HomeMy WebLinkAbout2576 WELLSPRING ST; ; CBR2022-1135; PermitPrint Date: 12/12/2022 Permit No: CBR2022-1135
Building Permit Finaled
Residential Permit
Job Address:
Permit Type:
Parcel #:
Valuation:
Occupancy Group:
2576 WELLSPRING ST, CARLSBAD, CA 92010-5604
BLDG-Residential
2081902700
$20,000.00
Work Class:
Lot #:
Project #:
Cogen
Status:
Applied:
Issued:
04/04/2022
04/22/2022
Finaled Close Out:12/12/2022
#of Dwelling Units:
Track #:
Plan #:
Closed - Finaled
Plan Check #:
Orig. Plan Check #:Bathrooms:
Final Inspection:05/26/2022Bedrooms:Construction Type:
Occupant Load:
Code Edition:
Sprinkled:
INSPECTOR:Alvarado, Tony
9.62KW RESIDENTIAL ROOF MOUNTED SOLAR PV; 26 MODULES (E-REVIEW)Description:
Project Title:
Applicant: SOLAR OPTIMUM INC
ARNOU AGHAMALIAN
614 W COLORADO ST
GLENDALE, CA 91204-1104(818) 804-3122
Contractor: SOLAR OPTIMUM INC
614 W COLORADO ST
GLENDALE, CA 91204-1104
(818) 804-3122
AMOUNTFEE
SB1473 – GREEN BUILDING STATE STANDARDS FEE $1.00
SOLAR–RESIDENTIAL: per kW $268.00
STRONG MOTION – RESIDENTIAL (SMIP)$2.60
Total Fees:$271.60 Total Payments To Date:$271.60 Balance Due:$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad CA 92008-7314 ï 442-339-2719 ï 760-602-8560 f ï www.carlsbadca.gov
Building Division Page 1 of 1
{"Cityof
Carlsbad
X
XXX
2576 Wellspring St. Carlsbad, 92010
9.62 KW residential roof mounted solar PV; 26 Panasonic 370W modules & 26 Enphase microinverters
9.62 26
Nataly Noriega Andrew Inocelda
614 W Colorado St 2576 Wellspring St.
Glendale CA 91204 Carlsbad CA 92010
818-804-3122
permitting@solaroptimum.com
Solar Optimum
614 W Colorado St.
Glendale CA 91204
818-804-3122
permitting@solaroptimum.com
972228 C10
BLOS005245-04-2019
04/04/2022Nataly Noriega
( City of
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check ________ _
Est. Value
PC Deposit
Date
Job Address ___________________ Unit:. _____ .APN: ___________ _
CT/Project #: __________________ Lot #:. ____ Year Built: _________ _
BRIEF DESCRIPTION OF WORK:
□ New SF: Living SF, _____ Deck SF, ___ Patio SF, ____ Garage SF __ _
Is this to create an Accessory Dwelling Unit? O Y O N New Fireplace? O YO N, if yes how many? ___ _
D Remodel: _____ SF of affected area Is the area a conversion or change of use? 0 YO N
□ Pool/Spa:. ____ SF Additional Gas or Electrical Features? ____________ _
□Solar: ___ KW, ___ Modules, Mounted:0Roof O Ground, Tilt: 0 YO N, RMA: 0 YO N,
Battery:O YQ) N, Panel Upgrade: O y fil>N
Other:
PRIMARY APPLICANT PROPERTY OWNER
Name: Name:
Address: Address:
City: State: Zip: City: State: Zip:
Phone: Phone:
Email: Email:
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: Business Name:
Address: Address:
City: State: Zip: City: State: Zip:
Phone: Phone:
Email: Email:
Architect State License: CSLB License #: Class:
Carlsbad Business License # (Required):
APPLICANT CERTIFICATION: I certify that I have read the application and state that the above information is correct and that the information of the plans is accurate. I
agree ta comply with all City ordinances and State laws relating to building construction.
NAME (PRINT): ________ _ SIGN_: _________ DATE: ______ _
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Email: Building@carlsbadca.gov
REV. 04/22
X
STATE COMPENSATION INSURANCE FUND
9013440 05/18/2022
Nataly Noriega 04/04/2022
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON SIGNING
THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO PERMIT ISSUANCE.
