HomeMy WebLinkAbout3239 CAMINO DE LOS COCHES; 100; FPC2019-0232; Permitäty of PERMIT REPORT Carlsbad Print Date: 05/11/2022 Permit No: FPC2019-0232 Job Address: 3239 CAMINO DE LOS COCHES, # 100, CARLSBAD, CA 92009-8966 Status: Closed - Finaled Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers Parcel #: 2550313000 Track #: Applied: 10/04/2019 Valuation: $126,925.79 Lot #: Issued: 10/21/2019 Occupancy Group: Project #: Finaled Close Out: 11/14/2019 #of Dwelling Units: Plan #: Bedrooms: Construction Type: Final Inspection: Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix Plan Check #: Project Title: Description: YOFIT -SPRINKLER TI (10 HEADS) Applicant: FPContractor: AMERICAN AUTOMATIC FIRE SUPPRESSION AMERICAN AUTOMATIC FIRE SUPPRESSION INC INC JAZZMIN DEEKEN 9925 PROSPECT AVE, #STE B 9925 PROSPECT AVE, U B SANTEE, CA 92071 SANTEE, CA 92071 (619) 562-3010 (619) 562-3010 FEE AMOUNT FIRE NFPA 13 or 13R System 7 - 100 heads $553.00 Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov cci Worldwide i Fire Protection Contacts www.tyco-fire.com tq Products Series TY-FRB, 56 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers described in this data sheet are quick response, standard coverage, decorative 3 mm glass bulb-type spray sprinklers designed for use in light or ordinary hazard, commercial occupan- cies such as banks, hotels, and shop- ping malls. The recessed version of the Series TY- FRB Pendent Sprinkler, where applica- ble, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following: A two-piece Style 15 Recessed Escutcheon with recessed adjust- ment up to 5/8 inch (15,9 mm) from the flush pendent position. A two-piece Style 20 Recessed Escutcheon with recessed adjust- ment up to 1/2 inch (12,7 mm) from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Intermediate level versions of Series TY-FRB Sprinklers are described in Technical Data Sheet TFP357. Sprin- kler guards and shields are described in Technical Data Sheet TFP780. IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 NOTICE The TYCO Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this doc- ument, as well as with the applicable standards of the National Fire Protec- tion Association, in addition to the stan- dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY313 .......Upright 5.6K, 1/2" NPT TY323 ......Pendent 5.6K, 1/2" NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and VdS Approved CE Certified Sprinklers with Polyester Finish are UL and C-UL Listed as Corrosion-Resis- tant Sprinklers. Maximum Working Pressure 175 psi (12.1 bar) 250 psi (17.2 bar)* *The maximum working pressure of 250 psi (17,2 bar) only applies to the listing by Un- derwriters Laboratories, Inc. (UL). Discharge Coefficient K=5.6 GPM/psi112 (80,6 LPM/bar1/2) FEBRUARY 2014 Temperature Rating 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) Finishes Sprinkler: Refer to Table A Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated Physical Characteristics Frame ...................Bronze Button..............Brass/Copper Sealing Assembly.........Stainless Steel w/TEFLON Bulb ......................Glass Compression Screw........Bronze Deflector.................Bronze TFPI72 TFPI72 Page 2 of 4 Components: 1 - Frame 2 - Button 3 - Sealing Assembly * Temperature rating is ** Pipe thread connections per ISO 7-1 4 - Bulb indicated on Deflector. can be provided on special request. 5 - Compression Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm) 6 - Deflector* DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN STYLE 15or20 RECESSED ESCUTCHEON 2' (50,8 mm) 7/16" (11,1 mm) I NOMINAL MAKE-IN (50,8 mm) 1/2" NPT** CROSS SECTION UPRIGHT WRENCI- FLATS DEFLECTOR * f-.-- 2-7/8' (73,0 mm) DIA. PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers are intended for fire protec- tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Prevention Data Sheets). Only the Style 15 or Style 20 Recessed Escutcheon is to be used for recessed pendent installations. Installation The TYCO Series TY-FRB, 5.6 K-factor, Upright (1Y313) and Pendent (TY323) Sprinklers must be installed in accor- dance with this section. General Instructions Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) and 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min- imum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch- eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1. Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. / WRENCH RECESS /(USE ONLY FIGURE 2 W- TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W- TYPE 7 RECESSED SPRINKLER WRENCH TFPI72 Page 3 of 4 Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 2). With ref- erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Torque sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions. Step A. After installing the Style 15 or Style 20 Mounting Plate over the sprin- kler threads, and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Step C. After ceiling installation and fin- ishing, slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprin- kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be maintained and ser- viced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any other authorities hav- ing jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. 2-7/8 DIA. (73,0 mm) - 2-1/4 DIA. FACE OF (57,2 mm) SPRINKLER FITTING 5/8 (15,9 mm) FLUSH 3/8±5/16 (9,5±7,9 mm) MOUNTING I SURFACE (3,2 mm) /8" J CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm) TY-FRB PLATE 3/4' (19,1 mm) FIGURE 4 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON 2-7/8" DIA. (73,0 mm) FACE OF SPRINKLER 2-1/4" DIA. FITTING - (57,2 mm) 5/16±1/4" \ I 1/2(12,7mm) (7,9±6,4 mm) F FLUSH 17, SURFACE CLOSURE mm) 1/8" MOUNTING CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) TYFRB PLATE 7/8" (22,2 mm) FIGURE 5 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFPI72 Page 4 of 4 P/N*77_XXX_X_XXX I SPRINKLER I TEMPERATURE I FINISH J- RATINGS SIN 1 NATURAL BRASS I 370 I 5.6K UPRIGHT (1/2NPT) TY313 3 PURE WHITE (RAL9010)** POLYESTER 371 5.6K PENDENT (1/2" NPT) TY323 POLYESTER SIGNAL WHITE (RAL9003) Use suffix "I" for ISO 7-1 connection; 9 CHROME PLATED for example, 77-370-4-175-I - ** Eastern Hemisphere sales only TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION 135 135°F (57°C) 155 155°F (68°C) 175 175°F(79°C) 200 200° F (93°C) 286 286°F (141°C) Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Num- ber (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB Upright or Pen- dent (specify) Sprinkler, SIN (specify), K=5.6, Quick Response, (specify) tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify: Style 15 Recessed Escutcheon with (specify*) finish, P/N (specify*) Specify: Style 20 Recessed Escutch- eon with (specify*) finish, P/N (specify*) * Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. tqco TEFLON is trademark of The DuPont Corporation. Fire Protection Products Worldwide I tqC170 Contacts www.tyco-fire.com Series TYFRB - 56 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description The Series TY-FRB, 5.6 K-factor, Hori- zontal and Vertical Sidewall Sprinklers described in this data sheet are quick response -standard coverage, dec- orative 3 mm glass bulb type spray sprinklers designed for use in light and ordinary hazard, commercial occu- pancies such as banks, hotels, shop- ping malls, etc. They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Sidewall sprinklers are com- monly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable. The recessed version of the Series TY-FRB Horizontal Sidewall Sprinkler is intended for use in areas with a fin- ished wall. It uses a two-piece Style 10 Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush sidewall position, or a two-piece Style 20 Recessed Escutch- eon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush side- wall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe nipples to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit- ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. NOTICE The Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Numbers TY3331................Horizontal 1Y3431 .................. Vertical JULY 2018 Technical Data Approvals UL and C-UL Listed FM Approved LPCB Approved NYC Approved (Refer to Table A for complete approval information including corrosion resistant status.) Maximum Working Pressure Refer to Table B Discharge Coefficient K=5.6 GPM/ps1112 (80,6 LPM/bar112) Temperature Ratings Refer to Table A TFPI76 * Temperature rating is indicated on Deflector ** Pipe thread connections I per ISO 7-1 can be provided on special 2-7/8 IDA. request (73,0 mm) TFPI76 Page 2 of 6 1 - Frame DEFLECT( HAT 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Compression Screw 6 - Deflector* DEFLECT( 1 - Frame HAT 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Compression Screw 6 - Deflector* 0 9/16 WRENCH 1/2** 9/16 WRENCH 1/2 (14,3 mm) FLATS NPT (14,3 mm) FLATS NPT 1 , \77 - 1-13/16" 7/16' (46,0 mm) (11,1 mm) CENTERLINE NOMINAL OF SPRINKLER MAKE-IN WATERWAY 1-1/2 (38,1 mm) ESCUTCHEON PLATE SEATING ______ 2-3/16" SURFACE (556 m) STYLE 1Oor2O RECESSED ESCUTCHEON ALL FINISHES EXCEPT POLY-STAINLESS Tj 1-13/16" 7/16" (46,0 mm) (11,1 mm) CENTERLINE NOMINAL OF SPRINKLER MAKE-IN WATERWAY 1-1/2' (38,1 mm) ESCUTCHEON PLATE SEATING ______ 2-3/16' SURFACE (55,6 mm) POLY-STAINLESS FINISH ONLY STYLE 10 RECESSED ESCUTCHEON *Temperature rating is indicated on Deflector FIGURE 1 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS Finishes Sprinkler: Refer to Table C Recessed Escutcheon: Signal or Pure White, Jet Black, Grey Aluminum, Chrome Plated, or Brass Plated Physical Characteristics Frame ............................Bronze Button ......................Brass/Copper Sealing Assembly. . Beryllium Nickel w/TEFLON Bulb...............................Glass Compression Screw.................Bronze HSW Deflector .....................Bronze VSW Deflector.....................Copper Poly-Stainless Physical Characteristics Frame ............................Bronze Button ................L316 Stainless Steel" Bulb ...............................Glass Compression Screw .....L316 Stainless Steel" HSW Deflector ..............Copper/Bronze Sealing Assembly. Gold Plated Beryllium Nickel w/TEFLON *Type L316 stainless steel (UNS 31603) per ASTM A479/479M or BS EN 1008 WN1.4404. Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The Series TY-FRB, 5.6 K-factor, Hor- izontal and Vertical Sidewall Sprin- klers are intended for fire protection systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Prevention Data Sheets). Only the Style 10 or 20 Recessed Escutcheon, as applicable, is to be used for recessed horizontal installations. 7/16' (11,1 mm) NOMINAL MAKE-IN 1/2** NPT RENC LATE TFPI76 Page 3 of 6 Installation The Series TY-FRB, 5.6 K-factor, Hori- zontal and Vertical Sidewall Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft (9,5 to 19,0 N'm). Higher levels of torque may distort the sprin- kler and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insuf- ficient adjustment in the escutcheon plate by under-or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. Series TY-FRB Horizontal and Vertical Sidewall Sprinkler Installation The Series TY-FRB Horizontal and Vertical Sidewall Sprinklers must be installed in accordance with the fol- lowing instructions. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water- way perpendicular to the back wall and parallel to the ceiling. The word "TOP" on the Deflector is to face towards the ceiling. Vertical sidewall sprinklers are to be installed in the pendent or upright position with the arrow on the Deflec- tor pointing away from the wall. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 5), With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. * Temperature ** Pipe thread rating is connections indicated on per ISO 7-1 can Deflector, be provided on special request. ESCUTCHEON PLATE SEATING SURFACE F - 2-3/16 (55,6 mm) 1-1/2 (38,1 m Series TY-FRB Recessed Horizontal Sidewall Sprinkler Installation The Series TY-FRB Recessed Horizon- tal Sidewall Sprinklers must be installed in accordance with this section. Step A. Recessed horizontal sidewall sprinklers are to be installed in the hori- zontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word "TOP" on the Deflector is to face towards the ceiling. Step B. After installing the Style 10 or 20 Mounting Plate over the sprinkler threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 6). With reference to Figure 1, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprin- kler wrench flats. Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 10 or 20 Closure over the Series TY-FRB Sprin- kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. 