City of Carlsbad
Sprinkler Permit
Permit No: AS040020
7400 CIRCULO
Status: PENDING
SEQUOIA
SPRINK Applied 2/12/2004
2236931800 Approved: 2/23/2004
0
Issued: 2/23/2004
Inspector:
THE OAKS RECEREATION CENTER OH AS PLAN CHECK &
INSPECTIONS
Owner:
INNOVATIVE FIRE PROTECTION
405 VERNON WAY
EL CAJON
(619) 593-8200
Fees($) Add'I Fees ($) Total($) Balance($)
506 0 506 0
1 /1
ASWow
HYDRAULIC DESIGN INFORMATION SHEET
Date: February 06, 2004 ~,. Name: THE OAKS RECREATION CENTER
Location: THE VILLAGE OF LA COSTA
CARLS BAD, CALIFORNIA
System No.: DESIGN AREA #1
Contract No.:
Building: ROOF/ABOVE CEILING PROTECTION
Contractor:
File Name: 0337-1.the
Construction: [E] Combustible D Noncombustible
Occupancy: ASSEMBLY, A-3 TYPE V-NR FULLY SPRINKLERED
AHJ: CARLSBAD FIRE DEPARTMENT
Drawing No.: FP-2
Calculated by: OD
Ceiling Height:
============== SYSTEM DESIGN
~ NFPA 13: ~ Light Hazard D Ordinary Hazard Group: □ Extra Hazard Group:
Figure: Curve:
D Other (Specify):
D Specific Rulling:
Made By: Date:
SLOPES ft
Area of Sprinkler Operation: 1500 sqft System Type: ~ Wet D Dry D Deluge D Pre-Action
Density:
Area per Sprinkler:
0.10 gpm/sqft
130 sqft
Hose Allowance Inside:
Hose Allowance Outside:
gpm
100 gpm
gpm
SPRINKLER or NOZZLE
Make: GLOBE
Size: 1/2 in
Model: GFR-UPRIGHT
K-factor: 5.6
Rack Sprinkler Allowance: Temperature Rating: 200 °F
CALCULATION SUMMARY
Flow Required: 376.70 gpm Pressure Required: 78.02 psi At: POC
"C" Factor Used: Overhead: 120 Underground: 150/140
WATER FLOW TEST PUMP DATA
WATER SUPPLY ===============
TANK OR RESERVOIR
Date: 01-27-2004 Rated Capacity: gpm Capacity:
Time: 8:20 AM At: psi Elevation:
Static: 100 psi Elevation: ft
Residual: 90 psi WELL
Flowing: 1430 gpm Proof Flow:
Elevation: 0-0 ft
Location: CIRCULO SEQUIOA AND LA COSTA AVENUE, CARLSBAD, CALIFORNIA
Source of Information: OLIVENHEIN MUNICIPAL WATER DISTRICT WO#430480
gals
ft
gpm
COMMODITY STORAGE =============
Commodity:
Storage Height
Storage Method: Solid Pile: %
Class:
Area:
Palletized:
Location:
Aisle Width:
% Rack: %
===============RACKSTORAGE==============
D Single Row
D Double Row
D Multiple Row
FLUE SPACING
Longitudinal:
D Conventional Pallet
D Slave Pallet
in Transverse:
Horizontal Barriers Provided:
D Automatic Storage
0 Solid Shelving
D Open
D Encapsulated
D Nonencapsulated
CLEARANCE FROM TOP OF STORAGE TO CEILING
in ft in
File: 03~7-1.the
WATER SUPPLY INFORMATION:
Static (psi):
Residual (psi):
@ (gpm):
Hose (gpm):
System req. (gpm):
@ (psi):
Supply available:
Safety margin:
90.00
81.00
1,430.00
100.00
376.70
78.02
89.24 psi
11 .22 psi
Maximum velocity in the system is:
Continuity at all nodes satisfied to:
Pipe Type Legend
B 1 = Blue Brute PVC Class 150
01 = Ductile Iron Class 51
1 O = Schedule 10
40 = Schedule 40
NOTES:
Hydraulic Summary
16.28 ft/sec in the pipe between Nodes: BOR and TOR
0.01 gpm
Fitting Type Legend
T = Tee (flow turned 90 degrees
GV = Gate valve
E = 90 degree standard elbow
Page 1 of 1
THE WATER FLOW TEST INFORMATION USED FOR THIS HYDRAULIC CALCULATION HAS BEEN REDUCED BY 10%
OF THE ACTUAL WATER FLOW TEST PROVIDED BY THE OLIVEN HEIN MUNICIPAL WATER DISTRICT
02/06/04 "THE" Sprinkler Program 2001
P:ile: 03.37-1. the Page 1 of 1
Node Pressure Flow Hose Elevation K-factor Area Density
