Loading...
HomeMy WebLinkAbout2426 TOWN GARDEN RD; ; FPC2019-0056; PermitF1:1Il:1Ii]I FUe12eTimit Print Date: 03/02/2022 Job Address: 2426 TOWN GARDEN RD, CARLSBAD, CA 92009 Permit Type: FIRE-Construction Commercial Work Class: Parcel #: 2132601000 Track #: Valuation: $4,557,980.00 Lot #: Occupancy Group: Project #: #of Dwelling Units: Plan #: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check #: Plan Check #: Permit No: FPC2019-0056 Status: Closed - Finaled Fixed Extinguishing Syste Applied: 03/11/2019 Issued: 03/20/2019 DEV2016-0015 Finaled Close Out: 04/14/2021 Inspector: Final Inspection: Project Title: VIASAT BRESSI RANCH CAMPUS Description: VIASAT BLDG 14 - FM-200 FIRE SUPPRESSION SYSTEM IN MDF ROOM 1-038 1ST FLR Applicant: SCHMIDT FIRE PROTECTION INC GORDON SWOPE 4760 MURPHY CANYON RD SAN DIEGO, CA 92123-4321 (619) 871-9753 FPContractor: SCHMIDT FIRE PROTECTION CO INC 4760 MURPHY CANYON RD SAN DIEGO, CA 92123-4321 (858) 279-6122 FEE AMOUNT FIRE Special Extinguishing System $586.00 Total Fees: $586.00 Total Payments To Date: $586.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov slalom WSchmidt Fire Protection Co., Inc. 11 4760 MURPHY CANYON RD • SAN DIEGO, CA 92123 • (858) 279-6122 • FAx (858) 279-3583 VIASAT Building 14 2426 Town Garden Road Carlsbad, CA 92001 FM-200 FIRE SUPPRESSION SYSTEM MDF ROOM 1-038 SUBMITTAL PACKAGE Design by: Gordon E. Swope SET (NICET Level-IV #078621) (619) 871-9753 gordon@schmidtfireprotection.com.com I I I I I I I I Date February 4, 2019 e. V it Kidde Fire Systems KFS Hydraulic Flow Calculation Program v4.00 (FM-200) UL: EX4674 / Component of FM Approved System Schmidt Fire Protection, Co. Inc. 4760 Murphy Canyon Road San Diego, CA 92123 Gordon Swope SET (NICET #078621) Phone: 858.279.6122 (619.871.9753 c) File Name: VIASAT-14_MDF.FC4 Consolidated Report Customer Information Company Name: VIASAT BLDG-14 Address: Phone: Contact: Title: Project Data Project Name: MDF ROOM 1-038 Designer: G.E. SWOPE Number: Account: Location: Description: Enclosure Report Elevation: 0 ft (relative to sea level) Atmospheric Correction Factor: 1 (NFPA 2001) Enclosure 1 MDF ROOM 1-038 Enclosure Temperature: Number of Nozzles: Calculation Date/Time: Friday, February 15, 2019, 6:58:21 AM Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal Key ID: 2129303002 Page: 1of 6 'Kidde Fire Systems Consolidated Report Minimum: 70 F Width: Maximum: 70 F Length: Max. Concentration: 0.00 % Height: Design Concentration: Volume: Adjusted: 7.13 % Non-permeable: Minimum: 7.00 % Total Volume: Mm. Agent Required: 106.0 lb Adjusted Agent Required: 108.0 lb 11.9 ft 16.4 ft 15.9 ft 3106.3 ft 0.0 ft 3106.3 ft Agent Source Report Agent: FM-200 / Propellant N2 (FM-200 is a Trademark of DuPont) Cylinder Name: 125 lb Cylinder w/LLI Cylinder Part Number: 90-100121-001 Agent Per Cylinder: 108.0 lb Fill Density: 60.4 lbs / cubic ft Number of Main Cylinders: 1 Number of Reserve Cylinders: 0 Cylinder Empty Weight: 96.0 lb Weight, All Cylinders + Agent: 204.0 lb Floor Area Per Cylinder: 0.89 ft 2 Floor Loading Per Cylinder: 229 lbs / ft 2 Calculation Date/Time: Friday, February 15, 2019, 6:58:21 AM Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal Key ID: 2129303002 Page: 2o16 Kidde Fire Systems Consolidated Report Parts Report Total Agent Required: 108.0 lb Cylinder Name: 125 lb Cylinder w/LLI (Part: 90-100121-001) Number of Cylinders: 1 Nozzle I Nozzle Type Diameter Nozzle Area Part Number E1-N1 180° 1-1/4 in 0.9047 in 2 90-194016-375 I Pipe & I Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions 40T 1-1/4 in 15.08 ft 5 0 0 0 Other I Objects Name Quantity Part Number I 1-1/2 in. Valve Outlet Adapter 1 283904 System Acceptance Report System Discharge Time: 8.5 seconds I Percent Agent In Pipe: 15.4% Percent Agent Before First Tee: 0.0% I Dead Volume: 0.0% (0.0 lb) Enclosure Number: 1 Enclosure Name: MDF ROOM 1-038 I Minimum Design Concentration: 7.00% Adjusted Design Concentration: 7.13% I Predicted Concentration: 7.13% Maximum Expected Agent Concentration: 7.13% (At 70 F) I Calculation Date/Time: Friday, February 15, 2019, 6:58:21 AM Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal Key ID: 2129303002 I Page: 3 of 6 'Kidde Fire Systems Consolidated Report Maximum Allowed Enclosure Pressure: 10.00 lbs / ft 2 Installed Vent Area: 0ft2 Predicted Minimum Vent Area (Negative): 1 ft2 Predicted Minimum Vent Area (Positive): 0 ft2 Predicted Enclosure Pressure (Negative): N/A Predicted Enclosure Pressure (Positive): N/A Minimum Adjusted Agent Agent Nozzle Required Required Predicted Average Agent Nozzle Delivered Pressure El-Ni 106.0 lb 108.0 lb 108.0 lb 107 psig Calculation Date/Time: Friday, February 15, 2019, 6:58:21 AM Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal Key ID: 2129303002 Page: 4 of 6 'Kidde Fire Systems Consolidated Report Pipe Network Report Total Total Pipe Start End Pipe Pipe Pipe Elevation Equivalent Nozzle Nozzle Nozzle Nozzle Description Section Node Node Type Diameter Length Union Change Length Name Size Type Area Cylinder - On Man./End 0 2 1-1/2 in 2.99 ft 0 2.99 ft 50.00 ft Adapter System 2 3 1-1/2 in 0.22 ft 0 11.80 ft Pipe System 3 4 40T 1-1/4 in 0.50 ft 0 ------0.50 ft Elbow (90) System 4 5 401 1-1/4 in 0 ------3.70 ft Pipe System 564QT 1-1/4 in 11.00ft011.00ft 11.00 ft Elbow (90) System 6 7 40T 1-1/41n 3.70ft Pipe System 7 8 - 40T 1-1/41n 1.00 ft 0_ - ------ - 1.00 ft Elbow (90) System 8 9 40T 1-1/4 in 0 3.70 ft Pipe System 9 10 40T 1-1/4 in 1.92 ft 0 1.92 ft 1.90 ft Elbow(90) System 10 11 40T 1-1/4 in 0 3.70 ft Pipe System 11 12 40T 1-1/4 in 0.50 ft 0 0.50 ft Elbow (90) - System 12 13 401 1-1/4 in 0 3.70 ft Pip System 13 14 - 40T - 1-1/4 in 0.16 ft 0 - 0.20 ft - El-Ni 1-1/4 in 180° 0.9047 in 2 Key ID: 2129303002 Page: 5 of 6 Kidde Fire Systems Consolidated Report Key ID: 2129303002 Page: 6of6 Table 1: FM-2000 Physical Properties Chemical Formula CF3CHFCF3 Molecular Weight 170.03 Freezing Point -204F (-131C) Boiling Point at 1 Atm 2.6F (-16.4C) Critical Temperature 215.1F (101.7C) Critical Density 38.76 lb/ft3 (621 kg/m3) Critical Pressure 422 PSIA (29.0 bar absolute) Critical Volume 0.0258 cu ft/lb (1.61 Ukf) Ozone Depletion Potential 0 Table 2: FM-2000 Fire Protection Properties Cup Burner Concentration (n-Heptane) 6.70% v/v Use Concentration for n-Heptane 8.00% v/v Use Concentration for Acetone 8.30% v/v Use Concentration for Isopropanol 9.00% v/v Use Concentration for Toluene 7.00% v/v Use Concentration for Class A (Surface Fires) * 6.25% v/v * Note: Automatic only per NFPA 2001 Table 3: FM-2000 Toxicity Properties NOAEL (No Observable Adverse Effect Level) 9.0% LOAEL (Lowest Observable Adverse Effect Level) 10.5% COMPATIBILITY F or Use Series With Kidde ECS HFC-227ea X Kidde ECS Advanced Delivery FM-200® X Kidde ECS Fire Suppression System Component Description FM-200®Fire Suppression Agent (Kidde Fire Systems Effective: June 2014 K-90-1900 Rev BA FEATURES Non-Ozone Depleting Safe for Total Flooding of Occupied Spaces Clean - No Residue to Clean Up Non-Damaging to Hazard Contents Fast Acting EXTINGUISHING AGENT FM2000 Agent (1,1,1,2,3,3,3-heptafluoropropane) is a compound of carbon, fluorine and hydrogen (CF3CHFCF3). It is colorless, odorless and electrically non-conductive. It suppresses fire by a combination of chemical and physical mechanisms without affecting the available oxy- gen. This allows personnel to see and breathe, permitting them to leave the fire area safely. FM-200 Agent has acceptable toxicity for use in occupied spaces when used as specified in the United States Environ- mental Protection Agency (EPA) Significant New Alternative Policy (SNAP) program rules. Although FM-2000 Agent is considered non- toxic to humans in concentrations necessary to extinguish most fires, certain safety considerations should be observed when applying and handling the agent. The discharge of FM-2000 Agent may create a haz- ard to personnel from the undecomposed agent itself and from the decomposition products which result when the agent is exposed to fire and other hot surfaces. Exposure to the agent is generally of less con- cern than is exposure to the decomposition products. Unnecessary exposure to the agent or the decomposition products should be avoided. TOXICITY In tests, the acute toxicity of FM2000 Agent was shown to be equiva- lent to that of Halon 1301. FM-2000 Agent has been evaluated for car- diac sensitization through test protocols approved by the US EPA. The EPA's SNAP Program classifies FM-2000 Agent as acceptable for use as a total flooding agent in occupied spaces. Refer to the SNAP pro- gram rules for more information. CLEANLINESS FM2000 Agent is clean, leaves no residue, thereby eliminating costly after-fire clean-up, and keeping expensive "down-time" to a minimum. Most materials such as steel, stainless steel, aluminum, brass, and other metals as well as plastics ,rubber and electronic components are unaffected by exposure to FM-200 Agent. I APPROVALS FM-2000 Agent complies with the NFPA Standard 2001: Standard for Clean Agent Fire Extinguishing Systems, EPA SNAP Program (Signifi- cant New Alternate Policy), Underwriters Laboratories, Inc. (UL) and Factory Mutual Research Corporation (FMRC). USE FM-2000 Agent is used in total flooding fire suppression systems. It is I stored in steel containers, and is super-pressurized with nitrogen to aid in expelling the agent. The discharge time is 10 seconds or less. The maximum fill density of the agent storage is 70 lb./ft.. I This literature is provided for informational purposes only. KIDDE- FENWAL, INC. assumes no responsibility for the product's suitability for I a particular application. The product must be properly applied to work correctly.lf you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, Inc. 02014 Kidde-Fenwal, Inc. Active Fire Suppression Agent UL Component Recognized FM Approved RoHS Complaint FM-200 is a registered trademark of E.I. du Pont de Nemours and Company. Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners. Kidde Fire Systems 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com The MSDS format adheres to the standards and regulatory requirements of the United States and may not meet regulatory requirements in other countries. DuPont Page Material Safety Data Sheet ---------------------------------------------------------------------- FM- 200 6402FR Revised 28-FEB-2008 ---------------------------------------------------------------------- CiMICAL PRODUCT/COMPANY IDENTIFICATION ---------------------------------------------------------------------- Material Identification FM-200 is a registered trademark of DuPont. CAS Number 431-89-0 Formula : CF3 ClIP CF3 Molecular Weight : 170.03 CAS Name : Propane, 1,1,1,2,3,3,3-Heptafluoro- Tradenames and Synonyms FM2 00 FE-227 2- Hydroperf luoropropane Propane, 1,1,1,2,3,3,3-Heptafluoro- HFC- 227 eaHP 2 -Hydroheptafluoropropane Heptafluoropropane 2 -H-heptafluoropropane 1,1,1,2,3,3, 3-Heptafluoropropane R-227 R227 HFC-227ea Company Identification MANUFACTURER/DISTRIBUTOR DuPont Fluoroproducts 1007 Market Street Wilmington, DE 19898 PHONE NUMBERS Product Information : 1-800-441-7515 (outside the U.S. 302-774-1000) Transport Emergency : C}MTREC 1-800-424-9300(outside U.S. 703-527-3887) Medical Emergency : 1-800-441-3637 (outside the U.S. 302-774-1000) ---------------------------------------------------------------------- COMPOSITION/INFORMATION ON INGREDIENTS ---------------------------------------------------------------------- Components Material CAS Number 96 1,1,1,2,3,3,3-Heptafluoropropane 431-89-0 99.95 I 6402FR DuPont Page 2 Material Safety Data Sheet ---------------------------------------------------------------------- I HAZARDS IDENTIFICATION Potential Health Effects Based on animal data, overexposure to FM-200 by inhalation may cause suffocation, if air is displaced by vapors, and irregular heart beat with a strange sensation in the chest, "heart thumping," apprehension, lightheadedness, feeling of fainting, dizziness, weakness, sometimes progressing to loss of consciousness and death. FM-200 may cause frostbite if liquid or escaping vapor contacts the skin. FM-200 may cause "frostbite-like" effects if the liquid or escaping vapors contact the eyes. In one study, human volunteers were selected to inhale FM-200 at a concentration of 6000 ppm but the study was terminated due to a rise in pulse rate that was believed to be unrelated to the chemical. In a subsequent study with human volunteers inhaling concentrations up to 8000 ppm no clinically significant effects were observed for any of the measured laboratory parameters. Individuals with preexisting diseases of the cardiovascular system or nervous system may have increased susceptibility from excessive exposures. Carcinogenicity Information None of the components present in I equal to or greater than 0.1% are as a carcinogen. this material at concentrations listed by IARC, NTP, OSHA or ACGIH ---------------------------------------------------------------------- FIRST AID MEASURES ---------------------------------------------------------------------- First Aid INHALATION If inhaled, immediately remove to fresh air. If not breathing, give artificial respiration. If breathing is difficult, give oxygen. Call a physician. SKIN CONTACT Treat for frostbite if necessary by gently warming affected area. EYE CONTACT In case of contact, immediately flush eyes with plenty of water for at least 15 minutes. Call a physician. 6402FR DuPont Page 3 Material Safety Data Sheet (FIRST AID MEASURES - Continued) INGESTION I Ingestion is not considered a potential route of exposure. ---------------------------------------------------------------------- FIRE FIGHTING MEASURES ---------------------------------------------------------------------- Flaimnable Properties 1,1,1,2,3,3, 3-Heptafluoropropane is not flaimnable, however in the presence of a flame or ignition source it may decompose to form toxic hydrogen fluoride or carbonyl fluoride. Non-flammable. Extinguishing Media Use media appropriate for surrounding material. Fire Fighting Instructions I Self-contained breathing apparatus (SCRA) may be required if cylinders rupture or release under fire conditions. Keep cylinders cool with water spray applied from a safe distance. ---------------------------------------------------------------------- ACCIDENTAL RELEASE MEASURES ---------------------------------------------------------------------- Safeguards (Personnel) NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL) sections before proceeding with clean-up. Use appropriate PERSONAL PROTECTIVE EQUIPMENT during clean-up. Evacuate personnel, thoroughly ventilate area, use self-contained breathing apparatus. Keep upwind of leak - evacuate until gas has dispersed. Initial Containment Use forced ventilation to disperse vapors. I I I I I I 6402FR DuPont Page 4 Material Safety Data Sheet ---------------------------------------------------------------------- I HANDLING AND STORAGE ---------------------------------------------------------------------- Handling (Personnel) I Do not breathe gas. Avoid contact with eyes, skin, or clothing. Wash thoroughly after handling. Wash clothing after use. Storage Store in a clean, dry place. Store below 52 C (126 F). ---------------------------------------------------------------------- I EXPOSURE CONTROLS/PERSONAL PROTECTION Engineering Controls I Use only with adequate ventilation. Keep container tightly closed. Personal Protective Equipment I EYE/FACE PROTECTION Wear safety glasses or coverall chemical splash goggles. I RESPIRATORS Wear NIOSH approved respiratory protection, as appropriate. I PROTECTIVE CLOTHING Where there is potential for skin contact have available and wear as appropriate impervious gloves, apron, pants, and jacket. I Exposure Guidelines Exposure Limits I FM-200 AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA * AEL is DuPont's Acceptable Exposure Limit. Where governmentally I imposed occupational exposure limits which are lower than the AEL are in effect, such limits shall take precedence. ---------------------------------------------------------------------- I PHYSICAL AND CHEMICAL PROPERTIES ---------------------------------------------------------------------- Physical Data I Boiling Point -16.4 C (2.5 F) Melting Point -131 C (-204 F) Vapor Pressure : 65.7 psia @ 25 C (77 F) (453.3 kPa) Liquid Density : 1.386 g/cm3 @ 25 C (77 F) (86.53 lb/ft3) I Critical temperature : 101.6 C (214.9 F) Critical pressure : 424.7 psia (2930 kPa) Odor : None. I F 6402FR DuPont Page 5 Material Safety Data Sheet (PHYSICAL AND CHEMICAL PROPERTIES - Continued) Form Liquified Gas ---------------------------------------------------------------------- STABILITY AND REACTIVITY ---------------------------------------------------------------------- Chemical Stability Stable at normal temperatures and storage conditions. Avoid sources of heat or open flame. Incompatibility with Other Materials Incompatible with strong reducing agents such as alkali metals (e.g., sodium, potassium), alkali-earth metals (e.g., magnesium, calcium), and powdered aluminum or zinc. Decomposition Decomposes by reaction with high temperature (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid, carbonyl fluorides, carbon monoxide and carbon dioxide. Polymerization Polymerization will not occur. ---------------------------------------------------------------------- TOXICOLOGICAL INFORMATION ---------------------------------------------------------------------- Animal Data FM-200: Inhalation 4 hour LC50: > 788,698 ppm in rats Repeated exposure of rats by inhalation for 4 weeks at concentrations up to 50,000 ppm revealed no toxicologically significants effects. The NOEL for this study was 50,000 ppm. A 90-day inhalation study in rats did not find any exposure related effects at 105,000 ppm. The NOEL for this study was 105,000 ppm. Cardiac sensitization, a potentially fatal disturbance of heart rhythm associated with a heightened sensitivity to the action of epinephrine, occurred in dogs at 105,000 ppm. The NOAEL for cardiac sensitization was 90,000 ppm. In a different study to evaluate cardiac sensitization in dogs, concentrations of 90,000, 105,000, and 140,000 ppm caused a dose-related increase in incidence and severity; at 90,000 ppm efffects were minimal or mild in nature. Inhalation studies in rabbits and rats do not suggest developmental toxicity at concentrations up to I U 6402FR DuPont Page 6 Material Safety Data Sheet I (TOXICOLOGICAL INFORMATION - Continued) 105,000 ppm. Tests have shown that FM-200 does not cause genetic damage in bacterial or mammalian cell cultures. Tests in animals for carcinogenicity or reproductive toxicity have not been conducted. ---------------------------------------------------------------------- DISPOSAL CONSIDERATIONS I Waste Disposal Treatment, storage, transportation, and disposal must be in I accordance with applicable Federal, State/Provincial, and Local regulations. Incinerate material in accordance with Federal, State/Provincial and Local requirements. TRANSPORTATION INFORMATION Shipping Information I DOT Proper Shipping Name : Heptafluoropropane Hazard Class 2.2 I I.D. No. (UN/NA) : UN 3296 DOT Label(s) Nonflammable Gas ---------------------------------------------------------------------- I REGULATORY INFORMATION U.S. Federal Regulations I TSCA Inventory Status :Listed. TITLE III HAZARD CLASSIFICATIONS SECTIONS 311, 312 Acute Yes I Chronic : No Fire : No Reactivity : No Pressure : No OTHER INFORMATION I NFPA, NFPA Rating Health : 1 I Flammability : 0 Reactivity 1 I NPCA-W1IS Rating Health : 1 Flammability : 0 I I I 6402FR DuPont Page 7 Material Safety Data Sheet (Continued) Reactivity 0 Personal Protection rating to be supplied by user depending on use conditions. ---------------------------------------------------------------------- The data in this Material Safety Data Sheet relates only to the specific material designated herein and does not relate to use in combination with any other material or in any process. Responsibility for MSDS : MSDS Coordinator > : DuPont Fluoroproducts Address Wilmington, DE 19898 Telephone : (800) 441-7515 This information is based upon technical information believed to be reliable. It is subject to revision as additional knowledge and experience is gained. End of MSDS SAFETY CAP I I I Component Description 3-3 COMPONENT DESCRIPTIONS 13-3.1 HFC-227ea Cylinder/Valve Assemblies HFC-227ea is stored in steel cylinders as a liquid, superpressurized with nitrogen to 360 PSIG I at 70°F (25 bar gauge at 210C). The cylinder valve assembly is equipped with a supervisory pressure switch connection for monitoring cylinder pressure, a pressure gauge and a safety burst disc in compliance with DOT requirements. I In addition, each cylinder/valve assembly is provided with a safety cap and a protection cap which is a safety feature to prevent uncontrolled, accidental discharge. I The safety cap must be installed on the discharge outlet whenever a charged A cylinder/valve assembly is not connected to the system piping. Failure to install the safety cap could result in violent movement of the container in the event of ' WARNING inadvertent actuation. Failure to follow these instructions could cause death, personal injury and/or property damage. I Figure 3-3 through Figure 3-6 represent typical cylinder assemblies. See Table 3-4 for cylinder dimensions. CYLINDER VALVE PRESSURE GAUGE 180 APART FROM SYPHON TUBE OPEN END CYLINDER Figure 3-3. Typical Cylinder Assembly, 10 to 70 lb. CYLINDER VALVE LIQUID LEVEL INDICATOR LIFTING LUGS CYLINDER NAMEPLATE Figure 3-4. Typical Cylinder Assembly, 125 lb and 200 lb and 300 lb Manufactured through April 2014. October 2014 3-4 06-236115-001 SAFETY CAP VAVLE JQUID LEVEL INDICATOR LIFTING LUGS Component Description I - 0 A Figure 3-5. Typical Cylinder Assembly, 200 and 350 lb Manufactured After April 2014. VALVE ORIENTA11ON PLAN VIEW SAFETY BURST DISC ASSEMBLY Figure 3-6. 