1 - Frame 4 - Bulb 7 - Ejection 2 - Button 5 - Compression Spring 3 - Sealing Screw Assembly 6 - Deflector* ARROW MUST POINT AWAY FROM AND BE J@ Care and Maintenance The Series TY-FRB, 5.6 K-factor, Hori- zontal and Vertical Sidewall Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Spriklers PERPENDICULAR TO THE BACK WALL SURFACE SHOWN SHOWN CROSS PENDENT UPRIGHT SECTION FIGURE 2 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS TFPI76 Page 4 of 6 - 5/8±1/4 (15,9±6,4 mm) MOUNTING FACE OF SURFACE SPRINKLER FITTING CLOSURE 2-7/8" DIA. SERIES (73,0 mm) TY-FRB 2-1/4" DIA. (57,2 mm) MOUNTING - PLATE 1/8" I (3,2 mm) 1-1/4(31,8mm) 3/4(19,1 mm) 3/4' (19,1 mm) 1/4" (6,4 mm) FIGURE 3 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON - - 1/2±1/8" (12,7±3,2 mm) MOUNTING FACE OF SURFACE SPRINKLER FITTING CLOSURE 2-7/8 DIA. SERIES (73,0 mm) TY-FRB 2-1/4" DIA. MOUNTING (57,2mm) PLATE 1/8" (3,2 mm) 1-1/4(31,8mm) 1/2(12,7mm) 1(25,4mm) 1/4(6,4mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON / WRENCH RECESS / (END 'A' USED FOR 60 1/2' NPT MODELS) FIGURE 5 W-TYPE 6 SPRINKLER WRENCH WRENCH RECESS ) I I PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 W-TYPE 7 RECESSED SPRINKLER WRENCH TFPI76 Page 5 of 6 SPRINKLER FINISH (See Note 11) K TYPE TEMP. BULB LIQUID NATURAL BRASS PLATED POLYESTERC POLY- STAINLESSC LEAD COATED 135°F (57°C) Orange 155°F (68°C) Red HORIZ. 175-F (79'C) Yellow SIDEWALL 1,2, 3,4,9, 10 1,2,3,9 1,2 1,2,3,9 (TY3331) 200°F (93°C) Green 286°F (141°C) Blue 5.6 RECESSED 135°F (57°C) Orange 155°F (68°C) Red 1/2 in. NPT HORIZ. SIDEWALL (TY3331)a 1, 2,4,9,10 1,2,9 1,2 N/A 175°F (79°C) Yellow Figure 3 Green 200°F (93°C) RECESSED 135°F (57°C) Orange 155°F (68°C) Red HORIZ. SIDEWALL (TY3331)b 1, 2, 3, 4, 9 N/A N/A 175°F (79°C) Yellow Figure 4 Green 200°F (93°C) VERTICAL 135°F (57°C) Orange 155°F (68°C) Red 5.6 SIDEWALL 175°F (79°C) Yellow 1/2 in. Installed 5, 6, 7, 8, 9 N/A 5, 6, 7, 9 NPT Pendent or 200°F(93°C) Green Upright Blue 286°F (141°C) NOTES: Listed by underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflec- tor to ceiling distance. Listed by Underwriters Laboratories Inc. for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflector to ceiling distance. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflector to ceiling distance. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a4 to in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. Listed by Underwriters Laboratories for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06 & 007a/04) as Quick Response Sprinklers. Approved by the City of New York under MEA 354-01-E. 10.Approved by the Loss Prevention Certification Board )LPCB Ref. No. 094a/06) at a 4 to 6 in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Whore Lead Coated Sprinklers are noted lobe FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. Installed with Style 10)1/2 in. NPT) 3/4 in.Total Adjustment Recessed Escutcheon. Installed with Style 20(1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon. Frame and deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprikter that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprin- kler condition and the long term integ- rity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. TFPI76 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED 250 PSI (17,2 BAR) HORIZONTAL SIDEWALL (1Y3331) or 175PS1 (12,1 BAR) RECESSED HORIZ. SIDEWALL (TY3331) 5.6 1/2 in. (SEE NOTE 1) NPT ___________________________ VERTICAL SIDEWALL 175 PSI (12,1 BAR) (TY3431) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 — XXX — X — XXX SIN SPRINKLER I I FT EMPERATURE I FINISH I I RATINGS 378 I HORIZONTAL SIDEWALL I TY3331 375 I VERTICAL SIDEWALL I TY3431 1 NATURAL BRASS - POLY-STAINLESS GREY 2 ALUMINUM (RAL9007)1 POLYESTER PURE WHITE (RAL9010)2 POLYESTER SIGNAL WHITE (RAL9003) POLYESTER - JET BLACK (RAL9005)3 POLYESTER 7 LEAD COATED 9 CHROME PLATED 135 135°F(57°C) 155 155-F (68-C) 175 175-F (79-C) 200 200°F (93°C) 286 286°F(141°C) NOTES: Available for TY3331 only. Eastern Hemisphere sales only. Available in 155°F (68CC) or 200°F (93CC temperature rating only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections: Specify: Series TY-FRB (specify SIN), (specify K-factor), (specify) Horizontal Sidewall or Vertical Sidewall Sprinkler, Standard Response, Standard Coverage, (specify) temperature rating, (specify) finish or coating, P/N (specify from Table C) Recessed Escutcheon Specify: Style (10 or 20) Recessed Escutcheon with (specify*) finish, P/N (specify*) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700 C 2018 Johnson Controls. All rights reserved. All specifications and other Information shown Were current ansi document revision data and are subject to change Without notice. Johnson NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are resist e,ed trademarks at NaSvr,cl Fire Prvlevtivn Association: Controls TEFLON is n registered IrodemaAc olOuPanI Worldwide tqciclo Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 140 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers are decorative glass-bulb sprinklers designed for use in light or ordinary hazard occupancies. They are intended for use in automatic sprinkler systems designed in accor- dance with standard installation rules, such as NFPA 13, for a maximum cov- erage area of 400 ft2 (37,2 m2) as com- pared to the maximum coverage area of 130 ft2 (12,1 m2) for standard cover- age sprinklers used in ordinary hazard occupancies, Series EC-11 and EC-14 Extended Coverage Sprinklers feature a UL and C-UL Listing that permits their use with unobstructed or non-combus- tible obstructed ceiling construction as defined and permitted by NFPA 13, as well as a specific application listing for use under concrete tees. Series EC-11 and EC-14 Extended Cov- erage Sprinklers have been fire tested to compare their performance to that of standard coverage spray sprinklers. These tests have shown that the pro- tection provided is equal to or more effective than standard coverage spray sprinklers. Corrosion-resistant coatings, where applicable, help extend the life of copper alloy sprinklers beyond that which occurs when exposed to corrosive atmospheres. Although corrosion-resistant coated sprinklers IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 passed standard corrosion tests of the applicable approval agencies, this testing is not representative of all pos- sible corrosive atmospheres. Conse- quently, it is recommended that the end user be consulted with respect to the suitability of these corrosion-resistant coatings for any given corrosive envi- ronment. The effects of ambient tem- perature, concentration of chemicals, and gas/chemical velocity should be considered, along with the corrosive nature of the chemical to which the sprinklers will be exposed. LL.1tL.I Series EC-11 and EC-14 Extended Cov- erage Sprinklers described herein must be installed and maintained in compli- ance with this document, as well as with the applicable standards of the NFPA, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the perfor- mance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Numbers TY5137 ............Upright, 11.2K TY5237 ............ Pendent, 11.2K 1Y6137 ............Upright, 14.0K TY6237...........Pendent, 14.0K TY5137 is re-designation for C5137, G1894. and S2510 TY5237 is re-designation for C5237, G1893, and S2511 TY6137 is a re-designation for C6137, G1896, and S2610 TY6237 is a re-designation for C6237, G1895, and S2611 OCTOBER 2018 Technical Data Approvals TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers are UL and C-UL Listed. Refer to Table A for complete sprinkler approval information including corrosion-resistant status. The approv- als apply to the service conditions indi- cated in the Design Criteria section. Series EC-11 and EC-14 Extended Cov- erage Sprinklers are FM Approved. Refer to Table A for complete sprinkler approval information including corro- sion-resistant status. The approvals apply to the service conditions indi- cated in the Design Criteria section. TFP22O 2-7/16" (61,9 mm) UPRIGHT & PENDENT I- 1/2"(12,7mm) J NOMINAL MAKE-IN UPRIGHT TFP22O Page 2 of 8 WRENCH FLAT 3/4" ESCUTCHEON PLATE NPT** SEATING SURFACE 16" 1 6* nm) - 5 CROSS PENDENT SECTION Components: 1 - Frame 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Compression Screw 6 - Deflector * Temperature rating is indicated on Deflector. ** Pipe thread connections per ISO 7-1 can be provided on special request. FIGURE 1 SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS 11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237) 14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237) ASSEMBLY The Style 60 Two-Piece Flush Escutch- eon (Figure 4) is UL Listed for use with the Series EC-11 and EC-14 Pendent Sprinklers. Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 3/4 in. NPT Discharge Coefficients K = 11.2 GPM/p5i½ (161,3 LPM/bar"") K = 14.0 GPM/p5i½ (201,6 LPM/bar½) Temperature Ratings Refer to Table A Finish Sprinkler: Refer to Table A Recessed or Flush Escutcheon: White-Coated, Chrome-Plated, and Brass-Plated Physical Characteristics Frame ............................Bronze Button............................Bronze Sealing Assembly . Beryllium Nickel w/TEFLON Bulb ........................Glass (3 mm) Compression Screw ................Bronze Deflector ...........................Brass Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, which- then allows the sprinkler to activate and flow water. Design Criteria TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must only be installed in accordance with the appli- cable UL and C-UL Listing or FM Approval requirements as indicated below. Only Style 30 or 40 Recessed Escutcheons are to be used for recessed installation, as applicable. Refer to Tables A, B, and C, for more information. UL and C-UL Listing Requirements Series EC-11 and EC-14 Extended Coverage Sprinklers may be used for the coverage areas shown in Table D, based on maintaining the minimum specified flow rate as a function of coverage area and haz- ard group for all sprinklers in the design area. Series EC-11 and EC-14 Extended Coverage Sprinklers are permitted to be used with unobstructed or non-combustible obstructed ceil- ing construction as defined and permitted by NFPA 13; for example: Unobstructed, combustible or noncombustible, ceiling con- struction with a deflector to ceiling/roof deck distance of 1 t 12 in. (25 to 300 mm). Obstructed, non-combusti- ble, ceiling construction with a deflector location below struc- tural members of 1 to 6 in. (25 to 150 mm) and a maximum deflector to ceiling/roof deck dis- tance of 22 in. (550 mm). Series EC-11 and EC-14 Extended Coverage Sprinklers, specifically tested and listed for non-combus- tible obstructed construction, are permitted to be used within truss- es or bar joists having non-com- bustible web members greater than 1 in. (25.4 mm) when apply- ing the 4 times obstruction crite- ria rule defined under "Obstruc- tions to Sprinkler Discharge Pattern Development". To prevent cold soldering, the minimum allowable spacing be- tween Series EC-11 and EC-14 Ex- tended Coverage Sprinklers is 8 ft (2,4 m) for upright sprinklers and 9 ft (2,7 m) for pendent sprinklers. Series EC-ii and EC-14 Extended Coverage Sprinklers are to be in- stalled in accordance with all oth- er requirements of NFPA 13 for extended coverage upright and pendent sprinklers; For exam- ple, obstructions to sprinkler dis- charge, obstructions to sprinkler pattern development, obstructions to prevent sprinkler discharge from reaching hazard and clearance to storage. TFP22O Page 3 of 8 Hazard Type Temperature Bulb Liquid Sprinkler Finish (See Note 5) Natu ral Brass I Chrome Plated I Polyester* Lead Coated 135°F (57°C) Orange Upright K=11.2 (TY5137) 1, 2, 3, 4 155°F (68°C) Red 175°F (79°C) Light Pendent Yellow 200°F (93°C) Green 1, 2, 4 1, 2,4 Table B describes UL and C-UL K11.2 (TY5237) K=14.0 (1Y6237) 286°F (141°C) Blue Recessed Pendent K=11.2 (TY5237) K=14.0 (TY6237) 135°F (57°C) Orange 1, 2, 3,4 N/A Sensitivity Rating Table C describes FM Sensitivity Rating 155°F (68°C) Red 175°F (79°C) Yellow With Style 30 Escutcheon 1, 2, 4 200°F (93°C) Green 286°F (141°C) Blue Ordinary Table B describes Upright K11.2 (TY5137) K14.0 (TY6137) Pendent K=11.2 (TY5237) 135°F (57°C) Orange 1, 2, 3, 4 Red 1, 2, 3, 4 155°F (68°C) 175°F (79°C) Yellow 1, 2, 4 200°F (93°C) Green UL and CUL Sensitivity Rating K=14.0 (TY6237) Blue 286°F (141°C) Recessed Pendent 135°F (57°C) Orange Table C describes 155°F (68°C) Red FM Sensitivity Rating K=11.2 (TY5237) K=14.0 (TY6237) With Style 30 or 40 1, 2, 4 N/A Di75°F (79°C) Yellow Escutcheon 200°F (93°C) Green NOTES Listed by Underwriters Laboratories, Inc. (UL) Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) Approved