HomeMy WebLinkAbout2270 CAMINO VIDA ROBLE; L; AS050247; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS050247
2270 CAM INO VIDA
Job Address:
ROBLE
Permit Type: SPRINK
Parcel No: 2130504700
Lot #: 0
Reference No.:
Status: ISSUED
Applied 12/2/2005
Approved:
Issued:
PC #: Inspector:
Project Title: SPEC SUITE L FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Applicant:
AZTEC FIRE PROTECTION
8109 COMMERCIAL STREET
LA MESA, CA
(619) 464-5625
Owner:
2270 CAM INO VIDA ROBLE LLC
685 TURQUOISE ST
LA JOLLA CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
120 0 120 0
A soso 2.4
.ti,co •/•Fire ..& &itdin.:
/ Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500 I
Series TYFRB - 28,4.2,5.6, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position.The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any otherauthorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.81K, 1/2'NPT
TY1231 - Pendent 2.8K, 112'NPT
TY2131 - Upright 4.21K, 112"NPT
TY2231 - Pendent 4.21K, 1/2NPT
TY3131 - Upright 5.61K, 1/2'NPT
JULY, 2004
'..
TY3231 - Pendent 5.61K, 112'NPT
TY4131 - Upright 8.01K, 3/4NPT
TY4231 - Pendent 8.01K, 3/4NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/barl/2)
K = 4.2 GPM/psil/2 (60,5 LPM/bar112)
K = 5.6 GPM/ps1112 (80,6 LPM/barl'2)
K = 8.0 GPM/ps11'2 (115,2 LPM/barll2)
Temperature Ratings
Refer to Table A and B
TFPI7I
ESCUTCHEON 7116 (11,1 mm)
PLATE SEATING ** NOMINAL
SURFACE MAKE-IN
T_
2-114
(57,2 mm) T
SSP DEFLECTOR* H— 2-7/8' (73,0 mm) DIA.
7/16"(11,11 mm)
** NOMINAL
NPT MAKE-IN
ESCUTCHEON
PLATE SEATING
SURFACE
2-J16.
6mm)
(55,6 mm)
1
(38,
STYLE 10or20
RECESSED
ESCUTCHEON
WRENCH
FLATS
Page 2 of 8 TFPI7I
STYLE 10 or 20
RECESSED SSU* ESCUTCHEON DEFLECTOR
(11,1 mm) I
NOMINAL I
LI
7/1& I
WRENCH
MAKE-IN
2-3/16'
7 FLATS
(55,6 mm)
1/2NPT** t SSP DEFLECTOR * H- 27/80 (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1,2 INCH NPT
SSU*
DEFLECTOR
6*
7/16'
MAKE-IN
WN(
0MIr
11,1mm)
AL I
,, : I 2-3/16'
$ (55,6 mm) 3
/
1/2' NPT** t
1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2K-FACTOR, 1/2 INCH NPT
Finishes Bulb ..............Glass
Sprinkler: Refer to Table A and B Compression Screw .....Bronze
Recessed Escutcheon: White Coated, Deflector .......Copper/Bronze
Chrome Plated, or Brass Plated Bushing (K=2.8) .......Bronze
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
4-
7/16" (11,1 mm)
NOMINAL
MAKE-IN 1/2" **
NPT
SSu*
DEFLECTOR
6*
1/2" 5
(12,7 mm) I
NOMINAL I
:
4
MAKE-IN
2-1/4"
$ (57,2 mm) /
I 3
3/4' NPT** I
UPRIGHT CROSS SECTION
TFPI7I Page 3 of 8
ESCUTCHEON
PLATE SEATING
SURFACE
T_
2-3/16" 6
mm)
(55,6 mm)
1
(38,
STYLE 100r20
RECESSED SSU* ESCUTCHEON DEFLECTOR
/
-zr
7/16"
(11,1 mm) 1
NOMINAL I
MAKE-IN
2-3/16"
' J WRENCH (55,6 mm)
FLATS I
—1 1/2"NPT SSP DEFLECTOR* 1— 2-7/8" (73,0 mm) DIA.
