Loading...
HomeMy WebLinkAbout3300 CAMPO AZUL CT; ; FPR2016-0009; PermitPERMIT REPORT cäty of Carlsbad Print Date: 05/19/2022 Permit No: FPR2016-0009 Job Address: 3300 CAMPO AZUL CT, CARLSBAD, CA 92010-5700 Status: Closed - Finaled Permit Type: FIRE-Construction Residential Work Class: Multifamily Fire Alarm Parcel #: 1670404500 Track #: Applied: 11/21/2016 Valuation: $0.00 Lot #: Issued: 11/30/2016 Occupancy Group: Project #: DEV10045 Finaled Close Out: 03/25/2021 #of Dwelling Units: Plan #: Bedrooms: Construction Type: Final Inspection: Bathrooms: Orig. Plan Check #: INSPECTOR: Wong, Cindy Plan Check #: Fieri, Dominic Project Title: QUARRY CREEK Description: AGAVE AT THE PRESERVES: SPRINKLER MONITORING SYSTEM FEES ASSESSED INCLUDE 4 PLANCHECK FEES FOR EACH OF THE 4 TYPES OF DEVICES AND 18 INSPECTION FEES FOR EACH BUILDINGS FPContractor: HCI SYSTEMS INC 4585 MURPHY CANYON RD SAN DIEGO, CA 92123-4318 (909) 628-7773 FEE AMOUNT FIRE Expedited Plan Review Per Hour - Office Hours $198.00 FIRE Sprinkler Monitoring $767.00 FIRE Sprinkler Monitoring $899.00 FIRE Sprinkler Monitoring $371.00 FIRE Sprinkler Monitoring $1,295.00 Total Fees: $3,530.00 Total Payments To Date: $3,530.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 1 I www.carlsbadca.gov Parsley Consulfing Plan Review Comments for Agave at the Preserve Sprinkler Monitoring page 2 of 2 I) The requirements contained in NFPA 72, section 7.7.2 must be verified, including: A documentation cabinet installed at an approved location [7.7.2.1] Record documentation is required to be stored in that cabinet [7.7.2.2] Indication on the control unit as to the cabinet location should be provided if the cabinet is not at the control unit. [7.7.2.3] Cabinet should be prominently labeled "SYSTEM RECORD DOCUMENTS" [7.7.2.4] Contents of the cabinet are to be accessible only by authorized personnel. [7.7.2.5] 0 Cabinet should include copies of record of completion, record of inspection and testing, and risk analysis. [7.8.2] We strongly recommend the following operational tests be performed once the system installation has been completed. a. A "power off' test, where the normal power supply is shut off, and the system is left to function on battery power alone for a period of 24 hours, at which time the system should still be functioning and operational. At the end of the end of the above test, prior to the primary power being restored, the system should be placed in an "alarm" condition for a period of not less than five minutes, during which time all notification appliances, including the off-station notification, are to function as designed. Once the two prior tests have been completed, the current level in the batteries should be checked, the primary power restored, and at the end of 48 hours the current level checked again to verify that the charging function of the panel is both operational, and able to recharge the batteries within the time period specified by NFPA-72. Once the test in item "c" has been completed, one of the leads to the battery should be disconnected, to determine that the system will provide notification of an "off-normal" power condition to the monitoring company. File: c:\Plan Rev iews\Rev2 16365.1 .Docx Pr&2.o ((P,, ox 9 j CI Systems Inc. FIRE / LIFE SAFETY & LOW VOLTAGE SPECIALISTS California Contractor's License # 905493 Sprinkler Monitoring System Complete Material Submittal Prepared for: AGAVE AT THE PRESERVE 3128 Ceja Place, Carlsbad, CA 92008 4585 Murphy Canyon Road, San Diego, CA 92123 Phone: (858) 560-7000 FAX: (858) 560-7007 Website: www.hcisystems.net AGAVE AT THE PRESERVE 3128 Ceja Place, Carlsbad, CA 92008 Manufacturer Device Model # Description C.S.F.M. # KIDDE FX-5RD Fire Alarm Control Panel 7165-1657:0102 EST FIRESHIELD FSP-302 Fire Alarm Control Panel 7165-1657:0102 TELGUARD TG-7FS Cellular Dialer 7300-1402:0109 EST 511C Photoelectric Smoke Detector 7272-1657:0126 EST 270A-SPO Analog Single Action Pull Station 7150-1657:0111 0 > Small Building Fire Alarm Solutions UnitedTechfloIogies Technology that saves lives Conventional Fire Alarm Systems FX-1ORD, FX-10R,(FX-5Rb' FX-5R * FDNY COA 6230 Overview These systems incorporate features designed to simplify installation, operation and maintenance, including front panel programming, one person walk testing, and selectable IDC and NAC types. In addition, when used with CleanMe® -compatible smoke detectors, these con- trol panels provide intelligent type features such as remote mainte- nance alert and automatic drift compensation that significantly reduce the chance of a false alarm and simplify maintenance calls. Standard Features Available in 5 and 10 zone (lDC) models CleanMe® feature provides remote annunciation of a dirty detector Automatic drift compensation with select detectors reduces false alarms and extends dust life Listed to ANSI/UL 864 10th Edition Models with fully integrated upload/download DACT enables PC programming Zone or NAC pairs convertible to single Class A circuits Combination Waterfiow and Supervisory lDCs NACs programmable by zone and individually selectable for notification appliances, continuous, temporal outputs, or coded Front panel programmable simplifies installation and servicing Precision synchronization with compatible notification appli- ances and optional audible silence over two wires On-board relays for Alarm, Supervisory and Trouble Optional serial bus relay modules are programmable for Com- mon, Zone, or Matrix activation Optional serial bus remote annunciator family One person walk-test (audible or silent) Optional City Tie and Reverse Polarity Modules Trim ring available for semi-flush mounting • Kidde brand conventional fire alarm systems consist of 5 and 10 zone fire alarm control panels (FACP), an optional integrated upload/download DACT (dialer), intelligent/analog type detector features, serial annunciator modules, and serial remote relay mod- ules. All FACPs and components are Listed to the 10th edition of the ANSI/UL 864 standard and CSFM/FDNY approved. Kidde systems are powerful enough to meet the demands of today's life safety installations while leaving plenty of room to grow in the future, They support Class A operation by combining pairs of on-board lDCs or NACs to provide the necessary Class A circuits. For example, the FX-10RD comes factory set to support 10 Class B lDCs and 4 NACs. But it can be field-configured to provide 5 Class A lDCs (no Class B DC's), and 2 Class A NACs - or any other com- bination of circuits that fall within the circuit-pairing parameters. FX-IOR(D) FX-5R(D) Class BlDCs UptolO Upto5 Class AlDCs Upto5 Upto2 Class BNACs upto4 Upto2 Class A NACs Up to 2 1 NAC Power 7.0 amps 3.5 amps Auxiliary power 0.5 amps 0.5 amps Notes: C/ass A operation will reduce the number of available Class B IDCs and/or NACs, depending on the panel configuration. See Specifications for details. Page 1 of 8 flATA SHEET K85005-0126 'Jol lo b. to porO. Issue 2.2 Application Kidde conventional fire alarm systems provide smoke and fire de- tection, occupant notification and off-premises signaling for small- to medium-sized buildings. Each IDC can be configured for either Class B or Class A opera- tion and one of eight operating modes: Alarm —with or without smoke detector verification including discrimination of contact devices Waterflow Alarm; Waterflow Alarm/Supervisory (Combination DC); Supervisory (Latching/non-latching); Monitor (non alarm or supervisory) Signal Silence Drill Cross zoning NACs may also be configured for either Class E or Class A operation. Additionally, NACs can be individually configured for one of six outputs. These are Genesis, Genesis (AN silenceable), Continuous, Temporal, Coded, and City Tie. The Genesis selec- tion allows independent horn control over two wires and provides precision synchronization of notification appliances, all without the need for a signal master accessory. When configured for compatible notification appliances, the Alarm Silence function will silence connected audible appliances but strobes will remain active until the panel is reset. When Genesis Mode is selected, both the horns and strobes on compatible notifi- cation appliances will be synchronized across all NACs. Note: Zones may be selected for either latching or non-latching operation. Always check with your AHJ regarding approval of silencing audible while leaving strobes flashing. Detectors with intelligent features at a conventional price When combined CleanMe® -compatible smoke detectors, Kidde systems provide intel- ligent features at a conventional price. If a CleanMe® detector drifts out of the UL sensitivity Replaceable range, Kidde's patented remote optical maintenance reporting sends an