, and UL label.
APPROVAL: Listed as photoelectric type smoke detectors for use with listee's separately listed base
Model DB-11, DB-HR or DB-XIIRS (CSFM Listing No. 7300-0067:134) and separately listed
compatible fire alarm control units. Model DGH-11 detector guard housing is listed for use
only with FP-11 and HFP-11. Refer to listee's Installation Instruction Manual for details.
NOTE:
*Rev. 09-27-2004
ri This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
ftV1 operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0067:0134 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models DB4T, DB4TS, DB4F, DB4TF, DB4FS, DB3S, ADB3, ADBX3, DB-HR, *DB2HR
DBX3RS, DB-11, DB-XIIRS, ADBI60, ADB-11, ADBH-11,SBGA-34, ADBX-11 and 8837
detector bases and Model DB-ADPT detector/base adapter. Suitable for use wth Models
RR2 or RR3 auxiliary relays. Model DB-11 is suitable for use only with Model RR-11 or
RR-11F auxiliary relay. Models DB-11 base, ADBH-11 audible base, and DB-HR, *DB2..HR
relay bases are intended to be used with Models HFP-11, *HFpO..11 and HFPT-11 Intelligent
Series smoke and heat detectors (CSFM Listing No. 7272-0067:0223 and 7270-0067:0224).
Model SBGA-34 audible base is intended to be used with Models HFP-11, HFPT-11, or
HFPO-11 detectors (CSFM Listing No. 7272-0067:0223 and 7270-0067:0224), Models
FDOT42I, FD042I, 0H921 and 0P921 detectors (CSFM Listing No.7272-0067:0258),
Models FDT421 and H1921 detectors (CSFM Listing No.7270-0067:0262), and Models
F000T44I, FDOOTC44I, 00HC941 and 00H941 detectors (CSFM Listing
No.7270-0067:0260). *Model DB2-HR Relay Base can be used also with Intelligent Series
smoke detectors type FDOT421, F00421, 01-1921, 0P921(CSFM Listirg
No.7272-0067:0258), FDT421, H1921 (CSFM Listing No.7270-0067:0262'1, and FDOOT44I,
FDOOTC44I, OOHC94I, 00H941 (CSFM Listing No.7270-0067:0260). Refer to listee's data
sheet for additional detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable cc-des & ordinances
and in a manner acceptable to the authority having jurisdiction. Model DB- 11, ADBH-11,
SBGA-34, DB-HR and *DB2..HR may be installed on the ceiling or on the wall.
MARKING: Listee's name or SIEMENS, model number, electrical rating and UL label.
APPROVAL: Listed as detector bases for use with separately listed compatible smoke detec:or heads
and fire alarm control units.
*Rev. 0.4-15-14 gt
Tfts-lsting is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewsd
the test results and/or other data but does not make an independent verification of any claims. This, listing is rot
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
v% opera:ional requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By:: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM IL
LISTING SERVICE
LISTING No. 7150-0067:0036 Page 1 of 1
CATEGORY: 7150 -- FIRE ALARM PULL BOXES
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchaksiemens.com
DESIGN: Models MS-5, -51 -52, -52C, -53 through -57, -60, -60DAP, -60DP, -60KS, -151, -157, -500
through -507, -511, -512, -512C, -513, -513C, -514, -514C, -515, -516, -517, -517C, -518, and
MS-MI; MH-51, -57, -501, -507, -511, -517, -517C, -518; MSX-1, -2, -20, -100; MHX-1, -100;
MSl-1, -2, -10, -lOB, -20,-20B, -60, -6ODA; MSI-MB6; HMS-S, -D, -M noncoded manual pull
stations. Single action, double action, and double action distinct type. Refer to listees data
sheet for additional detailed product description and operational considerations.
INSTALLATION: In accordance with listees printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name or Cerberus Pyrotronics, model number, electrical rating and UL label.
APPROVAL: Listed as manual pull stations for use with separately listed electrically compatible fire alarm
control units. Models with prefix MH are suitable for use with Halon extinguishing system.
Models HMS-S, -0, -M are addressable.
* The following manual pull boxes meet the requirements of UL Standard 38, 1999 Edition
and California amendments: Models MS-151, -157, -501; MSI-10B, MSI-20B and HMS-S, -0,
-M.
*Rev 03-25-14 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0067:0242 Fage 1 of I
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Siemens Industry, Inc. Buildng Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Control Unit Accessories. Refer to listee's data sheet for detailed product description and
operational considerations. Accessories are listed as follows:
HTRI-S, -D, -R Addressable Switch Interface Module
HTRI-M Addressable Interface Module
HUM Loop Isolator Module
HZM Conventional Zone Loop
ILED-HC, -HW Remote Lamps
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicaDle codes and ordnances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, and UL label.