600 and 900 lb. Cylinder with 3" Valve The Kidde ECS System equipment listed herein is designed for an operating temperature range of 32°F to 130°F (0°C to 540C). Table 3-1 shows the container temperature-pressure relationship based on a maximum fill density of 70 lb./ft.3 (1121 kg/ml). The latest version of the Flow Calculation Software User's Guide 06-236271-001 is designed for a 70°F (21°C) container operating/storage temperature. Therefore, the container operating and storage temperature must be in the range of 60°F to 80°F (16°C to 27°C) for a single unbalanced system protecting two or more separate hazards. If the container operating and storage temperature is outside this range, an insufficient quantity of agent may be discharged from one or more discharge nozzles. I I 06-236115-001 3-5 October 2014 I Component Description Table 3-1. Container Temperature-Pressure Correlation (Based on a cylinder fill density of 70 lb./ft.3 or 1121 kg/M3) Temperature Nominal Charge, Pressure OF °C PSIG Bar 32 0 288 19.9 40 4.4 303 20.9 50 10 321 22.2 60 15.6 340 23.5 70 21.1 360 24.8 80 26.7 381 26.3 90 32.2 402 27.7 100 37.8 425 29.3 110 43.3 449 31 120 48.9 475 32.7 130 54.4 502 34 If desired, the 125, 200, 350, 600 and 900 lb. cylinders can be provided with an integral Liquid Level Indicator (see Paragraph 3-3.2). Table 3-2. Cylinder, Equivalent Lengths Part Number Nomenclature Discharge Outlet Equivalent Length w/o Flex Hose Equivalent Length w/ Flex Hose ft. m ft. m 90-100010-001 10 lb. Cylinder 11/2" 61.8 18.84 65 19.81 90-100020-001 20 lb. Cylinder 11h" 61.8 18.84 65 19.81 90-100040-001 40 lb. Cylinder 11/2" 61.8 18.84 65 19.81 90-100070-001 70 lb. Cylinder 11/2" 61.8 18.84 65 19.81 90-10012X-001 125 lb. Cylinder 11/2" 61.8 18.84 65 19.81 90-10020X-001 200 lb. Cylinder 2" 59 17.98 65 19.81 90-10035X-001 350 lb. Cylinder 59 17.98 65 19.81 90-10060X-001 600 lb. Cylinder (old style) 21h" 59 17.98 65 19.81 90-10060X-100 600 lb. Cylinder (new style) 50 15 80 24 90-10090X-001 900 lb. Cylinder 3" 50 15 80 24 October 2014 3-6 06-236115-001 Component Description Table 3-3. Dimensions, HFC-227ea Cylinder/Valve Assemblies for Vertical Installation Only Part Number Valve w/LLI Height Diameter Volume Valve Outlet Height C A B in. m in. m ft.3 m3 in. m 90-10001X-001 11/2" No 17.3 0.44 7.07 0.18 0.167 0.0047 13.3 0.33 90-10002X-001 11/2" No 24.97 0.64 7.07 0.18 0.286 0.0081 21 0.53 90-10004X-001 11/2" No 26.76 0.68 9 0.23 0.572 j 0.0162 22.8 0.58 90-10007X-001 11/2" No 38.83 0.99 9 0.23 1 0.0283 34.9 0.89 90-100121-001 11/2" Yes 35.93 0.92 12.75 0.33 1.788 0.0506 32 0.81 90-100125-001 11/2" No 35.93 0.92 12.75 0.33 1.788 0.0506 32 0.81 90-100200-101 2" No 52.75 1.34 12.75 0.33 2.859 0.081 47.5 1.21 90-100201-101 2" Yes 52.75 1.34 12.75 0.33 2.859 0.081 47.5 1.21 90-100350-001 2" No 58.36 1.49 16 0.41 5 0.1416 53.1 1.35 90-100351-001 Yes 58.36 1.49 16 0.41 5 0.1416 53.1 1.35 90-100600-001 21/2" No 56.72 1.45 22 0.56 8.572 0.2427 50.5 1.28 90-100601-001 21/2" Yes 56.72 1.45 22 0.56 8.572 0.2427 50.5 1.28 90-100600-100 No 58 1.47 22 0.56 8.68 0.246 50.5 1.28 90-100601-100 3" Yes 58 1.47 22 0.56 8.68 0.246 50.5 1.28 90-100900-001 3" No 70 1.78 24 0.61 13 0.368 62 1.57 90-100901-001 3" Yes 70 1.78 24 0.61 13 0.368 62 1.57 October 2014 3-8 06-236115-001 I Component Description Table 3-4. Fill Range HFC-227ea Cylinder/Valve Assemblies for Vertical Installation Only Part Number Fill Range Empty Weight Gross Weight Mm. Fill Max. Fill lb. kg lb. kg lb. kg lb. kg 90-10001X-001 6-10 3-4.5 25 11 30 14 35 16 90-10002X-001 9-20 4-9 31 14 40 18 51 23 90-10004X-001 18-40 8-18 38 17 55 25 78 35 90-10007X-001 30-70 14-31.5 52 24 82 38 123 56 90-100121-001 54-125 24.5-56.5 98 45 152 69 223 101 90-100125-001 54-125 24.5-56.5 98 45 152 69 223 101 90-100200-101 86-200 39-90.5 133 60 219 100 333 151 90-100201-101 86-200 39-90.5 133 60 219 100 333 151 90-100350-001 150-350 68-158.5 201 91 351 159 555 250 90-100351-001 150-350 68-158.5 203 92 353 160 557 251 90-100600-001 258-600 117-272 335 152 593 270 935 425 90-100601-001 258-600 117-272 337 153 595 270 937 426 90-100600-100 258-600 117-272 362 165 620 281 962 437 90-100601-100 258-600 117-272 362 165 620 281 962 637 90-100900-001 390-900 177-408 505 230 895 407 1405 637 90-100901-001 390-900 177-408 505 230 895 407 1405 637 I 1 I 1 06-236115001 3-9 October 2014 Component Description 3-3.2 Liquid Level Indicator The optional Liquid Level Indicator (LLI) consists of a hollow metal tube inserted into a special fitting in the top of the 125, 200, 350, 600 or 900 lb HFC-227ea cylinder. See Table 3-5 for part number information. The indicator is provided with a graduated tape which senses the position of a toroidal magnet encased within an internal float riding on the liquid surface. The graduations on the tape indicate the liquid level within the cylinder (see Figure 3-10). READING TAKEN AT TOP EDGE OF FITTING CAP GRADUATED TAPE SHOWN IN MAGNETIC INTERLOCK POSITION READY TO TAKE READING. O-RING BRASS TUBE TAPE INSIDE BRASS TUBE HFC-227ea LIQUID LEVEL ,- HFC-227ea k. CYLINDER MAGNETIC END OF I TAPE ENGAGES I IN MAGNETIC FIELD I OF FLOAT WHEN TAPE IS PULLED UP TO TAKE READING. - MAGNET EMBEDDED IN FLOAT. FLOAT - FLOATS ON SURFACE OF LIQUID HFC-227ea. FREE TO MOVE UP OR DOWN OUTSIDE OF BRASS TUBE. RETAINER. FLOAT RESTS HERE WHEN CYLINDER IS EMPTY. Figure 3-10. Liquid Level Indicator Table 3-5. Liquid Level Indicator Part Numbers Cylinder Liquid Level Tape Part Number 125 06-400125-001 200 WK-400200-000 350 WK-400350-000 600 WK-400600-000 900 WK-400900-000 October 2014 3-10 06-236115-001 Component Description 3-3.3 Cylinder Mounting Equipment Steel straps and brackets are used to mount the cylinders in a vertical position. Cylinder straps (P/N WK-283945-000, WK-283934-000, 06-235317-001, WK-292971-000, WK-281866-000, WK-294651-000, and 06-236125-001) are available, for all size cylinders (see Figure 3-11 and Table 3-6 and Table 3-7). F (hole size) C I IID -f Figure 3-11. Cylinder Mounting Straps Table 3-6. Dimensions-Cylinder Mounting Straps Part Number Cylinder Size _________________ Cylinder O.D.A Dimensions* lb B C D E F WK-283945-000 10 20 7.07 6.48 9.62 8.62 1.00 2.78 0.437 WK-283934-000 40 70 9.00 8.16 11.69 10.69 1.00 3.50 0.437 06-235317-001 125, 200 new style 12.75 12.175 16.18 14.56 1.75 5.59 0.625 WK-292971-000 200 old style 13.6 13.09 17.06 15.44 1.75 6.06 0.625 WK-281866-000 350 16.00 15.50 19.50 17.88 1.75 7.25 0.625 WK-294651-000 600 22.00 21.56 1 25.75 j 24.12 j 1.75 10.25 0.625 06-236125-001 900 24.00 23.75 27.75 1 26.00 1 1.75 12.13 0.625 *Note: Dimensions are in millimeters. 06-236115-001 3-11 October 2014 B (valve outlet conr- —' A (system pipe c..... J1 Component Description I 3-3.7.2 Valve Outlet Adapters, P/N WK-283904-000, P/N WK-283905-000 and P/N WK-283906-000 A valve outlet adapter connects the cylinder valve outlet to the discharge piping when a flexible discharge hose is not used (see Figure 3-27 and Table 3-14). Note: 3" valve cylinders are equipped with a roll-groove outlet. Use a standard groove-groove connection in lieu of a valve outlet adapter. Figure 3-27. Valve Outlet Adapter Table 3-14. Dimensions, Valve Outlet Adapter Part Number Size A B C D in mm in mm WK-283904-000 11/2 11/2" to 111/2 NPT 1.874" 2.69 68.33 2.50 HEX 63.5 WK-283905-000 2" 2" to 111/2 NPT 2.500" 12 UN) 3.12 79.25 3.00 HEX 76.2 WK-283906-000 21/2" 21/2"to 8 NPT 3.00" 12 UN) 3 76.2 3.75 HEX 95.2 3-3.7.3 Check Valve, 1/4-inch, P/N WK-264985-000 Check Valves are installed in sections of piping in main/reserve systems to prevent the actuation of the reserve system when the main system is discharged. 1/4-inch check valves are installed in the pilot manifold to ensure the proper number of cylinders are discharged (see Figure 3-28). D OFFILOW IRECTION 114 in.-I8NPT (rYP.) 2.00 in. 0.81 in. (51 mm) I (21 mm) HEX Note: Install the valve with the arrow pointing in the direction of flow. Figure 3-28. Check Valve I 06-236115-001 3-25 October 2014 METAL STAMP X-XXX (DASH NO.) IN .093.031 HIGH CHARACTERS ON ANY FLAT F Kidde ECS Fire Suppression System Component Description 180 Degree Pendant Nozzle §110 V V,F Kidde Fire Systems Effective: June 2014 K-81-9150 Rev BA I FEATURES For Use with UL Listed, ULC Listed & FMRC Approved Systems I • RoHS Compliant PIN: 90-19401X-XXX Pipe Size A B C D 1/2" (12.20 mm) 1.25" (31.75 mm) 1.250" (31.75 mm) 1.687" (42.84 mm) 2.000"(50.80 mm) 3/4" (19.05 mm) 1.50" (38.10 mm) 1.375" (34.92 mm) 1.950" (48.89 mm) 2.296"(58.31 mm) (25.40 mm) 1.75" (44.45 mm) 1.562" (39.67 mm) 2.218" (56.33 mm) 2.671" (67.84 mm) 1W(31.75 mm) 2.25" (57.15 mm) 1.750" (44.45 mm) 2.656" (67.46 mm) 3.250"(82.55 mm) 11/2" (38.10 mm) 2.50" (63.50 mm) 1.950" (48.89 mm) 2.950" (74.93 mm) 3.625"(92.07 mm) (50.80 mm) 3.00" (76.2 mm) 1.968" (49.98 mm) 2.875" (73.02 mm) 3.656" (92.86 mm) Note: A selection of orifices are available for each nozzle size. Consult your Kidde Design and Installation Manual for details. COMPATIBILITY Series For Use With Kidde ECS HFC-227ea X This literature is provided for informational purposes only. KIDDE- FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. The product must be properly applied to work correctly.lf you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, Inc. ©2014 Kidde-Fenwal, Inc. Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners. Kidde Fire Systems 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com ARIESTM Fire-Alarm/Suppression System Control Unit VKidde Fire Systems A UTC Fire & Security Company Effective: March 2007 K-76-600 1 I I FEATURES Distributed Intelligence to Sensor Level Fully-Digitized Communications Protocol Up to 255 Points without Device-Type Restrictions Inherently Power Limited USB Communications Port Internet Accessible I Triple-R Protection Against Inadvertent Extinguishing- • Simple Programming System Activation • UL Listed and FM Approved I DESCRIPTION The ARIESTM Fire Alarm/Suppression System Control Unit is a compact control unit that provides one signaling line circuit, four notification-appliance circuits, two releas- ing circuits, and four on-board relays. Two of the four notification-appliance circuits are user-configurable to actuate one solenoid valve for control of a special extin- guishing system or a pre-action/deluge sprinkler system. A 5.4 Amp, filtered and regulated power supply provides charging capabilities for batteries up to 70 Ah. The ARIES Control Unit annunciates alarm, trouble, and supervisory events via an 80-character, backlit LCD dis- play with integral status LEDs. Event acknowledgment, alarm silence, and system reset are accomplished with dedicated control keys. Basic user and maintenance operations such as viewing history or isolation com- mands to initiating points and system outputs are per- formed via the control keys and associated digit keys. A security password prevents unauthorized access to the system. SIGNALING LINE CIRCUIT The signaling line circuit communicates with up to 255 SmartOne® automatic initiating devices, monitor mod- ules, and control modules via a highly-efficient, fully-digi- tized protocol. The SmartOne communications protocol imposes no limitations on the mix of