chamberl alert to the control panel. This feature reduces the chance of a false alarm and simplifies service calls. In addition, CleanMe® -compatible smoke detectors have built-in drift compensation that extends the time between cleanings. If cleaning is ever necessary, it is literally a snap with the Kidde exclusive replaceable optical chamber. For a complete list of CleanMe® compatible smoke detectors, visit http://Kidde-fire.com. Panel LED Display The following system LEDs display the panel's status: Alarm - panel is in the alarm state; Trouble - panel is in the trouble state; Supervisory - panel is in the supervisory state; - Power - indicates the status of the AC power source; Disable - indicates when any IDC, NAC, relay or the DACT is disabled; Annunciator Trouble - indicates trouble on the remote an- nunciator bus; Battery Trouble - indicates battery or charging problems; Ground Fault - indicates a short between any panel circuit and ground; Walk Test - indicates that one or more lDCs are in the walk test mode; Alarms Silenced— indicates that the panel is in the alarm sta:e with one or more NACs silenced. Waterflow - indicates that one or more circuits have detected an active waterfiow switch. Service Detector - indicates the presence of a dirty oetectcr with CleanMell compatible ESL smoke detectors. Remote Disconnect - indicates off site communicaticn has been disabled. Each IDC has a disable switch and three LEDs: S Alarm - red - indicates that the 100 is in the alarm state; Trouble - yellow - indicates that the IDC is in the troule state or is disabled (when flashing); Supervisory/Monitor —yellow - indica:es that the IDC is in the supervisory state or the monitor state (when flashing), Each NAC also has a disable switch and a trouble/disable LED. Status indication with the DACT/Dialer installed The optional upload/download dialer's LCD display provides two lines x 16 characters of text. For programming, the top line displays the programming step and the lower line displays the selected option. All system events are displayed on the LCD with cls1om zone messages. During normal operation, the LCD will display any off-normal condition present in the panel. IP and Cellular Communications Several popular third-party IP/Cellular communicators have been tested with the FX conventional control panels and are conpatib I- ity listed to UL864. The IP/Cellular communicators meet NPA72 2013 edition requirements for sole or secondary transmiss on paths. Using IP/Cellular communicators can reduce the cost of ownership by eliminating POTS lines. Please see the FX con- venti onal control panel compatibility documentation part number 3131019-EN for a full list of compatible communicators. Page 2of8 DATA SHEET K85005-0126 Not to be tr.cd for installation purpoe Issue 2.2 Upload/Download DACT/Dialer The built-in DACT/Dialer is a multifunc- tion module that provides communi- cations, modem capability, and LCD display functions. Its primary function is as a Digital Alarm Communica- tor Transmitter (DACT). As a DACT, it transmits event messages to a Digital Alarm Communicator Receiver (DACR) at a monitoring facility. The monitoring facility then notifies the fire department and other responsible parties of the event. Programmable options include split or dual reporting to two DACRs. The DACT module can also be used as a modem to connect the panel to both local and remote computers for uploading and downloading of con- figuration data (programming), panel status and event history. For security, the modem can be configured to ac- cept programming on incoming calls or it can be required to call a prepro- grammed number before accepting downloads and sending uploads. The DACT module can be configured to work as all of the above, or as only an LCD display or LCD display and modem. The DACT/Dialer installs be- hind the front panel display. Note: All panel versions are available with factory installed DACT See order table for ordering informa- tion. Power Connections N 4L Cabinet Main AC D From 120 Vac, 15A, 60 Hz 8 Dedicated r% wiring block branch circuit and fuse '4 holder 1 Fuse Dual transformer ° AC wiring block",, N2 L2 00 N L o o Main Tie wrap Main controller mounts transformer board TBI o o 0 .0 Mounting studs Options Off-premise communication A fully integrated upload/download dialer is available for reporting events to a monitoring facility. The DACT also supports uploading or downloading of system configuration, status and event history. The DACT is programmable for either single or dual line opera- tion. It also supports split and dual reporting for two digital alarm receivers. The DACT brings additional features to the panel including a 32-character alphanumeric LCD display, local or remote PC pro- gramming and an event history log. Remote Annunciators and Relays The serial bus standard on Kidde conventional control panels is another installation time-saver. This circuit allows the connection of Remote System Indicators (FSRSI), Remote Zone Indicators (FSRZI- A, FSRZI-SA) and Remote Relay Modules (FSRRM24) over a four- wire (data and power) circuit. Annunciator and relay modules can be installed up to 1,000 feet from the panel on 18-gauge wire. Modules are also available for City Tie (CTM) and Reverse Polarity (RPM) connections. Remote Relay Module The Remote Relay Module (FSRRM24) is one feature of the system that sets these systems apart from other panels in their class. This module has five Form C relays rated at 1 amp each. It can be configured to function in either a zone relay mode or a common system mode. The Remote Relay Module When configured in the zone relay mounts on a plastic track inside an MFC-A cabinet, mode, relays energize when the as- sociated IDC is active. The module can be configured for activation by lDCs 1 up to two through 5 or lDCs 6 through 10. One RRM24s can be mounted in an relay is automatically associated with FSRRM-SII snap each IDC. track Up to two FSRRM-S11s can be mounted in an When configured in the common v "RRM MFC-A. S nup track system mode, relays energize or de-energize when the panel changes state. One relay is available orp,exioos deolce TO next deviox Connnonxtetunout. for each of the following functions: Alarm, Supervi- 1i'1 [T sory, Trouble, Power Loss, Monitor. IIM F.1 1 1 00 00000 II The FSRRM24 mounts on a plastic snap track and can be installed in an MFC-A enclosure. The panel will support two RRMs of each configuration for a total of six on the 10-zone panel. WIN Plug connector , • .— .° Page 3 of 8 DATA i K85005-0126 NC t to' t to, it t t,. c. r0 Issue 2.2 Remote Annunciators — This family of systems has several remote annunciation op-ions. The serial — remote annunciator bus can be run up to 1000 feet (305 m) on untwisted : non-shielded 18-gauge cable. Several annunciator models round out the —: family to provide a range of features and functions. As many as three an- nunciator modules may be mounted in a standard electrical box, sharing — — an attractive trim plate that blends with any decor. The FSRSI can be installed alone or with one or more FSRZI-As. The FSRSI and FSRZI-A require trim plates (ordered separately). These are available in one, two or three gang models. Each panel will support two FSRSls. Compatible electrical boo nT TO 0.01 deol0. FSRAIO, FSRA10C Remote LED annunciators The FSRA10 is a remote annunciator with capacity for up to ten zones. It includes ten bi-color LEDs (red/yellow) for indicat- ing active zones, and ten yellow LEDs for indicating zone troubles. The (C) option adds common control switches. Both ver- sions mount to standard North American 4-inch square electrical boxes. A surface zone panel. box is also available. Works only with 10 or 24V0C power control panel From Note. supply PC--- —. Remote System Indicator - Remote Zone Indicator —F Remote Zone Indicator (FSRSI) The FSRSI is ideal for common system annuncia- tion. It includes five LEDs and a local silence/lamp test switch. The LEDs indi- cate power status, alarm, supervisory, trouble and ground fault. The silence >-1 switch will silence the conatdonin+ - i .?T onboard trouble sounder if active. The switch can 24V I also be used to initiate a 4 IN lamp test of the LEDs on all connected FSRSls and FSUIM Graphic Driver/Interface The FSUIM is a universal interlace module that can be used by to drive graphic ainunciators. It also allows control panels to control, or be controlled by, other control panels. The FSUIM provides five supervised switch inputs and nine dry contact relay outputs. Nine LEDs provide visual confirmation wnen each relay is energized. The FSUIM is shipped with a plastic snap track for mounting in an MFC-A enclosure. FSRZI-As. (FSRZI-A) The FSRZI-A is used to indicate F zones in the al.rm state. It contains five red LEDs. Depending on the J setting selected, the LEDs will indicate either >_.... IDCs 1 through 5 or IDCs 6 through 10. The panel can P0onn support two modules po- grammed for each selection. 