psi gpm gpm feet gpm/(psi)½ sqft gpm/sqft
POC 78.02 376.70 -10.000 Source
BF1 72.61 0.00 0.000
BF2 57.54 0.00 0.000
DIP 56.00 0.00 0.000 I
BOR 55.34 0.00 0.500
TOR 48.63 0.00 11.170
1 32.36 0.00 11.170
2 20.06 0.00 11 .170
3 19.58 0.00 11 .170
4 18.73 0.00 11 .170
5 18.15 0.00 11 .170
6 18.09 0.00 11 .170
7 16.25 0.00 11 .500
8 15.74 0.00 11.500
9 16.26 0.00 11 .170
101 12.90 20.11 10.000 5.60 130.00 0.155
102 11.48 18.98 10.000 5.60 130.00 0.146
103 15.82 22.27 11 .500 5.60 130.00 0.171
104 15.33 21 .92 11.500 5.60 130.00 0.169
105 12.81 20.04 11.500 5.60 130.00 0.154
106 12.41 19.72 11 .500 5.60 130.00 0.152
107 11 .69 19.14 11 .500 5.60 130.00 0.147
108 11.32 18.84 11 .500 5.60 130.00 0.145
109 8.16 16.00 11 .500 5.60 130.00 0.123
110 7.90 15.74 11 .500 5.60 130.00 0.121
111 7.24 15.06 11 .500 5.60 130.00 0.116
112 7.00 14.82 11 .500 5.60 130.00 0.114
113 13.36 20.47 13.000 5.60 130.00 0.157
114 9.63 17.38 10.000 5.60 130.00 0.134
115 8.40 16.22 10.000 5.60 130.00 0.125
02/06/04 "THE" Sprinkler Program 2001
File: 0:r.37-1. the Page 1 of 1
Begin End Flow Diameter Type Fittings C-Value Length Eqv Length Ttl Length Frie Loss Ttl FL Elev Loss Velocity
Node Node gpm inches feet feet feet psi/ft psi psi ft/s
POC > BF1 276.70 4.270 81 TGVE 150 26.000 64.399 90.400 0.012 1.08 4.33 6.20
BF1 > BF2 276.70 4.280 01 4E 140 15.000 71 .665 86.670 0.013 15.07 0.00 6.17
The Flow Dependent Pressure Loss Device in the preceding pipe accounts for 13.91 psi of the total friction loss.
BF2 > DIP 276.70 4.270 81 E 150 109.000 20.125 129.120 0.012 1.54 0.00 6.20
DIP 1> BOR 276.70 4.280 01 E 140 15.000 17.916 32.920 0.013 0.44 0.22 6.17
BOR > TOR 276.70 2.635 10 120 11 .000 0.000 11 .000 0.1 89 2.08 4.62 16.28
TOR > 1 276.70 2.635 10 4E 120 53.000 32.948 85.950 0.189 16.27 0.00 16.28
> 2 276.70 2.635 10 120 65.000 0.000 65.000 0.189 12.30 0.00 16.28
2 > 3 276.70 2.635 10 120 2.500 0.000 2.500 0.189 0.47 0.00 16.28
3 > 4 237.61 2.635 10 120 6.000 0.000 6.000 0.143 0.86 0.00 13.98
4 > 5 145.10 2.635 10 120 10.000 0.000 10.000 0.057 0.57 0.00 8.54
5 > 6 54.07 2.635 10 120 6.500 0.000 6.500 0.009 0.06 0.00 3.18
4 > 7 92.51 1.610 40 T 120 0.500 8.000 8.500 0.275 2.33 0.14 14.58
5 > 8 91 .03 1.610 40 T 120 0.500 8.000 8.500 0.267 2.27 0.14 14.35
6 > 9 54.07 1.380 40 T 120 2.500 6.000 8.500 0.216 1.83 0.00 11 .60
3 > 101 39.09 1.049 40 T2E 120 7.000 9.000 16.000 0.449 7.19 -0.51 14.51
101 > 102 18.98 1.049 40 120 12.000 0.000 12.000 0.118 1.42 0.00 7.04
7 > 103 22.27 1.380 40 T 120 4.330 6.000 10.330 0.042 0.43 0.00 4.78
8 > 104 21 .92 1.380 40 T 120 4.330 6.000 10.330 0.041 0.42 0.00 4.70
7 > 105 70.24 1.380 40 T 120 3.830 6.000 9.830 0.350 3.44 0.00 15.07
8 > 106 69.11 1.380 40 T 120 3.830 6.000 9.830 0.339 3.34 0.00 14.82
105 > 107 50.20 1.380 40 120 6.000 0.000 6.000 0.188 1.13 0.00 10.77
106 > 108 49.39 1.380 40 120 6.000 0.000 6.000 0.182 1.09 0.00 10.59
107 > 109 31 .06 1.049 40 120 12.000 0.000 12.000 0.294 3.53 0.00 11 .53
108 > 110 30.55 1.049 40 120 12.000 0.000 12.000 0.285 3.42 0.00 11 .34
109 > 111 15.06 1.049 40 120 12.000 0.000 12.000 0.077 0.92 0.00 5.59
110 > 112 14.82 1.049 40 120 12.000 0.000 12.000 0.075 0.90 0.00 5.50
9 > 113 20.47 1.049 40 TE 120 8.500 7.000 15.500 0.136 2.11 0.79 7.60