automatic initiating devices and monitor/control modules on the signaling line circuit. Each SmartOne initiating device has a micropro- cessor, memory, and decision-making algorithms to inter- rupt normal control-unit communications and initiate an alarm signal. This distributed intelligence to the sensor level ensures rapid response to all types of initiating signals, and is far superior to the various sequential, poll and respond com- munication schemes employed by others that rely on the control unit to make all alarm decisions. SmartOne smoke detectors manage their individual drift compensa- tion routines, and have pre-alarm and alarm thresholds that are configurable in 0.1 percent-per-foot increments throughout the entire range of Listed sensitivities. The control unit can dynamically adjust the smoke detector alarm thresholds as the result of one or more alarm-initi- ating events to confirm that a fire requiring the rapid action of an associated extinguishing system has occurred. SmartOne smoke detectors can also be config- ured for non-latching operation that requires them to measure smoke signatures in excess of their alarm thresholds for the entire pre-discharge time period in order to discharge the extinguishing system. This pre- vents a transitory event that mimics a smoke signature such as the leakage of air-conditioning fluid from acci- dentally discharging the extinguishing system. SmartOne heat detectors have pre-alarm and alarm thresholds that are programmable in 1°F intervals. I The signaling line circuit can be wired for Class-A, Style-6 or Class-B, Style-4 operation. Optional isolator modules can be used for a Class-A, Style-7 circuit. RELEASING CIRCUITS The ARIES Control Unit has two releasing circuits that can be configured to actuate releasing devices via any of the following ways: Single control head or solenoid valve Two series-supervised, parallel-actuated control heads or solenoid valves. One Metron actuator These releasing circuits can be used to actuate various Kidde control heads for waterless-extinguishing-system storage containers, or solenoid valves for sprinkler con- trol that fall within the Factory Mutual System Groups A, B, D, E, and G. A releasing circuit can actuate an unmatched pair of control heads or solenoid valves because it activates these releasing devices in parallel, not in series. This means that a releasing circuit can acti- vate the control valves for a waterless suppression sys- tem and a back-up pre-action-sprinkler system simultaneously which makes efficient use of the control unit's circuitry and increases system reliability by enabling a single action to operate both extinguishing systems. The releasing circuits are protected against inadvertent activation via the main microprocessor by the ARIES exclusive "Triple-R" (for triple redundancy) safeguard system. The "Triple-R" system requires that the main microprocessor issue two release commands, of oppo- site polarity and via separate signaling channels, and that these commands be combined with a signal from the control unit's watchdog timer confirming proper micropro- cessor operation, in order to activate a release circuit. This triply-redundant release-command requirement ensures that an electrical transient or disturbance that temporarily interferes with the operation of the main microprocessor will not inadvertently activate an extin- guishing system. NOTIFICATION-APPLIANCE CIRCUITS The ARIES Control Unit has four notification-appliance circuits (NACs). Each circuit can provide up to 1.5 Amps @ 24 Vdc for horns, strobes, chimes, or other notification appliances. Power for the notification appliances is fully filtered and regulated. Each NAC is programmable, and supports continuous and master-coded outputs for audi- ble devices. The NACs' coded patterns are dynamically adjustable and can be programmed to sound different codes to notify the occupants of progressively-more-seri- ous conditions. Both circuits are supervised, power limited, and are com- patible with conventional, UL Listed, 24 Vdc notification appliances. They can also be used with the following Kidde synchronizable horns and strobes without the requirement of an external synchronization module: MT Series Multi-Tone Horns and Horn/Strobes NS Series Horn/Strobes NH Series Horns RS Series Strobes The MT and NS Series notification appliances provide the option to use silenceable horns and non-silenceable strobes on the same NAC. Two of the NACs are also user-configurable to activate one solenoid for special-extinguishing-system actuation or pre-action/deluge sprinkler-system actuation like the regular releasing circuits. These NACs are also protected against inadvertent activation via the main microproces- sor by the ARIES "Triple-R" safeguard system when they are configured for releasing applications. ON-BOARD RELAYS AND AUXILIARY POWER The ARIES has four Form-C relays. Three of the four relays are user-programmable for any system condition and the fourth relay is dedicated to trouble conditions. Each relay is rated for 1 Amp @ 28 Vdc. Two auxiliary power outputs are provided, each with a 1- A output. These auxiliary power outputs are user config- urable for resettable or continuous power. INTEGRATION WITH SPECIALTY DETECTION SYSTEMS The ARIES is designed to integrate seamlessly with ORION TM XT High Sensitivity Smoke Detectors (HSSD®) via one or more ORION XT Interface Modules (PALM). It also integrates with Kidde's AlarmLineTm Cable via AlarmLine Addressable Modules and with Linear Heat- Sensing Cable (LHS) via regular monitor modules. The PALM permits an HSSD to be connected to the sig- naling line circuit and report pre-alarms and alarms in an addressable manner analogous to a SmartOne smoke detector. The AAM permits an AlarmLine cable to be connected to the signaling line circuit and report pre-alarms and alarms in an addressable manner analogous to a Smart- One heat detector. The LHS can report as a point-spe- cific alarm via an Al Monitor Module. PROGRAMMING The ARIES configuration tool is used to program the con- trol unit for each individual, site-specific application. Pro- gramming is for control-by-event scenarios, and consists of entering a series of conditional control statements that logically join initiating points to control-unit-based outputs and remote control modules. Each SmartOne field device can be assigned a location message of up to 40 charac- ters via the ARIES configuration tool. A USB Device Port is available to connect to a laptop computer for applica- tion upload. -2- SPECIFICATIONS 120 Vac, 50 Hz, 3.2 A 220/240 Vac, 50/60 Hz, 1.6 A 5.4 A @ 24Vdc Filtered and Regulated Inher- ently Power-Limited 70 Ah Maximum Capacity 12 Ah Fits Within Enclosure 255 Devices Maximum, Style-4, - 6, or -7 (with Isolater Modules) Class-A, Style-Z or Class B, Style-Y 24 Vdc, 1.5 A (maximum per circuit) Suitable for Synchronized Notifi- cation Appliances Configurable for: - One or two Control Heads and/ or Solenoid Valves - One Metron Actuator 24 Vdc, 2.4 A (maximum per circuit) Each Configurable as: Class-A, Style-Z or Class-B, Style-Y NAC, 24 Vdc, 1.5 A (Maximum per circuit) Suitable for Synchronized Notification Appliances OR Primary AC Power: Power Output: Battery (Sealed, Lead- Acid Only): I Signaling Line Cir- cuit: 2 Notification Appli- ance Circuits: 2 Releasing Circuits: 2 Combination Circuits: Release Circuit with One Control Head or Solenoid Valve 24 Vdc, 2.4A (maximum per circuit) Relays: 3 Programmable and iTrouble Relay. - 1.0 A @ 30 Vdc (resistive) -0.5A30Vdc (inductive) -0.5A @ 120 Vdc (inductive) 2 Auxiliary-Power Programmable for Resettable or Outputs: Continuous Output 1 A @ 24 Vdc (each output) 2 RS-232 Serial Ports: Bi-Directional 9600 Baud, 8 Data Bits, 1 Stop Bit, No Parity I RS485 Maximum 31 Remote Addresses Communications Port: (RDCM and ATM-L) I USB Device Port: USB Serial A front panel-activated AutoLearn routine can be exe- cuted that will create a general alarm, one input activates all outputs application to speed the system-configuration process. The more sophisticated Auto-Setup routine allows the ARIES System to be automatically configured for the typical control scenario utilized by waterless fire- suppression systems. OPTIONAL MODULES REMOTE LCD ANNUNCIATOR The ARIES Control Unit supports up to 15 remote LCD annunciators called RDCMs. This remote annunciator uses the same 80-character, backlit LCD display found on the main control unit. The RDCM permits remote event acknowledgment, alarm silencing, and system reset, and is secured with a key lock. User- and mainte- nance-level functions are also possible from the remote annunciator. GRAPHIC-ANNUNCIATOR DRIVER The Model ATM-L Annunciator Driver Module provides the ARIES Control Unit with up to 32 programmable, supervised LED outputs for graphical or tabular annunci- ators, along with 6 system-level LED outputs and 5 sys- tem-level inputs circuits for functional switches. The system-level LEDs correspond to the following gen- eral conditions: Module Power, Pre-Alarm, Alarm, Alarm Silence, Supervisory, and Trouble. The input circuits for functional switches provide for the following operator intervention: System Reset, Event Acknowledgment, Alarm Silence, Fire Drill, and Lamp Test. The ARIES supports up to 16 graphic annunciator driver modules. INTELLIGENT COMMUNICATIONS MODULE The Intelligent Communications Module (1CM) can be used to access the ARIES System via the Internet to view system status and current events and to download the history log. The 1CM can be programmed to transmit up to five e-mails upon the occurrence of any unsolicited event in the system. The e-mail message embeds a link with the IP address of the control unit that sent the mes- sage for instant access to the remote system. The 1CM can be accessed using any standard Web- browsing program and requires no special proprietary software. The 1CM also allows the ARIES Control Unit to report as a slave device via the Modbus TCP/IP Protocol to a mas- ter monitoring system for automated process control. -3- 1 Dimensions: Enclosure Only: 14-1/4 in. W 19 in. H x 5 in. D Enclosure with Door: 14-13/32 in. W 19-5/32 in. H x 5 in. D Optional Modules: - RDCM Remote Display Module - ATM-L Annunciator Driver Module - 1CM Internet-Accessible/Mod- bus-Conversion Module ORDERING INFORMATION Part Number Description 76-600000-001 ARIES Control Unit (Red) 76-600000-007 Trim Ring (Red) I I Kidde, HSSD, and SmartOne are registered trademarks of Kidde-Fenwal, Inc. ARIES, ORION, and AlarmLine are trademarks of Kidde-Fenwal, Inc. This literature is provided for informational purposes only. KIDDE-FENWAL, INC. I Kidde Fire Systems assumes no responsibility for the product's suitability for a particular application. The I product must be properly applied to work correctly. I If you need more information on this product, or if you have a particular problem or ques- I A UTC Fire & Security Company tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 8812000. 