0,pm000l00010a 24 IN V C IN COIVT - COTflflO1000. oioaonn0000 To 1001 dm10. (FSRZI-SA) The FSRZI-SA indicates zones in the Pdarm or Su- pervisory state. It contains five red and yellow LEDs for Common, Zone, or Matrix activation. Depending on the >_.. jumper setting, the LEDs will co,,nts000me, indicate either IDCs 1- 5 or 6 10. The panel supports two modules for each selection, 01000tJ.dto and can be jumper selected to provide Alarm or Supervi- 001 OUT sory indications. Ponenod - Conrlurdc000nnd. Comnunl1000n bolt To loot 000n,. F SRAIO, FSRA1OC Wiring From control panel r 2N ( 24V or 24V0C supply [ 24V ( ) 24V To next N U N.U. remote module From I c ( C controlpanel N.u.I [ ON: Group l - - - OFF: Group 2 000000000 7117) 0 (L signs P01.1 LImp Cat-Intl Spilnb. TtLNnbu010 'ml From control panel ro O. otow or24VDCpower[ Supply To neat From [c. _____________________________________________ remote module control panel Lc Co H H r Page 4of8 DATt. SHEET K850050126 Not 10 be (L1Otd PUP I0itUeull,.tuOfl )o000nJs Issue 2.2 S Remote Annunciator Specifications General Agency Listings UL864 (S3000), ULC, CSFM, FDNY Remote Annunciators FSRSI Remote System Indicator FSRZI-A/FSRZI-SA Remote Zone Indicator Maximum per System All panels: 2 10 zone panel: 4 5 zone panel: 2 Current Requirements Standby: 17 mA Alarm: 56 mA Standby: 8 mA Alarm 76 mA Voltage Range Minimum: 18.8 Vdc; Maximum: 27.3 Vdc Maximum Circuit Capacitance 0.03 pF Maximum Circuit Resistance 13 Ohms Wire Size 18 - 12 AWG (0.75 mm2 - 2.5 mm2) Mounting ANSI/N EMA OS1 -1996 1-3 gang electrical box Operating Environment Temperature: 32 - 120° F (0- 49° C); Humidity: 93% RH, non-condensing Remote Relay Module - FSRRM24 Configured for Zone Mode Configured fo' Common Mode Maximum per system 10 zone panel: 4; 5 zone panel: 2 All panels: 2 Current Requirements Standby: 10 mA; Alarm: 70 mA Standby: 26 mA; Alarm: 70 mA Voltage Range Minimum: 18.8 Vdc; Maximum: 27.3 Vdc Contact Rating 1 A@ 30 Vdc Maximum Circuit Capacitance 0.03 pF Maximum Circuit Resistance 13 Ohms Wire Size 18 - 12 AWG (0.75 mm2 -2.5 mm2) Mounting Single FSRRM24 mounts in plastic track (included) or up to two FSRRM24:s in an FSRRM-S1 111" track ordered should installed enclosure. _separately. _FSRRM24s_ _be_ _in_an_MFC-A Operating Environment Temperature: 32- 120° F (0- 49° C); Humidity: 93% RH, nor-condensing Dimensions 2-3/4" W x 3-3/8" H x 1-1/2" D (65.9 mm W x 85.7 mm H x 38.1 mm D) F-Series Remote Annunciators FSRA10 FSRA10C Common Controls No I Yes - Compatibility 10-Zone Panels Only. Dimensions 5-5/8"x81/2"x1 ½" in(14.3cmx21.4cmx3.8cn) Mounting North American 4-inch square electrical box Power Wiring 18 to 12 AWG (0.75 to 2.50 sq mm) Data Wiring 18 to 12 AWG (0.75 to 2.50 sq mm) twisted pair (6 twists per foot minimum) Operating voltage 18.8 to 27.3 Vdc Supply must be UL/ULC listed for fire protective signaling systems. Do not use FACP accessory power outputs that are interrupted when the panel is reset. Standby current 17 mA Alarm current 98 mA - Operating environment Temperature: 32 to 120 °F (0 to 49 °C); Humidity: 0 to 93% RH, noncondensing at 90 OF (32 °C) FSUIM Universal Input Module Mounting MFC-A enclosure Wire size 12 to 18 AWG (0.75 to 2.5 sq mm) Operating voltage 21.2 to 27.3 Vdc Circuit capacitance 0.03 pF, max. Circuit resistance 13 ohms, max. Switch inputs Quantity: 5 End-of-line resistor: 4.7 k ohms ½ W Relay outputs Quantity: 9 Type: Common Style: Form C Contact rating 30 Vdc at 1 A (resistive load) Standby Current 53 mA Alarm Current 114 mA Operating environment Temperature: 0 to 49 °C (32 to 120 °F); Humidity: 0 to 93% RH, noncondensing at 32 °C (90 °F) Page 5of8 OA,A Si-i F FT K850050126 Not i' b - ,.d -t . . .... ' - - - Issue 2.2 Q .° 0 0 0 01 Surface mounting holes - 0 E co E a) 0 0 Dl D4 S Control Panel Specifications Control Panels FX-10R(D) FX-5R(D) Initiating Device Circuits - lDCs (Available combinations shown at right) Class B 10 8 6 4 2 0 5 3 1 Class A 0 1 2 3 4 5 0 1 2 Notification Appliance Circuits - NACs (Available combinations shown at right) Class B 4 2 2 0 2 0 Class A 0 1 1 2 0 1 Power Supply 7.5 amps total 4.25 amps total NAC Voltage Rating 24 Vfwr Maximum NAC current 2.0 amps each, 7.0 amps total 2.0 amps each 3.5 amps total AC Input 120 Vac 60 Hz.. 230 Vac 50/60Hz... 2.2 amps 1.1 amps 1.25 amps 0.6 amps Base Panel Current Draw Standby... Alarm... 128 mA 242 mA 4 mA.) V4-mA Panci Battery Charge Capacity (sealed lead acid only) Up to two 24 Ah batteries, 18 Ah in cabinet Up to 24 Ah, 10 Ah max in cabinet * Auxiliary Current 0.5 amps max. May be programmed as resettable. Auxiliary Output 24 Vdc regulated IDC Alarm Current 3.0 mA (Consult detector compatibility list p/n 3101019-EN for maximum detectors per circuit) IDC Circuit Maximum loop resistance: 26 Ohms; Maximum loop capacitance: 0.03 pF IDC Operating Voltage 16.9 to 29 Vdc UL Detector lD 100 Alarm Contact (normally open Form C) 30 Vdc @ 1 A (resistive load) Trouble Contact (Form C) 30 Vdc @ 1 A (resistive load) Supervisory Contact (normally open Form C) 30 Vdc © 1 A (resistive load) Operating Environment Temperature: 32 - 120° F (0 -49° C); Humidity: 5 - 93% RH, non-condensing Terminals (wire gauge) 18 - 12 AWG (0.75 mm2 -2.5 mm2) Asynchronous Serial Communications Maximum resistance: 13 Ohms; Maximum capacitance: 0.03 pF Agency Listings UL864 (S3000), ULC-S527, CSFM, FDNY ir iarger oarzanes are required, use an external battery aJinet. DACT - F-DAT (mounts in panel) Receivers Supports two receivers with two phone numbers each Communications Protocol Contact ID (SIA DC-05), 4/2 (S A DC-02 P3) Programming Front panel controls or PC with appropriate software Telephone line connection Two RJ31X (plug-to-pUg) cords suzplied with DACT Telephone lines Two or one loop start lines on the public switched telephone network. Pulse or DTMF. Telephone wall connector RJ31 XICA31 X equiv. or RJ38XJCA38X equiv. Communications Compliance Industry Canada CS-03; FCC/CFR 47 Parts 15 & 68; NFPA 72; UL 864; ULC S527 Operating Environment Temperature: 32-120° F (0-49° C); Humidity: 93% RH, non-condensing Current requirements Standby: 65 mA; Alarm: 107 mA Agency Listings UL864 (S3000). CSFM, FDNY Dimensions Model D1* D2 03 D4 D5* Five- 19.5 in 3.75 in 9.13 in 10.5 in 1L.23 in zone (49.5 cm) (9.5 cm) (23.2 cm) (26.67 cm) (36 14 cm) Ten- 30 in 3.75 in 7.75 in 21.27 in 13.0 in zone (76.2 cm) (9.5 cm) (19.7 cm) (34.D cm) 38.1 cm) *Add I V2 inches (3.81 cm) to Dl and D5 dimensions fc' him 4t Page 6of8 DATA SHEET K850050126 Not to be used fo; tobtahatior. ourpo~ ~ s Issue 2.2 Ordering Information Part Description Ship Wt. lb. Number (kg.) Control Panels FX-10R Conventional Fire Alarm Control Panel, Red - 10 Class B lDCs and 4 Class B NACs, 7.OA NAC power, (Pairs of lDCs and NACs convertible to single Class A circuits), 120VAC power source, 24VDC output Conventional Fire Alarm Control Panel, Red - 10 Class B lDCs and 4 Class B NACs, 7.OA NAC power, (Pairs of FX-10RD lDCs and NACs convertible to single Class A circuits), upload/download DACT/modem, 120VAC power source, 30.5 (13.8) 24VDC output FX-1ORF Conventional Fire Alarm Control Panel, Red - 10 Class B lDCs and 4 Class B NACs, 7.OA NAC power, (Pairs of lDCs and NACs convertible to single Class A circuits), 120VAC power source, 24VDC output, French Canada FX-5R Conventional Fire Alarm Control Panel, Red -5 Class B lDCs and 2 Class B NACs, 3.5A NAC power, (Pairs of lDCs and NACs convertible to single Class A circuits), 120VAC power source, 24VDC output - Conventional Fire Alarm Control Panel, Red - 5 Class B lDCs and 2 Class B NACs, 3.5A NAC power, (Pairs of lDCs IJ fX-5RD. and NACs convertible to single Class A circuits), upload/download DACT/modem, 120VAC power source, 24VDC 24.4 (11.1) output FX-5RF Conventional Fire Alarm Control Panel, Red, 5 Class B lDCs and 2 Class B NACs, 3.5A NAC Power, 120V, 24Vdc Output, French Canada F-1R1M35R Semi-flush trim ring for FX-5R(D) 1.7 (0.8) F-TRIM1 OR Semi-flush trim ring for FX-1OR(D) 2.2(l.0) Related Items F-XTR120 Expander Transformer, 120 Vac - For FX-1O only 4.0(1.8) EOL3 6-1 1 Required UL listed End of Line Resistors - One 3.6K Ohm and one 1.1K Ohm. 0.1 (0.5) One required for each IDC configured as combination waterflow, and supervisory. EOL-P1 Required ULC listed End of Line Resistor Plate - includes one 1.1K, 3.6K and 4.71K Ohm resistor 1.0 (0.5) Off Premises Communications F-DACT Upload/dowload digital Communicator/modem/LCD module (Mounts