HomeMy WebLinkAbout2200 FARADAY AVE; 100; FPC2017-0050; PermitJ 1:1 P11:11:1'] •
4LCity of
Carlsbad
1R IftU
-
Print Date: 04/20/2022 Permit No: FPC2017-0050
Job Address: 2200 FARADAY AVE, # 100, CARLSBAD, CA 92008-7233 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2121206000 Track #: Applied: 02/16/2017
Valuation: $2,743,717.92 Lot #: Issued: 03/01/2017
Occupancy Group: Project #: Finaled Close Out: 03/01/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: GREATCALL - FIRE ALARM TI
Applicant: FPContractor:
NOVA SECURITY NOVA SECURITY
CORY HILL 8779 COTTONWOOD AVE, # STE 103
358 RIVER TRAIL PL SANTEE, CA 92071457
SANTEE, CA 92071-6907 (619) 448-3007
(619) 448-3007
FEE AMOUNT
FIRE TI Fire Alarm System $601.00
Total Fees: $601.00 Total Payments To Date: $601.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
GREAT CALL
SUITE 100
2200 FARADAY AVE. CARLSBAD, CA. 92008
Fire Alarm Submittal
02-14-17
Submitted By;
NVA
SEC URTY
8779 Cottonwood Ave. Suite 103
Santee, CA. 92071
619-448-3007
Cont Lie. C-10# 802053
Contact: Cory Hill
GREATCALL
Fire Alarm Submittal
Equipment List
NOTE: ALL FIRE ALARM EQUIPMENT IS EXISTING TO REMAIN RELOCATE DEVICES AS SHOWN ON PLANS
Description Model Manufacture CSFM#
Strobe Multi-cd cig mnt STC COOPER 7125-0785:168
Strobe Multi-cd wall mnt ST COOPER 7125-0785:168
Horn/Strobe Multi-cd cig mnt HSC COOPER 7125-0785:168
Horn/Strobe Multi-cd wall mnt HS COOPER 7125-0785:168
GOOPEftNotifkat ion:
E~PdE=D~_ I Strobe, Horn Strobe, and Horn
Notification Appliances
Description:
The INheelocke Exceder M Series of notification appliances feature
a sleek modern design that will please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelock® ExcederTM Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® Exceder' Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre-wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
completewith a Contact Cover for protection against dirt,dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
Save up to 480/6 in current draw®
- Up to 9 models now in 1 appliance
- Save upto 1 4% cost of lnstallatlon®
@I
Sleek Modern Aesthetics
PAI
Fingev Slide Switches
Voltage Test Points
Multiple Voltages
3 Audible Settings
90, 95, 99 dB €;, 8 Candela Settings
Wall- 15/1575/o/7S/o5/119/1a5/18S
CiIii, - 15/30/60/75/95/1 15/150/177
U Universal Mounting Base
Ceiling and Wall
Mounts to 5 Backbox Types
Environmentally Friendly
Law Current Draw
Compatibility and Requirements
-Synchronize using the Wheelock 'Sync Modules or panels with built-in Wheelock' Patented Sync Protocol
Compatible with lii"Regulated Voltage using filtered VEX or unfiltered VRMS Input voltage
- Strobes produce 1 flash per second over the "Regulated range
Compared to competitive models Patented
Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FORTHE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EFERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes: .
General Notes,
- Strobes ara d inei t Bath at I flash per ecnd mininlurn
JI ancieIe ratings represent minirnun tctive st?zbe inti yf3ase in UL Standard 1971.
Snts Exdr Strobe pra1its ar List-.;d uflr ULStandariis 1971 and 44 frimj-or us wIth a tmpratur ran •t 32*F t3 10F OC to 4 1 and maximum hLlllidityQt93% (i i%) UL 464 % UL 1971).
Series Eder hms are undrtJL standard 454 tar audible signal appliances (Indtwr use anfo.
Horn Strobe Ratingsper UL 1971 & Anechoic at 24VDC
_______
24VDC 12VDC
Regulated Voltage Model 15 15/75 30 .60 75 95 110 115 135 150 177 185 15 15/75 RangeVDC
HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 0.242 0.282 0.125 0.159
l-ISC 8.0-33.0 008 0.102 0.141 0.148 0.176 1 0.197 0.242 10282' - 0.125
UL Max CUrrent" at A:nechoic 95 dBA
24VDC 12VDC
Regulated Voltage Model 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
UL Max Current~ at Anechoic 90 dBA
24VDC 12VDC
Regulated Voltage Model 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 0.184 0.226 10.267 0.120
Horn Ratings per UL Anechoic
Model Regulated Voltage
Range VDC 99 dB 95 dB 90 dB
HN 16-33.0 0.064 0.044 0.022
HNC 16-33.0 0.084 0.044 0.022
HN 8.0-17.5 0.047 0.026 0.017
HNC 8.0-17.5 0.047 0.026 0.017
F"'T --
. I
'd"
Y -
UL max current rating is the maximum RMS current within the listed Voltage range 16-33 VDC for 24 VDC units). For strobes the
UL max current is usually at the minihium listed voltage (IS VDC for 24 VDC units). For audibles the Max current is usually at the
maximum listed voltage (3 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
Specification & Ordering Information
Sync WI
1Model Strobe DSM or 12124 VDC Mounting
Candela Wheelock Power Options
Supplies
HSR 15/1575/30/75/95/110/1351185 X X UMB"
X X UMB" HSW 15/1575130/75195/1101135/185
HSRC 15/30/60/75/95/115/150/177 X X LiMB"
HSWC 15/30/60175/95fl15/150/177 X X UMB"
EITII.
STR 15/1575/30/75/95/110/135/185 X X UMB"
STW 15/1575/30/75/95/110/135/185 X X UMB"
STRO 15130160/75/951115/150/177 X X LiMB"
STWC 15/30/60/75/95/115/150/177 X X LiMB"
LiMB" B" HNR X X
- X X 7 'F7
UMB" HNW
HNRC X X
HNWC X X UMB"
12VDC made Isfeature 15 & 15/75 settings "UMB = Universal Mounting Base
NOTE Due to continuous development of our products specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions
Architects and Engineers Specifications
The notification appliances shall be Wheelock' Excedertm' Series HS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HNAudible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices forthe Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuit wiring by FireAlarm Control Panel (FACP) with the ability to operate from 8t0 33VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HNAudible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24"
H x 4.58" W 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68"x 1.50" D.
When synchronization is required, the appliance shall be compatible with WheeIock's DSM Sync Modules, Wheelock Power Supplies
or other manufacturer's panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal maybe silenced
while maintaining strobe activation when used with Wheelock synchronization protocol.
Wall Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
[Member
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
Wheelock' (DC) SAFEPATH' wAVEfS7) Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No 7125-07850i6 Page 1 of 1
CATEGORY 7125 FIRE ALARM DEVICES FOR TH HEARING IMPAIRED
LISTEE: Cooper Wheelock Inc;7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conovercooperindustries.com
DESIGN Exceder Series Models ST strobe HS horn strobe and HN horn Model ST is a synchronous
and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a C' may be
added for ceiling models and/or a '-NR' may be added for non-resettable models. For non
-NR models and optional 'S' for silver fascia may be added. Refer to Iistee's data sheet for
additional detailed product description and operational considerations.
RATING: Electrical: 12 VDC/24VDC/FWR
Candela (wall): 15,15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling): 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only'
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee 's
Installation Instructions Manual for details.
Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. OSEM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other
Date Issued: July 01, 2016 :ListingExpiies, June 3O,2O17
Authorized By: DAVID CASTILLO, Program Coordinator
Fite Engineering Division