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 K-76-600 Rev AC © 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920 www.kiddefiresystems.com DS-PS Addressable SmartOne Protocol Photoelectric Smoke Detector FOR KIDDE FIRE SYSTEMS INTELLIGENT CONTROL UNITS FEATURES fr"Kidde Fire Systems Effective: January 2017 K-76-1O1 Optical smoke sensing technology Field-replaceable smoke chamber Works with SmartOne® communication protocol Compatible with Kidde, Fenwal and Chemetron branded intelligent control units Operates in conjunction with SmartOne CPD-7052, PSD-7152 and THD-7252 legacy detectors Detector head and terminal base design (bases sold separately) Low-profile design blends into ceiling DESCRIPTION Attractive 6 in. diameter trim ring provided with bases Electronic Addressing performed with SmartOne Hand-Held Programmer Advanced data analysis reduces chance of nuisance alarms Two-color (green/red) LED Suitable for raised floor and plenum applications FM Approved cULus Listed California State Fire Marshal Listed The DS-PS Photoelectric Smoke Detector is an intelligent device that uses an optical photoelectric sensing chamber to detect smoke. The detector's built-in microprocessor measures and analyzes sensor readings, making comparisons to historical data and filtering signal patterns that are not typical of fires to prevent unwanted alarms. The practical design of the DS-PS increases efficiency, saves installation time, cuts costs and extends life safety and property protection capabilities. The DS-PS detects extremely small particles of combustion and triggers an alarm at the first sign of smoke. With its high-perfor- mance forward scattering reflective response technology, the photoelectric smoke sensor responds quickly and reliably to a wide range of fire types, especially slow burning fires fueled by combustibles typically found in modern multi-use buildings. ADDRESSING DS-PS detectors feature electronic addressing. No addressing switches are used. LEDS OS-PS detectors use an LED to indicate the detector's condition. In normal condition, a flashing green LED indicates that the con- trol unit is performing background supervision and a flashing red LED indicates an alarm condition. LED PULSE MODES Normal, Standby: (green) flash at 9-second repetition rate Alarm: (red) flash at 2.5-second repetition rate INSTALLATION A OS-PS detector mounts to North American 1-gang boxes, 3-1/2 inch or 4 inch octagon boxes, and to 4 inch square electrical boxes 1-1/2 inches (38 mm) deep. LOCKING FEATURE The compatible detector bases include an optional locking fea- ture that prevents removal of the detector without use of a tool. To eliminate this feature, prior to placing the detector in a difficult-to- reach location, break and remove the plastic lever arm from the base. SENSITIVITY The alarm sensitivity is the minimum obscuration level at which the detector initiates an alarm condition and can be specified via the control unit menus or the remote configuration software. The control unit to which the detectors are connected is capable of interrogating each detector to determine its sensitivity. The table below lists the acceptable smoke sensitivity ranges for open air and in-duct detection: Model Detection elements Factory-assigned Adjustable alarm sensitivity point setting DS-PS Photoelectric (open air) 2.0% obscuration/ft. 0.9 to 3.5% obscuration/ft. DS-PS Photoelectric (in-duct) 2.0% obscuration/ft. 0.9 to 2.0% obscuration/ft. DETECTOR BASES I The DS-PS detector head attaches easily to these compatible bases. Detector bases have wiring terminals that are accessible from the "room-side" after mounting the base to the electrical box. A trim ring is supplied with the 4-inch base to help hide sur- face imperfections. Model DS-SB Standard Base: Connects the detector to the Signaling Line Circuit (SLC). I .Model DS-RB Relay Base: Connects the detector to the Signaling Line Circuit (SLC) and provides optional Relay functionality to the DS-PS detector. ACCESSORIES SIGA-DMP Detector Mounting Plate: The SIGA-DMP Duct Detector Mounting Plate is a 7 in. (178 mm) square mounting plate with a 4 in. (100 mm) square electrical box used to directly mount a DS-PS smoke detector inside an air duct. The SIGA-DMP includes screws for mounting the detector base and a rubber gasket that forms an airtight seal between the mounting plate and the air duct wall. 2-SPRCI Replacement Smoke Chamber: If cleaning of the DS-PS detector is unsuccessful, replacement of the smoke chamber may be necessary. 70-600000-100 Hand-Held Programmer: The SmartOne Hand-Held Programmer (with DS Series Programming Adapter) can be purchased separately to conveniently set the DS-PS electronic address in this manner. The control unit software can alternatively be used to set detector address. SM200-I2PKG Canned Smoke: A package of 12 canned smoke aerosol cans is available for purchase for routine testing of the DS-PS detector. PROTOCOL This product will operate only on a Kidde Fire Systems fire alarm-suppression control unit employing SmartOne communi- cations protocol. TECHNICAL SPECIFICATIONS Operating voltage 24 VDC (nominal) Current Normal Operating 150 pA Alarm 220 IJA Air velocity-Open Area ULJcUL: 0 to 4,000 ft./min (0 to 20.32 m/s) FM: 0 to 300 ft./min (0 to 1.52 m/s) Air velocity-In Duct [1] ULJcUL: 0 to 4,000 ft./min (0 to 20.32 m/s) Wall mounting: distance from ceiling 12 in. (305 mm) max. Compatible bases DS-SB (Standard), DS-RB (Relay) Operating Environment Temperature 32 to 120°F (0 to 49°C) Relative humidity 0 to 93% RH, non-condensing Storage temperature —4 to 140°F (-20 to 60°C) SLC Protocol SmartOne Environmental compensation Automatic Color White head and base Construction High impact engineering polymer Mounting Plug-in Shipping weight 0.44 lb. (164 g) [1] For duct installation, use a SIGA-DMP duct mounting plate. 2 ORDERING INFORMATION DS-PS Intelligent Photoelectric Smoke Detector, head only DS-SB Detector Mounting Base, 4 in. diameter, with 6 in. trim ring, for 2-wire connection to SmartOne SLC DS-RB Detector Mounting Base, 4 in. diameter, with relay option and 6 in. trim ring, for 2- wire connection to SmartOne SLC K i d d e Fire Systems SIGA-DMP Duct mounting plate for DS-PS detector 2-SPRCI Replacement smoke chamber for DS-PS 70-600000-100 SmartOne Hand-Held Programmer and accessories with DS Series Detector Programming Adapter 70-600000-110 DS Series Detector Programming Adapter SM200-I2PKG Canned smoke for functional testing of smoke detectors I I I I K-76-1O1 Effective: January 2017 REGULATORY INFORMATION lorth American CAN/ULC-S529-09, UL 268, UL 268A, standards FM Approvals 3230 JL/cUL smoke 0.9 to 3.50 %/ft. (2.95 to 11.48%/m) sensitivity range obscuration (Open Area Use) 0.9 to 2.0 %Ift. (2.95 to 6.56%/m) obscuration (In-Duct Use) NOTE: Detector sensitivity is selected at control unit or with remote configuration software. Default is 2.0%/ft (Alarm), 1.5%/ft (PreAlarm) :CC compliance This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. rondu,~tryCanada This Class A digital apparatus complies with mliance Canadian ICES-003. INTEGRATION OF DETECTORS DS-PS detectors can be mixed in any order with SmartOne legacy detectors on a Kidde Fire Systems intelligent control unit running SmartOne protocol. COMPATIBLE CONTROL UNITS Kidde ARIES NETLink Kidde ARIES Kidde PEGAsys * Fenwal FenwalNET 8000-ML Fenwal FenwalNET 6000 Fenwal FenwalNET 2000 * Chemetron MICRO MLX Chemetron MICRO SLX * OS Series detectors are compatible with FenwalNET 2000 and PEGAsys control units running software version 82.4. Note that FenwalNET 2000 and PEGAsys control units are no longer UL Listed or FM Approved. DS Series detectors have not been compatibility-tested on legacy control units older than FenwalNET 2000 and PEGAsys. - 0. TO I SMARTONE CONTROL UNIT I CPD-7052, PSD-7152 OR or THD-7252 DETECTOR ANOTHER DETECTOR (Not Polarity Sensitive) 7 OS-PS or DS-HFS \\ DETECTOR TO C) NEXT DETECTOR Figure 1: Combining Legacy Detectors with OS Series Detectors (Class B, Style 4 Wring Style Shown) NOTES: Detectors are not polarity sensitive. Terminals 3 and 7 (SmartOne) or Terminals 2 and 4 (DS Series) can be reversed. SmartOne and DS Series detectors can be installed in any order. SLC loop is not sensitive to the location of the control unit (can be left or right end of loop). Four-wire loops will be wired as above, bringing loose end of loop back to the control unit. SOFTWARE NOTE: The DS-PS detector does NOT support configurable alarm settings below 0.9%1ft. If a OS-PS is configured with a thresh- old below 0.9%/ft. for Alarm or 0.7%/ft. for Pre-Alarm, the detec- tor will operate at the lowest allowable setting. If the control unit is running software version 1.2.11 (for Single Loop panel) or software version 2.1.2 (for Multi-Loop panel) or later, the mes- sage 'INVALID THRESHOLD" will be reported on the Keypad! Display. However, if the control unit is running an older version of software, no message will be reported. fKidde Fire Systems K-76-101 Effective: January 2017 To next detector DS-RB Relay Base - Class B, Style 4 Wiring Shown TERMINAL DESIGNATIONS: Number Description Not used 2 SLC IN/OUT 3 Not used 4 SLC IN/OUT 5 Not used 6 Not used 7 Not used From control unit or From previous detector To next detector OS-SB Standard Base - Class B, Style 4 Wiring Shown TERMINAL DESIGNATIONS: Number Description 1 Normally Open 2 SLC IN/OUT 3 Common 4 SLC IN/OUT 5 Not used 6 Normally Closed 7 Not used From control unit or From previous detector I EXPORT INFORMATION (USA) Jurisdiction: EAR US ECCN: EAR99 This document does not contain any All trademarks are the property of their respective owners. export-controlled technical data. This literature is provided for informational purposes only. Kidde-Fenwal believes this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. Kidde-Fenwal, Inc. assumes no responsibility for the product's suitability for a particular application. The product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact Kidde-Fenwal, Inc., Ashland, MA 01721 USA. ?Kidde or Fire Systems I I I I K-76-101 Rev AA ©2017 Kidde-Fenwal, Inc. Kidde Fire Systems 400 Main Street Ashland, MA 01721 USA Ph: 508.881.2000 www.kiddefiresystems.com Addressable Contact Input Device Effective: January 2011 FEATURES Monitors N.O. or N.C! Unpowered Contacts Full Digital Communications Class B Initiating Device Circuit Remote-led Output Alarm Test from Control Unit Keypad UL Listed #S3743 FM Approved #ODA9AY CSFM #7300-1076:144 DESCRIPTION The SmartOne® Addressable Contact Input Device (Al) is an intelligent field device with its own microprocessor, memory and electronics necessary to interface N.O. or N.C. unpowered contacts to the FenwalNET control units. All of the electronics are contained in a high-impact polymer case, creating a very small and durable device for installation. Two types of Al's are available: an Al/NC for interfacing to normally-closed devices and an Al/NO for interfacing to normally-open devices. The Al may be located up to 2,500 feet from the