{OPTION A): LICENSED CONTRACTOR DECLARATION:
lherebyaffirmunderpenaltyofperjurythatlamlicensedunderprovisionsofChapter9(commencingwithSection7000)ofDivision3
of the Business and Professions Code, and my license is inf ul l force and effect. I also affirm under penalty of perjury one of the
following declarations (CHOOSE ONE}:
D I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. PolicyNo. __________________________________________ _
-OR-
D I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name:------------------------•
Policy No. _____________________________ Expiration Date: _________________ ,
-OR-
D Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _______________________ .Lender's Address: ______________________ _
CONTRACTOR CERTIFICATION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and
utilities/utility easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detail within these plans inconsistent with the site plan are
not approved for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show
the correct dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utilities. The existing and proposed
use of each building as stated is true and correct; all easements and other encumbrances to development have been accurately shown and labeled as well as all on-site grading/site preparation.
All improvements existing on the property were completed in accordance with all regulations in existence at the time of their construction, unless otherwise noted.
NAME (PRINT): __________ SIGNATURE: __________ DATE: ______ _
Note: If the person signing above is an authorized agent for the contra t tter of authorization on contractor letterhead.
-OR-
{OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-
D I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-D I am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND,
D FORM B-61 "Owner Builder Acknowledgement and Verification Form" is required for any permit issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors./ understand that a copy of the applicable law, Section 7044 of the Business and Professions Code, is available upon request when this application is
submitted or at the following Web site: http:Ilwww.leginfo.ca.gov/ calaw.html.
OWNER CERTIFICATION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and utilities/utility
easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detail within these plans inconsistent with the site plan are not approved
for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show the correct
dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utilities. The existing and proposed use of each
building as stated is true and correct; all easements and other encumbrances to development have been accurately shown and labeled as well as all on-site grading/site preparation. All
improvements existing on the property were completed in accordance with all regulations in existence at the time of their construction, unless otherwise noted.
NAME (PRINT): __________ SIGN: _________ DATE: _____ _
