Loading...
HomeMy WebLinkAbout2320 CAMINO VIDA ROBLE; ; FPC2017-0280; PermitOki Il:1II.]I Print Date: 05/19/2022 Job Address: 2320 CAMINO VIDA ROBLE, CARLSBAD, CA 92011-1562 Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm Parcel #: Track #: Valuation: $0.00 Lot #: Occupancy Group: Project #: #of Dwelling Units: Plan #: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check #: Plan Check#: Permit No: FPC2017-0280 Status: Closed - Finaled Applied: 10/04/2017 Issued: 10/23/2017 Finaled Close Out: 03/25/2021 Final Inspection: INSPECTOR: Wong, Cindy Project Title: Description: LUXTERA -FIRE ALARM (PANEL UPGRADE) Applicant: FPContractor: JOHNSON CONTROLS SECURITY SOLUTIONS JOHNSON CONTROLS SECURITY SOLUTIONS LLC LLC - DONOTUSE MALCOLM D'COSTA 3870 MURPHY CANYON RD, # 140 3870 MURPHY CANYON RD, # 160 SAN DIEGO, CA 92123-4403 SAN DIEGO, CA 92123-4403 (561) 226-8210 (619) 805-5300 FEE AMOUNT FIRE Sprinkler Monitoring $371.00 Total Fees: $371.00 Total Payments To Date: $371.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1760-602-8561 f I www.carlsbadca.gov HIGHLIGHTED SET Cut Sheets and CSFM Listing Sheets For: LUXTERA 2320 Camino Vida Roble Carlsbad, California 92011 Installer: Integrated S:ecurity 3870 MURPHY CANYON ROAD SUITE 140 SAN DIEGO, CA. 92123 (800) 289-2647 LIC 4977249 (C-b, C-7) FPC20I 7-0280 2320 Camino Vida Roble DF-5241 6:D • A3-20 MS-5UD(E)MS-1 OUD(E) Series) 4j FIreLITeALarmS Five Zone Fire Alarm Control Panel (Len Zone Fire Alarm Control Panel) by Honeywell General The MS-51JID-3(E) is a five-zone FACP (Fire Alarm Control Panel) and the MS-10UD-7(E) is a ten-zone FACP. These con- trol panels provide reliable fire signaling protection for small to medium-sized commercial, industrial, and institutional build- ings. Both panels include built-in communicators for Central Station Service and remote upload/download. Each of these FACPs is compatible with System Sensor's microprocessor-based i3 series detectors. These conventional smoke detectors can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory "freeze" signal when the ambient temperature falls below the detector rating. Additionally, both the MS-5UD-3 and MS- 1OUD-7 are compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterf low devices, tamper switches, and other normally-open contact devices. Refer to the Fire-Lite Device Compatibility Document for a complete listing of compatible devices. Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special applica- tion resettable and nonresettable power outputs. The FACPs supervise all wiring, AC voltage, battery level and telephone line integrity. Activation of a compatible smoke detector or any normally- open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the communicator and FACP alarm relay, and operate an optional module used to notify a remote station or initiate an auxiliary control function. New options include a UL listed printer, PRN-6F and FireLite's IPDACT Internet Monitoring module. The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD per- mit monitoring of alarm signals over the Internet saving the monthly cost of two telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. NOTE: The MS-5UD-3E and MS-10UD-7E offers the same fea- tures as the MS-5UD-3 and MS-I0UD-7 but allow connection to 240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 120 VAC and the 240 VAC versions of these panels. NOTE: For ULC-listed models, see DF-60440. Features Listed to UL Standard 864, 9th edition. Built-in DACT (Digital Alarm Communicator/Transmitter). Style B (Class B) IDC (Initiating Device Circuit) - MS-5UD-3 - five lDCs. - MS-1 OUD-7 - ten lDCs. Style Y (Class B) NAC (Notification Appliance Circuit) - spe- cial application power - MS-5UD-3 - four NACs. - MS-10UD-7 - four NACs. Notification Appliances may be programmed as - Silence Inhibit. - Auto-Silence. - Strobe Synchronization for System Sensor, Wheelock, Gentex, Faraday, or Amseco devices. - Selective Silence (horn-strobe mute). - Temporal or Steady Signal. - Silenceable or Nonsilenceable. Optional CAC-5X Style Z (Class A) Converter Module for NACs and lDCs (2 required for MS-1 OUD-7). Form-C Relays for Alarm, Trouble and Supervisory - Con- tact Ratings 2.0 A@ 30 VDC or 0.5 A @ 30 VAC (resistive). 3.0 A total system current for MS-5UD-3. 7.0 A total system current for MS-1 OUD-7. Optional Dress Panel DP-51050 Optional Trim Ring TR-CE for semi-flush mounting. 24 volt operation. Low AC voltage sense. Alarm Verification. PAS (Positive Alarm Sequence). Automatic battery trickle charger. Up to eight ANN-BUS annunciators: - Optional 8 zone Relay Module ANN-RLY. - Optional LED Annunciator Module ANN-LED, - Optional Remote Annunciator ANN-80. - Optional Remote Printer Gateway ANN-S/PG. - Optional LED Annunciator Driver ANN-I/O. Optional 4XTMF module (conventional reverse polarity/city box transmitter). PROGRAMMING AND SOFTWARE: Can be programmed at the panel with no special software or additional equipment. Programmable Make/Break Ratio. Upload/Download (local or remote) of program and data via integral DACT. DF-52416:D • 07/26/2010 - Page 1 of 4 USER INTERFACE: Built-in DACT (Digital Alarm Communicator/Transmitter). Integral 80-character LCD display with backlighting and keypad. Real-time clock/calendar with automatic daylight savings adjustments. ANN-BUS for connection to remote annunciators. Audible or silent walk test capabilities. Piezo sounder for alarm, trouble, and supervisory. Controls and Indicators LED INDICATORS FIRE ALARM (red) SUPERVISORY (yellow) TROUBLE (yellow) AC POWER (green) ALARM SILENCED (yellow) CONTROL BUTTONS ACKNOWLEDGE ALARM SILENCE SYSTEM RESET (lamp test) DRILL Terminal Blocks AC Power —TB1: MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 50/60 HZ, 1.00 A. MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 A. MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ, 3.80 A. MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50/60 HZ, 2.20 A. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Supervised, nonpower-limited. Battery (sealed lead acid only) - J12: Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 A. Supervised, nonpower-limited. Maximum Charger Capacity: 18 AH battery for MS-5UD- 3(E), and 26 AH battery for MS-1 OUD-7(E). [Two 18 Ah bat- teries can be housed in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or BB-55.] '_' (• '- '-.' Depth = 5.207" (13.23 cm) Top ______ Door = 16.821" (42.73 cm) _ Depth = I 5.257" ,I Backbox = 16.65" (42.29 cm) 4 3353 cm)' Door = 19.26' (48.92 cm) Backbox = 19.0 (48.26 cm) Left Side Right Side Bottom Cabinet Measurements Page 2 of 4— DF-5241 6:D • 07/26/2010 Minimum Battery Size: 7 AH. Initiating Device Circuits - TB4 (and TB 6 on MS-i OUD-7 only): Alarm Zones 1 -5 on TB 4 (MS-5UD-3 and MS-1 OUD-7). Alarm Zones 6- 10 on TB6 (MS-1 OUD-7 only). Supervised and power-limited circuitry. Operation: All zones Style B (Class B). Normal Operating Voltage: Nominal 20 VDC. Alarm Current: 15 mA minimum. Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL- listed). Standby Current: 2 mA. Refer to the Fire-Lite Device Compatibility Document for listed compatible devices. Notification Appliance Circuits - TB5 (and TB 7 on MS- 1OUD-7 only): Four NACs Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 3.0 A for MS-5UD-3, 2.5 A maximum per NAC; 7.0 A for MS-10UD-7(E), 3.0 A maxi- mum per NAC. End-of-Line Resistor: 4.7K ohm, 1/2 watt (Part #71252) Max. Wiring Voltage Drop: 2 VDC Refer to the Fire-Lite Device Compatibility Document for com- patible listed devices. Form C Relays - T138: Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Special Application Resettable Power - TB9: Jumper selectable by JP31 for resettable or nonresettable power. Operating voltage: 24 VDC nominal. Maximum available current: 500 mA - appropriate for pow- ering four-wire smoke detectors. Power-limited circuit. Refer to the Fire-Lite Device Compatibility Document for listed compatible devices. Remote Sync Output - TB2: Remote power supply synchro- nization output, only required for the MS-5UD-3. 24 VDC nom- inal special application power. Maximum current is 40 mA. End-of-Line Resistor: 4.7K ohm. Supervised and power-lim- ited circuit. Product Line Information MS-5UD-3: Five-zone, 24-volt Fire Alarm Control Panel (includes backbox, FLPS-3 power supply, technical manual, and a frame & post operating instruction sheet). 