9 > 114 33.60 1.049 40 3E 120 15.000 6.000 21 .000 0.340 7.14 -0.51 12.47
114 > 115 16.22 1.049 40 120 14.000 0.000 14.000 0.088 1.24 0.00 6.02
02/06/04 "THE" Sprinkler Program 2001
"'O C ro
E a,
0
a, ~ C -~
(./)
Yi >
>-0.. 0.. ::,
(./)
OJ ro ~
<(
Cf)
I ~r ®-I'--I'--N J ..
0 0 0 0 0 0 0 0 0) co I'--c.o l/)
(!sd) amssaJd
0 0 0 0 0 v ("') N
0 0 (D
0 0 v
0 0 N
0 0 0
0 0 co
0 0 c.o
0 0 v
0 0 N
0
E 0..
-9
~ 0
U::
Bulletin 131 Rev. H
Reliabl~ Model GFR
Model GFR Recessed
Quick Response
Sprinklers
Model GFR Sprinkler Types
Standard Upright
Standard Pendent
Horizontal Sidewall
HSW1 Deflector
Intermediate Level Upright
Intermediate Level Pendent
Conventional
Model GFR Recessed
Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
HSW1 Deflector
Approvals
1. Underwriters Laboratories, Inc. (UL)
2. Underwriters' Laboratories of Canada (ULC)
3. NYC BS&A No. 587-75-SA
6. MIL-S-901C andMIL-STD-167-1
7. NYC MEA 258-93-E
Upright Pendent
UL ListingCategory
Sprinklers, Au to matic & Open
Quick Response Spri1 kier
UL Guide Number
VNIV
Product Description
Reliable Models GFR and GFR Recessed s~ are
Quick Response fusible sol dertype au to rnatic sprin lders.
These sprinklers have demonstrated response times in
laboratory tests which are five times faster than standard
response sprinklers.
This quick response enables the Models GFR and
GFR Re cessed Sprin klers to ap ply wa ter to a fire much
faster than standard response sprinklers of the same
temperaturerating.
Application
Quick response sprinklers are used in fixed fire pro tec-
tion sys terns: Wet, Dry, De luge or Preaction. Care must
be exercised that the orifice saze, tern per a ture rating, de-
flee tor style and sprin kier spacing are in accordance with
the lat est published standards of the National Fire Proteo-
tion Association or the approving Authority Having Juris-
diction. Quick response sprinklers are intended for
standard area cover age and standard water densities as
specified in NFPA 13. Quick response sprinklers and
stan dard response sprin kJers should not be inter mixed.
Intermediate
Level Pen dent
Intermediate
Level Up right
SmallOrif1eeUpright
Conventional Horizontal Sidewall
HSW 1 De flee tor
Recessed
Horizontal Sidewall
HSW 1 De flee tor
Recessed Pendent
TheReliableAutomaticSprinklerCo., Inc. 525 North MacQuesten Parkway, Mount Vernon, NevvYork 10552
Model GFR Quick Response Lpright, Pen dent& Conventional Sprinklers
Upright Pendent Conventional Small Orifice Up right
In stal la tion Wrench: Model D Sprin kier Wrench
In stal la tion Data
Sorin klerTvoe
Standard-Upright(SSU) and Pen dent (SSP)
De flee tors Marked to Indicate Position
½" (15mm) Standard Ori flee with ½" N PT (R½) Thread
1/,6"(11mm) Small Ori flee with½" NPT (R½) Thread (11 mm)
¾" (10mm) Small Orifice with½" NPT (R½) Thread (10mm)
10mm Ori flee XLH with R ¾ Thread
1¼2"(20mm) LargeOrifieewith¾" NPT(R¾) Thread
Con ven tional-lnstall in Uo riaht or Pen dent Position
10mm Ori flee XLH with R ¾ Thread
15mmStandardOrifieewith½" NPT (R½) Thread
Norn inal KFactor
us Metric
5.6 00
4.2 00
2.8 40
4.2 00
8.0 115
4.2 00
5.6 00
Sorin kier Heiqht Approvals
2½"(73mm) 1,2,3,6,7
3X6" (81mm) 1,2,3,7
3¾'6" (81 mm) 1,2,3,7
73mm
21,(6" (77mm) 1,2,3,7
73mm ____________ ...