in control panel) 1.0 (0.5) F-DACT1 Digital Communicator/Modem/LCD module (Compatible with new v4.0 control panels) F-DACT1 F Digital Communicator/Modem/LCD module (Compatible with new v4.0 control panels), French American electrical Reverse Polarity Module (Requires MFC-A or other listed fire alarm UIMI 3.0 Remote Annunciation Remote System Indicator - Includes LEDs for display of Power, Alarm, Supervisory, Trouble and Ground Fault, FSRSI trouble sounder and silence/lamp test switch. Single gang trim plate included, multi-gang plates ordered 0.3 (0.1) separately. Mounts in a single or multi-gang North American electrical box. FSRZI- A Remote Zone Indicator - Includes red LEDs for five lDCs. Single gang trim plate included, multi-gang plates 0.3(0.1) ordered separately. Mounts in single or multi-gang North American electrical box. Remote Zone Indicator - Includes LEDs for five lDCs. Single gang trim plate included, multi-gang plates ordered FSRZI-SA separately. Mounts in single or multi-gang North American electrical box. Jumper selected Alarm (red) or 0.3 (0.1) Supervisory (amber) indications. FSAT1 Annunciator Trim Plate, 1 gang 0.1 (0.05) FSAT2 Annunciator Trim Plate, 2 gang 0.1 (0.05) FSAT3 Annunciator Trim Plate, 3 gang 0.1 (0.05) FSAT4 Annunciator Trim Plate, 4 gang 0.1 (0.05) K-FSRA10 Single Unit 10 zone remote annunciator for FX-10 K-FSRA1OF Single Unit 10 zone remote annunciator for FX-1O, French K-FSR.A10C Single Unit 10 zone remote annunciator for FX-10 (with common controls) K-FSRA1OCF Single Unit 10 zone remote annunciator for FX-10 (with common controls), French FSUIM Common Function Graphic Driver/Interface - 9 relays and 5 switch inputs for common system indicators & controls Remote Relay Module FSRRM24 Remote Relay Module - Five Form C relays. Configurable for IDCs 1-5, or 6-10, or common system indications or 0.4 (0.2) matrix mode. Requires MFC-A or other listed fire alarm enclosure. FSRRM-S1 1 11" Mounting track. Holds up to two FSRRM24s. 0.4 (0.2) Accessories MFC-A Multi-function Cabinet (fire alarm accessory enclosure) 7.0 (3.2) . Programming Tools FA-CU Fire alarm configuration utility. This CU is available for download only. Visit www.kiddefx.kidde.com. Page 7 of 8 DATA SHE FT K85005-0126 'Zot tu ' . c ,' t I _ .' Issue 2.2 PPI viNOir Technology that saves lives Contact us... Email: kidde.flre@fs.utc.com Web: kidde.com/engineeredsystems 1016 Corporate Park Drive Mebane, NC 27302 Kidde is a registered mark in the United States and other countries. © 2018 Walter Kidde Portable Equipment. All rights reserved. Page 8 of 8 DT#. SHEET K85005-0126 Not tic, b used for n. jtc purp. Issue 2.2 Standard Features Available in 3, 5, and 10 IDC models IDC or NAC pairs convertible to single Class A circuits (10 and 5 IDC panels only) CleanMe® provides remote annunciation if a detector drifts out of UL/ULC limits reducing the chance of a false alarm Combination Waterflow and Supervisory lDCs reduces wire and zone counts NACs programmable by zone and individually selectable for Genesis, continuous, temporal outputs, r coded Front panel programmable simplifies installation and servicing Optional fully integrated DACT/Dialer for PC programming Genesis option allows precision synchronization and audible silence over two wires without additional modules On-board relays for Alarm, Supervisory and Trouble Optional serial bus relay modules are programmable for com- mon or zone activation Optional serial bus remote annunciator family One person walk-test (audible or silent) Expandable power supply on 10 100 panel reduces booster power costs Trim ring available for semi-flush mountirg Supports 2M, "EC", 6200, 400, 500 and 700 series detectors e 0 7165-1657: 0102 FDNY COA 6019 S3000 ¶ST Life Safety & Communications ES I Catalo 1' Small Building Intelligent & Conventional Fire Alarm Solutions FireShield Plus Conventional Fire Alarm Control Panels Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm control panels, an integrated DACT/Dialer, serial annunciator modules, and serial remote relay modules. All of these components are microprocessor-controlled. The FireShield Plus family is ideal for both new and retrofit installations alike. FireShield Plus incorporates features designed to simplify installa- tion, operation and maintenance. These include front panel pro- gramming, one person walk testing, and selectable IDC and NAG types. In addition, when used with Edwards CleanMe® -compatible smoke detectors, FireShield Plus provides analog type features such as remote maintenance alert and automatic drift compensa- tion that reduce false alarms and simplify maintenance calls. FSP502 and FSP1 004 panels support Class A operation by combining pairs of on-board initiating curcuits (IDCs) or notifica- tion circuits (NACs) to provide the necessary Class A circuits. For example, the FSP1 004 comes factory set to support 10 Class B IDCs and four NACs. But it can be field-configured to provide five Class A IDCs, no Class B IDCs, and two Class A NACs - or any other combination of circuits that fall within the circuit-pairing parameters. Class B IDCs FSP1 004 Up to 10 FSP502 Up to 5 FSP302 3 Class A IDCs Up to 5 Up to 2 Not supported Class B NACs Up to 4 Up to 2 2 Class A NACs Up to 2 1 Not supported NAC Power 3.5 amps* 3.5 amps 3.5 amps Auxiliary power 0.5 amps 0.5 amps 0.5amps Note: Class A operation will reduce the number of available Class B IDCs and/or NACs, depending on the panel configuration. See Specifications on page 5 for details. *Expandable to 7.0 amps Page lof8 DATA SHEET 850050126 Not to be used for instalation purposes. Issue 2 Application FireShield Plus provides smoke and fire detection, occupant notification and off-premises signaling for small- to medium-sized buildings. Each IDC can be configured for either Class B or Class A opera- tion and one of eight operating modes: Alarm —with or without smoke detector verification including discrimination of contact devices Waterilow Alarm; Waterilow Alarm/Supervisory (Combination IDC); Supervisory (Latching/non-latching); Monitor (non alarm or supervisory) Signal Silence Drill Cross zoning NACs may also be configured for either Class B or Class A operation. Additionally, NACs can be individually configured for one of six outputs. These are Genesis, Genesis (MI silenceable), Continuous, Temporal, Coded, and City Tie, The Genesis selec- tion allows independent horn control over two wires and provides precision synchronization for Genesis devices, all without the need for a Genesis Signal Master accessory. When configured for Genesis notification appliances, FireShield Plus's Alarm Silence function will silence connected Genesis audible appliances but Genesis strobes will remain active until the panel is reset. When Genesis Mode is selected, both the horns and strobes on Genesis and Enhanced Integrity notification appliances will be synchronized across all NACs. Note: zones may be selected for either latching or non-latching operation. Detectors with intelligent features at a conventional price When combined with Edwards CleanMe® -compatible smoke detectors, FireShield Plus provides intelligent features at a conventional price. If a CleanMe® detector drifts out of Rep/ac the UL/ULC sensitivity range, chamt EST's patented remote mainte- nance reporting sends an alert to the FireShield Plus control panel. This feature reduces the chance of a false alarm and simplifies service calls. In addition, CleanMe® -compatible smoke detectors have built-in drift compensation that extends the time between cleanings. If cleaning is ever necessary, it is literally a snap with EST's exclusive replaceable optical chamber. Panel LED Display The following system LEDs display the panel's status: Alarm - panel is in the alarm state; Trouble - panel is in the trouble state; Supervisory - panel is in the supervisory state; Power - indicates the status of the AC power source; Disable - indicates when any IDC, NAC, relay or the DACT is disabled; Annunciator Trouble - indicates trouble on the remote an- nunciator bus; Battery Trouble - indicates battery or charging problems; Ground Fault - indicates a short between any panel circuit and ground; Walk Test - indicates that one or more lDCs are in the walk test mode; Alarms Silenced - indicates that the panel is in the alarm state with one or more NACs silenced. Waterfiow - indicates that one or more circuits have detected an active waterfiow switch. Service Detector - indicates the presence of a dirty detector. Remote Disconnect - indicates off site communication has been disabled. Each IDC has a disable switch and three LEDs: Alarm - red - indicates that the IDC is in the alarm state; Trouble - yellow - indicates