by Factory Mutual Research Corporation (FM) Approved by the City of New York under MEA 177-03-E Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers N/A = Not Available Frame and Deflector only Pendent only TABLE A LABORATORY LISTINGS AND APPROVALS Light Hazard Ordinary Hazard Area Style ftxft 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F (57°C) (68°C) (79°C) (93°C) (141°C) (57°C) (68°C) (79°C) (93°C) (141°C) Upright or Pendent - - - - - OR OR OR OR OR 14 x 14 Style 30 Recessed - - - - - OR OR OR OR OR Style 40 Recessed - - - - - OR OR OR OR OR Upright or Pendent OR* QR* OR* OR* QR* SR SR SR SR SR 16 x 16 Style 30 Recessed QR* QR* QR* OR* OR* SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent QR* QR* OR* OR* OR* SR SR SR SR SR 18 x 18 Style 30 Recessed QR* OR* OR* OR* OR* SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent QR* QR* OR' SR* SR* SR SR SR SR SR 20 x 20 Style 30 Recessed QR* QR* QR' SR* SR* SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR NOTES OR = Quick Response SR = Standard Response N/A =Not Applicable Does not apply to Upright K=14.0 TABLE B SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS (REFER TO TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS) TFP22O Page 4 of 8 HC-1 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max Noncombustible Unobstructed, 11.2 EC Pendent or 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Upright Combustible Unobstructed Noncombustible Unobstructed, 11 2 EC . Pendent 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Recessed Combustible Unobstructed Style 30 Quick 10 20 100 400 Up to 30 Combustible Obstructed 11.2 EC EC Pendentor 14.0 Upright 11 2 EC . Pendent 10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Recessed Style 30 10 20 100 400 Over 30 and upt045 Noncombustible Unobstructed 11.2 EC 14.0 EC Upright HC-2 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max 10 20 100 400 Up to 30 Noncombustible Unobstructed, 11.2 EC Upright 10 20 100 400 Upto30 14.0 EC Pendent or Upright Combustible Unobstructed Quick 10 16 100 256 Over 30 and 11.2 EC 14.0 Upright upt045 EC HC-3 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-Factor Style Response Min Max Min Max 10 16 100 256 Up to 30 11.2 EC Upright 10 20 100 400 Upto30 14.0 EC Pendent or Upright ______ Noncombustible Unobstructed, Combustible Unobstructed Quick 10 16 100 256 Over 30 and upt045 11.2 EC, 14.0 EC Upright NOTES The design for K 11.2 SC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0 EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar). For flow criteria, refer to FM Loss Prevention Data Sheet 3-26. Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations. TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS UL and C-UL Specific Application Listing Requirements for Installation under Concrete Tees Series EC-11 and EC-14 Extended Cov- erage Upright and Pendent Sprinklers (TY5137, TY5237, TY6137 and TY6237) have a UL and C-UL Specific Applica- tion Listing for use under concrete tees when installed as follows: 1. Stems of the concrete tee con- struction must be spaced at less than 7.5 ft (2,3 m) on center but more than 3 ft (0,9 m) on center. The depth of the concrete tees must not exceed 30 in. (762 mm). The maxi- mum permitted concrete tee length is 32 ft (9,8 m). However, where the concrete tee length exceeds 32 ft (9,8 m), non-combustible baffles, equal in height to the depth of the tees, can be installed so that the space between the tees does not exceed 32 ft (9,8 m) in length. 2. The sprinkler deflectors are to be located in a horizontal plane at or above 1 in. (25,4 mm) below the bottom of the concrete tee stems. 3. When the sprinkler deflectors are located higher than a horizontal plane 1 in. (25,4 mm) beneath the bottom of the concrete tee stems, the obstruction to sprinkler dis- charge criteria requirements of NFPA 13 for extended coverage upright and pendent sprinklers applies. TFP22O Page 5 of 8 Description Area ft x ft Light Hazard 0.10 GPM/ft2 Group Ordinary Hazard 0.15 GPM/ft2 Group 11 Ordinary Hazard 0.20 GPM/ft2 ____________ GPM ___________ PSI GPM ___________ PSI GPM PSI 14x14 30 7.2 30 7.2 39 12.1 TY5137 16x16 30 7.2 39 12.1 51 20.7 18x18 33 8.7 49 19.1 65 33.7 (K=11.2) Upright 20 x 20 40 12.8 60 28.7 80 51.0 14 x 14 30 7.2 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 TY5237 18 x 18 33 8.7 49 19.1 65 33.7 (K=11.2) Pendent 20x20 40 12.8 60 28.7 80 51.0 14 x 14 N/A N/A 39 7.8 1 51 13.3 16x16 N/A N/A 39 7.8 51 13.3 TY6137 18x18 N/A N/A 49 12.3 65 21.6 (K=14.0) Upright 20x20 N/A N/A 60 18.4 80 32.7 14 x 14 37 7.0 39 7.8 51 13.3 TY6237 16 x 16 37 7.0 39 7.8 51 13.3 18 x 18 37 7.0 49 12.3 65 21.6 (K=14.0) Pendent 20 x 20 40 8.2 60 18.4 80 32.7 NOTES 1 ft=0.3048 m 1 W = 0.093 m2 1 GPM = 3.785 LPM 1 psi = 0.06895 bar 1 GPM/ft2 = 40.74 mm/mm TABLED FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS FM Approval Requirements Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprin- klers are to be installed in accor- dance with the applicable FM Loss Prevention Data Sheet for limited use in buildings of specific roof construc- tion and for the protection of certain specific ordinary hazard (non-storage and/or non-flammable or combustible liquid) occupancies. Information pro- vided in the FM Loss Prevention Data Sheets relates to, but is not limited to, hydraulic design, ceiling slope, and obstructions, minimum and maximum allowable spacing, and deflector-to- ceiling distance. These criteria may differ from UL and/or NFPA criteria. Therefore, the designer should review and become familiar with FM requirements before proceeding with design. Installation TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286'F (141°C) temperature ratings. A leak-tight 3/4 in. NPT sprinkler joint should be obtained by apply- ing a minimum-to-maximum torque of 10 to 20 ft-lb (13,4 to 26,8 Nm). Higher levels of torque may distort the sprin- kler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutch- eon Plate by under or over-tightening the Sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler with the deflector parallel to the mounting surface. Install pendent sprinklers in the pendent position; install upright sprinklers in the upright position. Step 2. After installing the Style 30, 40, or 60 mounting plate (or other applica- ble escutcheon) over the sprinkler pipe threads and with pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. Step 3. For upright or pendent sprin- klers, wrench-tighten using only the W-Type 3 (End A) Sprinkler Wrench. For the pendent sprinkler installed with Style 30, 40, or 60 Escutcheon, wrench-tighten the sprinkler using only the W-Type 22 Sprinkler Wrench. Apply the wrench recess of the appli- cable sprinkler wrench (Figure 5 and 6) to the sprinkler wrench flats (Figure 1). TFP22O Page 6 of 8 2-7/8 DIA. 1/2±1/8 (73,0 mm) 1/2' (12,7 mm) (12,7±3,2 mm) 2-1/4' DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) S FITTING R 'E1 (3,2 mm) =///_li5 MOUNTING JT PLATE CLOSURE ____________ . 