120 VAC operation. MS-5UD-3E: Same as MS-5UD-3 except for 240 VAC opera- tion. MS-10UD-7: Ten-zone, 24-volt Fire Alarm Control Panel (includes backbox, FLPS-7 power supply, technical manual, and a frame & post operating instruction sheet). MS-i OUD-7E: Same as above with 240 VAC FLPS-7. IPDACT, IPDACT-212UD Internet Monitoring Module: Mounts in bottom of enclosure with optional mounting kit (PN IPBRKT). Connects to primary and secondary DACT tele- phone output ports for internet communications over customer provided ethernet internet connection. Requires compatible Teldat Visoralarm Central Station Receiver. Can use DHCP or static IF. (See data sheet DF-60407 for more information.) IPBRKT: Mounting kit for IPDACT in common enclosure. IPSPLT: Y Adaptor option to allow connection of both panel dialer outputs to one cable input to IPDACT (sold separately). OPTIONAL MODULES CAC-5X: Optional (Class A) Converter Module. Converts Style B (Class B) Initiating Device Circuits to Style D (Class A); and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). Connects to J2 on the MS-5UD-3 and MS-10UD- 7(E) main circuit board and to J7 on the MS-10UD-7(E). NOTE: Two Class A Converter Modules are required for the ten- zone panel. 4XTMF: Transmitter module. Provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. Includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm conditions exists. Mounts to the main circuit board connectors J4 and J5. COMPATIBLE ANNUNCIATORS ANN-80: Remote LCD Annunciator. Mimics the information displayed on the FACP's LCD. Red. (For white, order: ANN- 80-W.) ANN-LED: LED Annunciator with three LEDs for each zone: Alarm, Trouble, and Supervisory. Mounts in the DP-51050(B) dress panel. Red. (For white, order ANN-LED-W.) ANN-RLED: LED Annunciator with three alarm (red) indica- tors for up to 30 input zones or addressable points. (Red. For white, order ANN-LED-W.) (See DF-60241). ANN-RLY: Relay module. Mounts inside the cabinet. Provides ten Form C relays. ANN-S/PG: Serial/parallel printer gateway. Provides a connec- tion for a serial or parallel printer. ANN-I/O: Driver module. Provides connections to a user-sup- plied graphic annunciator. ACCESSORIES DP-51050: Optional dress panel. Restricts access to the sys- tem wiring while allowing access to the membrane switch panel. BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-75. BB-55: Battery backbox, holds up to two 25 AH batteries. TR-CE: Optional trim-ring for semi-flush mounted cabinets. PRN-6F: UL listed printer. DF-52416:D • 07/26/2010— Page 3 of 4 SYSTEM SPECIFICATIONS System Capacity Annunciators .8 Electrical Specifications MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.OA MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 A MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 A. MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 A. Wire size: minimum 14 AWG (2.0 mm2) with 600 V insula- tion, supervised, nonpower-limited Cabinet Specifications Door: 19.26 (48.92 cm.) high x 16.82' (42.73 cm.) wide x 0.72' (1.82 cm.) deep. Backbox: 19.00 (48.26 cm.) high x 16.65' (42.29 cm.) wide x 5.25' (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65' (49.91 cm.) wide. Shipping Specifications Dimensions: - 20.00" (50.80 cm.) high - 22.5' (57.15 cm.) wide - 8.5' (21.59 cm.) deep. Weight: 27 lb (12.20 kg) Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 - 49°C/32 - 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the systems standby batteries and the electronic components may be adversely affected by extreme tempera- ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15— 270C160 - 80°F Agency Listings and Approvals The listings and approvals below apply to the basic MS-51LID-3 and MS-i OUD-7 control panels. In some cases, certain mod- ules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for lat- est listing status. UL Listed: File S624 FM Approved CSFM: 7165-0075:0214 MEA: MEA: 333-07-E NOTE: For ULC-listed models, see DF-60440. NFPA Standards The MS-5UD-3(E) and MS-10UD-7(E) complies with the fol- lowing NFPA 72 Fire Alarm Systems requirements: - LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). - AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). - REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) - PROPRIETARY (Automatic, Manual and Waterflow). - CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). - OT, PSDN (Other Technologies, Packet-switched Data Network) FireLite® Alarms and System Sensor® are registered trademarks of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended lobe used for installation purposes. I SO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENCINEERINC & MMURCTURING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 4 of 4— DF-52416:D • 07/26/2010 Calculating the System Current Draw Power Supply Calculations 73 Calculating the System Current Draw 7.31 Oyerview The control panel must be ablcto'power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column I in Table 7.3 on page 118. The control panel must support a larger load current during a fire alarm condition. To calculate the fire alarm load on the power supply, use Calculation Column 2 in Table 7.3 on page 118. The secondary power source (batteries) must be able to power the system during a primary power loss. To calculate the non-lire alarm load on the secondary power source, use Calculation Column 3 in fable 7.3 on page 118. When calculating current draw and the battery size, note the following: Primary' refers to the main power source for the control panel 'Secondary' refers to the control panel's backup batteries All currents are given in amperes (A). Section 7,2 shows how to convert milliamperes and microamperes to full amperes. To convert.. Multiply Example Milliamperes (mA) to mA x 0.001 3 mA x 0.001 = 0.003A amperes (A) Microamperes (PA) to PA x 0.000001 300 hA x 0.000001 = 0.0003 A amperes (A) Table 7.2 Converting to Full Amperes 73.2 How to Use Table 73 on page 118 to Calculate System Current Draw Use Table 7.3 on page 118 to calculate current draws as follows: I. Enter the quantity of devices in all three columns Finer the current draw where required. Refer to the Device Compatibility Document for compatible devices and their current draw Calculate the current draws for each in all columns Sum the total current for each column Copy the totals from Column 2 and Column 3 to Table 7.4 on page 119 Following are the types of current that can be entered into Table 7.3 on page 118: / Calculation Column I - The trimary supply current load that the control panel must support during a non-fire alarm condition, with AC power applied. / Calculation Column 2 - The primaly supply current load that the control panel must support during a fire alarm condition, with AC power applied. / Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm condition during a loss of AC power. MS-5(!D & iviS- JUL/B Series .44anual P/N 52626:C4 3/7/2014 117 Power Supply CalculaiJons Calculating the System Current Draw Table 7.3 contains three columns for calculating current draws. For maximum output current avail- ability per circuit and per panel, refer to Section 1,2, "Specifications", on page 15. For each col- umn, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 119. Calculation Column I Calculation Column 2 Calculation Column 3 Device Type Primary, Non-Fire Alarm Current Secondary, Fire Alarm Current Secondary, Non-Fire Alarm (amps) (amps) Cunt (amps) oty X(current Total X currontdrawJ Qty Total . XJcwmnt Total draw = I qz I draw Main Circuit Board MS-5UD X(O.110]= X[O.21411 2 X[O.110]= or 1 1 1 MS-i DUD X[0.1 331=. X[0.282]1 2 X[0.133]= CAC-5X - (. ] X[O.001= F J XO.001]= - [ 3 X[0.001] 4XTMF - [ ] X(0.005= I J X10.01111= [ 3 X[0.005]= 1 max. 1 max. 1 max. ANN-SEC card I J X[0.003]= I J X[0.003]= I I X[O.003] I max. I max. I max. ANN80(C) - 3 X[0.037]= f J X0.040]= I I X[0.015]= ANN-I/O = 3 X[O.035]= I I X(0.200]= I 3 X[0.035] ANN-RLY ] X10.01 5]= I Xf0.0753= F3 X(0.015] ANN-(R)LED _ I X[0.028]= 1 1 X[0.068]= [3 X(0.0283's ANN-SJPG I 3 XI0.045]= 13X[O.045]= [I X(0.0453 2-wire Detector - 3 Xl 1 '= b X[0.0401= [ ] X[ ]= Heads 4-wire Detector ( 3 X( i4= 1 1 1 X[0,040] F I X( ]' Heads Power [ ] X0.0251= [ ] X[0.025]= [ I X[0.0253= Supervision Relays6 NAG #1 [ I XI 1= NAG #2 [ 3 XI NAG #3 NAG #4 Current Draw 3,,, 1 F 1= from TB9 (nonalarm) Sum each column7 for . Primary Non-Alarm = Secondary Alarm = Secondary Non-Alarm = totals Table 7.3 System Current Draw Calculations If using the Reverse Polarity Alarm output, add 0.005 amps: if using the Reverse Polarity Trouble output, add another 0.005 amps. - The current draw shown represents one zone (lDC) on the main circuit board in alarm. One zone consumes 0.040 amps. An ANN-LED is supplied standard with the MS-5UDC and MS-IOIJDC. Refer to the Device Compatibility Document for standby current. Enter the number of IDCs used minus one. Must use compatible listed Power Supervision Relay. Total current draw listed above cannot exceed 3.25 amps for the MS-5UD-3(E), 3.28 for the MS-10UD-3(E), 7.25 for the MS-5UD-7(CIE), and 7.28 for the MS-10UD-7(C/E). 