that the IDC is in the trouble state or is disabled (when flashing); Supervisory/Monitor - yellow - indicates that the IDC is in the supervisory state or the monitor state (when flashing). Each NAC also has a disable switch and a trouble/disable LED. Status indication with the DACT/Dialer installed The dialer's LCD display provides two lines x 16 characters of text. For programming, the top line displays the programming step and the lower line displays the selected option. All system events are displayed on the LCD with custom zone messages. During normal operation, the LCD will display any off-normal con- dition present in the panel. S Page 2018 DATA SHEET 85005-0126 Not to be used for installation purposes Issue 2 DACT/Dialer The optional DACT/Dialer is a multi- function module that provides commu- nications, modem capability, and LCD display functions. Its primary function is as a Digital Alarm Communica- tor Transmitter (DACT). As a DACT, it transmits event messages to a Digital Alarm Communicator Receiver (DACR) at a monitoring facility. The monitoring facility then notifies the fire department and other responsible parties of the event. Programmable options include single or dual line operation, and split or dual reporting to two DACRs. The DACT module can also be used as a modem to connect the panel to both local and remote computers for uploading and downloading of con- figuration data (programming), panel status and event history. For security, the modem can be configured to ac- cept programming on incoming calls or it can be required to call a prepro- grammed number before accepting downloads and sending uploads. The DACT module can be configured to work as all of the above, or as only an LCD display or LCD display and modem. The DACT/Dialer installs be- hind the front panel display. Note: All panel versions are available with factory installed DACT See order table for ordering informa- tion. Options Off-premise communication A fully integrated FireShield Plus DACT/dialer is available for reporting events to a monitoring facility. The DACT also supports uploading or downloading of system configuration, status and event history. The DACT is programmable for either single or dual line operation. It also supports split and dual reporting for two digital alarm receivers. The DACT brings additional features to the panel including a 32-character alphanumeric LCD display, local or remote PC pro- gramming and an event history log. Remote Annunciators and Relays The serial bus standard on all FireShield Plus models is another instal- lation time-saver. This circuit allows the connection of Remote System Indicators (FSRSI), Remote Zone Indicators SRZl-A, FSRZI-SA) and Remote Relay Modules (FSRRM24) over a four-wire (data and power) circuit. Annunciator and relay modules can be installed up to 1,000 feet from the panel on 18-gauge wire. Modules are also available for City Tie (CTM) and Reverse Polarity (RPM) connections. Power Connections Cabinet . Main AC wiring block 3 From 120 Vac, 15 A. 60 Hz Dedicated branch circuit and fuse \ —OR— holder From 230 Vac, 15 A, 50160 Hz 1. Fuse II Dedicated branch circuit Dual transformer o AC wiring block\ N2 L2 as N L Main Tie wrap/ Main controller mounts transformer 7.7=7n. board TSI o ,o ®' o' Mounting XTR studs (optional transformer) J4 a @ o' Plug connector Remote Relay Module The Remote Relay Module (FSRRM24) is one component of the system that sets FireShield Plus apart from other panels in its class. This module has five Form C relays rated at 1 amp each. It can be configured to function in either a zone relay mode or a common sys- The Remote Relay Module tem mode. mounts on a plastic track inside an MFC-A cabinet. When configured in the zone relay mode, relays energize when the as- sociated IDC is active. The module can UPto4RRM24S be configured for activation by lDCs 1. can be mounted in an FSRRM-SII through 5 or IDCs 6 through 10. One aP track. uP to relay is automatically associated with can be mounted L each IDC. inanMFC-A. R. Snap track When configured in the common system mode, relays energize or de- From corroal panel when the panel or previous device To nest device communication out, changes state. One relay Comn,unlceton cu'o is available for each of the following functions: Alarm, Supervisory, Trouble, Power Loss, Monitor. 00 24vC °?8?8 C NC1 The FSRRM24 mounts on a *F1 r'i 1-1 il plastic snap track and can be installed in an MFC-A or uTs?OuT 00000 4uT2NC other listed fire alarm enclo- _ ______________ sure. The panel will support Tsflreldooste two RRMs of each configu- ration for a total of six on the 10-zone panel. Page 3 of 8 DATA SHEET 85005-0126 Not to be used for installation purposes Issue 2 Remote Annunciators Compatible electrical box — — The FireShield Plus family has several remote annunciation options. The r serial remote annunciator bus can be run up to 1000 feet (305 m) on un- twisted non-shielded 18-gauge cable. Serial annunciator models round out F-9 the family to provide a range of features and functions. As many as three annunciator modules may be mounted in a standard electrical box, sharing — — an attractive trim plate that blends with any decor. The FSRSI can be installed alone or with one or more FSRZls. The FSRSI and FSRZI-A require trim plates (ordered separately). These are available in one, two or three gang models. Each panel will sup- port two FSRSIs. Remote System Indicator I — I Remote Zone Indicator I Remote Zone Indicator (FSRSI) I I (II)) I I (FSRZI-SA) mon system annunciation. — indicate zones in the alarm —: to indicate zones in the [ j a local silence/lamp test LEDs. Depending on the It contains five bi-color It includes five LEDs and state. It contains five red alarm or supervisory state. The FSRSI is ideal for corn- The FSRZI-A is used to r The FSRZI-SA is used switch. The LEDs indicate jumper setting selected, i LEDs. Depending on the -- power status, alarm, super- . the LEDs will indicate either ' - _. jumper setting selected, visory, trouble and ground >..... lDCs 1 through 5 or lDCs 6 the LEDs will indicate either a pmVandfllc, fault. The silence switch will 1corcxm'* through 10. The panel can j >1 lDCs 1 through 5 or lDCs I comroaao,x, )fl silence the onboard trouble ' >—i I support two modules pro- >._I] 6 through 10. The panel buzzer if active. The switch grammed for each selection. I.Po,. >—, I I I supports two modules ,.LL.LL F— mnNI can also be used to initiate ' programmed for each Se- 24V IN C IN a lamp test of the LEDs on 24V IN C IN 24—rr1 lection, and can be jumper all connected FSRSls and 4H L selected to provide Alarm * FSRZls. or Supervisory indications *® P—,-. ~J o PP_Z__' L _ I L.0 __ To neAt deolce TO flOAt decO, FSRA10, FSRAIOC FSUIM Graphic Driver/Interface Remote LED annunciators The FSUIM is a universal interlace module that can be used by The FSRA10 is a remote annunciator with FireShield to drive graphic annunciators. It also allows FireShield capacity for up to ten zones. It includes ten RE control panels to control, or be controlled by, other control panels. bi-color LEDs (red/yellow) for indicating The FSUIM provides five supervised switch inputs and nine dry active zones, and ten yellow LEDs for mdi- cating zone troubles. The (C) option adds contact relay outputs. Nine LEDs provide visual confirmation when each relay is energized. The FSUIM is shipped with a plastic snap common control switches. Both versions ! mount to standard North American 4-inch track for mounting in an MFC-A cabinet or other listed fire alarm square electrical boxes. A surface box is J... enclosure. also available. From orzoVOcpowor[ control panel 1+ supply I FSRA10, FSRA10C Wiring T€ir From o o a o o o o a o control panel [ 24V ' hirl 24V (lIT or 24VDC supply I24V L..,J L To next L ..j Occet Ao,np C From control panel N: Group 1 Fro C g FU module control r24VDC r[+ N ] emte°module control pan., [CC C -I H H 47kEOLR Page 4018 DATA SHEET 85005-0126 Not to be used for irtstaltat.on purposes. Issue 2 S Remote Annunciator Specifications General Agency Listings I UL864 (53000), ULC-S527, CSFM Remote Annunciators FSRSI Remote System Indicator FSRZI-NFSRZI-SA Remote Zone Indicator Maximum per System All panels: 2 10 zone panel: 4 3 or 5 zone panel: 2 Current Requirements Standby: 17 mA Alarm: 56 mA Standby: 8 mA Alarm 76 mA Voltage Range Minimum: 18.8 Vdc; Maximum: 27.3 Vdc Maximum Circuit Capacitance 0.03 pF Maximum Circuit Resistance 13 Ohms Wire Size 18- 12 AWG (0.75 mm2 - 2.5 mm2) Mounting ANSI/N EMA OS 1-1996 1-3 gang electrical box Operating Environment Temperature: 32 - 120° F (0- 49° C); Humidity: 93% RH, non-condensing Remote Relay Module - FSRRM24 Configured for Zone Mode Configured