1-3/8" (34,9 mm) 1-1/8" (28,6 mm) FIGURE 2 SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 1/2 IN. TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 2-7/8" DIA. 5/8±1/4" - (73,0 mm) - 3/4' (19,1 mm) (15,9±6,4 mm) 2-1/4' DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) SPRINKLER 1/8' FITTING (3,2 mm) MIA MOUNTING MOUNTING SURFACE PLATE CLOSURE 1-3/8"(3 mm) 7/8" (22,2 mm) FIGURE 3 SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 3/4 IN. TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 2-7/8' DIA. (73,0 mm) INTERNAL 2-1/4' DIA. I I DIMENSIONS OF (57,2 mm) I STYLE 60 ESCUTCHEON I I CLASS15OMALLEABLE FACE OF IRON REDUCING SPRINKLER FITTING: I SPRINKLER FITTING 3/8 (9,5 mm) ABOVE TO 1/8" (3,2 mm) BELOW MOUNTING MOUNTING SURFACE 1/8" SURFACE JTh\ I ACCOMMODATE (3,2 mm) / ESCUTCHEON PLATE SEATING SURFACE: 1/4' (6,4 mm) ABOVE CLOSURE 5/16(587mm_ TO 1/2' (12,7 mm) BELOW 3/4,, NPT MOUNTING SURFACE; MOUNTING 1-13/16" (46,0 mm) 3/4" (19,1 mm) TOTAL PLATE ADJUSTMENT FIGURE 4 SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY WITH 3/4 IN. TOTAL ADJUSTMENT STYLE 60 TWO-PIECE FLUSH ESCUTCHEON "FITTING SIDE" TOWARDS SPRINKLER FITTING /\ WRENCH RECESS / (END "A") FIGURE 5 W-TYPE 3 SPRINKLER WRENCH WRENCH RECESS -_ - WRENCH HEX FIGURE 6 W-TYPE 22 RECESSED SPRINKLER WRENCH TFP22O Page 7 of 8 PIN 51 - XXX -X -XXX SIN j SPRINKLER TEMPERATURE FINISH1 RATING 893 11.2K Pendent TY5237 1 NATURAL BRASS 135 135°F (57°C) 894 11.2K Upright TY5137 SI? LITE 155 155°F (68°C) - POLYESTER 895 14.0K Pendent TY6237 JET BLACK (RAL9005) 175 175°F (79°C) - POLYESTER 896 14.0K Upright TY6137 200 200°F (93°C) 7 LEAD COATED - 286 286°F(141°C) 9 CHROME-PLATED - 000 OPEN2 NOTES: Escutcheon ordered separately. OPEN indicates the sprinkler assembly without glass bulb, button, and sealing assembly. TABLE SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Care and Maintenance TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal- lation section, for more information. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this doc- ument, as well as with the applicable standards recognized by the Approval agency, such as NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing con- tractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series EC-11 or EC-14 (specify) Sprinkler, SIN (specify), (specify) K-factor, Pendent or Upright (specify) Extended Coverage, (specify) temperature rating, (specify) finish, P/N (from to Table E) Recessed Escutcheon, Two-Piece Specify: Style (30 or 40) Two-Piece Recessed Escutcheon with (specify) finish, P/N (specify*) Refer to Technical Data Sheet TFP770 Flush Escutcheon, Two-Piece Specify: Style 60 Two-Piece Flush Escutcheon with (specify) finish, P/N (specify**) **Refer to Technical Data Sheet TFP778 Sprinkler Wrenches Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001 Specify: W-Type 22 Recessed Sprinkler, Wrench, P/N 56-665-7-001 TFP22O Page 8 of 8 1400 Pennbrook Parkway Lansdale, PA 194461 Telephone +11-215-362-0700 02019 Johnson Controls. All rights reserved. All specifications and other Information shown were current as of document revision data and are subject to change without notice. Johnson .1 NATIONAL FIvE PROTECTION ASSOCIATION and NFPA ore registered trademarks of Nations l Fire Protection Acoeviatiorri TEFLON iso reglntnrad trademark 01 DuPont Controls 11 Malleable Iron Threaded Pipe Unions Pressure - Temperature Ratings Temperature Pressure Class 150 Class 250 Class 300 'psi .I: :bar psi bar p5 oar 200 to 1500 -28.9° to 300 20.7 65.60 500 34.5 €OC 4.4 2000 93.30 265 18.3 455 31.4 55C 37.9 2500 121.10 225 15.5 405 27.9 50F 34.3 3000 148.9° 185 12.8 360 24.8 LEO 517 3500 176.70 150 10.3 315 21.7 415 28.6 4000 204.40 110 7.6 270 18.6 370 25.5 4500 232.20 75 5.2 225 15.5 325 22.4 5000 260.00 - - 180 12.4 2E0 19.3 5500 287.80 - - 130 9.0 230 15.9 Note: Unions with Copper or Copper Alloy seats are not intended for use where temeruture exces 450°F c®us APPROVED Malleable Iron Threaded Fittings Pressure - Temperature Ratings Temperature Pressure Class 150 Class 300 __________ Sizes Yr-i (6-15 mm) Sizes 11,/V-2' Sizes 21/u _30 (32-51 mm) 64-76 mm) (F bar psi' hà' pi pitr 200 to 1500 -28.9 to 65.60 300 20.7 2,003 137.9 1,500 103.4 ,000 68.9 200° 93.3 255 18.3 1,785 123.1 1,350 93.1 910 62.7 250° 12 1. 1 225 15.5 1,575 108.6 1,200 82.7 325 56.9 3000 148.9 135 12.8 1,360 93.6 1,050 724 735 50.7 350° 176.7 150 10.3 1,150 79.3 900 62.1 350 44.8 4000 204.4 - - 935 64.5 750 51.7 560 38.6 4500 232.2 - - 725 50.0 600 41.4 475 32.8 500° 260.0 1 - - 510 35.2 450 37.011 385 26.5 5500 287.e, - - 300 20.7 300 20.7 300 20.7 Anvil Class 153/300 Malleable Iron Fittings conform to ASME B16.3 and Unions conform to ASME B16.39. For Listings/Approval Details and Limitations, visit our vebsite @ www.anvilintl.com or contact an Anvil/AnvilStar Sales Representative. ALL ELBOWS & EES N" (10 DN ard LARGER ARE 130% GAS TESTED AT A MINIMUM CF 100 PSI. (6.9 bar) ~~) twww.anvilintl.com 17 PF-11.10 =1 =2 •i . i. SPRINKLER CATALOG 1Ii \\\ 4: . .- 1, •;' '. i-:: I. r c®us LISTED <s> APPROVED L NFPA ;•; t LMI=LJI JDYTHF I=nr-w I Wim 1SIIIYAIJA Bull Moose Tube® is a customer focused, growth oriented manufacturer and marketer of tubular products, where success is based on a commitment to meeting the customer's perception of quality. Our strength resides in our people working together to satisfy customers and to promote business growth by achieving superior financial performance. www.BullMooseTube.com sales@bullmoosetube.com 800.325.4467 BULL MOOSE TUBE COMPANY ran sprin Ii iprcedto r-. ® - rlleet'I rir r iitiestandrI iriI- Trt . !* ' -''• - :-' I ?.' I -- - -.- :': • ?