Note: If the erson si nin above is an authorized a ent for the ro e owner include form B-62 si owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Email: Building@carlsbadca.gov
2
REV. 04/22
Building Permit Inspection History Finaled
PERMIT INSPECTION HISTORY for (CBR2022-1135)
BLDG-Residential 04/04/2022Application Date:Permit Type:Owner:
Cogen 04/22/2022Work Class:Issue Date:Subdivision:
11/22/2022Expiration Date:Status:
IVR Number: 39758
Closed - Finaled 2576 WELLSPRING ST
CARLSBAD, CA 92010-5604
Address:
Scheduled
Date
Inspection Type Inspection No. Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
05/26/2022 05/26/2022 BLDG-35 Solar Panel 183614-2022 Passed Tony Alvarado Complete
BLDG-Electric Meter
Release
183735-2022 Passed Tony Alvarado Complete
BLDG-Final Inspection 183613-2022 Passed Tony Alvarado Complete
COMMENTS PassedChecklist Item
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
Thursday, May 26, 2022 Page 1 of 1
{cityof
Carlsbad
Solar Optimum, Inc., 614 W. Colorado St., Glendale, CA 91204
Tel: (818)745-1475
STRUCTURAL
CALCULATIONS
for
SOLAR ELECTRIC SYSTEM FOR
ANDREW INOCELDA RESIDENCE
AT
2576 WELLSPRING STREET, CARLSBAD, CA 92010
SOLAR
OPTIMUM
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
INPUT DATA
Exposure category (B, C or D)C
Importance factor, pg 77, (0.87, 1.0 or 1.15)I = 1.00 Category II
Basic wind speed (IBC Tab 1609.3.1V3S)V = 110 mph
Topographic factor (Sec.6.5.7.2, pg 26 & 45)Kzt =1 Flat
Building height to eave he =18 ft
Building height to ridge hr =25 ft
Building length L = 81.29 ft
Building width B = 42.15 ft
Effective area of components A = 11 ft2
DESIGN SUMMARY
Max horizontal force normal to building length, L, face = 31.12 kips
Max horizontal force normal to building length, B, face = 16.39 kips
Max total horizontal torsional load = 303.68 ft-kips
Max total upward force = 64.94 kips
ANALYSIS
Velocity pressure
qh = 0.00256 Kh Kzt Kd V2 I =24.01 psf
where:qh = velocity pressure at mean roof height, h. (Eq. 6-15, page 27)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79)= 0.91
Kd = wind directionality factor. (Tab. 6-4, for building, page 80)= 0.85
h = mean roof height = 21.50 ft
< 60 ft, [Satisfactory]
< Min (L, B), [Satisfactory]
Design pressures for MWFRS
p = qh [(G Cpf )-(G Cpi )]
where: p = pressure in appropriate zone. (Eq. 6-18, page 28).pmin =10 psf (Sec. 6.1.4.1 & 6.1.4.2)
G Cp f = product of gust effect factor and external pressure coefficient, see table below. (Fig. 6-10, page 53 & 54)
G Cp i = product of gust effect factor and internal pressure coefficient.(Fig. 6-5, Enclosed Building, page 47)
= 0.18 or -0.18
a = width of edge strips, Fig 6-10, note 9, page 54, MAX[ MIN(0.1B, 0.4h), 0.04B,3] =4.22 ft
Net Pressures (psf), Basic Load Cases Net Pressures (psf), Torsional Load Cases
18.37 0.00 18.37
(+GCp i ) (-GCp i )(+GCp i ) (-GCp i )(+GCp i ) (-GCp i )
1 0.52 8.07 16.71 0.40 5.28 13.93 1T 0.52 2.02 4.18
2 -0.69 -20.89 -12.25 -0.69 -20.89 -12.25 2T -0.69 -5.22 -3.06
3 -0.47 -15.56 -6.92 -0.37 -13.21 -4.56 3T -0.47 -3.89 -1.73
4 -0.41 -14.28 -5.64 -0.29 -11.29 -2.64 4T -0.41 -3.57 -1.41
1E 0.78 14.39 23.04 0.61 10.33 18.97 0.00
2E -1.07 -30.02 -21.37 -1.07 -30.02 -21.37