118 MS-51/D & MS- lOUD Series Manual- P/N 52626:C4 3/712014 (a1cv1aiing the Battery Size Power Supply Calculations 7.4 Calculating the Battery Size Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in All), required to support the control panel under the loss of AC power. Complete Table 7.4 afo1lows: Enter the totals from Fable 7.3 on page 118, Calculation Columns 2 and 3 where shown Enter the NFPA Standby and Alarm times (refer to 'NFPA Requirements' below) Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in All) Write the ampere hour requirements on the Protected Premises label located inside the cabinet door Secondary Standby Load Required Standby Time (total from Table 7.3 Calculation (24 hours) Column 3) I X[ J AH Secondary Alarm Load Required Alarm Time (total from Table 7.3 Calculation (for 5 mm., enter 0.084. Column 2) for 10 mm., enter 0168) X[ ] = AH Sum of Standby and Alarm Ampere Hours = AH Multiply by the Derating Factor X 1.2 Battery Size, Total Ampere Hours Required -- = AH Table 7.4 Total Secondary Power Requirements at 24 VDC 7.4.1 NFPA Battery Requirements NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm 7.4.2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 7.4. The control panel can charge batteries in the 7 All to 26 AH range. The control panel cabinet is capable of housing batteries up to 18 All. Batteries larger than 18 AH require the BR-26, B13-55, or other UL listed external battery cabinet. For Canadian applications, the minimum battery size is 12 AH and the maximum battery size is I8AH. tilS5UD & MS-lOtjD Series Manual— P/N 52626:C4 3/7/2014 119 uoisinij 5uueeu1e5u3 ei!/ JOJOU!piOOo W&J5OJd 'oT111sv3 ainva :A pozuoqny (8Oz 'oc eunr) di&Jii7 LM 'iO Aini' :penssl JI.fl0 jo/pue SU0ij3flJ1SUi u0!jeIIeSUi jLS ejep SjS!I 0j J4èI !J1!J0 U0!jellejsU! .io sjuwinboi Ieuo!1eJdo TOeJJOO 4!J9A 0j psn aq IOU pinoqs 6U!TS!I S!q[ pjS!I W9! eqj jo uoiepuww0oeJ Jo juawasiopue ue 0U S1 6U11S1I SiL]j SW!ep AUe JO UOtjeolj!JOA juopuodopu! ue OPW IOU soop jriq eep JO!.flo jo/pue SjflSOJ 1S1 oqj poMoIA0J S814 JJejS 6U1J00U!6U9 oJ!d lueoIdde oqj Aq pojjiwqns ejep e3!uqao uodn peseq S! 6u11s!I !q± 16 g-c-po AO spuooes jc peeoxe IOU i.is poijed soosai,'pJeai eq (wioio aji4 4o Aelep) ainjeal uoiToo!4iJeA wy GJIA JOJ :9ION UOq!pe '-116 'i7ge Piepueis in 40 STUOW9J!flbeJ aqj soow T!Ufl I0J1UOO s!ql SI!1eP J04 jenuew UO!TOIIOTSUi Sjejnloe4nUeW 01 JO4OH SeO!flep 6U1103!pUI pue 6u!eq!u! eiqiwdwoo PT!I Aioeedos ql!M osn J04 hUn I0JTU00 WJ00 aJ 4 0 Se pesr :1VAofddV leqel in pue 6Uq2J Ieo!JJOOIO JeqwnU japow 'eweu SeOSfl :ONI)lVIfiJ UO!10!pS!Jn1 6u!Aeq IcT!J0L11fle eqi ol eqeideooe ieuuew e U! pue SeoUeU!pJ0 pue sepoo elqeo!Idde 'sU0!Tor,JTsu! UO!TBIIOTSU! POTU!Jd seelsil qM O0UepJ0000 UI :N0IIV11VISNI AJepu000S OGA 'ijewud OVA OCZ JO OVA Q :J11 JO!TB0!UnWW03 wjelV amI Ieh!6!G dl 13VGdL E)InpoiN Sfl9NNV iciepuooes 3S-NNV enpoj /IGI A1H-MV einpoj J0T0PUflUUV a1-NNv OflDOAj JOTJ8AUOO XS-3V3 8IflP0VJ J8!WsUeJ1.dVqjX17 enpoj Aiddns JOMOd L-Sdld enpoj Aiddng J8M0d ':C-Scnd :shueuodwoo was, suoqeJepisuoo IeU0!heJedo pue uoqduosep lonpoid pel!eop J03 leeqs eiep s,ealsil ol ioe icJehe!JdoJd pU8 UO!lelS iewe3 uoqeis eowej IcJe!I!xnv 10001 :suo!heoildde 6U!M01104 eqh Jo4 pepuelul aie sepoj eseqj Pollelsu! APeOJIe 9IflP0W J0be!OUflUUe HThNNV pebS!l AleheJedes eq eeq leql sionpojd sbuoseJdeJ xijns eqj shonpoJd paje.i ZH 09 00 A 017Z siuesejdej xns ,, OLLL L-Sdld aqj 6U!Zil!Tfl TUe!JeA JeMod jejol dwe L aqj sbueseJdoJ x!J4n9 L- Oqb pue -Sd1d UT 6U!Z!l!bfl TUe!Jen JOMOd jejol dwe C aqj siuosojdaj xns £- ea (lova) Jo!wsueJT J0Te0!UflWWO0 WJeIe Ieh!6!P 8U!I-OAA1 10J681U! UB epfll0U! JU0 lcJos!AJodns pue aqno wiele J04 shndbno 0eU00 /'eIOJ GGJT pue 51!fl0J!0 OOUO!ldde UO!heo!J!TOU Jfl04 GABL1 SGU!l jonpoJd qToseuoz ndui UOT seq SO!JOS ano -sLeq1 pue seuoz Tndu! GA!4 51J S!J5 Gfl9-SLJ OL.LL sT!Ufl 10JTUO0 WJee eJ! 32-Gfl-Ol-SLAJ aNy 3L-Gnol -SLAJ L-anol -sLAJ CfaflO1.SLAJJ C-OflD I -SVJ L-anc-si 'OL-Gfl9-SV'J L-anc-SLIJ -aflc-SvJ -anc-SLAJ IOPOtJ :NotSa Wo011eMAouOH,sp1OuIceeIUe!J8 :l!ew 60L171 (cog) x8A L9LL-17917 (cot) spiouAoi u0u9 :peuo £S9I--O90 13 PJOJq1JON '000ld eT!1-8J!d eudQNI SV\JHV1VLITh]HI) :3jgfl Vl3IllPO3) 1lNfl 1O1NO3 LAJ1V1V Imi 99I/-) :A0931v3 e6e (PO:SLOO-J) °N ONILSI1 23IAI3S 9NIISI1 VdVJOOJd 9N1.LS11 S1VI1VVJ 9NIO1II1 - DNIèINIONJ JJId 1VHSWJ JIkJ JIV.LS 9H1 dO 3IddO N0I1310Id 3IId T A1S3J0d dO IN] VI1èI Vd]O VINI0dI1V3 19 I 65 DISCHARGE CHARACTERISTICS AT 25 C(77 F) • !E!IIIIIIU '!II U•uIIliIIU•I•UIIIIIlUU. UUIIIHIIUIIFJI•UIuIIIl•I. *uinuu.uuunhi.. 1 2 3 5 10 20 30 60 2 3 5 10 20 30 CLV H Discharge Time CHARGED l 620 VOLUME ___-.------- CHARGED 211 VOLTAGE DOG ow 20 0 0 CHARGING CURRENT Chargeing Time (h) Cycle service life l0 F 80 60 2L ' - 200 000 600 000 000 1100 Life (cycle) POER KINGDOM (Sealed Lead-Acid Batteries) S Specifications Nominal Voltage 12V Rated Capacity 7Ah Dimensions Total Height 3.98 inches (101mm) Height 3.74 inches (95mm) Length 5.94 inches (151mm) Width 2.56 inches (65mm) Approximate Weight 4.52 lbs. (2.05kg) Characteristic Capacity 77°F(25°C) 20h rate 7.00Ah lOh rate 6.50Ah 5h rate 5.95Ah I rate 4.20Ah 15 min rate 3.15Ah Internal Resistance Full Charged Battery 770F(250C) 25m Q Capacity Affected by Temperature (20h rate) 104°F(40°C) 102% 770F(25°C) 100% 32°F(0°C) 85% 5°F(-15°C) 65% Self-Discharge 68°F(20°C) (Capacity after) 3 month storage 90% 6 month storage 80% 12 month storage 60% Max. Discharge Current_77°F(25°C) 105A(55) Terminal Ti ,T2 Charge (Constant Voltage,250C) Cycle I 14.5-14.9V(-24mV/°C) j max. current: 2.1 A Float 13.6-13.8V(-18mV/°C) Constant Current Diarhare Characteristics (A.21;*Ci P8742 .12V)`Ah) 4.8 L F.V/TIME ,5min 10min 15min 30min 60min 3h 5h iOh 20h 9.60V 27.0 18.0 14.0 8.40 4. 70 1. 73 1.15 0. 71 0.37 102V 25. 7 17.1 13.4 8.06 4.55 1. 70 1.13 0. 70 0.36 10.5V 24.2 16.1 12.7 7.66 4. 35 1.65 1.10 0.68 0.35 Constant Current Dincharg Characteristics (Watt.25CI F.V/TIME 5min 10mm 15min 30min 60min 3h 5h 10h 20h 960V 301 203 160 94.2 54.4 20.6 13.8 8. 52 4.43 10.2V 287 191 153 90.4 52. 7 20.2 13.6 8.40 4. 33 10.5V 270 180 145 86.0 50.4 19.6 13.2 8. 17 4.21 System Sensor Pceries smoke detectors represer significant advancement in conventional detecti The /3 family is founded on three principles: ins tal, Photoelectric Smoke Detectors SYSTEM $ SENSOR ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included Large wire entry port In-line terminals with SEMS screws Mounts to octagonal and single-gang back boxes, 4-square back boxes, or direct to ceiling Stop-Drop 'N Lock attachment to base Removable detector cover and chamber Built-in remote maintenance signaling Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide-angle, dual-color LED indication Loop testing via EZ Walk feature Built-in test switch Agency Listings ® <Zf3> :: MEA MSFM C(1I1)US LISTED APPROVED approved approved 5911 3011446 7272-1653:152 290-01-E 2093 3180932 Installation ease. The P line redefines installation ease with its plug-in design.This allows an installer to pre-wire bases (included with heads). The large wire entry port and in-line terninals provide ample room for neatly routing the wiring inside the 3ase. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete :he installation, P heads plug into the base with a simple Stop-Drop 'NI Lock" action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LED- indicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol.The SENS-RDR, a wireless device, displays the sensitivityofi3 detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the il protocol, the EZ Walk loop tesi feature is available on 2-wire i1 detectors. This feature verifies :he initiating loop wiring by providing LED status indication at each detector. (fr Smoke Detector Specifications Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2W1-B, 4W1-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3/2-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2VVT-B, 4W7-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Operating Voltage Nominal: 1 2/24V non-polarized Minimum: 8.5V Maximum: 35V Maximum Ripple Voltage 30% peak to peak of applied voltage (Standby 2-7ire: 50 pA maximum average; 4-wire: 50 pA maximum average ximum Alarm Current) (i3 mA 1imited by control paneT)4 wire 20 mA @12 V 23 mA @24 V Peak Standby Current 2-wire: 100 pA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30V AC/DC Physical Specifications_____ Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4W1-B: 32°F to 100°F (0°C to 37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135°F (57,2°C) fixed FreezeTrouble 2WT-B and 4\NT-B only: 41°F (5°C) Sensitivity 2.50/o/ft nominal InputTerminals 14 to 22 AWG Mounting LED Modes LED Mode Green LED 31/2-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling Power-Up Sequence Ifor LED JIndication Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information PW-7B 0 V-7 117 (IAimkedbycontipanel) 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24V 4VVT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24V Accessories 2W-MOD2 2-wire loop test / maintenance module RI Removal / replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter SYSTEM 3825 Ohio AvenueS St. Charles, IL 60174 ISENSOR Phone: 800-SENSOR2 Fax: 630-377-6495 curncut product information, ~ncluding the latest version of thIs data sheat. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7272-1653:0152 Page 1 of 1 CATEGORY: (7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC) LISTEE: ystem_Sensor)Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: Vladimir.Kireyevhoneywell.com DESIGN: Models 2W1-B, 4W-B and 4WT-B(photoelectrictype smoke detectors. Models 2W-13) and 2WT-13 are 2-wire and model 4W-13 and 4W1-B are 4-wire detectors. Models 2VVT-B and 4W1-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental to the detector and is not intended for use as a required heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 8.5 - 35 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling mount. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mir.. NOTE: Formerly 7272-1209:210 06-20-05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 1LisigExpJ (June 30, 2018) Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 4/15/2015 System Sensor 2-re Compatibility for MS-10UD-3 by Fire-Lite 2-wire Corn patibilityjojr S (Manufacturer: Fire-Lite) (Model: MS-I0UD-3) Detector Max Zone Zone Base Model Style EOL Model Detectors Model ID 2151(T) BI1OLP, 20 N/A/CAC- B,D 4JKI A B401 5X LN/A JCAC) / N/A ICAC- 4JKI 2WT-B N/A 20 B, D* A 2WTA-B N/A 20 A/C B, D* 47K/ A 2WTR-B N/A 1 N/A/CAC- B,D* 4.7K/ A B110LP, 20 N/A/CAC- B,D 4.7K/ A B401 5X N/A D2 N/A 20 B,D A 1/1 TELULAR® Meets UL 864 requirements for sole or dual path communications technology Supports virtually all alarm formats for universal panel compatibility Connects to your central station's PSTN or lP receivers Increases your RMR while saving your customers money The Telguard TG-7FS is the ideal cellular alarm communications solution for commercial fire systems. The TG-7FS transmits alarm signals from the fire panel over the digital cellular network to the designated monitoring station. Compliant with the 2010 Edition of NFPA 72, the TG-7FS can serve as the sole communications path for the fire alarm system, replacing all of the landlines your customers currently dedicate to their master control unit. On average, cellular monitoring costs the end user significantly less than a dedicated landline. Furthermore, each month they will pay you instead of the local telephone company for the communications path. For each landline they replace with aTG-7FS, their monthly communications bill decreases while your RMR increases. Your customer currently has installed... FIRST PATH SECOND PATH You can replace it with... FIRST PATH SECOND PATH Customer Your RMR SAVES* INCREASES* Landline Fflylliii: iewi ra (5 min Supervision) Necessary r1TIIiii Cellular TG-7FS Not ....1 min Supery Necessary 'IL. TG-7FS Not (5 min Supervision) Necessary Savings based on the estimated monthly cost of a business line compared to the estimated customer charge for monthly cellular monitoring. By being able to signal failures to the central station within five minutes of an outage, the TG-7FS can be installed as the sole path for commercial fire installations. When installed with multiple communications technologies, such as DACT, it is acceptable to supervise the cellular communication path just once daily. For existing installations, all landlines can be swapped for a singleTG-7FS because of the new five minute supervision mode. Telguard TG-7FS-Sole Path Cellular Alarm Communicator for Commercial Fire System Specifications Standard Features Full data reporting Automatic self-test (5 minute, daily, weekly or monthly) Power supply with battery harness Locking, red metal enclosure Two programmable supervisory trip outputs Alarm format support for S1A2, Contact ID, pulse (3x1, 421, modem lie, & 111a2, DMP Telephone line monitor built-in Physical Details 75"H x 11.5W x 3.5"D, Weight: 8 lbs. Operating environment: 000 to +50°C; up to 95% humidity (non-condensing) Advanced Reliability Available relay output for tripping the alarm control panel when a trouble condition occurs Automatic Self-Tests with central station notification ensure the cellular system is operating 128 bit AES (Advanced Encryption Standard) alarm signals ensure authentication and security Accessories ACD-35/50/100 feet of low loss, high performance cable HGD-0 High gain, directional antenna LPD-0 Low profile, high gain antenna EXD-0 External, high gain antenna UL Listings Commercial Fire Listings 864 - Control units and accessories for alarm systems Commerical Burglary Listings 365 - Police station connected burglar alarm units and systems 1610- Central station burglar alarm units Residential Listings 985 - Household fire warning systems 1023- Household burglar alarm systems Power Transmit power 1.0-2.0W (maximum allowable) Current consumption 60mA (stand-by) 250mA itransmissioni Transformer supplied: 12VAC, 800mA UL listed plug-in Radio Transceiver Dual band cellular and PCS GSM 850MHz: Class 4 (2 watts) GSM 1900MHz: Class 1 0 watt) Antenna 9" dipole with 2dBi gain with 12 feet of cable and universal mounting bracket FCC part 15, 22, 24 & 68 compliant Pi: R 3.8 d fl ED Rg 0 C) O a _•0 o '4 8 - 5° 8 LEDs 2-5 LED I Ofl• 0 U 0 I ——-5 8 w 0hi-F 8 -- n - OUUU 3 —u oou• 0Al 5 rn 0 0 on..ca 00 8 ODE. 0 I 0000 8 0000 'I' 0000 (D 5 0 C)0 G)8 —I o. G)c.O co co TOTG-7FS 60 LEO 8 LED 7 LED 0 LEO 0 LEO 4 1 LED 3 LED 2 -DI 8 m Z e Z C 8 fl - M. 0 , 0 o 0 o = o C8 3 - - - - o • i O_ / onuonuonu fl - r 8 • 8 0 8 a 8 8 Telguard Model TG-7FS QUICK INSTALLATION GUIDE [SOLE PATH] Installation Summary There are seven steps in installing Telguard properly. IF YOU DO NOT PROCEED IN THE ORDER AND MANNER PRESCRIBED, YOU MAY NOT COMPLETE THE INSTALLATION IN THE TIME ALLOCATED. STEP 1: REGISTER FOR CELLULAR SERVICE Complete the Registration Form online at www.Telguard.com or fax the form to Telguard Customer Service prior to leaving for the job site. Telular requires this information to register and activate the unit. STEP 2: LOCATE UNIT AND MEASURE SIGNAL STRENGTH (RSSI) First, you will be confirming that Telguard has adequate cellular signal strength. Press the LED/RSSI Mode Toggle button one time, LEDs will now indicate signal strength. Minimum recommended is 3 (3 on solid) with multiple towers in range (LED 1 on solid). Press the LED/RSSI Mode Toggle button a second time to exit RSSI mode. STEP 3: CONFIGURE PANEL ALARMS FOR SOLE PATH CONNECTION Fire panels are typically provided with two Telco connections. Because the TG-7FS provides a single connection, the panel must be set up accordingly. The first method of installation is to configure the panel to disable the second Telco connection. If this is not an option due to panel limitations, it is possible to splice both TIP and RING connections from the panel into the single jack of the Telguard. The TG-7FS is capable of providing dial tone to both Telco connections. STEP 4: PROGRAM, ACTIVATE & TRANSMIT PANEL ALARMS OVER THE CELLULAR RADIO NETWORK Program the TG-7FS for Sole Path communication. You may do this by setting Memory Location 831 to a value of 3, using a butt-set. (See programming guide on reverse). LED 3 will be off when idle, if successful. Next, connect the alarm panel's digital dialer output to Telguard and verify that alarm signals can be reliably sent through Telguard over cellular to the central station digital receiver. A minimum of two alarm signals must be transmitted. (NOTE: THE FIRST ALARM WILL ACTIVATE THE UNIT AT THE TELULAR COMMUNICATION CENTER, IT WILL NOT GO TO THE CENTRAL STATION, ALL SIGNALS AFTER THE FIRST ARE SENT TO THE CENTRAL STATION) STEP 5: CONNECT SUPERVISORY TRIP OUTPUTS Next, you will wire Telguard's supervisory trip outputs to the alarm panel and then test. STEP 6: CONNECT TRIP INPUT (OPTIONAL) Optionally, you can wire the external relay input to the trip input lead and ground, and test. STEP 7: COMPLETE THE INSTALLATION Your last step will be to