HomeMy WebLinkAbout3247 CAMINO DE LOS COCHES; 210; FPC2019-0161; PermitPERMIT REPORT
(city of
Carlsbad
Print Date: 05/11/2022
Job Address: 3247 CAMINO DE LOS COCHES, #210, CARLSBAD, CA 92009-8970
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2550313100 Track #:
Valuation: $111,251.92 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPC2019-0161
Status: Closed - Finaled
Applied: 07/15/2019
Issued: 08/05/2019
Finaled Close Out: 09/25/2019
Final Inspection:
INSPECTOR: Salcedo, Felix
Fieri, Dominic
Project Title:
Description: ROW HOUSE -SPRINKLER TI (16 HEADS)
Applicant: FPContractor:
METRO FIRE AND SAFETY METRO FIRE AND SAFETY
MIKE LAVALLE 2733 VIA ORANGE WAY, # 103
2733 VIA ORANGE WAY, # STE 103 SPRING VALLEY, CA 91978-1717
SPRING VALLEY, CA 91978-1717 (619) 670-3500
(619) 415-2248
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRICNV
UPRIGHT CONVENTIONAL
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRISW
PENDENT VERTICAL
SIDEWALL
GLbBE
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response Series GL-QR Sprinklers are
a low profile yet durable design which utilizes a 3mm frangible
glass ampule as the thermosensitive element. This provides
sprinkler operation approximately six times faster than ordinary
sprinklers. While the Quick Response Sprinkler provides an
aesthetically pleasing appearance, it can be installed wherever
standard spray sprinklers are specified when allowed by the ap-
plicable standards. It offers the additional feature of greatly in-
creased safety to life and is available in various styles, orifices,
temperature ratings and finishes to meet many varying design
requirements. Quick Response Sprinklers should be used ad-
visedly and under the direction of approving authorities having
jurisdiction.
The heart of Globe's Series GL-QR sprinkler proven ac-
tuating assembly is a hermetically sealed frangible glass ampule
that contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the inter-
nal pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern depending upon the deflector style
used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings - 135°F (57°C), 155°F (680C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
Water Working Pressure Rating - 175 psi (12 Bars) QUICK RESPONSE Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C' HORIZONTAL LPCB/CE
SIDEWALL HORIZONTAL Frame - bronze • Deflector - brass • Screw - brass SERIES GL-QR/SW SIDEWALL
Lodgement Wire - stainless steel • Bulb seat - copper SERIES GL-QRISW
Spring - nickel alloy • Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
[N\L I ASSIFCATION AVAILABLE SPRINKLER BULB COLOR I N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARY ORANGE/RED
INTERMEDIATE YELLOW/GREEN
HIGH BLUE
MAR 2018 GFS-100a (Formerly A-20)
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
UPRIGHT PENDENT VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm)
4.2 (60 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Factory Bronze
5.6 (80 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Chrome
White Polyester'
8.0 (115 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Black Polyester2'3
8.0 (115 metric) I 3/4"NPT (20mm) 27/16" (6.2cm)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 9/16".
'FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
LISTINGS/A PPftO VA LS
MRATURE NYC - DOB
STYLE SIN K
FACTOR HAZARD' cULus FM LPCB2 CE MEA 135°F 155 175°F 200°F 286°F
(57°C) (68°C) (79°C) (93°C) (141°C) 101-92-E
GL2815 2.8 LH X X X X X X --- --- --- X
GL4215 4.2 LH X X X X X X --- --- --- X
UPRIGHT GL5615 5.6 LH/OH X X X X X X X X X X
GI-8115- 8.0* (½" NPT) LH/OH X X X X X X --- --- X
GL8118 8.0 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X --- --- X
' GL4201 4.2 LH X X X X X X --- --- --- X
PENDENT_ GL5601 5.6 LH/OH X X X X X X X X X X
GL8101* 8.0*(Y2NPT) LH/OH X X X X X X --- --- X
GL8106 8.0 LH/OH X X X X X X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X
SIDEWALLt GL8133 8.0 LH X X X X X X ---
GL2826 2.8 LH X X X X X X --- --- X
GL4226 4.2 LH X X X X X X --- --- --- X HORIZONTAL GL5626 5.6 LH/OH X X
,
X X X X X --- --- X SIDEWALL GL5627D 5.6 LH/OH X X X X X --- X X
GL8127 8.0 LH/OH X X X X X X ---
CONVENTIONAL GL5624 5.6 LH/OH X X X X X --- X X
(OLD STYLE) GL8125 8.0 LH/OH X X X X X --- --- --- X
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA1 3 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
INSTALL IN ACCORDANCE TO B55306 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OR ORDINARY HAZARD
LH: LIGHT HAZARD
*1/2 NPT, FOR RETROFIT ONLY
2 LPCB REF. NO. 147c/05
ORDERING INFORMATION GLOBE® PRODUCT WARRANTY
SPECIFY Globe agrees to repair or replace any of its own manufactured
Quantity • SIN • Style • Orifice products found to be defective in material or workmanship for a
Thread Size • Temperature • Finishes desired period of one year from date of shipment.
Quantity - Wrenches - P/N 325390 (1/2"); For specific details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
GLBE
FIRE SPRINKLER CORPORATION
MAR 2018
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U.S.A. GFS-1 00a (Formerly A-20)
FPC20I9-0161
3247 CAMINO DE LOS CO
C
K
S
#210
ROW HOUSE- SPRINKLER T
1
6
H
E
A
D
S
)
2550313100
7/1512019
FPC20I9-0161