3E -0.67 -20.47 -11.83 -0.53 -17.05 -8.40 (+GCp i ) (-GCp i )
4E -0.62 -19.14 -10.50 -0.43 -14.65 -6.00 1T 0.40 1.32 3.48
5 -0.45 -15.13 -6.48 -0.45 -15.13 -6.48 2T -0.69 -5.22 -3.06
6 -0.45 -15.13 -6.48 -0.45 -15.13 -6.48 3T -0.37 -3.30 -1.14
4T -0.29 -2.82 -0.66
Roof angle =
G Cp f
Net Pressure with Net Pressure withG Cp f
Net Pressure withG Cp f
INOCELDA RES
Surface
Roof angle =
Surface
Roof angle =
G Cp f
Net Pressure with
Surface
Roof angle =
Wind Analysis for Low-rise Building, Based on ASCE 7-16 / IBC 2018 / CBC 2019
Transverse Direction
3 2 ZONE 2/3 BOUNDARY
Longitudinal Direction
Basic Load Cases
Transverse Direction Longitudinal Direction
Torsional Load Cases
INOCELDA RES
2576 WELLSPRING STREET,
CARLSBAD, CA 92010
LOAD CRITERIA
WEIGHT OF MODULE 41.88 LB
MODULE LENGTH 5.44 FT
MODULE WIDTH 3.25 FT
MODULE AREA 17.68 FT^2
UNIT WT OF MODULE 2.37 PSF
AVG RACKING WT 0.3 PSF
TOTAL AVG WT (MODULE+RACKING)2.67 PSF
NO OF MODULE 26
CONNECTION POINT TRIB LENGTH 2.75 FT
CONNECTION POINT TRIB WIDTH 6 FT MAX. SPACING
CONN POINT TRIB. AREA 16.5 FT^2
LOAD PER CONN PT LOAD 44 LB
ROOF SLOPE 22.00 DEGREE
SLIING FORCE 16.49 LB LOAD*SIN(ROOF SLOPE )
LOAD ON EXISTING ROOF
1) ROOFING 10.00 PSF
2) 5/8" PLYWOOD 1.8 PSF
3) ROOF RAFTER 3.1 PSF
4) INSULATION 1.5 PSF
5) MISC 1.5 PSF
TOTAL DL 17.90 PSF
ROOF AREA 3426 SF
TOTAL ROOF WT 61.33 KIP
WALL WT 2.96 KIP
TOTAL BUILDING DL 64.29 KIP
EACH MODULE AREA 17.68
TOTAL AREA OF MODULE 459.68 SF
TOTAL MODULE WT 2.76 KIP
ADDITIONAL DL ADDED TO EXISTING BUILDING 4.29 %
LATERAL LOAD ANALYSIS COMMENTS
SINCE TOTAL ADDED DL TO THE BUILDING IS LESS THAN 10%, PER CBC 2019 EXISTING LATERAL
RESISTING ELEMENTS WILL NOT BE AFFECTED
VERTICAL LOAD ANALYSIS COMMENTS
PER CBC SECTION 1607.9.1.1 EXCEPTION 2, THE ROOF LL CAN BE PERMITTED TO BE
RATIONALLY REDUCED TO 10 PSF AT THE AREA OCCUPIED BY THE SOLAR MODULES
THEREFORE, DESIGN LOAD BY ADDING SOLAR MODULE OF 2.75 PSF IS LESS THAN WITHOUT
MODULES AND HENCE EXISTING FRAMING WILL THEREFORE BE OK.
INOCELDA RES
2576 WELLSPRING STREET,
CARLSBAD, CA 92010
CONNECTION DESIGN
VELOCITY PRESSURE, qh 24.01 PSF (SEE WIND LOAD CALC)
A) LATERAL FORCE Fh FOR ROOFTOP STRUCTURES (FOR ONE CONN POINT)
(ONE SCREW PER CONN POINT)
HORIZONTAL WIND FORCE, Fh = qh * Gcr * Af ASCE 7-16, Eq. 29.4.4
WIDTH OF BUILDING, B 42.15 FT
MEAN HEIGHT OF BLDG, H 25 FT
CONNECTION POINT TRIB LENGTH, l 6 FT MAX. SPACING
CONNECTION POINT PROJECTED HEIGHT, h1.03 FT [2.75' SIN(ROOF SLOPE)]
VERTICAL PROJECTED AREA, Af 6.18 FT^2
Gcr 1.9 IF(B*H*0.1>Af,1.9)ASCE 7-16, Eq. 29.4.4
WIND LATERAL FORCE, Fh 281.9 LB
SLIDING FORCE 16.49
DESIGN LATERAL FORCE 298.41
B) VERTICAL FORCE Fv FOR ROOFTOP STRUCTURES ( (FOR ONE CONN POINT)
VERTICAL WIND FORCE, Fv = qh * Gcr * Ar ASCE 7-16, Eq. 29.4.4
WIDTH OF BUILDING, B 42.15 FT
LENGTH OF BLDG, L 81.29 FT
CONNECTION POINT TRIB LENGTH, l 6 FT
CONNECTION POINT TRIB WIDTH, w 2.55 FT [2.75' COS(ROOF SLOPE)]
HORIZONTAL PROJECTED AREA, Ar 15.30 FT^2
Gcr 1.4 IF(B*L*0.1>Ar,1.5)ASCE 7-16, Eq. 29.4.4
WIND VERTICAL FORCE, Fv 514.3 LB
DESIGN WITHDRAWL FORCE 514.3
INOCELDA RES
2576 WELLSPRING STREET,
CARLSBAD, CA 92010
CONNECTION DESIGN
DESIGN LATERAL FORCE 298.414