ç ): - •:- c®us LISTED I H APPROVED I [] A. OAFSA 4: NFPA I ADVANTAGES OF BULL MOOSE TUBE® EDDY PIPE® FAMILY All pipe products are UL Listed (for U.S. and Canada), and have been approved by Factory Mutual. Excellent production and coating capabilities, tighter tolerances, and our unique steel properties make our pipe excellent for roll grooving, welding, threading, and plain end fittings. All products are certified to ASTM Al 35 and A795 Type E, Grade A. Available in specific cut to order lengths from regular mill rollings. More popular sizes available with coating or bare. Ultra Eddy®, Eddy Flow®, Eddylite®, and Eddythread 40® offer cost savings along with superior hydraulics without compromising service life. Sprinkler pipe inventory stocked in Masur Ohio; Gerald, Missouri; Casa Grande, Arizona; Kent, Washington; and Dallas, Texas. All Bull Moose (black) sprinkler pipe includes our exclusive EDDY GUARD Il® MIC preventative coating. Bull Moose Tube® sprinkler pipe is FBCTM compatible. PRODUCTS Schedule 10 and Schedule 40: FM approved and UL listed sprinkler pipe. Eddythread 40®: Light threadable Schedule 40 replacement with corrosion resistance ratio of 1.0. Eddylite®: Lightwall threadable with standard outside diameter. Eddy Flow®: Cost effective replacement for Schedule 10. Ultra Eddy®: Lightwall roll groovable pipe. Bull Moose galvanized steel sprinkler pipe is hot dipped galvanized to meet ASTM Al 23 standards. All products are stencilled to meet FM & UL specifications. PROTECTION Eddy Guard Il®: Bull Moose Tube® is producing product that can resist bacteriological growth even after multiple rinse-outs. You know MIC corrosion can impact your installation and your property. Specify Bull Moose Tube® "Eddy Guard Il®" and feel comfortable knowing that you are getting Eddy Pipe® product you trust with the bacteria resistance you need. Eddy Guard Il® is NFPA 13 and NFPA 13R system compatible for use in hybrid systems as well as FM approved. All information contained herein is accurate as known at the time of publication. Bull Moose Tube® reserves the right to change product specifications without notice and without incurring obligation. ano drid(la), CVflTfl( productsrdo notThi4ui approvals andlistings ' •t Moose Tube made th to have them approve OurSrhed ne 1 Oand have a pressure ratinc and, have been throug rigorous testing as ou pipe products. Schedu suppIiedroHqroovm .Bull MooTube's Sc - .andSchedLile 44ipes dipped galvanized to n Al 23 standardsAlI pr st icillid to meet FM sfic3ubns. 45 , tASTM J(ts are .- S LI S SCHEDULE 10 PIPE SPECIFICATIONS NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE 1.097 JL157L11.4iiLft J .80 JL :J!iij l FEW 9J 5L 11/2 1fli900T1682 77 [2091bs/ft 3031 -. jIff 21I2 - _ [2635 492 I53IbtftjE893l 350Q 260 ________ 341iift 957k 41L _4500 4260 ll25OJ 562 ifL SCHEDULE 40 PIPE SPECIFICATIONS NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE L i 315 1-049 10 11,68 lbs/ft[ 2.055 IL 70 j660 a 380 10Q 2Jft E2Th1TL 12 [Th 900 ] i6 100 Till 23i5 r 2 06] ' rThoL7L 366ft Ei i4L=30= fl21/2*_T2.875 2 468 100 80I/ft j 3L1 io 3Q68 8[bftI b3 - 4* r 4500 1 4026 100 10.80-16 T3i]r19 i *Only available in Casa Grande, AZ **Corrosion Resistance Ratio per latest UI Directory Listing c®us LISTED <> APPROVED ONFSA NFPA - -- PIPE PREPARATION For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket, pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer's instructions for the specific fitting used. For Additional Information Contact (800) 325-4467 www.buIlmoosetube.com - , Or From Canada Call (800) 882-4666 sales@builmoosetube.com 1819 Clarkson Road Chesterfield, MO Gerald, MO Kent WA Casa Grande. AZ Dallas TX Masury, OH BULL MOOSE TUBE cosr,jy 63017 FireLock® Outlet-I ILPCBI SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating ½, 3/4, and 1/15, 20 and 25 mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and other outlet products. Available for P14 through 76.1 mm/32 to 76.1 mm piping systems, Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe. When tightened, the assembly compresses the gasket onto the OD of the pipe. The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Gasket: Grade "E" EPDM - Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade "E" Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: Orange enamel (North America, Latin America, Asia Pacific) Red enamel (Europe) JOB/OWNER CONTRACTOR ENGINEER System No Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com vIcTAuLIc IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV G Ai tauIicr U152 1 DIMENSIONS IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS FireLock® Outlet-T STYLE 922 Nominal Size i nchesimm Hole Diameter Dimensions - i nc hes/milli meters Approx. Weight Each Run X Branch +0 * 0641.5 V 1 1/4 ½ 1 3A6 130 1.83 1.10 3.87 2.56 1.0 x 32 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45 3/4 11/16 1.28 1.83 1.10 3.87 2.56 1.1 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 1 1 3A6 1.52 2.18 1.10 3.87 2.56 1.2 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 11/3 ½ 1 3A6 1.42 1.95 1.22 4.08 2.56 1.2 x 40 15 30.2 36.1 49.5 1 31.0 103.6 65.0 0.54 3/4 1 3A6 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 1'/16 1.64 2.30 1.22 4.08 2.56 1.3 25 302 41.7 58.4 31.0 1 103.6 65.0 0.59 2 ½ 1'/16 1.66 2.19 1,46 4.60 2.56 1.3 x 50 15 30.2 1 42.2 55.6 37.1 116.8 65.0 0.59 3% 1 3/16 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 1 3/16 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 64.5 37.1 1 116.8 65.0 0.68 2½ ½ 1 3/16 1.91 2.44 1.71 5.40 2.56 1.6 x 65 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 3% 1 3/16 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 0.73 1 1 3Ao 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 70.9 1 43.4 137.2 65.0 0.73 /2 1/l6 1.91 2.44 1.71 5.50 2.56 1.6 X 76.1 mm 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73 3% 13A6 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 620 43.4 139.7 65.0 0.73 1 1 3A6 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 1 0.80 f Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional) male pipe threads only. Use of male threaded products with special features, such as probes, dry pen- dent sprinklers, etc., should be verified as suitable for use with this Victaulic product. Failure to verify suitability in advance may result in assembly problems or leakage. Center of run to engaged pipe end for NPT threads (dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 10.52 2 Aictaulicr REV C, IPS, CARBON STEEL PIPE - HOLE CUT PRODUCTS iU.ZL PERFORMANCE Run Size x Outlet Size Equivalent Length of 1 inch Schedule 40 Steel Pipe (per UL 213, Section 16) (C=120)*, FT Inches/mm Feet/meters x 40 25 1 ¶1 A. 21/2 65 4. 