for Common Mode Maximum per system 10 zone panel: 4; 3 or 5 zone panel: 2 All panels: 2 Current Requirements Standby: 10 mA; Alarm: 70 mA Standby: 26 mA; Alarm: 70 mA Voltage Range Minimum: 18.8 Vdc; Maximum: 27.3 Vdc Contact Rating 1 A@ 30 Vdc Maximum Circuit Capacitance 0.03 pF Maximum Circuit Resistance 13 Ohms Wire Size 18 - 12 AWG (0.75 mm2 - 2.5 mm2) Mounting Single FSRRM24 mounts in plastic track (included) or up to four FSRRM24s in an FSRRM-S1 1 11" track ordered separately. FSRRM24s should be installed in an MFC-A or other listed fire alarm enclosure. Operating Environment Temperature: 32 - 120° F (0 - 49° C); Humidity: 93% RH, non-condensing Dimensions 2-3/4" W x 3-3/8" H x 1-1/2" D (65.9 mm W x 85.7 mm H x 38.1 mm D) F-Series Remote Annunciators FSRA10 FSRA10C Common Controls No . Yes Dimensions 5-5/8' x 81/2" x 1 ½' in (14.3 cm 21.4 cm x 3.8 cm) Mounting North American 4-inch square electrical box or listed enclosure Power Wiring 18 to 12 AWG (0.75 to 2.50 sq mm) Data Wiring 18 to 12 AWG (0.75 to 2.50 sq mm) twisted pair (6 twists per foot minimum) Operating voltage 18.8 to 27.3 Vdc Supply must be ULIULC listed for fire protective signaling systems. Do not use FACP accessory power outputs that are interrupted when the panel is reset. Standby current 17 mA Alarm current 98 mA Operating environment Temperature: 32 to 120 °F (0 to 49 °C); Humidity: 0 to 93% RH, noncondensing at 90 IF (32 °C) FSUIM Universal Input Module Mounting MFC-A cabinet or listed fire alarm enclosure Wire size 12 to 18 AWG (0.75 to 2.5 sq mm) Operating voltage 21.2 to 27.3 Vdc Circuit capacitance 0.03 pF, max. Circuit resistance 13 ohms, max. Switch inputs Quantity: 5 End-of-line resistor: 4.7 k ohms 1/2: W Relay outputs Quantity: 9 Type: Common Style: Form C Contact rating 30 Vdc at 1 A (resistive load) Standby Curent 53 mA Alarm Current 114 mA Operating environment Temperature: 0 to 49 °C (32 to 120 °F); Humidity: 0 to 93% RH, noncondensing at 32 °C (90 °F) S Page 5 of 8 DATA SHEET 85005-0126 Not to be used for installation purposes Issue 2 0 Dimensions Model DI* D2 D3 D4 D5* Three- & 19.5 in 3.75 in 9.13 in 10.5 in 14.23 in five- zone (49.5 cm) (9.5 cm) (23.2 cm) (26.67 (36.14 cm) cm) Ten-zone 30 in 3.75 in 7.75 in 21.27 in 15.0 in (76.2 cm) (9.5 cm) (19.7 cm) (54.0 cm) (38.1 cm) *Add 1½ inches (3.81 cm) to Dl and 05 dimensions fo. :nm kit D4 Control Panel Specifications Control Panels FSPI 004 FSP502 FSP30 Initiating Device Circuits - lDCs (Available combinations shown at right) Class B 10 8 6 4 1 2 1 0 5 3 1 Three Class B tDCs Class A 0 1 2 3 4 5 0 1 2 Notification Appliance Circuits - NACs (Available combinations shown at right) Class B 4 2 2 0 2 0 Two Class B NACs Class A 0 1 1 2 0 1 Power Supply 4.25 amps expandable to 7.5 amps 4.25 amps total 4.25 amps total NAC Voltage Rating 24 Vfwr Maximum NAC current 2.0 amps each, 3.5 amps total 7.0 amps w/ optional transformer 2.0 amps each 3.5 amps tctal 2.0 amps each 3.5 amps total AC Input 120 Vac 63 Hz. . 230 Vac 50/60Hz... 2.2 amps w/ optional transformer 1.1 amps w/ optional transformer 1.25 amps 0.6 amps 1.2 amps 0.6 amps Base Panel Current Draw Standby... Alarm... 128 mA 242 mA 104 mA 224 mA mA) (80jmAl Panel Battery Charge Capacity (seed lead acid on,) Up to two 24 Ah batteries, 18 Ah in cabinet Up to 24 Ah, 10 Ah max in cabinet * Auxiliary Current 0.5 amps max. May be programmed as resettable. Auxiliary Output 24 Vdc regulated IDC Alarm Current 3.0 mA (Consult detector compatibility list p/n 3100468 for maximum detectors per circuit) IDC Circuit Maximum loop resistance: 13 Ohms; Maximum loop capacitance: 0.03 i.iF DC Operating Voltage 16.9 to 29 Vdc UL Detector ID 100 Alarm Contact (normally open Form C) 30 Vdc @ 1 A (resistive load) Trouble Contact (Form C) 30 Vdc @ 1 A (resistive load) Supervisory Contact (normally open Form C) 30 Vdc @ 1 A (resistive load) Operating Environment Temperature: 32 - 120° F (0- 49° CI; Humidity: 5 - 93% RH, non-condensing Terminals (wire gauge) 18 - 12 AWG (0.75 mm2 -2.5 mm2) Asynchronous Serial Communications Maximum resistance: 13 Ohms; Maximum capacitance: 0.03 pF Agency Listings UL864 (53000), ULC-S527, CSFM - If larger batteries are required, use an external battery cabinet. DACT - F-DACT (mounts in panel) - Receivers Supports two receivers with two phone numbers each Communications Protocol Contact ID (SIA DC-05), 4/2 (SIA DC-02 P3) Programming Front panel controls or PC with appropriate software Telephone line connection Two RJ31X (plug-to-plug) cords supplied with DACT Telephone lines Two or one loop start lines on the public switched telepione network. Pulse or DTMF. Telephone wall connector RJ31 X/CA31 X equiv. or RJ38X/CA38X equiv. Communications Compliance Industry Canada CS-03; FCC/CFR 47 Parts 15 & 68; NFPA 72; UL 864; ULC S527 Operating Environment Temperature: 32-120° F (0-49° C:; Humidity: 93% RH, non-condensing Current requirements Standby: 65 mA; Alarm: 107 mA Agency Listings UL864 (53000) ULC-5527, CSFM Page 6of8 DATA SHEET 85005-0126 Not to be used for installation purposes. Issue 2 Ordering Information Part Number Description Ship Wt. lb. Control Panels Conventional Fire Alarm Control Panel - 10 Class B lDCs and 4 Class B NACs FSP1 004* 30.5(13.8) (Pairs of lDCs and NACs convertible to single Class A circuits), 120 Vac Conventional Fire Alarm Control Panel - 10 Class B lDCs and 4 Class B NACs FSP1 004-2 30.5(13.8) (Pairs of lDCs and NACs convertible to single Class A circuits), 230 Vac. Grey cabinet. Conventional Fire Alarm Control Panel -5 Class B lDCs and 2 Class B NACs FSPSO2* 18.5 (8.4) (Pairs of lDCs and NACs convertible to single Class A circuits), 120 Vac Conventional Fire Pdarm Control Panel -5 Class B lDCs and 2 Class B NACs FSP5O2-2 18.5(8.4) (Pairs of lDCs and NACs convertible to single Class A circuits), 230 Vac. Grey cabinet. FSP302* Conventional Fire Alarm Control Panel -3 Class B lDCs and 2 Class B NACs, 120 Vac 15.0 (5.2) FSP302*2 Conventional Fire Alarm Control Panel -3 Class B lDCs and 2 Class B NACs, 230 Vac 18.0 (8.2) FTRlM35* Semi-flush trim ring for FSP302 and FSP502 1.7 (0.8) F-TRlM1 0* Semi-flush trim ring for FSP1 004 2.2 (1.0) * Insert "G" for Gray cabinet or "R" for Red cabinet. Insert "F" for French language (grey cabinets, not available on 220v versions) Insert "GD" or "RD' for red and gray cabinets with dialer installed. Related Items F-XTR120 Expander Transformer, 120 Vac - For FSP1 004* only 4.0 (1.8) F-X1R230 Expander Transformer, 230 Vac - For FSP1 004*2 only 4.0 (1.8) EOL3 6-1 1 Required UL listed End of Line Resistors - One 3.6K Ohm and one 1.1K Ohm. 0.1 (0.5) One required for each IDC configured as combination waterilow and supervisory. EOL-P1 Required ULC listed End of Line Resistor Plate - includes one 1.1K, 3.6K and 4.7K Ohm resistor 1.0 (0.5) Off Premises Communications F-DACT Digital Communicator/Modem/LCD module (Mounts in control panel) 1.0 (0.5) RPM Reverse Polarity Module 3.0 (1.36) CTM City Tie Module (Requires 4" square or 2-gang North American electrical box) 1.0 (0.5) Remote Annunciation FSRSI . Remote System Indicator - Includes LEDs for display of Power, Alarm, Supervisory, Trouble and Ground Fault, trouble sounder and silence/lamp test switch. Single gang trim plate included, multi-gang plates ordered separately. Mounts in a single or multi-gang North American electrical box. 0.3 (0.1) FSRZI-A Remote Zone Indicator - Includes red LEDs for five lDCs. Single gang trim plate included, multi-gang plates ordered separately. Mounts in single or multi-gang North American electrical box. 0.3(0.1) FSRZI-SA Remote Zone Indicator - Includes LEDs for five lDCs. Single gang trim plate included, multi-gang plates ordered separately. Mounts in single or multi-gang North American electrical box. Jumper selected ,Jarm (red) or Supervisory (amber) indications. 0.3 (0.1) FSAT1 Annunciator Trim Plate, 1 gang 0.1 (0.05) FSAT2 Annunciator Trim Plate, 2 gang 0.1 (0.05) FSAT3 Annunciator Trim Plate, 3 gang 0.1 (0.05) FSAT4 Annunciator Trim Plate, 4 gang 0.1 (0.05) FSRA10 Single Unit 10 zone remote annunciator for FSP1 004 - Insert "F" after p/n for French language option FSRA10C Single Unit 10 zone remote annunciator for FSP1 004 (with common controls) - Insert "F" after p/n for Frencn language option FSUIM Common Function Graohic Driver/Interface - 9 relays and 5 switch inouts for common system indicators and controls Remote Relay Module FSRRM24 Remote Relay Module - Five Form C relays. Configurable for lDCs 1-5, or 6-10, or common system indications. 