attach earth ground, and permanently mount the unit. The LED/RSSI mode will reset to normal after 10 minutes. Setup & Programming the Operating Parameters in the Telguard TG-7F5 When the Telguard is received from the factory and is powered up for the first time, it is immediately ready for activation, provided the default settings are what you want (note: registration form must be sent to Telular). The STC LED # 2 will flash to indicate any failure conditions. The Mode LED # 3 will be on and the STC 1 and STC 2 relays will be tripped. If changes are required to the default settings, the Telguard can be programmed using a line-mans butt-set connected to T & R Test Points or a POTS phone connected to the panel RJ-45 jack (black connector where the alarm panel is normally connected). TO PROGRAM THE Telguard TG-7FS Put the line-mans butt-set in talk mode or pick up the POTS phone. Dial "#', you will hear 2 beeps. Press #, * this will put the Telguard into a Master Access programming mode, 2 beeps. Enter changes required. The syntax for programming a specific memory location is as follows: MEMORY LOCATION (3-digits), will respond with 2 beeps, then VALUE, will respond with 2 beeps. Then press * you will hear 2 beeps then hang up. This saves the change and exits the programming mode. Mem Loc. Field Default Value Setting 831 Telco Primary/Cellular Backup Mode of operation 1 2 = cellular Primary/Telco Backup 3 = Cell Only 01 = 4x2 pulse, 40pps 2300 hz 02 = 4x2 pulse, 20pp5 2300 hz 03 = 4x2 pulse, lopps 1400 hz 04 = 3x1 pulse, 40pp5, 2300 hz 833 C/C Reporting Format 09 05 = 3x1 pulse, 20pp5, 2300 hz 06 = 3x1 pulse, lopps, 1400 hz 07 = Radionics lie or 111a2 08 = Contact ID 09 = Auto Format Detect 11 = S1A2 (300 Baud) 12 = DMP Enter the SUM TOTAL of the events that you wish to trip the STC relay by STC1 Trip Output 04 ADDING the corresponding values: 850 Reporting (LFC only) 00 = Not used 04 LFC 32 = DTF Normally Open 01 = AC Failure 08 = NSC 63 = ALL 02 = Low Battery 16 = RFC Enter the SUM TOTAL of the events that you wish to trip the STC relay by STC2 Trip Output 59 ADDING the corresponding values: 851 Reporting (all except LFC) 00 = Not Used 04 = LFC 32 = DTF Normally Closed 01 = AC Failure 08 = NSC 63 = ALL 02 = Low Battery 16 = RFC 1=30 seconds 4=10 minutes 7=45 minutes 852 STC Trip Delay for NSC 2 (60 sec) 2=60 seconds 5=20 minutes 8=60 minutes 3=3 minutes 6=30 minutes 9=24 hours 0 = terminate STC history display mode 858 STC History N/A 1 = start STC history display mode 2 = clear STC history 861 CFC Number of Events 0 (disabled) 0 = disabled 2 = 4 attempts 1 = 2 attempts 3 = 8 attempts 862 CFC Between Events 1(30 sec) 1 = 30 seconds 3 = 70 seconds 5 = 90 seconds 2 = 60 seconds 4 = 80 seconds 6 = 99 seconds 868 PPF Delay 0 (disabled) 0 = disabled, 1 = 10 seconds, 2=20 seconds, ... 15=150 seconds 872 AC Failure Delay 02 (2 hours) 0-24 hours 873 Trip Input Reporting 0 (no report) 0 = no report 1 = report trip 874 Trip Input Restoral Reporting 0 (no report) 0 = no report 1 = report restoral 875 Trip Input Swinger Function 0 (disabled) 0 = swinger function disabled 1 =swinger function enabled 899 Factory Default unit NOTE: SPECIAL LED INDICATIONS DURING ACTIVATION If the Telguard fails to confirm activation it will be displayed on the LEDS: System Status LEDs Activation Indications LEDS 1-5 FLASHING FAILED ACTIVATION - SIGNAL TOO WEAK LED #1 & LED #4 FLASHING ACTIVATION ERROR -CALL TECH SUPPORT LED #1 ON ACTIVATION SUCCESSFUL LED #1 Off NOT ACTIVATED NEED TO CONNECT PANEL AND TRIP ZONE On either a FAILED ACTIVATION or ACTIVATION ERROR, the unit MUST BE RESET BY PRESSING THE RSSI BUTTON TWICE. The activation message MUST BE RESENT or the TELGUARD will not transmit signals through the cellular network. Repeat step 4 above. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. CATEGORY: (7300-1402:0110) Page 1 of 1 (7300-- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES] LISTEE: (TELULAR CORP.3225 Cumberland Blvd, Suite 300, Atlanta, GA 30339 Contact: Raj Kosaraju (678) 264-2012 Fax (678) 264-2062 Email: rkosaraju@telular.com DESIGN: Models LV001 *TG7LVA01 *TG7LVF01 and TG-KIT(ital cellular communicator) Lsn) Models are digital cellular radio alarm transmission devices used to provide a primary (sole or with a back-up) or back-up transmission path using cellular for control communicators. Refer to listee's printed data sheet for additional detailed product description and operational considerations RATING: 120 Vac INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as digital cellular radio alarm transmission devices. Refer to listee's Installation Instruction Manual for details. NOTE: Burglary and other non-fire functions were not examined. *04072017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 (ipgExpJ (une3O,2018J Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division PS712 (i2V7Ah) 4.8 lmI t1t H 65 DISCHARGE CHARACTERISTICS AT 25 C(774 ) uuuuiuuuuui•uuuiiiiuu I ;;;-; U•lIflhIIUuiPIimi iuiIIiIUUUliiuiiiIi•u. uiuiiuumuuuirauuuuuiiii•u. uuuiiiuiuiuuuuiiii•u: UIIEiiII•UIIIIIUO 1 2 3 5 10 20 30 60 2 3 5 to 20 30 I rr H Discharge Time CHARGED me VOLUME _,,........____'- CHARGED VOLTAGE - 61 BM 2 00 B. 004 LOS - 20 0 0 CHARGING CURREN Chargeing Time (h) Cycle service life 200 200 600 BOB 1000 0200 Life (cycle) POER KINGDOM (Sealed Lead-Acid Batteries) Specifications Nominal Voltage 12V Rated Capacity 7Ah Dimensions Total Height 3.98 inches (101mm) Height 3.74 inches (95mm) Length 5.94 inches (151mm) Width 2.56 inches (65mm) Approximate Weight 4.52 lbs. (2.05kg) Characteristic Capacity 77°F(25°C) 20h rate 7.00Ah lOh rate 6.50Ah 5h rate 5.95Ah lh rate 4.20Ah 15 min rate 3.15Ah Internal Resistance Full Charged Battery 770F(250C) 25m Capacity Affected by Temperature (20h rate) 104°F(40°C) 102% 77°F(25°C) 100% 320F(0°C) 85% 50F(-150C) 65% Self-Discharge 68°F(200C) (Capacity after) 3 month storage 90% 6 month storage 80% 12 month storage 60% Max. Discharge Current_77°F(25°C) 105A(5s) Terminal TI J2 T2 Charge (Constant Voltage,250C) Cycle I 14.5-14.9V(-24mV/C) max. current: 2.1 A Float 13.6-13.8V(-18mV/°C) (Tnnstnt Current ffinrhnra ChrrteriNties (A F.V/TIME 5min lomin 15min 30min 60min 3h 5h 10h 20h 9.60V 27.0 18.0 14.0 8.40 4. 70 1. 73 1.15 0. 71 0.37 10.2V 25.7 17. 1 13.4 8.06 4. 55 1.70 1.13 0. 70 0 36 10.5V 24.2 16.1 12.7 7.66 4. 35 1. 65 1.10 0.68 0. 35 Constant Current Dincharf, Characteristics (Watt.25C F.V/TIME 5min 10min 15min 30min 60min 3h 5h 10h 20h 9.60V 301 203 160 94.2 54.4 20.6 13.8 8.52 4.43 10.2V 287 191 153 90.4 52. 7 20.2 13.6 8.40 4.. 33 10.5V 270 180 145 86.0 50.4 19.6 13.2 8.17 4.21 (E)POTTER The Symbol of Protection U.S. Pat. No. 3921989 Canadian Pat. No. 1009680 Other Patents Pending Potter Electric, Rd., 1990 GENERAL INFORMATION The Model VSR-F is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50mm thru 200mm). LPC approved sizes are 2" thru 8" (50mm thru 200mm). The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic re- tard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die- cast housing. The cover is held in place with two tamper resis- tant screws which require a special key for removal. A field in- stallable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch. ____(VSR-F)____ XVANE TYPE WATERFLOW1 LARM SWITCH WITH RETARD UL, ULCandCSFM Listed, FMandLPCBApproved,NYMEA Accepted, CE Marked Service Pressure: Up t0450 PSI (31 BAR) Minimum Flow Rate forAlarm: 10GPM(38LPM) Maximum Surge: 18 FPS (5,5 m/s) ContactRatings: Two sets of SPOT (Form C) 15.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2' conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 411P54 Rated Enclosure - use with appropriate conduit fitting. Temperature Range: 40'F/1 20'F, 4,5°C/49°C Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Sizes Available: Steel Pipe schedules 10 thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thru 200mm Note: For copper or plastic pipe use Model VSR-CF. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-130 Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090018 INSTALLATION: See Fig.2 These devices may be mounted on horizoctal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be in- stalled within 6" (15cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" (50mm) and 2 1i'2" (65mm) devices require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm ±2mm). All other sizes require a hole with a diameter of 2" ±1/8" (50mm ±2mm). Clean the inside pipe of all growth or other material for a dis- tance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft-lbs. (68 n-m) of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 www.pottersignal.com PRINTED IN USA MKT. #8800001 - REV W PAGE 1 OF 2 MFG. #5400761 - 7/02 FIG.4 To remove knockouts: Place screwdriver at edge of knock- outs, not in the center. SOPS. 76l-4 (E)POTTER The Symbol of Protection FIG. I I FIG. 2 VSR-F VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL ING DWG. 1923-3 CAUTION: An uninsulated section of a single conductor should not be looped around the termi- nal and serve as two sepa- rate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. OPTIONAL TAMPER SWITCH RETARD ADJUSTMENT; TO CHANGE TIME TURN KNOB (EITHER DIRECTION) FOR DESIRED TIME DELAY. USE THE MINIMUM AMOUNT OF RETARD NECESSARY TO PREVENT FALSE ALARMS. A "B" SETTING IS USUALLY ADEQUATE FOR THIS. FACTORY IS SET TO "B". TO INSTALL, DRILL HOLE AS INDICATED; PIPE SIZE HOLE SIZE 2 to 2 1/2" 1 1/4" +1/8" -1/16" (50mm to 65mm) (33mm ±2mm) 3" to 8" 2" ±1/8" (80mm to 200mm) 50mm ±2mm) Cover Tamper (with cover in place) DIRECTION WATERFLOW ~n . , I C NO NC (wHT) (RED) (elk) N DWG. #761-30 TIGHTEN NUTS ALTERNATELY TO AN EVENTUAL SOFT-LBS (68 n-m) OF TORQUE MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOW APPROX. RETARD SETTINGS (!N SECS,) o o F 25 B 20-40 C 35-55 0 50-70 E 60-90 DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME FIG. 3 TYPICAL ELECTRICAL CONNECTIONS NOTES: The Model VSR-F has two switches, one can be used to 2 SETS OF operate a central station, pro- NORMALLY N fl'CIS AATERFUON CLOSE ON ALARM zoos SOLO O1OS ON 995 POND, . PN€L prietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. A condition of LPC Approval of this product is that the electri- TNE NC MO NO UANO'CS OC 09POSIM IC OR NEUTRAL AC'-! OS 195 StArCH ME FON SELL cal entry must be sealed to AN ALARM C0*OT1OI r.c CONTACTS ARE NEGATIVE DC exclude moisture. NOON TIPS OCMS TI THE NORMAL CON3nDNL For supervised circuits see "Switch Terminal Connec- tions" drawing and caution note (Fig. 1). APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. TESTING The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F is not recommended or advisable. A minimum flow of 10 gpm (38 Lpm) is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. PRINTED IN USA MKT. #8800001 - REV W PAGE 2 OF 2 MFG. #5400761 - 7/02 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7770-0328:0001) Page 1 of 1 CATEGORY: (7770 -- VALVES/SWITCHES) LISTEE: (Potter Electric Sig)Co 1609 Park 370 Place, Hazelwood, 63042 United States Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999 Email: BillWpottersignal.com DESIGN: Vane and pressure type(ater flow alarm switches )isted below. Refer to listee's data sheet for detailed product description and operational considerations. Vane Types: VSR-CF VSR-D (VSR-F) VSR-SF VSR-FE-2 VS-SP VS-F VSR-SFG VSR-SFT VSG VSR VSR-S VSR-C VSR-ST VSR-SG Pressure Type: WFS-B WFSR-C WFSPD-B PS10 PS-10A PS-bOA WFSR-F PS100 INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL or FM label. APPROVAL: Listed as waterflow alarm switches for use with fire sprinkler systems. Vane models may be used in wet pipe systems; pressure models may be used in wet or dry systems. Model VSR-CF is for use on K, L or M copper pipe (2', 2-1/2", 3", 4") and listed CPVC pipe (2", 2-1/2", 3"). Model VSR-SF for use on 1", 1-1/4", 1-1/2" and *2 steel, copper or listed plastic pipe. Model VSG is for low flow rate. Model VSR-SFG and VSR-SFT are for use on 1", 1-1/4", 1-1/2" and *2 plastic pipe. Models VS-F, VSR-F, VSR-FE and VSR-FE-2 is for use on 2", 2-1/2", 3", 3-1/2", 4", 5", 6", 8" and 10" pipe. *Model VSR is for use on steel pipe sizes from 2" through 8". Vane type switches may be used outdoors when the outdoor temperature never falls below 40oF. Rev*5172007 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 is i g xplres une 30, 2018) Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division (E)POTTER The Symbol of Protection PCVS-1 Stock No. 1010107 PCVS-2 Stock No. 1010207 The Model PCVS is a weather proof and tamper resistant switch for monitoring the open position of fire sprinkler control valves of the post indicator, butterfly and other types. Depending on the model, one or two SPDT (Form C) contacts are provided which will operatewhen the valve position is altered from an open state. The unit mounts in a 1/2" NPT tapped hole in the post indicator or butterfly valve housing. The device is engaged by the indicating assembly of the post indicator or the operating mechanism of the butterfly valve, actuating switch(es) when the valve is fully open. The unit should be installed where it is accessible for service. The cover is held in place by two tamper resistant screws that require M , - ALVE) SU SWITë1i) UL and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked Dimensions: 4.75'L x 2.25W x 7.2H (stem extended) 12,1 cm Lx5,7cm Wx18,3cm H Weight: 1.35 lb. (0,61 kg.) Enclosure: Cover - Die-cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant finishes. Cover Tamper: Tamper Resistant Screws, Optional cover tamper kit available Mounting: 1/2" NPT Contact Rating: PCVS-1: One set of SPDT (Form C) PCVS-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: -40°F to +140°F (-40°C to 60°C) NEMA 4 and NEMA 6P Enclosure (1P67) when used with appropriate watertight conduit fittings. Indoor or Outdoor Use (Not for use in hazardous locations. See bulletin no. 5400694 PIVS-U-EX for hazardous locations.) Conduit Entrances: Two knockouts for 1/2" conduit provided. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-1 3D Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replace- ment or additional cover screws and hex keys are available. See ordering information. OPTIONAL COVER TAMPER SWITCH: A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information. TESTING: The PCVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). ORDERING INFORMATION MODEL DESCRIPTION STOCK NO. PCVS-1 Potter Control Valve Switch (single switch) 1013107 PCVS-2 Potter Control Valve Switch (double switch) 1010207 -- Cover Screw 5490344 -- Hex Key for Cover Screws and Installation Adjustments 5250062 PBK-S Pratt Butterfly Valve Kit - Up to 12" (300mm) 0090133 PBK-L Pratt Butterfly Valve Kit - 14" (355mm) and Up 0090132 PVK Pratt Valve Kit 1000060 -- Optional Cover Tamper Switch Kit 0090131 KBK Kennedy Butterfly Valve Kit 0090143 For pressure reducer type valve installation kits (if required) contact valve manufacturer. Potter Electric Signal Company 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833• www.pottersignal.com PRINTED IN USA MKT. #8820001 - REV T PAGE 1 OF 4 12/01 (E)POTTER The Symbol of Protection FIG. I DIMENSIONS FIG. 2 PCVS-1, -2 CONTROL VALVE SUPERVISORY SWITCH PARTS (12.1cm) (57cm) (9.2cm) I (50cm) I 3 00 I I (WHITE) (7.6cm) I I (KEG L (BLACK (13,2cm) 191.20 .75 I I (1,9cm) .85 1 ,q2.2cm ,9cm)FOR I oj 1.12 KNOCKOUTS (20.8cm)f ELECTRCk CONNECTIONS 1.20 85 (2 j NEW RORCrED AND RWAXHWAY SECTUN REMOVED (3,0 cm) 12 (0-30m) I2 I I 3,12 (4.0cm) (7,9cm) Ii NEW EXEWCED II U__________ Ii DWG. 1980-1 Li GROUND SCREW TRIP ROD LOCITNG SCREW CET HEAD SCREW LE NUT TYPICAL INSTALLATIONS ON POST INDICATOR VALVE HOUSINGS (SEE Refer to Fig. 2 for the location of parts described in the following instructions. NOTE: If the sprinkler system is in service the owner or authorized representative should be notified, before any work is done on the system, that the valve controlling the water supply to the system may be closed for periods of time during the installation and testing of this device, resulting in all or portions of the system being inoperative during these periods. If the system is not in service and valve is closed, be sure that opening the valve will not allow any unwanted water flow due to openings in the system, such as heads off, broken or incomplete piping, etc. Position the valve to fully open (OPEN" should appear in the window of the housing). Partially close the valve while observing the direction that the target assembly moves. Reopen the valve. If the valve housing is predrilled with a 1/2" NPT for installation of a monitoring switch, remove the 1/2' plug and fully open the valve. Make sure that "OPEN" appears in the window of the housing. GO TO STEP NO. 6. Remove the head and target assembly (consultation with valve manufac- turer is recommended). If the target assembly moved up as the valve was closed, measure the distance from the bottom of the head to the lower part of the target assembly that will contact the trip rod of the PCVS (see Fig. 3). This is usually a plate or bar on the target assembly, on a side adjacent to the "OPEN/SHUT" plates. Subtract 1/8" from the measurement. If the target moved down as the valve was closed, measure the distance from the bottom of the head