1.1•iiii Hazen-Williams coefficient of friction is 120 FireLock® Outlet-I STYLE 922 www.victaulic.com ,s$(c;:tauIic.f' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. RflI r 10V;9 3 FireLock® Outlet-I STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. For complete contact information, visit www.victaulic.com 'j4'ctauiic. 10.52 3355 REV G UPDATED 12/2009 vlcTAuLlc IS REGISTERED TRADEMARK OF vICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 1052 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER I thru 4 inch pipe LISTED FOR STEELJCPVC 1/2 & 3/4 inch pipe 5 thru 8 inch pipe SIZE - ROD- 3/8" or 1/2" SIZE - SYSTEM PIPE - 1/2" thru 8" MATERIAL - Carbon Steel, Mil. Galvanized to G-90 spec. LISTING/APPROVAL - C®U8TDUs2 03-EX 2551 1"- 8" 4e> Approval guide - 1"- 8" OSHPD OPA-0601 See Website. CONFORMS WITH: Federal Specification WW-H-171E, Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE - 650°F. FUNCTION - Pipe hanger component of an AFCON hanger. To support steel, CPVC or copper pipe. INSTALLATION - Per NFPA 13, 13R, 13D, these instructions and the CPVC or copper pipe manufacturers instructions. FEATURES - * Sized and listed exclusively for use with #310 Surge Restrainer. * Band edge is offset for EASY pipe insertion. * Custom fit swivel nut for better retention in ring. ORDERING - Part #, pipe size. NFPA 13 PIPE ROD I WT. 5 WT.+250 UL TEST LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 11/2 3/8 54.15 520.75 750 2 3/8 76.95 1 634.75 750 21/2 3/8 118.35 841.75 850 3 1 3/8 162.30 1061.50 1050 4 3/8 246.00 1460.00 1500 5 1/2 349.45 1996.75 2000 6 1/2 476.35 2631.75 2650 8 1/2 1 711.00 3805.00 4050 11/09 551 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 310 RING RESTRAINER Restraint SIZE - One size fits 3/4 thru 2 inch AFCON#300 Ring Hanger. MATERIAL - Carbon Steel. FINISH - Mu. Galvanized. LISTINGS - Sus 203-EX 2551 Listed only for use with AFCON #300 Ring Hanger. FUNCTION - To restrain movement of sprinkler pipe toward the knurl nut of the ring hanger. To prevent upward movement of pipe that supplies a pendent sprinkler below the ceiling. INSTALLATION - Per NFPA 13 and CPVC manufacturers instructions on steel, CPVC, or copper pipe. Snap into locking position on swivel nut of AFCON #300 Ring Hanger. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FEATURES - * Listed only for use with AFCON #300 Ring Hanger. ORDERING - Part # and size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction wilt apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 1/08 Not less than Wood Flooring 2' nominal width Product Features No pre-drilling required. Not less than ! I: ir Quick to install using the Sammy 3' nominal Nut Driver with an 18V cordless thickness (2-1/2') (depth or side Wood Joist drill/driver. of vertical member) - - - 'Saves time from traditional Double Sheebock methods. Ceiling Reduces installation cost _________Composite i Truss Consult truss manufacturer for recommended installation point *Pre-driffing maybe required for G 25-380. Tool available on page I IT Made in the U.S.A. __ 1/4' 8003957 GST 200 114x2 1760 (Fir) 25 125 1'T480097GSj100-'/47x'3" 206j) 2512 3/8 8006957 GST.75 114x3/4 564 (3/4' Ply) 25 125 887957GS,ffi l74 3{oo 2525 3/8' 8008957 GST 20 1/4 x 2' 1760 (Fir) 850 1475 25 125 3180689251 2 1760 850 252 kilo 3/8 8009925 GST 25-380 3/8x2-112' 213 (Fir) 1500 25 125 #14 lack 7_4 1500 14Z5 2 3/8' 8069925 GST 30-SS 1/4x3 2060 (Fir) 25 125 Nut Driver Part# 8113910 1i44 2,1802fr) 25125 3/8" 8012925 GST 60 1/4 x 6" 2230 (Fir) 25 125 112013925SJ2 1]42 l76J(//) 25f2 1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125 172825GT313 1/43 2275JEJr1 251 1/2' 8016925 GST4 1/4x4' 2180 (Fir) 25 125 i728017925TI6 1/46' 23IirJ 2b12 #14 SW Red Nut Driver Part# 8114910 Product Features Eliminates distortion of threaded rod. • Saves time from traditional methods. 'Accommodates up to 3 'Ia" x 12 pitch roof. • Reduces installation cost. 'Allows 17" deflection from vertical. • Made in the U.S.A. 3/8' 8141957 SH-GST 30 1/4x 3' 1720 (Fir) 1500 1475 25 125 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact wi;h the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. ARL For the most up to date information, visit www.sammysuperscrew.coin 47' Lamm --- \w - •"I- 4 #14 Black Nut Driver Part# 8113910 I Floor Joist Product Features No pre-drilling required. Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. Saves time from traditional methods. Reduces installation cost Made in the U.S.A. Not less than 2' nominal width / (1-1/2') up to 3-1/2' ripe; not less than 3' (2-1/2') nominal width 4' & 5' pipe .4 I Minimum 2-1/2' from bottom for branch lines. Minimum 3' from bottom for main linen. Exception: This requirement shall not apply to 2' or thicker nailing strips resting on top of steel beams. Insert the appropriate nut driver into a 3/8" or 1/2" portable drill. Insert the SAMMYS into the #I4SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation. When the nut driver spins free on the SAMMYS, stop the drill and remove. The unit is now ready to receive 1/4' 3/8" or metric all thread rod or bolt stock. Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. -' 114' 8Cfj WG00 74i' 6221iEJi) 25 t25 1/4' 8019957 SWG 200 1/4x2' 1725 (Fir) 25 125 - 37ll ——BO07 SW0 171 622r(id 300 25 12# X 3/8" 8021957 SWG 20 1/4x2' 1725 (Fir) 1050 25 125 218807.392 SWG 850 12 #14 SW Red XSjl. 3/8' L 8022925 SWG 25-380 3/8 X 2-1/2" 2249 (Fir) 1500 25 125 Not Driver 3/8'8023925 SWG'30 1j43 188(EJr) 25 12 Part#8114910 Insert the appropriate nut driver into a .3/8' or 1/2" portable drill Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position. Push the face of the nut driver tight to the member When the nut driver spins freely on the SAMMYS, stop drill and remove. The SAMMYS is now ready to receive 1/4", 3/8", 1/2" or metric all thread rod, bolt stock. (The 1/2" requires the #14S W red nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. mpj on EXISHIM ER , I Fol!'11 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, ::ontinoe drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.