monitored device with #18 AWG wir- ing. An end-of-line-resistor is required for supervision of the wiring to the device. FIELD PROGRAMMING System address, owner location message and reporting type are programmable via the compatible control unit configuration software program. The System address is a 4-digit number that uniquely identifies each device. The owner location message is a 40-character, alpha numeric message that describes the location of the device. The reporting type is assigned to the Al depending on the functionality of the device being monitored. SUPERVISION The Al continuously monitors the integrity of the follow- ing: Continuity of supervised wiring Power/Communications circuit voltage Internal power supply Memory data Faulty entering of data into Al memory STATUS LED A remote status LED may be connected to the Al. ALARM TEST Any or all Als can be tested by command from the com- patible control unit. Results of the test may be printed out at the system printer. SPECIFICATIONS Input Voltage: 16.5-27.5VDC Standby Current: 450 mA Max Alarm Current: 450 mA Max Operating Temperature: -31 - 151°F (-35 -660C) 0 - 95% RH LED PULSE MODES Normal: 9 second interval Trouble: LED isoff Alarm: 2 second interval Acceptable Wire Size: 14,16, I8AWG Installation: The Al can be mounted in a North American 2-1/2-in. (64 mm) deep, 1-gang box, or standard 4-in, square box, 1-1/2-in. (38 mm) deep with cover. - Page 8 of 25 - I Addressable Relay Output Device Effective: January 2011 FEATURES Full-Digital Communications Addressable Control Point Unpowered, SPDT Relay Contacts Control-by-Event And/or By Time Operation Status Indicator Unique Internal Supervision UL Listed FM Approved CSFM Approved DESCRIPTION The SmartOne® Addressable Relay Output Device (AO) is an addressable output module for control of auxiliary equipment such as air handlers, door release and eleva- tor recall. The AO connects directly to a compatible control unit's signaling line circuit (SLC) and contains a SPDT relay to control auxiliary equipment. All of the electronics are con- tained in a small high-impact polymer case. This creates a small and durable device for installation. The AO is field programmable with a unique four-digit address and a 40-character owner location message. The AO relay may be set or reset on command from the control unit. In addition to combinational-logic programming that uti- lizes system inputs (i.e., events) to activate this device, the unit may be programmed for real-time clock opera- tion. The real-time clock programming permits the AO to be activated and deactivated by the time of day, calendar date and day of the week. SUPERVISION The AO is continuously monitored for: Internal power supply voltages Faulty entering of data into AO's memory Relay state equals command state An internal set of relay contacts provides a feedback sig- nal that confirms the activation of the addressable relay output. If the relay fails to operate at the appropriate time, the device transmits a trouble report for display by the control unit. STATUS LED A status LED is mounted on the unit. SPECIFICATIONS Input Voltage: 16.5-27.5VDC Standby Current: 400 pA, Typical Alarm Current: 400 pA, Typical Contact Ratings: Resistive Contact Rating: - 2A@3OVDC Inductive Rating (Motor Control): - 1.OA @ 30 VDC, 0.6 PF.6A @ 120 VAC, 0.35 PF Pilot Duty - 0.6A @ 30 VDC, 0.35 PF Operating Environment: -31°F - 151°F (-35°C - 66°C) at 0-95% RH EMI Immunity: Meets UL 864 Dimensions: 2.3" x 1.8" x 0.8" nominal Shipping Weight: 5.1oz(145g) LED Pulse Modes: Normal: - 9 second interval Trouble: - LED isoff Alarm: - 2 second interval Acceptable Wire Size: 14, 16, 18AWG Installation: The AO can be mounted in a North American 1-1/2-in. (64 mm) deep 1-gang box, or standard 4-in, square box 1-1/2-in. (38 mm) deep with a cover. I I I I I I I I I I -Page 12 of 25- FRONT VIEW COVER REMOVED SIDE SECTION PT FEMALE, TO SYSTEM PIPING BOX 3 EACH SIDE 1/2" CONDUIT KNOCKOUTS Kidde ECS Fire Suppression System Component Description Pressure Operated Switch FEATURES For Use with UL Listed, ULC Listed and FM Approved Systems S S Kidde F ire Systems Effective: June 2014 See Kidde® Manual 06-236225-001 for USCG Approval PIN: 81-486536-000 UI I "— TO RESET PUSH STEM TO SET POSITION 15 AMP 125 VAC 10 AMP 250 VAC L 3/4 HP 1-2-3 PH 125-480 VAC 1/2" SUPPLY PIPE WITH UNION FRONT VIEW OPERATED -- SET NC c• C. C NC NC — — I -----L — — — - / 0 0 0 NO NO NO PRESSURE INLET WIRING DIAGRAM 4 SWITCH COVE EiI WIRING I SCREW TERMINALS I 'HP-i I PtNo. STEM SHOWN IN SET POSITION- PULL. UP ON STEM TO MANUALLY OPERATE SWITCH L- 0.375" 8 COVER SCREWS NOTES: The switch may be mounted in any position; how- ever, the preferred installation is upright, as shown. Any load connection to the switch must not exceed the switch rating, and shall utilize a suitable protec- tion device (i.e., circuit breaker, fuse). Contact Ratings (3 PDT): — 15Amp@125Vac — 1OAmp@250Vac — 3/4 HP@250Vac — 1,2or3Phase 1 COMPATIBILITY or Use F Series With Kidde ECS HFC-227ea X Kidde ECS Advanced Delivery FM2000 X FM-200 is registered trademark of E.I. du Pont de Nemours and Company. Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners. This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. The product must be properly applied to work correctly.lf you need more information on this product, or if you have a particular problem or question, contact Kidde-Fenwal Inc. Ad AV- 2 V,F Kidde Fire Systems K-90-5180 Rev BA ©2014 Kidde-Fenwal, Inc. Kidde Fire Systems 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com Kidde ECS Fire Suppression System Component Description Electric Control Head, Stackable Explosion Proof Kidde F i re Syste m s Effective: June 2014 K-81-9150 Rev BA FEATURES For use with UL Listed, ULC Listed & FMRC Approved Systems P/N: 82-486500-010 ELECTRIC CONTROL HEAD, PART NO. 486500-01 IS RATED FOR USE IN HAZARDOUS (CLASSIFIED) LOCATIONS CLASS 1, DIV. I, GROUPS C, D AND CLASS II, DIV. II, GROUPS E, F, G BETWEEN -40F AND 140F. USE CONDUIT SEAL WITHIN 18 IN. (45cm) OF THIS DEVICE. __F-2A ON - 1/2°-14NPT CONDUIT CONNECTION VG-LEADS S OVVIVL IMU I 1.25-18 UNEF-213 CONNECTION Note: This control head is polarized. Improper wiring will VOLTAGE: 24 VDC result in failure of this device to operate. CURRENT: 0.2A CONTINUOUS DRAW Electric control head, PIN: 82-486500-010, is designed for installation directly on 487 Series Halon and Kidde ECS agent valves only. This control head must not be A installed on any other type of halon or agent cylinder valve, nitrogen valve, car- WARNING bon dioxide cylinder valve, FE-13 cylinder valve or Stop (Directional) valve. Installa- tion of this control head to any other device (e.g., pressure operated control head) will result in failure of device to operate. COMPATIBILITY Series or Use F With Kidde ECS HFC-227ea X Kidde ECS Advanced Delivery FM-200® X This literature is provided for informational purposes only. KIDDE- FENWAL, INC. assumes no responsibility forthe product's suitability for a particular application. The product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL Inc. ©2014 Kidde-Fenwal, Inc. FM-200 is a registered trademark of E.I. du Pont de Nemours and Company. Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners. Kidde Fire Systems 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com I In-Line Releasing Device WKidde Fenwal Installation Instructions Effective: November 2004 S.d I I DESCRIPTION The in-Line Releasing Device, P/N 06-220023-001, is used to make a single-or dual-solenoid releasing circuit power limited. See Figure 1. - Figure 1. In-Line Releasing Device SUPPLIED PARTS in-Line Releasing Device, P/N 06-220023-001 REQUIRED TOOLS No.2 Fiat-Head Screwdriver. Small Rat-Head Screwdriver. PROCEDURE The In-Line Releasing Device is polarity-sensitive and must be connected as shown in Figure 2 for a single- solenoid circuit or as shown in Figure No. 3 for a dual- solenoid circuit. The red lead of the in-Line Releasing Device must be connected to the field wiring from Terminal I of the re- leasing circuit. The black lead must be connected to the control head or solenoid valve. Use wire. nuts to connect the In-Line Releasing Device to field wiring and leads from control heads and sole- noid valves. I I I I I I. . . Red Black . Control Head for Agent Storage fl Red container -_______ =JJ or I lneReleasIngDevl Black Solenoid Valve for Sprinkler I system Release- or Combo- Circuit Terminals I JUNCTION BOX (enlarged for clarity) Note: S S Junction box for in-Line Releasing Device must be close nlppied to control head or enclosure for solenoid valve. I Figure 2. Single-Control-Head or -Solenoid Releasing Circuit Release-Circuit ____ Terminals I Red Black Control Head for Agent Storage Red Container IneReleasing Dene Or Black Solenoid Valve for Sprinkler System Red Black In-Line Releasing Devi L~~Container JUNCTION BOX Control Head for Agent Storage or (enlarged for clarity) Black Solenoid Valve for Sprinkler System Note: Junction box for in-Line Releasing Device must be close nippied to control head or enclosure for solenoid valve. Use separate Junction boxes when control heads or solenoid valves are remote from each other. Figure 3. Dual-Control-Head or -Solenoid Releasing Circuit Kidde-Fenwal Is registered trademark of Kidde-Fenwel Inc. This llterstwe is prosided for Informational purposes only. KIDOE-FENWAL.INC. assumes no responsibility for the products suitability for a particular application. The product must be prop- erly applied 10 work correctly. if you need more Information on thia product, or If you have a particular problem or question, contact KlDDE.FENWl. INC.. Ashland. MAUI 721. Telephone: (508) 081-2000 06-236541-001 RevAA 02004 Kldde-Fenwal Inc. Printed In USA fKidde Fenwal Kidde-Fenwal, lnc.Ci 400 Main StreetO Ashland, MA 01721 U.S.A.LJ www.kldde-fenwa!,com I Component Description I Control Head Monitor (Explosion Proof Assembly) P/N 85-100000-100 Kidde Fire Systems Effective: November 2015 K-85-3000 Rev AA FEATURES UL Listed, ULC Listed, and FM Approved for use with systems listed in the Compatibility table. REACH and RoHS compliant The Control Head Monitor (CHM) with explosion proof assembly provides supervision for control head placement in normal and explosive environments in one easy to install component. EOL Resistor After Last - Device Blue i1. Control Head I IBlue White Monitor Control Panel Open when in activated position Figure 1. Control Head Monitor with Explosion Proof Assembly 1/2-14 NPT Note: Wires are 48' in length. I - -IIIIIIITI2 88OHEX 6.10 Figure 2. Control Head Monitor Dimensions I This CHM can be placed between the discharge valve and an electric or electric/cable operated control heads for retrofitting the existing system: I For US and Canada explosive proof installations, seal all conduits within 18 WARNING inches from the end of the component. I I I 1 I MATERIAL Body and Trigger: Brass Weight: 1.7 lbs. ORDER INFORMATION Part Number Description 85-100000-100 Control Head Monitor 85-100000-002 