0.4 (0.2) Requires MFC-A or other listed fire alarm enclosure. FSRRM-S1 1 11" Mounting track. Holds up to 4 FSRRM24s. 0.4 (0.2) Accessories MFC-A Multi-function Cabinet (fire alarm accessory enclosure) 7.0 (3.2) Batteries 12V4A 4.5 Ah Sealed Lead Acid Battery - 12 Vdc (2 required) 5(2.27) 12V6A5 7.2 Ah Sealed Lead Acid Battery - 12 Vdc (2 required) 6(2.72) 12V1 OA 11 Ah Sealed Lead Acid Battery - 12 Vdc (2 required) 10 (4.45) 12V1 7A 18 Ah Sealed Lead Acid Battery - 12 Vdc (2 required) 13 (5.90) 12V24A 26 Ah Sealed Lead Acid Battery - 12 Vdc (2 required) 20 (9.07) Page 7018 DATA SHEET 85005-0126 Not to be used for ins:allatron purposes Issue 2 Finpnw-~-~ S Contact us... Email: edwards.fire@fs.utc.com Web: www.est-fire.com EST is an EDWARDS brand. 1016 Corporate Park Drive Mebane, NC 27302 In Canada, contact Chubb Edwards... Email: inquines@chubbedwards.com Web: www.chubbedwards.com © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Specifications subject to change without notice. Edwards is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation. Page 8of8 DATA SHEET 850050126 Not to be used for instalation purposes Issue 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7165-1657:0102 Page 1 of I CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: EDWARDS, A Division of UTC Fire & Security Americas Corporation, Inc.8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Conover (941) 739-4358 Fax (941) 308-8123 Email: rhonda.conover@fs.utc.com DESIGN: Models FireShield series FS302x, FS502x, FS1004x, *Models FireShield PlusFSP302 FSP502x, FSP1004x, *Models FireworX series FX-3x,1FX-5x FX-110x and *Models FSC- series E-FSC302x, E-FSC502x, E-FSC1004x fire alarm control units. The suffix x' may include any of the following alpha and/or numbers: G, R, G-2, GF,GD'AD) GC or *F. Models FSDACT and *F..DACT digital alarm communicator transmitter. Local, auxiliary, central station, remote station, automatic, manual, watertlow and sprinkler supervisory service. Refer to listee's data sheet for detailed product description and operational considerations. RATING: 120 VAC Primary, 24 VDC Secondary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as fire alarm control units for use with separately listed compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual for details. This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition. *This control unit meets the requirements of UL-864, 9th Edition Standard. NOTE: 1. For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 2. Formerly 7165-1591:102, 7165-1501:129 7-29-10 ma This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 Listing Expires (June 30, 2018, Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division CELLULAR ALARM TG=7FS CONIMUNICATOT) FOR 3G/4G NETWORKS TELG UAR D COMMERCIAL FIRE PRODUCT FEATURES Meets UL 864 requirements for sole, primary or backup path communications. Provides RMR protection by leveraging technology that operates on 3G/4G networks. Supports listen-in, two-way voice verification over cellular. Minimizes false alarms by providing dual paths for self-tests. Falls back to 2G (GSM) if a 3G/4G network isn't available. The Telguard TG-7FS is the ideal cellular alarm communications solution for commercial fire systems. The TG-7FS transmits alarm signals from the fire panel over the digital cellular network to the designated monitoring station. Compliant with the 2010 Edition of NFPA 72, the TG-7FS can serve as the sole communications path for the fire alarm system. It replaces ( \ all of the landlines currently dedicated to the master control unit. On average, cellular monitoring costs the end user significantly less than a dedicated landline. For each landlinc replaced with a TG-7FS, the monthly communications bill decreases. By being able to signal failures to the central station within five minutes of an outage, the TG-7FS can be installed as the sole path for commercial fire installations. For existing installations, all lancllines can he swapped for a single TG-7FS because of the new five minute supervision mode. The TG-7FS can also be installed as a backup path and upgraded to sole path at a later date. TELGUARD Power Radio Transceiver Physical Details Standard Features I CELLULAR ALARM TG=7FS COMMUNICATOR FOR 3G/4G NETWORKS , —lI Tolguard technology allows full data reporting for unlimited point-to-point signal details and maximum transmitting power for superior in-building penetration. Telguard products are easy to install, economical, and UL Listed. Accessories ACD 12, ACD 35. ACD 50, ACD 100: 12/35/50/100 feet of low loss, high performance cable. HGD-0: High gain directional antenna. EXD-0: External antenna. UL Listings Commercial Fire 86 control units & accessores for I re alarm syscms Commercial Burglary 365 Police Station connected burglar niarm units and systems 1610 Central station burglar alai n units: Line security set s'des Residential 985 Household In e yarning systems 0 II '50.1 Curr'rri produc ,rrcr r5rcrrr'. irn UL _ni rrrs vi, us, lcIgjrd corn. \l!E! NFPALISTED "'(iS 0. INVLJNATIONL ielgLiard, a Division of klular Corporation • 2727 Paces Ferry Road SE • Suite 1-800 • Atlanta, GA 30339 USA 800-229-2326, Option 5 www.Telguard.com Copyright 2012 Telulai Corporation All Rights Reserved CERTIFICATE OF COMPLIANCE Certificate Number 20120308 - S50526A Report Reference S5052 - 2007 April 26 Issue Date 2010 March 08 Issued to: TELULAR CORP 311 SWACKERDR SUITE 4300 CHICAGO, IL 60606 USA This is to certify that Control Unit Accessories, System, Control Units and Accessories, Household representative samples of System Type, Central Station Alarm Units, Police-station-connected Alarm Units & Household Burglar Alarm System Units Fire Alarm and Security Equipment: Models, TG7G0004, TG7GA004 and TG7GFS04. All these models are suitable for Standard Line Security. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 864, "Control Units and Accessories for Fire Alarm Systems," ANSI/UL 985, "Household Fire-Warning System Units," ANSI/UL 1610, "Central-Station Burglar-Alarm Units," ANSI/UL 1635, "Digital Alarm Communicator System Units," ANSI/UL 365, "Police Station Connected Burglar Alarm Units and Systems," ANSI/UL 464, "AudibIe Signal Appliances" and ANSI/UL 1023, "Household Burglar-Alarm System Units." Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing, aid Follow-lip Service. The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word "LISTED"; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) a indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product. William R. Carney, Director, North M,.,tcan Csrtlflcetlon Programs ULLLC Any Information and documentation Involving Ut. Mark services ar, provided on behalf of Ut. LLC (UL) crony euthorts.d license, of UL For qu.sons, pleas. contact, local Ut. Customer Semis. Representative at wsw,ttcomkontictus Page 1 of 1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7360-14020169 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: TELULAR CORP.3225 Cumberland Blvd, Suite 300, Atlanta, GA 30339 Contact: Raj Kosaraju (678) 264-2012 Fax (678) 264-2062 Email: rkosaraju@telular.com DESIGN: Models TG7LAA02, *TG7LA00I *TG7LAP01 TG7LA002, *TG7LAF01 TG7LAF02, and TGKITLA2 digital cellular radio alarm transmission system for fire/burglar alarm system control units. Models TG7LAA02 and TG7LA002 are household application. Model *TG7LAF0I TG7LAF02, and TGKITLA2 are for commercial application. Refer to listees printed data sheet for additional detailed product description and operational considerations INSTALLATION: In accordance with listees printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as digital cellular radio alarm transmission devices to provide a standalone transmission path (cellular) for a listed compatible fire and burglar alarm control unit. It may also provide a backup communication path when used in conjunction with a DACT. This product is to be connected to a listed control panel in accordance with the installation instructions provided by the manufacturer. NOTE: Burglary and other non-fire functions were not examined. * Revised 10.03.2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct IlV operational requirements or installation criteria. Refer to listee s data sheet installation instructions and/or other Date Issued: July 01, 2017 Listing Expires (June 30, 2018 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Edwards Signaling Catalog P Conventional Initiating Two-Wire Conventional Smoke Detector 5110 1•1 Overview The Edwards 5110 is an economical, conventional photoelectric, direct-wire smoke detector with drift compensation. The 5110 continually monitors its own sensitivity and operational status, and provides a visual indication if it drifts out of the sensEtiv- ity range or fails internal diagnostics. Additional diagnostic informa- tion is activated by applying a magnet near the detector's integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if service is required. The magnet test causes the LED to blink. The number of blink counts corresponds to a smoke detector sensitivity range. This meets NFPA 72 field sensitiv- ity test requirements without the need for external meters. The chance that a 5110 will need maintenance is significantly decreased because of the built-in drift compensation. This feature, usually only available in analog systems, allows the detector to automatically adjust its sensitivity over time as it becomes dirty increasing the life of the detector. And, if the 5110 ever needs cleaning, it's literally a snap with FireworX's patented field replace- able optical chamber. The 5110 also features an alarm verification feature to further reduce the chance of a nuisance alarm. Normal sensing occurs every 9 seconds. This rate doubles when a signal exceeding the alarm threshold value is sensed. Two additional successive signals above the threshold level will initiate an alarm. See installation instructions for information about correct instala- tion and maintenance. Standard Features Self-diagnostics continually monitors detector's operation and meets NFPA 72 sensitivity test requirements Built-in drift compensation reduces nuisance alarms Field-replaceable optical chamber makes servicing a snap Small, low-profile design blends in with any environment Large SEMs type terminals speeds wiring connections while ensuring a secure connection Cost effective for the largest installations Page 1 of 2 DATA SHEET S85001-0595 Not to be used for installation purposes Issue 2 JftcH Smoke Detector Technology Most homes have battery operated ionization smoke detectors. These detectors react quickly to flaming fires but usually take longer to detect smoldering fires - the most com- mon type of fire that occurs in homes. Edwards 5110 smoke detectors utilize photoelec- tric smoke detection technology. Photoelectric smoke detectors continually analyze the air for smoke particles and are more sensitive to smoldering fires than ionization detectors. Installing both ionization and photoelectric smoke detectors in your home provides the best possible protection for you and your family. Specifications Electrical yoitag (l?L24YPQ(a.5:33YDC), polarity_ .se!sitiye Maximum standby current 70pA Maximum alarm current 60mA Minimum reset time 1 sec Environmental Photoelectric sensitivity (3.1%+0.5% -1%' Operating temperature 32°F to 100°F (0°C to 37.8°C) Operating humidity 0-95% non-condensing Contact us... Phone: 1-800-336-4206 Web: www.edwardssignaling.cpm Edwards Signaling is an EDWARDS brand. 3 Farm Glen Boulevard Farmington, CT 06032 In Canada, contact Chubb Edwards... Email: inquines@chubbedwards.com Web: www.chubbedwards.com © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Specifications subject to change without notice. Edwards is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation. Physical Color White Detector dimensions 5" x 2" (12 x 5cm) Base dimensions 4.75" x 0.3" (12.5 x 0.8cm) Drift compensation adjustment 1%/ft. max Field wiring size' Regulations 18-12AWG Ir Listing UL 268, CSFM UL compatibility identifier S10A Ordering Information Model Description Listing 1511 C iPhotoelectric Smoke Detector, 2-wire, 12/24VDC, white" .UL268: Accessories SM200- Smoke! in a Can® aerosol spray for functional testing 12PKG SM-EXT 1 Smoke! in a Can® extension tube connects directly to can 211-10PKG Replacement optical chambers (package of 10) 500PLT-5PKG Mounting plate, adapts 511 C to 400 Series mounting footprint, 6" diameter S Page 2of2 DATA SHEET S850010595 Not to be used for installation purposes Issue 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (ñ72-1657:6'6 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: EDWARDS, A Division of UTC Fire & Security Americas Corporation, Inc.8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Conover (941) 739-4358 Fax (941) 308-8123 Email: rhonda.conover@fs.utc.com DESIGN: Models SIGA-PS and SIGA-PHS photoelectric smoke detectors. Model SIGA-PHS employs an integral 135SF fixed temperature heat sensor. This heat sensor is a supplementary device to the smoke detector and is not approved as a required heat detector. Refer to listee's printed data sheet for additional detailed product description, installation and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with listee's listed fire alarm control units and Model SIGA Series bases (CSFM Listing No. 7300-1657:120). Model SIGA-PS may be suitable for installation directly in the duct with the velocity range from 0-5000 feet/mm. NOTE: Model SIGA-PHS is not intended for use in lieu of a required heat detector. Formerly 7272-1591:126 and 7272-1388:186 S 7-29-10 ma This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 Listing Expires (June3O,2Oij Authorized By: DAVID CASTIL.LO, Program Coordinator Fire Engineering Division Edwaras Signaling Catalog t> Conventional Initiating dwards Signaling Fire Alarm Stations 270 Series Overview Edwards 270 Series Non-Coded Fire Alarm Stations are sturdy, 181 attractive, and designed for economical installation. The station is available in the following operational and functional designs: - The 270 Series provides a single action, break glass initiat- ing station. It is available with normally open (NO.), normally closed (N.C.) or combination N.O./N.C. contacts. The basic 270 Series have screw terminals for field connection. The 270A Series Manual Stations have 6 inch (150mm) wire leads. All non-coded statins are designed for either flush or surface mounting. For flush mounting a 4 inch standard North Ameri- can square box with single gang plaster cover should be used. For surface mounting the 270 Series, use P-027193 Cast Box, P-039250 Steel Box. Standard Features Pull lever Simple positive operation Break glass Attractive, streamline design Less than 5 lb pull force complies with ADA Solid, die-cast metal construction S Page 1 of 2 DATA SHEET S85001-0303 Not to be used for installation purposes. Issue 6 3••" - cern I (ISM mT[190mm( I L J j FRONT AST SURFACE BOX SIDE P.327193 3118" F_ (80mm) PJ 4.1/2" (I I4mm( H FRONT rM SIDE STEEL SURFACE 804 P.039230 Contact us... Phone: 1-800-336-4206 Web: www.edwardssignaling.com Edwards Signaling is an EDWARDS brand. 3 Farm Glen Boulevard Farmington, CT 06032 In Canada, contact Chubb Edwards... Email: inquiries@chubbedwards.com Web: www.chubbedwards.com © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Specifications subject to change without notice. Edwards is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation. WARNING: These devices will rot operate without electrical power. As fires frequently cause pow- er interruptions, we suggest you discuss further safeguards with your local fire protection specialist. fl Mounting r- (82mm) DOOR ROLEA2E WALL SJPFACE - FOR TEST A RESET AND GLASS REPLACE.ISNT GEN ALAIW IKEY SWITCH T. S.P.s.. (INCLUDED WITH 4.11r (1l4mm, PRE- SGNAL SATIONS) ONLY LJ P27165 3LSWOD FLUSH INSTALALTION USING P.024900 STEEL BOX Ordering Information All models are fire alarm red with Aluminum Strips. They are marked "Pull in Case ot Fire" on the pull Iandle. Cat No. Marking Switch Contacts Field Connections Pre- (top of Signal device) Single Double Open Screw Wire Pre- Pole Pole Circuit Terminals Leads Signal 270-DPO Fire Alarm 27C-SPO Fire Alarm V V V 27CA-DPO Fire Alarm V V (ASP Fire Alarm V V V Page 2of 2 - DATA SHEET S85001_0303 Nçt tot be used for insTallation purposes. lsst.e 6 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM is LISTING SERVICE LISTING No. 715O1657:0111 Page 1 of I CATEGORY: 7150 -- FIRE ALARM PULL BOXES LISTEE: EDWARDS, A Division of UTC Fire & Security Americas Corporation, lnc.8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Conover (941) 739-4358 Fax (941) 308-8123 Email: rhonda.conover@fs.utc.com DESIGN: Models 270, 270P, 270-SPO, 270A-SPO 270-DPO, 270A-DPO, 270-DOC, 276B, 277B, 278B, 279B, 279TC, 279P, 279T, 279L, 276A-REL, 278A-REL, 5966B, 5966BR, 5966BV, 5966BRV, 629613-270, 62968-1<279, 6296B-T279, 8557-13301, 8557-13311, 8558-13301, 8558-13311 and 8558-13312 manual pull stations*. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as non-coded fire alarm pull stations for use with separately listed compatible fire alarm control units. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. NOTE: 1. Models provided with two-wire lead and normally closed switch contacts are not approved for fire alarm signaling use. 2. Formerly 7150-1591:111, 7150-1388:121 and 7150-0073:117 7-29-10 ma TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued July 01, 2017 Listing Expires (June 30, 201 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division