iI
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE MAKE-IN NPT ESCUTCHEON
2-5116"
(58,7 mm) f
1-9/16" I (39,7 mm) WRENCH
e e
FLATS
I I
SSP DEFLECTOR* 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Design
Criteria
The Series TYFRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
Page 4 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL I CHROME WHITE I
LIQUID BRASS PLATED 1POLYESTER
135°F/57°C Orange
PENDENT
(TY1231)
and 1,2,3,5
155°F/68°C Red
175°F/791C Yellow
UPRIGHT 200°F/93°C Green
2.8
1/2'
(TY1131) 286°F/141°C Blue
NPT 135°F/57°C Orange
RECESSED
PENDENT 155°F/68°C Red
175°F/79°C Yellow (TY1231)*
Figure 5 1, 2, 5 200°F/93°C Green
135°F/57°C Orange
RECESSED
PENDENT 155°F/68°C Red
175°F/79°C Yellow (TY1231)-
Figure 6 200°F193°C Green
135°F157°C Orange
PENDENT
(TY2231) 155°F/68°C Red
175°F/79C Yellow and
UPRIGHT 200°F/93°C Green
4.2
1/2"
(TY2131)
1,2 286°F/141°C Blue
135°F/57°C Orange NPT
RECESSED
PENDENT
1550F/681C Red
175°F/79°C Yellow (TY2231)
Figure 7 200°F/93°C Green
135°F/57°C Orange
RECESSED
PENDENT 155°F/68°C Red
175°F179°C Yellow (TY2231)**
Figure 8 200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
TFPI 71
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.Ibs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/1410C
temperature ratings.
A leak tight 1/2 inch NPTsprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
112 NPT connections. A leak tight 314
TFPI7I Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED I
WHITE
POLYESTER
LEAD
COATED
5.6
1/2"
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5
155°F/680C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT 135°F/57°C Orange
1, 2, 4,5 N/A
RECESSED
PENDENT
(TY3231)"
Figure 9
1551F/681C Red
175°F/79°C Yellow
200°17/931C Green
135°F/57°C Orange
1, 2, 3, 4,5
I I I
I 1,2, 4,5
Green
N/A
RECESSED
PENDENT
(TY3231)"
Figure 10
155°F/68°C Red
175°F/79°C Yellow
2000F/930C
8.0
3/4"
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C Orange
1, 2, 3,4,5,6, 7
1,2,5
155°F/680C Red
175"F179°C Yellow
200°F/93°C Green
286°F1141°C Blue
NPT 135°F/57°C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)"
Figure 11
155°F/68°C Orange
175°F179°C Red
200°F/93°C Yellow
1,2,3,4,5 N/A
RECESSED
PENDENT
(TY4231)"
Figure 12
135°F/57°CN
Green
155°F/68°C
175°F179°C
2000F/930C
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k104) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40(3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2* NPT) or Style 30(3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8
- 2-7/8' DIA.
5/8±1/4'
(73,0 mm) 314' (19,1 mm)
(15,9±6,4 mm) 2-114' DIA. 1/4' (6,4 mm) I
SPRINKLER PLATE
FITTING
OF
1572 mm)
MOUNTING I
1/8' I
(3,2 mm)
SURF ACE
MOUNTING
1-5/1 6' (33,3 mm)I CLOSURE SERIES
TY-FRB 13/16'(20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA. -
5/8±1/4'
(73,0 mm) I 3/4'(19,1 mm)
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6,4 mm) I
FACE OF (57,2 MOUNTING I
SPRINKLER PLATE I FITTING
1/8'
MOUNTING
\/
SURFACE
SERIES 1-1/4' (31,8mm) CLOSURE 1YFRB 3/4' (19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
42 K-FACTOR, 1/2 INCH NPT
TFPI 71
- 2-7/8' DIA.
(73,0 mm) I 1/2±1/8' I 1/2"(12,7 mm) r (12,7±3,2 mm) 2-1/4' DIA. 1/4' (6,4 mm) 1
SPRINKLER PLATE I
FACE OF f57.2 mm) MOUNTING I
FITTING
R2 mm)
MOUNTING
SURFACE/
mm) SERIES 1-5/16' (33,3 m
TY-FRB 1-1/16' (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA. (73,0 mm) 1/2±1/8' I 1/2'(12,7 mm) r (12,7±3,2 mm) - 2-1/4 DIA. I 1/4'(6,4 mm) I I FACE OF (57,2 mm) MOUNTING I I SPRINKLER PLATE I
I
I FITTING
1/8'
(32 mm) I
MOUNTING
$1 SURFACE
SERIES 1-1/4' (31,8 mm)1 CLOSURE TYFRB 1' (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI 71
- 2-7/8' DIA.