Spacer, required when installing Control Head Monitor on to Stackable Pressure Operated Control Head (PIN 82-878750-000) COMPATIBILITY Series For Use With DIOM P/N Supplement P/N Kidde ECS with HFC-227ea Agent X 06-236115-001 06-236115-003 Kidde Modular ECS with HFC-227ea Agent X 06-236116-001 06-236116-002 Kidde ADS with FM-2001M Agent X 06-236068-001 06-236068-003 Kidde ECS with 3MTM NovecTM 1230 Fire Protection Fluid X 06-236553-001 06-236553-004 Kidde ADS with 3M Novec 1230 Fire Protection Fluid X 06-237256-001 06-237256-005 Kidde FE-13Tm Engineered Suppression System X 06-236169-002 06-236169-003 Note: Agency listings also apply the Fenwal Engineered Fire Suppression Systems, when the Control Head Monitor is used on these legacy product lines. Standards for US Approval Number Issue Date FM 3600 2011 FM 3615 2006 FM 3616 2011 FM 3810 2005 ANSI/ISA 60079-0 2013 ANSI/ISA 60079-1 2013 ANSI/ISA 60079-31 2013 Standards for Canadian Approval Number Issue Date CSA C22.2 NO. 0.4 2013 CSA C22.2 NO. 0.5 2012 CSA C22.2 NO. 25 2014 CSA C22.2 NO. 30 2012 61010-1 2012 CAN/CSA 60079-0 2011 CAN/CSA 60079-1 2011 US Hazardous Location Markings: Canada Hazardous Location Markings: Class I, Div 1, Groups CD Class I, Div 1, Groups CD Class I, Zone 1, AEx d IIB T6 Class I, Zone 1, Ex d IIB T6 Class II, Ill, Div 1, Groups EFG Class II, Ill, Div 1, Groups EFG Zone 21, AEx tb IlIC T85°C Zone 21, Ex tb IlIC T85°C Ta = -40°C to 60°C Ta = -40°C to 60°C Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property of their respective owners. This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. The product must be properly applied to work correctly.lf you need more information on this product, or if you have a particular problem or question, contact Kidde-Fenwal Inc. K11 idde Fire Systems K-85-3000 Rev M ©2015 Kidde-Fenwal, Inc. Kidde Fire Systems 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com I Key Maintenance Switch kidde Fire Systems A UTC Fire & Security Company Effective: May 2009 I K-76-606 FEATURES cFMus Approved to ANSI/UL 864, 9th edition, CANADA/ULC-S527 and ANSIINFPA 72 Stainless Steel Plate Status LED Indicators Surface or Flush Mount Installations Safely Disconnects Actuation Circuits by Shorting Metron Actuators Key Operated (Nonremovable When Operated) Four-Pole Double-Throw Switch Meets the Requirements of NFPA72 (2007 edition) I I DESCRIPTION This Key Maintenance Switch is a key-switch that discon- nects actuation circuits in the system to prevent acciden- tal discharge of fire suppression systems during maintenance operations. The Key Maintenance Switch provides a means to short the Metron Actuator circuit leads for safe disconnection of conventional and addressable control units. Refer to the installation wiring diagram for detailed wiring connec- tions. Two LEDS indicate "SYSTEM ARMED" or "SYSTEM INACTIVE" when the key is inserted and turned. The key can only be removed in the armed position. Key Maintenance Switch mounts to a 4-inch backbox and operates on 24 Vdc. Designed for mounting on the wall with a back box. Key Maintenance Switch can be installed in either surface mount or flush mount configurations. Key Maintenance Switch physically disconnects the release circuit wiring in addition to the trouble open signal, the switch provides a means to generate a supervisory condition. ORDERING INFORMATION Part Number Description 76-600000-200 Key Maintenance Switch 06-236881-001 Backbox I 4441111 i 1q11 Switch: 4PDT Key Switch - one set of contacts control indicators on the faceplate. - Three remaining contacts are available for application wiring. Device Current: 10 A @ 250 Vac 15A@ 125 Vac 15 Aup to 30 Vdc Electrical Life: 50,000 cycles - maintained 25,000 cycles - -momentary ENVIRONMENTAL Operating Temperature 32 to 120°F (0 to 49°C) Range: MECHANICAL Mechanical Life: 100,000 cycles Switch Plate Stainless Steel Construction: I I I This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes tsiaae I-ire systems no responsibility for the product's suitability for a particular application. The product must be A UTC Fire & Security Company properly applied to work correctly. 400 Main Street If you need more information on this product, or if you have a particular problem or question, Ashland MA 01721 contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. Ph: 508.881.2000 K-76-606 Rev AB © 2009 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920 www.kiddefiresystems.com I I Effective: January 2011 Addressable Manual Pull Station Kidde Fire Systems Series 3300 A UTC Fire & Security Company FEATURES Unique Field Labeling for either Fire Alarm or Suppression Applications Dual Action Operation Surface and Weatherproof Backboxes Flashing LED Keylock for Reset UL Listed #S5654 FM Approved cUL Listed #7150-1076:147 DESCRIPTION The Kidde® Addressable Manual Pull Stations is an intel- ligent initiating device that contains its own SmartOneTM Addressable Input (Al) module and interfaces directly to the Kidde PEGAsysTM and ARIESTM control panels. The initiating device circuit is wired as NFPA Class B. The Manual Pull Station is constructed of heavy die-cast aluminum for long life and uses an internal toggle switch for reliable operation. Similiar to the SmartOne devices, the unit is field pro- grammable using the control panel keypad or Hand-Held Programmer. The owner location message and reporting type can be customized by the use of a programming util- ity utilized with the control panel. A status LED is mounted on the unit and indicates the status by a 2 or 9 second flash interval. A Trouble condition inhibits the sta- tus LED completely. While the Pull Station is designed for quick, efficient emergency response, its double action PUSH/PULL levers prevent accidental operation. The Pull Station can be mounted in an indoor or outdoor weatherproof backbox (Model SBG-32S or Model SG13- 32C) or a North American 2-1/2 in. (64 mm) deep single- gang box. The Station terminal block on the Al module accepts 14, 16 and 18 AWG (1.5 mm2, 1.0 mm2, and 0.75 mm2) wire. Size #18 is the minimum requirement. FIRE ALARM OR SUPPRESSION RELEASE LABELING The Pull Station has a unique labeling method which pro- vides the installer the greatest amount of flexibility with- out the expense of having to carry extra inventory. Seven heavy-duty Lexan® self-adhesive labels are shipped with each station: PUSH PULL 'I 9. FIRE ALARM • FM-200 RELEASE NOVEC 1230 RELEASE • FE-13 RELEASE FIRE SYSTEMS • HALON RELEASE RELEASE - Page 22 of 25 - SPECIFICATIONS DIMENSIONS Station Type: Double Action, with integral SmartOne Addressable 1-5/64 in. (27 mm) Module 1 Initiating Device Circuit: 3-1/4 In. _ 31/32 In. (83 mm) (24 mm) EOL Resistor Value: - 0 K Ohm (06-129025-003) Max. Circuit Resistance: - 50 Ohm (25 ohm per conductor) FIRE FIRE ( 0 ........................ .. Max. Circuit Capacitance: SYSTEM SYSTEM RELEASE (f) - 0.1 pF I[ •11 PUSH Operating Temperature Range: 43/4 In. -40°F to 150°F (-40°C to 66°C) (121 mm) _____ _____ I I Operating Humidity Range: 0-95% RH Construction: 0 001M 'I Die-cast metal housing 2-1/4 in. MAX Compatible Electrical Boxes: (57 mm) Indoor: - Sheet metal Model SGB-32S Outdoor: - Weatherproof Die-cast Model SGB-32C Shipping Weight: 1.12lbs.(510g) SGB-32S INTERIOR SURFACE BACKBOX Dimensions: 4-3/4 in. H x 3-1/4 in. W x 2-1/4 in. D Construction: Steel sheet metal Conduit: Two knockouts for 1/2 in. conduit connectors, one on top and bottom Mounting: Mounts to the box with (4) 8/32 screws, which ship with each box SGB-32C WEATHERPROOF SURFACE BACKBOX Dimensions: 4-3/4 in. H x 3-1/4 in. W x 2-1/4 in. D Construction: Cast aluminum Conduit: One threaded opening for 1/2 in. conduit connector Mounting: Mounts to the box with (4) 8/32 screws and a foam gasket, which ship with each box - Page 23 of 25 - Model 878752 ov Suppression System Abort Station (Kidde Fire Systems i Effective: November November2014 FEATURES UL Listed Flush or Surface Mount One Normally Open Contact Sized for Double Gang Box DESCRIPTION The Kidde® Model 878752 Abort Station features a large, easy-to-operate abort push button. The momentary type switch is very easy to see due to its highly visible yellow color. The abort station stainless steel faceplate is clearly labeled with operation procedures—eliminating indeci- sion and hesitation. The Backbox is painted with red enamel and is provided with four 1/2-inch knockouts. The pre-drilled and tapped mounting tabs allow for easy attachment of the abort station. To make the Abort Station an addressable SLC device for use with Kidde Intelligent control units, one SmartOne® Model Al monitor module (purchased separately) must be installed into the backbox. The Model Al monitor mod- ule is seated inside a bracket (included) and easily installs with two mounting screws. A cULus-listed Abort Station for Canadian applications that require compliance to ULC S527-11 (3rd edition) is also available (blue faceplate with white raised lettering). Order PIN 84-878752-110. TECHNICAL SPECIFICATIONS Electrical Ratings: One normally open momentary contact, rated 2.5 Amps @ 120 Vdc Ambient Temperature: -13°F to 158°F (-25°C to 70°C) Terminals: Captive screws and saddle clamps accept 14 AWG to 24 AWG wire Mounting: Four 6-32 x 1/2-inch mounting screws included ORDERING INFORMATION Part Number Description Shipping Weight 84-878752-010 Abort Station 2 lb. (0.9 kg) 06-236881-001 Backbox, Red 1 lb. (0.45 kg) Model Al Addressable 5 oz. (145 g) 70-407008-001 Monitor Module, N.O. (includes bracket) Large Yellow Push Button Switch Abort Station Becomes Addressable SLC Device with installation of one (1) Model Al Addressable Monitor Module, N.O. 4-1/2 in. _ (1114 mm) I 4-1/2 in. PUSH! (114 mm) 0 HOLD 1-11/16 in1 SUPPRESSION SYSTEM ABORT ____ fKidde& (43 mm) 3-3164 in. I (71 mm) 2 in m) 4-5/8 in. (51 m 117mm 4-5/8 In. ii7mm Figure 1. Dimension Details This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems no responsibility for the product's suitability for a particular application. The product must be 400 Main Street properly applied to work correctly. Ashland, MA 01721 If you need more information on this product, or if you have a particular problem or question, Ph: 508.881.2000 contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. Fax: 508.881.8920 www.kiddefiresystems.com I FM-200® Component Description (Ir Kidde Fire Systems I Warning Nameplate (FM-200) A UTC Fire & Security Company 'Effective: April 2007 FEATURES I . For Use with UL Listed, ULC Listed and • See Kidde Manual 90-FM200M-021 for FM Approved Systems USCG Approval I P/N: 06-231865-739 1 10.000 0.063 I 0.340 9.360 I 10.340 I WARNING THIS AREA IS PROTECTED BY A I 0.062 FM-200 EXTINGUISHING 5.000 4.360 SYSTEM. DO NOT ENTER WITHOUT I AUTHORIZATION DURING OR I . AFTER DISCHARGE `- 0.281 .005 DIA. TYP. 4 HOLES MATERIALS Aluminum Type 1100—H14, 0.032 ± 0.003 Thick. All Let- ters to be 48 pt., Alternate Gothic #2, Etched 0.003 to 0.005 and Filled in With Red Chip Proof Enamel Color No. 21105 per Fed. Stc. 595 Finish: One Coat Clear Lacquer Both Sides FM-200 is a registered trademark 01 the Great Lakes Chemical Corporation This literature is provided for informational purposes only. KIDDE-FENWAL INC. assumes Kidde Fire Systems no responsibility for the products suitability for a particular application. The product must be A UTC Fire & Security Company properly applied to work correctly. 