USE LAG SCREW 5/16"INCH
CAPACITY PER ONE SCREW, ZII 320 LB (NDS 2018 REFERENCE DESIGN VALUE, SEE ATTACHED)
DESIGN CAPACITY, ZII'425.6 LB
DESIGN IS GOOD
DESIGN WITHDRAWL FORCE 514.26
USE LAG SCREW 5/16"INCH
WITHDRAWL CAPACITY 227 LB (NDS 2018 REFERENCE DESIGN VALUE, SEE ATTACHED)
DESIGN WITHDRAWL CAPACITY 754.775 LB
DESIGN IS GOOD
COMBINED WIND SHEAR/UPLIFT 0.46 0.492 0.96 < 1.0 DESIGN IS GOOD
(UPLIFT)(SHEAR)
USE 5/16" DIA X 2 1/2" (EMBEDMENT) LAG SCREW PER CONNECTION POINT
Table 9.2A Lag Screw Withdrawal Design Values (W)1
Tabulated withdrawal design values (W) are in pounds per inch of thread penetration into side grain 0 Length of thread pene1ration in mam meml:ier shall not include the length of the tapered.tip (see Ap
·Specific
Gravity
G 1/4" 5/16"
Lag Screw Unthreaded Shank Diameter, D2
3/8" 7/16" 1/2" 5/8" 3/4"
0.55 260 307 . 352 395 437 516 592
7/8"
664
·r;,;;:}~iJ1.s,o:E~U'. <~::22s;i ;: .. 266. /,,. 30$.:·.. ,;;: 341'. 378:'i . · ~· 44.T sa ... :_.:·57.0;
0.45 192 227 260 292 323 382 438 492
:~·,1i:!t:}:6Ao1J~:r: :t:f6ifit y_:: i9.o..?: · :: · ·21i'.'···· ;~,·24s-~1 • ··':· 2rrt .: '"1•~'320< )/,) .)m-~·.-,
0.35 132 156 179 200 222 262 300 337
1 Tabulated withdrawal design values (W) for lag screw connections shall be multiplied by all applicable adjustment factors (s~ .
Table 7.3.1).
2 Interpolation is permitted.
Table 9.3A Lag Screw Design Values (Z) for Single Shear (two member
with both members of identical species
Side Lag
Member Screw
Thickness Diameter G=0.55 G=0.50 G=0.45 G=0.40
t.
inches
1-1/2
2-1/2
D ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
inches lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs.
1/4 230 180 1'80 170 220 170 170 160 210 160 160 150 200 150 150
{\5/lfri~, :f3fili'!f'2jo\.r"2s6'~·.23If :,i3i0'~$fo-·:::"f40·\.;,220, ,~.s:fi?T-2:io<· '22<fY200 i .. 2W·T201F'I\:2 .
"3/8 ~--· ·.-.420 . :ioo ,, 300" 280 .. 400 ... 290. '290 .. 260 . Jso"' 270 '210 ., 240 .360 , :zso'•" 250
';:'ii,f6 r: .:;srw~';,~Qit:5100:1; ~79' :_ 550f'i)~O. ':'-. ~80 :'. }40, .. 520'.,':350: .. ,,.350' ·:. 310 : .. 490'.' 33&:;:s:W:;
1/2 750 520 520 460 710 480 480 430 680 440 450 400 640 390 420
:.· ..5rf1:/ J 1t.of..f.7tlb:r .. 1~0':: 630. !:H20::: ;_:630: .:: · 130. .. ~s6o·: l,1>60 ~ (s6~ •.. ··~so · 500 :Joo~ ; s 1if'.,;l3._.
~ 1• m1~ m1m ~1~ ~1~ mm ~1m ~ ~
.7/8,·:.: .. 2100J )ci8~():~oo.':.'..941r )950·· rooo 12so· s·6o'. 1810· 900 : i110 · 180 )660 · 170· YJ3P'~
I 2560 1280 1660 1140 2390 1130 1530 1050 2220 950 1390 950 2050 800 1260
. HI&.,·,· 3080~-tJso::19so 1Jso. '.~sso: 1180 1800, H80:. 2690 1010 •. l65o . 1ou>-2490 · 840,,, ~~%;.
1-1/4 3650 1440 2270 I~ 3430 1250 2100 1250 3210 . 1060 1920 1060 2990 910 1760 9IO , .
1 Tabulated lateral design values (Z) for lag screw connections shall be multiplied by all applicable adjustment factors (ANSI/~&B
2 Tabulated lateral design values (Z) are for "full diameter" lag screws (see Reference 6) inserted in side grain with lag screw axis P
and with the following lag screw bending yield strengths (Fy1,): Fy1, = 70,000 psi for D = 1/4", Fyb = 60,~00 psi for D = 5/16", f>:".:=c
AMERICAN WOOD COUNCIL