to the upper portion of the target assembly that will contact the trip rod of the PCVS (see Fig. 4). Add 1/8" (3,2mm) to this measurement. Mark the housing at the proper location. Using a 23/32" (18,2mm) drill bit, drill and then tap a 1/2" NPT in the housing on the side that coincides with the portion of the target assembly that will engage the trip rod of the PCVS. Replace the head and target assembly. Loosen the socket head screw that holds the nipple in the PCVS and remove the nipple. Screw the locknut that is provided onto the nipple. Screw the nipple into the 1/2" NPT hole in the valve housing - hand tighten. Tighten the locknut against the valve housing to secure the nipple firmly in place. Insert a scale or probe thru the nipple to measure the distance from the FIGS. 3 THRU 6) open end of the nipple to the target assembly. Subtract 1/2" (12,5mm) from this measurement. NOTE: In some cases, it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. Using the special tool provided, loosen the two cover screws and remove the cover from the PCVS. Loosen the locking screw that holds the trip rod in place and adjust the rod length, from the end of the collar to the end of the rod, using the dimension determined in Step 9. Tighten the locking screw to hold the rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step 11 procedure. Partially close the valve (3 to 4 revolutions of the handle/hand wheel). Slide the PCVS unit as far as possible onto the nipple, observing which direction the rod will move when the valve is closed. Orient the device to actuate the switches when the valve is open. Tighten the socket head screw in the collar. Carefully open the valve to the fully open position. As the target moves to the open position it should engage the trip rod and actuate the switch(es). There should be a minimum overtravel of 1/2 revolution of the handle/hand wheel after the switch(es) actuate (a continuity meter connected to each set of contacts is one method that could be used to determine this). Slowly close the valve. The switch must operate during the first two revolutions of the handle/hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal condition. NOTE: Small adjustments of the target position may be necessary (consultation with valve manufacturer is recommended). Complete the required electrical wiring, connections and tests. The valve should be operated through the entire cycle of fully closed and fully open to determine the integrity of the PCVS installation and the signaling system. Check that all electrical and mechanical connections are secure. When the installation and testing are complete, return valve to its proper position. Alternative installation forother post indicatorvalve housing shown in Fig. 5 and 6. PRINTED IN USA MKT. #8820001 -REV T PAGE 2 OF 4 12/01 DWG 98O-I3 POTTER PCVSI, -2 CONTROL VALVE The Symbol of Protection SUPERVISORY SWITCH FIG. 3 FIG. 4 FIG. 5 FIG. 6 METAL PLATE REPLACES TARGET MOVESID OWN STEEL UP AS TAMPER TRIPPING BLOCK - VALVE SWITCH REPLACES OPE IS SHUT OPEN *F AMPERMARKER OPEN SWITCHUT (I ARGET GLASS OCKNUT AS SHUT FLEXIBLE OVES TARGET 11 3/8ALVE MARKER ASSEMBLY SHUT CONDUIT (28,9cm) HOOD MOVES TARGET DOWN AS VALVE MOVES IS SHUT UP AS VALVE IS SHUT DWG. #980-30 Notes: Subject to the approval of the "authority having jurisdiction" the alternate method of installation shown in Fig. 5 may be used. In this method, one of the glass windows of the housing is replaced with a 1/4" thick metal plate that is cut to fit in place of the glass and drilled and tapped to receive the 1/2" NPT pipe nipple. In some cases it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. If the target is stationary and a hood arrangement is used, such as is shown in Fig. 6, the hood must be drilled with a 23/32" drill and tapped with a 1/2" NPT. The center line of this hole should be 1/8" below the portion of target assembly that strikes the PCVS trip rod. The 11 3/8" dimension shown is for a Glow Valve. Flexible conduit must be used for this type of installation. TYPICAL INSTALLATION ON A BUTTERFLY VALVE (SEE FIGS. 9 AND 10) Refer to Fig. 2 for location of parts described in the following instructions: Bi. Remove the 1/2" NPT plug from the gear operator case. Loosen the setscrew that holds the nipple in the PCVS and remove the nipple. Screw the locknut that is provided onto the nipple. Screwthe nipple into the 1/2" NPT hole in the gearoperator - hand tighten. Tighten the locknut against the case, to secure the nipple firmly in place. Partially close the valve (3 or 4 revolutions of the hand wheel or crank). Using the special tool provided, loosen the two cover screws and remove the cover from the PCVS. Loosen the locking screw that holds the trip rod in place. Estimate trip rod length required and extend slightly past that point. Slide the PCVS unit as far as possible onto the nipple, observing which direction the rod will move when the valve is closed. Orient the device to actuate switches when valve is open. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step B7 procedure. B8. Remove device from nipple and withdraw trip rod 1/32" (0,80mm) (this dimension is important). Tighten the locking screw to hold the rod in place. Re-install the device on the nipple. Tighten the screw in the collar against the nipple. NOTE: In some cases it may be necessary to remove the gear box cover to ensure correct operation (consultation with the valve manufacturer is recommended). B9. Carefully open the valve to its full open position, as the boss on the gear hub moves to the open position it must engage the PCVS trip rod and actuate the switch(es). There should be a minimum overtravel or revolution of the crank or hand wheel after the switch(es) actuate (a continuity meter connected to each set of contacts is one method that could be used to determine this). NOTE: Slight adjustment of gear stops may be necessary to prevent overtravel of the trip rod (consultation with valve manufacture is recom- mended). BID. Carefully close the valve. The switch(es) must operate during the first two revolutions of the crank or hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal condition. Bli. Complete the required electrical wiring, connections and tests. The valve should be operated through the entire cycle of fully closed and fully open to determine the integrity of the PCVS installation and signaling system. Check that all electrical and mechanical connections are secure. B12. When the installation and testing are complete, return valve to its proper position. FIG. 7 BREAKING EXCESSIVE ROD LENGTH SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL FIG. 8 1- 1 00006 01,110 OWG, 1923-3 CAUTION: An uninsulated section of a single con- ductor should not be looped around the terminal and serve as two separate connections. The wire must be sev- ered, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. PRINTED IN USA MKT. #8820001 -REV T PAGE 3 OF 4 12/01 (E)POTTER The Symbol of Protect/on PCVS-1, -2 CONTROL VALVE SUPERVISORY SWITCH ITT GRINNELL/KENNEDY INDICATING BUTTERFLY VALVE FIG. 8 F-1 o VALVE PARTIALLY CLOSED VALVE OPEN DWG, #980-6 PBK - PRATT IBV BUTTERFLY VALVE KIT FIG. 12 MODEL PBK-L Stock No. 0090132 (MDT-45 Actuator) MODEL PBK-M Stock No. 0090146 (MDT-35 Actuator) MODEL PBK-S Stock No. 0090133 (MDT-25 Actuator) Pratt Butterfly Valve Kit as used to mount a PCVS on a Pratt Model IBV Valve. Kits contain: Bracket, nuts and instructions Note: This application is subject to the approval of the authority having jurisdiction. PRINTED IN USA DRESSER INDICATING BUTTERFLY VALVE FIG. 10 --- ._._._.