400 Main Street If you need more information on this product, or if you have a particular problem or question. Ashland MA 01721 contact KIDDE-FENWAL. INC., Ashland, MA 01721. Telephone: (508) 881-2000. Ph: 508.881.2000 K-90-9030 Rev AB © 2007 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920 www.kiddefiresystems.com W5TEi Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrA/ed® Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. Features Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela Field-selectable candela settings on wall units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and three volume selections Universal mounting plate for wall units Mounting plate shorting spring checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert devices Compatible with MDL3 sync module Listed for ceiling or wall mounting R-Olu 1 71 The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement. Like the entire SpectrAlert Advance product line, wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections. F litAc F Agency Listings SISNAUNG ®<>MEA USTED $4011 (chimes, horn strobes, $5512 (strobes) APPROVED horns) 3023572 approved MEA452-05-E 7125-1653:186 (indoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) SpectrAlert Advance Specifications General SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync.Circuit° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model ______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model ______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply. I Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also I control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. I Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second I Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) I Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6L x 4.7W x 2.5D (142 mm Lx 119 mm W x 64 mm D) Horn Dimensions 5.6L x 4.7W x 1.3D (142 mm Lx 119 mm W x 33 mm D) Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 5.7"L x 4.8"W x 0.35'D (145 mm Lx 122 mm W x 9 m D) Notes: Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL 1 - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-1076:0183 Page 1 of 1 CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: KIDDE-FENWAL, 1NC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 Email: terrill.garlandkidde-fenwal.com DESIGN: Model ARIES fire alarm control unit. Automatic, manual, local, central station, waterfiow, sprinkler supervisory and releasing device services. Refer to the listee's data sheet for detafled product description and operational considerations. System components: 76-600000-001 ARIES Control Unit 76-600000-004 Motherboard 76-600000-011 Keypad/Display 06-118394-002 Power Supply 06-220023-001 In-Line Releasing Device (EOLD) 76-600000-002 Enclosure *76600000009 Network Interface Card RATING: Primary: 120/240 VAC, Standby: 24 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a fire alarm control unit for use with listee's separately listed electrically and functionally compatible initiating and indicating devices. Refer to manufacturer's Installation Manual for details. This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. This control unit meets the requirements of UL-864, 9th Edition Standard. NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. Rev 06-02-2006 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct i?Vt operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 3O,2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division I - CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - I FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-1076:0502 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: KIDDE-FENWAL, 1NC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 ' Email: terrill.garlandkidde-fenwal.com DESIGN: Model DS-PS Addressable photoelectric smoke detector. Refer to listee's data sheet for detailed product description and operational considerations. RATING: 24Vdc INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a photoelectric type smoke detector for use with listee's separately listed compatible fire alarm control unit Model ARIES (CSFM# 7165-1076:0183), Model FENWALNET 6000 (CSFM# 7165-1076:0184), Model FENWALNET 8000-ML (CSFM# 7165-1076:0194), Model ARIES NETLink (CSFM# 7165-1076:0195), Model MICRO SLX (CSFM# 7165-0061:0153) and Model MICRO MLX (CSFM# 7165-0061:0155). The panel programming limits for this device are from 0.9-3.5 percent perfoot obscuration for velocities from 0-300 ft/min.and 0.9-2.00 percent per foot obscuration for velocities from 300-4000 ft/mm. including installation inside ducts. Refer to manufacturer's Installation Manual for details. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires, which smolder for hours before bursting into flames. Sources of these fires may includecigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. I 09-08-2016 do I j\ This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff the test results and/or other data but does not make an independent verification of any claims. This has reviewed listing is not I - an endorsement or recommendation of the item listed. This listing should not be used to verify correct klIv%C operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTIL.LO, Program Coordinator I Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL T - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1076:0504 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: KIDDE-FENWAL, 1NC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 Email: terrill.garIandkidde-fenwal.com DESIGN: Models DS-SB and DS-RB detector bases. Model DS-SB is a standard base and Model OS-RB is a relay base. Refer to listee's data sheet for detailed product description and operational considerations. RATING: 30 Vdc, IA INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as detector bases for use with listee's Model OS-PS (CSFM# 7272-0176:0502) and Model DS-HFS (CSFM# 7272-0176:0503) detectors. Refer to manufacturer's Installation Manual for details. 11-02-2016 dc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct IVI operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1076:0120 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: KIDDE-FENWAL, INC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 Email: terriIl.garIandkidde-fenwal.com DESIGN: Models P/N 30-232001-001 front panel w/cutout for audible and PIN 30-232001-002 front panel w/o cutout for audible. These units have a manual release switch and abort switch. Models 878752-01/-02, 30-193000-001/-002 abort stations. Models 1296105, 30-193000-003 back boxes. Models 30-322003-003, 84-322003-003 Remote Display Unit Backbox. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. For indoor use only. MARKING: Listee's name, model number, and UL label. APPROVAL: Models 30-232001-001 and 30-232001-002 are listed as control unit accessories when used in conjunction with listees' separately listed fire alarm control units. Models 878752-011-02, 30-193000-001/-002 abort stations and Models 296105, 30-193000-003 back boxes are intended for use with listed releasing device control units. *Rev. 06-21-2003 BH This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct lvsG operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 1 Date Issued: July 01, 2018 Authorized By: DAVID CASTILLO, Program Coordinator I Fire Engineering Division Listing Expires June 30, 2019 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1076:0144 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: KIDDE-FENWAL, 1NC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 Email: terrill.garlandkidde-fenwaI.com DESIGN: Control Unit Accessories. Refer to listee's data sheet for additional detailed system description and operational considerations. Models 70-407008-001 and 70-407018-001; normally-open contact input devices Models 70-407008-002 and 70-407018-002; normally-closed contact input devices Models 70-408004-001 and 70-408014-001; addressable relay output devices Model 30-472001-000; remote trouble indicating panel Model 74-200041-001; limiting resistor Models 74-200012-001, 74-200012-002 and 74-200012-004; loop isolators Models 89-100081-001 AIM (AnaLASER Interface Module) and 89-100083-001 IIM-2000 (Stand Alone) Models 70-200200-001 and 70-200200-003 ASM (Addressable Signal Sounder Module), 73-100001-003 MM (Addressable AlarmLine Module), 73-100003-001 MM; NEMA 4 Enclosure, *Models *74800300001, *76800300001; RDCMs (Remote Display Control Modules) Models *74.800300..101 and *76800300101; RDM (Remote Display Modules) Enclosures Models 74-300004-032 and 76-200004-032 ATM-L; (Annunciator Driver Modules) Models 74-300005-032, and 76-200005-032 ATM-R; (Relay Driver Modules) Models 74-100017-001, 76-100010-001, 74-600000-014, and 74-600000-514; Battery Boxes. Models 74-600000-006, 74-600000-516 and 76-600000-006 Fiber-Optic Converter Cards (0CC) Models 06-220171-001 thru -007; Compensating Resistors. Models 70-600000-001 and 70-600000-002; Remote Releasing Modules Models 30-330002-001 and 84-330002-001; Addressable Manual Pull Stations. For indoor use with Model SGB-32S back box or outdoor use with SGB-32C back box. RATING: Electrical: 24 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: *Listed as control unit accessories for use with listee's separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. Rev. 08-20-12 gt 0 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct 1V% operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL I - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-1076:0147 Page 1 of 1 CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: KIDDE-FENWAL, 1NC400 Main Street, Ashland, MA 01721 Contact: Terrill Garland (508) 881-2000 Fax (508) 881-1773 Email: terrill.garlandkidde-fenwal.com DESIGN: Models BIO and Bi 1, 30-195000-002*, 30195000004*, 30-330001-001, 30-330001-002, 84-330001-001 and 84-330001-002 key lock, push bar, noncoded manual pull stations; Models 30195000001* and 30195000003* key lock, no push bar, noncoded manual pull station. Suitable for outdoor use when installed with Model SGB-32C back box. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 30 VDC INSTALLATION: In accordance with listee's printed installation, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as manual pull stations for use with separately listed and compatible fire alarm control units. * Only Models 30-195000-001, -002, -003, and -004 manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. XLF: 7150-1408:0107 *Update 06-22-09 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct ?VtC operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division I I I I I