73mm -------------
Model G FR Quick Response Up right & Pen dent In termed i ate Level Sprin klers
,_,~,. 0/o. _____ .,.
{114..Jmm}
u,m,ut
sp,thg
Upright
n, MAalmMtd .. .,.,,,.,,,
:1-7/18.
{87..Jmm}
Installation Wrench: Model D Sprin kier Wrench
lnstallationD ata
Sorin klerTvoe
Standard Up right (SSU) and Pen dent (SS P)
De flee tors Marked to Indicate Po si lion
½"(15mm)StandardOrificewith½"NPT (RY2) Thread
1½z''(20mm) LargeOrificewith¾" NPT(R¾) Thread
Norn i nal K Factor
us Metric
5.6 ID
8.0 115
NOTE -The pro tee tive shield must be as sem bled in the field per the assembly drawings.
2.
Pendent
Sorin kier Heiaht Aoorovals
2½" (73mm) 1,2,3,7
217i'6" (77mm) 1,2,3,7
Sprinkler
Identification
Number(SIN) ssu SSP
R3125 R3115
R3213 R3113
R3121 R3111
R3124 R3114
R3127 R3117
R3174
R3175
Sprinkler
Identification
Number <SIN) ssu SSP
R3195 R3115
R3197 R3117
Model GFR Quick Response Horizontal SidewallSprinkler
Deflector. HSW1
Installation Wrench:
Model D Sprin kier Wrench
Installation Data
NominalK Approval Organization
Factor and Tvoe of Ao oroval
Nominal S~rinkler Light Ordinary Orifice Thread Size us Metric eight Hazard Hazard
½"(15mm) ½"NPT (R½) 5.6 80 3Y1&" (84mm) 1,2,3,7 1,2,3,7
¼" (11mm) ½" NPT (R½) 4.2 60 31." {84mm) 1,2,3,7 -
¾" (1Cmn) ½" NPT (R½) 2.8 41 3Y." (84mm) 1,2,3,7 -
1¼"(20rm) ~"(84mm) 1,2,3,7 -¾" NPT (RY2) 8.2 119
" Identified by pintJe ex tending above de flee tor.
Model GFR Quick Response Recessed PendentSprinkl ers
Installation Wrench:
Model GFR1 Sprin kier Wrench
Installation Data
Sprin kier Type
Yi' (15mm) Standard Orifice
llllith Yi' f\Pf (R½) llYead
NominalK
Factor
US Metric
5.6 80
%" (11mm)SmalI0rificewith 4.2
Yi' NPT (R½) llYead
½"(10mm)Small0rificewith 2.8
Yi' NPT (R½) llYead
60
40
60 1CmnOrificeXLH W(h R,Ya
llYead
1½z" {20ml) ~ge()rjfice
vwfl 1/.c" NPT (R¾) llYead
4.2
8.0 115
Sprinkler
Height
l7/4 (73mm)
3¼ (81mm)
3¼ (81mm)
(73mm)
2'~6 {75mm)
Approvats0
1,2,3,7
1,2,3,7
1,2,3,7
1,2,3,7
Sprinkler
Identification
Num ber(SIN)
R3115
R3113
R3111
R3174
R3117
111 Refer to escutcheon data table for specific escutcheon approvals and dimensions.
Sprinkler
!dent.