5/8±1/4' (73,0 mm) 314'(19,1 mm)
(15,9±6,4 mm) - 2-1/4' DIA. 1/4' (6,4 mm)
FACE OF MOUNTING SPRINKLER PLATE FITTING
1/8'
71
MOUNTING,,"
SURFACE
CLOSURE SERIES 1-1/4'(31,8 mm)
TY-FRB 34'(19,11 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA. -
5/8±1/4' (73,0 mm) 3/4' (19,1 mm)
(15.9±6,4mm) _2-1/4-DIA.. 1/4' (6,4 mm)
FACE OF (57,2 mm) T1 MOUNTING
SPRINKLER 'ç 71 _.,..._. PLATE
FITTING 18
__ - _____________ (3,12 mm)
MOUNTING
/1
SURFACE
,
/'
CLOSURE SERIES 1-5/16' (33,3 mm)
TYFRB 13116'(20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
- 2-7/8' DIA.
(73,0 mm) 1/2±1/8' 1/2'(12,7 mm) r (12,7±3,2 mm) 2-1/4' DIA. 1/4'(6,4 mm) I
FACE OFqR mm) MOUNTING
i SPRINKLE PLATE I FITTING
1/8'
(32mm)
MOUNTIN
SURFAC
SERIES 1-1/4'(31,8 mm) CLOSURE TV-FRB 1'(25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
1/2±1/8' (73,0 mm) I 1/2"(12,7 mm)
r (12,7±3,2 mm) 2-1/4' DIA. 1/4'(6,4 mm) I
FACE OF (57,2 MM) I MOUNTING I I SPRINKLER I PLATE I FITTING
1/8'
(
3.2mm)
/ T__\_
MOUNTING
SURFACE
CLOSURE SERIES 1-5116"(33,3 mm
TY-FRB 1-1/16' (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
WRENCH RECESS
(END 'A' USED FOR
1/2' NPT MODELS)
WRENCH RECESS
(END 'B' USED FOR
3/4' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFPI7I
PIN 57-XXX-X-XXX
I L
MODELJSIN
330 2.8K UPRIGHT (1/2'NPT) TY1131
331 2.8K PENDENT (1/2'NPT) 1Y1231
340 4.2K UPRIGHT (1/2'NPT) TY2131
341 4.2K PENDENT (1/2"NPT) TY2231
370 5.6K UPRIGHT (1/2'NPT) TY3131
371 5.6K PENDENT (1/2'NPT) TY3231
390 8.0K UPRIGHT (3/4'NPT) TY4131
391 8.0K PENDENT (3/4'NPT) TY4231
I I SPRINKLER
135
155
175
200
286
RATING
135°F157°C
1 NATURAL BRASS 155°F168°C
4 WHITE POLYESTER 175°F179°C
3 WHITE (RAL9010)* 200*F/93*C
9 CHROME PLATED 286°F/141°C
7 1 LEAD COATED
* Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
Local distributor for avail-
abI1.indicate the fulrproduct
name. Refer to
the Price List for complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2' (15 mm) Style 10
Chrome Plated ............P/N 56-701-9-010
White Coated .............P/N 56-701-4-010
White RAL9O1O. ........... P/N 56-701-3-010 Brass Plated ..............P/N 56-701-2-010
1/2' (15 mm) Style 20
Chrome Plated ............P/N 56-705-9-010
White Coated .............P/N 56-705-4-010
White RAL9O1O. ........... P/N 56-705-3-010
Brass Plated ..............P/N 56-705-2-010
3/4' (20 mm)
Style 30
Chrome Plated ............PIN 56-705-9-011
White Coated .............P/N 56-705-4-011
White RAL9O1O ............ P/N 56-705-3-011 Brass Plated ..............P/N 56-705-2-011
3/4 (20 mm)
Style 40
Chrome Plated ............P/N 56-700-9-010
White Coated .............P/N 56-700-4-010
White RAL9010' ...........P/N 56-700-3-010
Brass Plated ..............P/N 56-700-2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446