__._i DWG. #980-7 (13mm) PVK - PRATT PIVA POST INDICATOR VALVE KIT (STOCK NO. 1000060) FIG. 13 MACHINE SCREW #8-32 I. L DWG. #91 Pratt Valve Kit as used to mount a PCVS on a Pratt Model PlVA Valve. Kit contains: Instructions, template, screw and nut. Note: This application is subject to the approval of the authority having jurisdiction. MKT. #8820001 -REVT 12/01 TYPICAL PRESSURE REDUCER TYPE VALVE INSTALLATION FIG. 11 COLLAR LOCKNUT NIPPLE Pcvs I/16(l.6mm) MIN_ GAP- DWG, #980-10 This figure shows the Model PCVS mounted on the valve yoke, with a bracket supplied by the valve manufacturer, to supervise a pressure reducer type valve. Note: This application is subject to the approval of the authority having jurisdiction. TYPICAL ELECTRICAL CONNECTIONS Please Note: This device should be wired in accordance with the applicable parts of the National Electrical Code, all state and local codes, applicable NFPA Standards and the requirements of the authority having jurisdiction. FIG. 14 LOCAL NO, TO POWER FOR CON. [IN N.C.INDICATING DEVICE INDICATING DEVICE O SUPERVISORY CIRCUIT !i_;-:. OF CONTROL PANEL END OF CON LINE I DWG. 1980-12 Contacts shown in normal (valve Open) condition. TYPICAL SWITCH ACTION OPEN VALVE POSITION CLOSED VALVE POSITION COM CON. sw #1 ~ffo_ It N.C. ~JN.C.' SW #2 SW #2 DWG. #980-I1 Switches Shown in Valve Open Position PAGE 4 OF 4 BRACKET AND LOCKNU1S SUPPLIED WITH P81< MOUNTING KIT CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7770-0328:0010) Page 1 cf 1 CATEGORY: (7770 -- VALVES/SWITCH ES) LISTEE:(Potter Electric Sigp)Co 1609 Park 370 Place, Hazelwood, 63042 United States Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999 Email: BillWpottersignal.com DESIGN: Supervisory_switches )listed below to monitor pressure, OS&Y, gate, globe/gate, Ply, tank temperature or water level valves. Refer to listee's data sheet for detailed product description and operational considerations. HLS-B WLS-W PS-120A OSYSU-2 PTS-B OSYSU-1 PIVS-B TTS-S WLS PTS-C RBVS *P515 WLS-S PS-40A OSYS-B PMS GVS TTS-W PCVS-2 PS4O PS12O *P525 INSTALLATION: In accordance with listee's printed instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model designation and FM or UL label. APPROVAL: Listed as sprinkler system supervisory switches. NOTE: Formerly 7738-0328:010 *Revision 09-07-2016 dc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 (JipgExpJ (June 30,2018) Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division SECTION2FIRE ALARM CABLE PART NUMBER AWG CONDUCTOR SHIELDED/ OVERALL] UNSHIELDED DIAMETER CONDUCTOR JACKET VOLTAGE WEIGHT MARKINGS TEMP PUT COLOR COLOR RATING (Ibs)IUnt UPS BLACK, WHITE, I WHITE I 300v 18,0 ADT 494469 I 60°C 500 RED, GREEN, LBS 121C 22 AWG REEL BROWN, BLUE, TYPE FPLP/ ORANGE, YELLOW, CMP VIOLET, GRAY, (UL) PINK, TAN BLACK, RED RED 16.0 ADT 493490 75°C 1000 LBS 2/08 AWG BOX TYPE FPLP/ CMP (UL) 8.0 ADT 493490 500 LBS 2/C18AWG BOX TYPE FPLP/ CMP (UL) LIGHT BLUE, 16.0 ADT 493493 60°C 1000 YELLOW LBS 2/C 18 AWG BOX TYPE FPLP/ CMP (UL) 8.0 ADT 493493 900 LBS 2/C18AWG BOX TYPE FPLP/ CMP (UL) AM 2.20 DON'T SEE IT? CALL 1-888-423-8947 ORDERS: PHONE 1-888-423-8947, FAX 847-797-3853 2.21 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. (7161-1295:0100) Page 1 f 1 CATEGORY: f7161 -- CABLES-FIRE PROTECTIVE SIGNALING LISTEE: (Comtran Cable)LLC.330A Turner Street, South Attleboro, MA 02703-7714 Contact: Bruce Lamoureux (508) 399-7004 Ext: 245 Fax (508) 399-7360 Email: Bruce.Lamoureux@comtrancorp.com DESIGN: Types FPL, FPLR andP Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes, NEC Article 760 and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, NEC rating and UL label. APPROVAL: Listed as power-limited fire protective signaling cable. 6-16-10 MA This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used tc verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2017 (June 30, 2018 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division &Lifcited Security /J7\ I 'O 11111 11111111111 0 II11 1111 II Fire Alarm Record of Completion 8806UE00 Date:/2 7Ci(tomer #: Job #: 0 Primary System #: U a 17.3 Secondary System Customer Name: ,Z , ,1 L #2,t Address (City/State/ZIP): A 3 C A Va'C6 Ra Representative of Protected Property (Name/Phone): S.4 t?y..r ,6"• 4 I 4. tj S 9 ' ? ._2_2 •7 Authority Having Jurisdiction: #: Location of As-Built Drawings: 1.. Location of Operation and Maintenance Manuals: Location of Inspection & Testing Reports:e__ Location of Control Panel: 4tec7'4, - ?rimary Telephone #: 7 ,,f' Secondary Telephone #: Does Tyco have a contract for testing and inspection in accordance with NFPA standard(s)? D Yes n No If no, who?: nspection Start Date: -- Inspection Frequency: Q Annually E Semiannually 0 Quarterly J Bimonthly 0 Monthly Weekly System Software Operating system (executive) software revision level(s): Site-specific software revision date: Revision completed by: (Name) (Company) (Date) 1. Type(s) of System or Service 4FPA 72, Chapter 8— Tyco Central Monitoring Center Means of transmitting signals from the premises to the central Station: (Check all that apply) Li Digital Alarm Communicator 0 McCulloh Li Multiplex 0 One-way Radio LI Two-way Radio LI Other -7,1,47 Means of transmission of alarms to the public fire service communications center: System locations: O NFPA 72, Chapter 6- Local If alarm is transmitted to location(s) off premises, list where received: .FPA 72, Chapter 8- Remote Station Telephone numbers of the organization receiving alarms: -. S'ô 065' 7 0 NFPA 72, Chapter 8- Proprietary Telephone numbers of the organization receiving alarm: O NFPA 72,Chapter9-Auxiliary Check type ofconnection: 0 Local Energy 0 Shunt 0 Parallel Telephone Telephone numbers of the organization receiving alarm: / - If alarms are retransmitted to a public fire service communications center or other, indicate name and telephone numbers of the organization receiving alarm: I- S Indicate how alarm is retransmitted: . Record of System Installation (Complete this section after installation is complete and wiring checked for opens, shorts, ground faults, and improper branching, but prior to conducting operational acceptance tests.) This system has been i stalled in accordance with the NFPA standards as shown below, was inspected by -- on/2/68/1/ 77 - , includes the devices shown in sections 4 & 6, and has been in service si ice This system has been installed in accordance with the standards as shown below: 'INFPA 72, Chapters '1 4 I"3 lj' j/ 9'6'EYc ).g 0 M 11 (Check all that apply) 70, NationalE/ectrica/Code, Article 760 1ufacturer's Instructions P'-`AHJ . t er ou Signed:------------- .. _._ . rganization: - - - .......................-- . .eprinted with permission from NFPA 77/@ 2002, National Fire Alarm Code® National , Copyright© 2002, Fire Protection Association, Quincy, MA 02169. This reprinted material is not :e complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. 20 12 Tyco Integrated Security. All rights reserved. (06/12) (p. '1 of 3) Integrated Security I Fire Alarm Record of Completion, cont. L 8806UE00 Record of System Operation Documentation in accordance with Inspection Testing Form, Figure 10.6.2.3, is attached All operational features and functions of this system were tested ,7,I date And found to be operating properly in accordance with the requirements of: iFPA 72, Chapters -'3 E j..6- '7 -8- -9 -10 Li 11 (Check all that apply) 70, National Electrical Code, Article 760 "1ufacturer's Instructions or Other ~urce: ,Lr L Signed. Lrganization: Signaling Line Circuits Quantity and class of signaling line circuits connected to system (see NFPA 72, Table 66.1): Quantity Style Class Alarm-Initiati Device and Circuits Quantity and class of signaling line circuits connected to system (see NFPA 72 Table 6.6. 1 ) : Quantity Style Class Manual Manual stations Non-coded Coded Transmitters Addressable Combination manual fire alarm and guard's tour coded stations Automatic Coverage: (Check all that apply) Li Complete Li Partial Li Selective Li Non-required Enter quantities and check if the devices are addressable. -. Smoke detectors -- Ion Photo Li Addressable Duct detectors Ion Photo Li Addressable Heat detectors FT RR FT/RR RC Li Addressable Sprinkler watedlow indicators: Non-code Coded - - Transmitters . Li Addressable The alarm verification feature is ,jab!ed Li Enabled ,changed from seconds to - - seconds. (i) Other (list): . Supervisory Signal-Initiating Devices and Circuits Guards Tour: 0 (a) Coded stations Li (b) Non-coded stations 0 (c) Compulsory guard's tour system comprised of transmitter stations and intermediate stations. Note: Combination devices are recorded under 5(b), Manual, and 6(a), Guard's Tour. (Check if provided.) Sprinkler System: Electric fire DumD: Valve supervisory switches Li (e) Fire pump power Li (b) Building temperature points Li (f) Fire pump running 10 (c) Site water temperature points Li (g) Phase reversal Li(d) Site water supply level points Li Other supervisory function(s) (specify): Electric-driven fire pump: Electric-driven generator: Li (h) Selector in auto position Li (k) Selector in auto position Li (i) Engine or control panel trouble Li (I) Control panel trouble Fire pump running Li (ml Transfer switches Li (n) Engine running printed with permission from NFPA 72 ® 2002, National Fire Alarm Code®, Copyright © 2002, National Fir e P r o t e c t i o n A s s o c i a t i o n , Q u i n c y , M A 0 2 1 6 9 T h i s r e p r i n t e d m a t e r i a l i s n o t z. complete and official position of the NFPA on the referenced subject, which is represented only by the standard i n i t s e n t i r e t y . 2012 Tyco Integrated Security. All rights reserved. (06/12) (p. 2 of 3)