Number (SIN)
R3135
R3133
R3131
R3137
ar"~ 7(~ "'lrt -7 L , , I ~-!:::--1-1' 1-----~
......-"'
Model GFR Quick Response Recessed Horizontal SidewallSprinklers
Deflector: HSW1
Installation Wrench:
Model GFR1 Sprin kier Wrench
Installation Data
Approval
NominalK Organization"' Sprinkler Thread Factor Tvoe of Ao oroval Identification
Nominal Size Sprinkler Light Ordinary Number
Orifice NPT us Metric Heiaht Hazard Hazard lSIN)
½" (15mm) ½'1R½) 5.6 81.0 3}{,"(84mm) 1,2,3,7 1,2,3,7 R3135
~"(11mm) Yz'1R½) 4.2 61.0 J,X," (84mm) 1,2,3,7 -R3133
½' (10mm) Y2'1RY2) 2.8 40.6 3}{," (84mm) 1,2,3,7 -R3131
1¼2" (20mm) ¾'1R½) 8.0 118.2 3}{a"(84mm) 1,2,3,7 -R3137
111 Re fer to escutcheon data table forspe cific escutcheon approvals and dimensions.
3.
-Model GFR& GFR RecessedQuickResponseSprinklers
Installation
Quick response sprinklers are in tended fer standard area
coverage and standard water densties as specified in
NFPA-13. Quick~~ and standard re-
sponse sprinklers should not be inter rrixed.
The Mcx:tel GFRRe cessed Quick Response Sprin kleris to
be in staled as shown. The Model F1 or F2 Es rutch eons i-
lustrated are the only recessed esa.tcheons to be used
YJitt1 the Model GFRPen dentorHcrizontal Sidewal Spril-
klers. The use of any other recessed es ruch eon will void
al approvals as a quick response sprin kier and negate an·
warranties.
When installing Model GFR ~, use the Model D
Sprinkler Wrench and when instar11g Model GFR Re-
cessed Sprinklers, use the Model GFR1 SJ)lin kier Wrench.
Any other type of wrench may cause sprin kier dam age.
Maintenance
The Models GFR and GFRRe cessed Sprinklers should be
inspected quartet1y and the sprin kier system maintained in
accordance with NFPA 25. Do not clean the sprinklers
with soap and water, am mo nia or any other deaning flu ids.
Re move any dust using a soft brush or gen tie vac u Lm ing.
Re move any sprin kier which has been painted {other than
factory applied) or dam aged in any way. A stock of spare
sprinklers should be maintained to alow quick re place-
ment of dam aged or operated sprinklers. Prior to in stal la-
tion, sprinklers should be main ta1ned in the original cartons
and packaging un tl1 used. This minimizes the potential for
damageresultanginimproperoperationornon-operation.
Ordering Information:
Sfecify . Spnn kier model
2. Sprin kier type
3. Orifice size
4. Temperaturerating
5. Sprin kier fin ish ·
6. Escutcheon type
7. Escutcheon finish {whereapplica ble)
Note:
'IJhen Recessed Model G FR/F1 er F2 are ordered, sprin kier
and es rutch eon are packaged separately.
Sprinkler Types
Standard Uprigt
Standard Pendent
SideYJall
-Hai zontal HSW1 De flee ta
Coovermnal
Recessed
-Pendent
-Hai zontal Soewal HSW 1 De flee ta
lrtmneciafe Lewi
-Uprigtt
-Pmcht
Finishes <1><2>
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Black Plated Britt Brass Ch ome Plated
Satin Chrome Satin Chrome
(11 Other finishes and col ors are avail able, con suit factory for de tais
(21 All sprin klers have black painted sol der links
Temperature Ratings
Sprinkler Maxi mum Ambient
Classification Rating Temperature
OF oc "F oc
165 74 100 38 Ordinary 212 100 150 66
Escutcheon Data
Escutcheon Face of Fitting
Model Approvals Adjustment To Ceil ing or
Wall Dimension
F1 1,2,3 ¾" (19mm) ¾" -1}(' (5mm-24mm)
F2 1,2,3, ·1,,, (13mm) }{:" -11):" (Smm-1 Bmm)
The eqlip mentpreserted in this bU le tin istobe in staled in accordance with the lat estpertinertStandardsofthe National Fr-eProtection Association. Factory Mutual ResearchCorporaaon,or
othersim i larorga ni za lions and also with the provisions of govern men talcodesoror dnanceswheneverapplica ble.
Prod uctsmanufacturedanddistributed by Re Ii ablehavebeenprotectlng life and propertjorover 80 years, and are In stalled and serviced by the most higtiyqual i lied and rep u ta blesprinlder
contractors located through Oltthe Urited States, Canada and foreign countries.
Manufactu"edbv ~
• The Re Ii able Au to matic Sprin kier Co., Inc. W RecycJecJ Re I I-ab I .,, 1:::1 m~ t':. <faxtices Rellisilnlnesildcae'4'daleda::dala '-(914) 668-3470 Corporate Of fices
www.reiablesprinkJer.com Internet Ad aess EG. Prned in U.SA 7/02 P/N9999970024