APPROVAL: Listed as control unit accessories for use with separately listed flrc alarm control unts. Refer
to listee's Installation Instruction Manual for details.
NOTE:
11-C4-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has revewed
the test results and/or other data bu: does not make an independent verification of an claims. This listing i.; not
an endorsement or recommendation of the item listed. This lis:ing, should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instruct3n5 and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0067:0252 Page 1 of 1
CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models ST-MC-RETRO-R, ZR-MC-W, ZR-MC-R, ZR-HMC-R, ZR-HMC-W intended for indoor
use on walls.
Models ST-MC-CW, ST-HMC-CW, ZR-MC-CR, ZR-MC-CW, ZR-HMC-CR, and ZR-HMC-CW
multi candela intended for indoor use mounted on the ceiling only.
Z -series strobes are intended for use with models ZB-R or ZB-W back boxes. ST - series
strobes are intended for use with models SHBBS surface back boxes. Model numbers may
be followed by alpha characters indicating lens orientation, lettering, and color. Refer to
listee's data sheet for additional detailed product description and operating considerations.
RATING: Electrical 16-33VDC/FWR
Candela: ST-MC-RETRO-R 15cd, 30cd, 75cd, llOcd
ZR-MC-W, ZR-MC-R 15cd, 30cd, 75cd, llOcd
ZR-MC-CR, ZR-MC-CW 15cd, 30cd, 75cd, 95cd
ST-MC-CW 15cd, 30cd, 75cd, 95cd
ZR-HMC-R, ZR-HMC-W 135/185cd
ZR-HMC-CR, ZR-HMC-CW 115/177cd
Flash Rate: 60 flashes I minute
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction. Models with suffix
-Ware wall mount only. Models with suffix -C are ceiling mount only. All models are for
indoor use only.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. Refer to listee's installation instruction manual
for details.
NOTE:
9-1 O-2007mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0067:0248 Page 1 of I
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter. pawchaksiemens.com
DESIGN: Models NH-R, NH-W, NH-CR, NH-CW, ZH-R, and ZH-W horns and models NS-MC-R,
NS-MC-W, ZH-MC-R, ZH-MC-W, ZH-HMC-R, AND ZH-HMC-W Horns / Strobes. Models
NS-MC-CR, NS-MC-CW, NS-HMC-CR, NS-HMC-CW, ZH-MC-CR, ZH-MC-CW, ZH-HMC-CR,
ZH-HMC-CW are horn I strobes for ceiling mount only. Suffix CR or CW are for ceiling and
color. Units are synchronized or non-synchronized strobes. Refer to Listee's data sheet for
additional detailed product description and operational
RATING: Electrical 16-33VDC/FWR
Candela: NS-MC-C, ZH-MC-C = 15/30/75/95 candela
NS-HMC-C, ZH-HMC-C = 115/177 cd
NS-MC, ZH-MC = 15/30/75/110 cd
ZH-HMC, = 135 /185 cd
Flash Rate: 60 flashes / minute
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as audible and audible //visual signaling devices for use with separately listed
electrically compatible fire control units. Models with strobe lights are suitable for the hearing
impaired. For indoor use only. All synchronization strobes shall be used with model DSC
sync control module (CSFM listing No. 7300-0067:212). Refer to manufacturer's installation
manual for details
Note: These appliances can produce a distinctive three- pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE:
09-07-2007
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the tast results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
ftV operEtional requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1402:0109 Page 1 of I
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: TELULAR CORP.3225 Cumberland Blvd, Suite 300, Atlanta, GA 30339
Contact: Raj Kosaraju (678) 264-2012 Fax (678) 264-2062
Email: rkosarajutelular.com
DESIGN: Models TG7G0004, TG7GFS04, and TG7GA004 digital cellular radio alarm transmission
system for fire/burglar alarm system control units. Models TG7G0004 and TG7GA004 are
household application and Mode TG7GFS04 is for commercial application.
Refer to listees printed data sheet for additional detailed product description and operational
considerations
INSTALLATION: In accordance with listees printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, electrical rating and UL label.
APPROVAL: Listed as digital cellular radio alarm transmission devices to provide a standalone
transmission path (cellular) for a listed compatible fire and burglar alarm control unit. It may
also provide a backup communication path when used in conjunction with a DACT. This
product is to be connected to a listed control panel in accordance with the installation
instructions provided by the manufacturer.
NOTE: Burglary and other non-fire functions were not examined.
Corrected 10-09-13 jp
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016