HomeMy WebLinkAbout5600 AVENIDA ENCINAS; ; FS050008; Permit6/2/22,1:48 PM FS050008 Permit Data
City of Carlsbad
Fixed Systems Permit
Permit No: FS050008
5600 AVEN IDA
Job Address: Status: ISSUED
ENCINAS
Permit Type: FIXSYS Applied 7/5/2005
Parcel No: 2100905000 Approved: 7/20/2005
Lot #: 0
Reference No.: Issued: 7/20/2005
PC #: Inspector:
Project Title: SAN DIEGO INTERNATIONAL FLORAL FIRE SUPPRESSION
SYSTEM PLAN CHECK & INSPECTIONS
Applicant: Owner:
SIMPLEX GRINNELL PALAMA HUNA L L C
9855 CARROLL CANYON RD 1420 BRISTOL ST N #100
SAN DIEGO CA NEWPORT BEACH CA
858-740-0100
Fees ($) Add'l Fees ($) Total ($) Balance ($)
115 0 115 0
1/1
ANSUL
DESIGN.
INSTALLATION
RECHARGE AND
MAI NTENANO
MANUAL
R-102 RESTAURANT,
FIRE SUPPRESSION
SYSTEM
(Standard UL 300 Listed)
I
II
"ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY
(MECHANICAL)
NOTE: AGENT TANK MUST S
ORDERED SEPARATE
OR SEE PAGE 3-4
RELEASE
MECHANIS
1~ REGULATOR
SHIPPING WI. 25 LB. (11 kg)
FIGURE 2
000136
REGULATED RELEASE ASSEMBLY (ELECTRICAL)
The ANSUL AUTOMAN Regulated Electrical Release Assembly
(Part No. 429856) is identical to the mechanical version except it
also contains a factory installed 120 VAC solenoid and electrical
switch.
The solenoid is used to provide electrical actuation of the release
mechanism. The electric switch is used to protect the solenoid by
opening the circuit to the solenoid once the system is fired.
Additional electrical switches can be added as required for auto-
matic equipment and gas shut-off accessories, as well as initiating
audible and visual alarms.
"ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY
(ELECTRICAL)
NOTE: AGENT TANK MUST
BE ORDERED
SEPARATELY
OR SEE PAGE 3-4
REGULATOR SWITCH
SOLENOID
SHIPPING WE 34 LB. (15 kg)
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-1
10-1-02 REV. 3
EXTINGUISHING AGENT
ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon - Part No.
79694 or 3.0 gallon - Part No. 79372) is a potassium-based solu-
tion designed for fast knock-down and suppression of grease-
related fires. The agent is shipped in plastic containers which pro-
vide one complete tank charge. Agent storage life expectancy is
twelve years. The distributor must record the batch numbers and
date of shipment receipt to be filed with each installation record.
ANSULEX LOW pH LIQUID FIRE SUPPRESSANT
3.0 GALLON 1.5 GALLON
SHIPPING WI. 35 LB. (16 kg) SHIPPING WT. 19 LB. (9 kg)
000136 000137
FIGURE 1
REGULATED RELEASE ASSEMBLY (MECHANICAL)
The ANSUL AUTOMAN Regulated Mechanical Release Assembly
(Part No. 429853) contains the regulated release mechanism,
expellant gas hose for agent tank hookup, and enclosure knock-
outs to facilitate installing actuation piping; expellant piping; detec-
tion system; and additional equipment. This regulated release
assembly is used in single, double, and multiple-tank systems and
must be mounted to a rigid surface. The release mechanism can
be used to interconnect both the actuation and expellant gas lines
as required per system design. The regulator is designed to allow
a constant flow of gas into the tank at 110 psi (759 kPa) when the
system is actuated. The agent tank must be ordered separately.
In single, double, and multiple-tank systems, the provided expel-
lant gas hose connects the agent tank to the bottom outlet of the
regulator. In double and multiple-tank system configurations, the
back outlet of the regulator is used as an expellant gas feed for
one additional tank-enclosure or tank-bracket hookup. The enclo-
sure contains the required knockouts to facilitate this connection.
If a pressure switch is to be attached to the regulator, additional fit-
tings are required.
The tank (ordered separately) is mounted within the enclosure.
The tank contains an adaptor/tube assembly with a burst disc
union. The burst disc helps prevent siphoning of the agent up the
pipe due to significant temperature fluctuations in the area where
the tank is located. The tank is mild steel and, under normal con-
ditions, requires hydrostatic testing every twelve years.
The detection and additional equipment required per system
design are connected to the release mechanism. The enclosure
contains knockouts to facilitate detection and additional hookups.
The system can be actuated automatically or manually. Automatic
actuation occurs when a fusible link within the detection system
separates in a fire condition. Manual actuation of the system
occurs when personnel pull on the remote manual pull station
pull ring.
FIGURE 3
000139
SECTION IX - APPENDIX
UL EX. 3470 ULC CEx747 Page 9-1
10-1-02 REV. 5
SYSTEM SELECTION GUIDE
NOTE: System Options do not cover all conceivable variations. They are listed here as a general guideline to show the most common
type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3-tank systems,
etc., other tank/cartridge combinations can be designed. The combinations below are based on ii flow, 3.0 gallon tanks and 5
flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate.
Total Tank Type of Carbon Dioxide Nitrogen
Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required
1-5 1 Single 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429)
6-11 1 Single 3.0 Gal. Reg. Release 101-20 (423441) LT-30-R (423435)
12-16 2 Double 1.5 Gal. Reg. Release 101-30 (423443) Double (423493)
3.0 Gal. Additional Tank
Double (423493)
LT-30-R (423435)
LT-A-101-30 (423491)
LT-20-R (423429)
LT-A-1 01 -30 (423491)
Double (423493)
LT-20-R (423435)
LT-A-1 01-30 (423491)
Double (423493)
LT-A-101-30 (423491)
LT-30-R (423435)
LT-A-101-30 (423491)
Double (423493)
LT-A-1 01-30 (423491)
Double (423493)
LT-A-101-30 (423491)
LT-20-R (423429)
LT-A-101-30 (423491)
LT-A-101-30 (423491)
17-22 2 Double 3.0 Gal. Reg. Release 101-30 (423443)-
3.0 Gal. Additional Tank
23-33 3 Multiple 3.0 Gal. Reg. Release 101-20 (423441)
3.0 Gal. Reg. Actuator 101-30 (423443)***
3.0 Gal. Additional Tank
23-27 3 Multiple 1.5 Gal. Reg. Release 101-10 (423439)
(Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)--
3.0 Gal. Additional Tank
28-33 3 Multiple 3.0 Gal. Reg. Release N/A
(Optional) (2) 3.0 Gal. Additional Tanks
34-38 4 Multiple 1.5 Gal. Reg. Release 101-10 (423439)
3.0 Gal. Reg. Actuator N/A
Double 3.0 Gal. Tank Box
34-38 4 Multiple 1.5 Gal. Reg. Release 101-30 (423443)
(Optional) 3.0 Gal. Additional Tank
30 Gal. Reg. Actuator 101-30 (423443)***
3.0 Gal. Additional Tank
39-44 4 Multiple 3.0 Gal. Reg. Release 101-20 (423441)
3.0 gal. Reg. Actuator N/A
Double 3.0 Gal. Tank Box
39-44 4 Multiple 3.0 Gal. Reg. Release 101-30 (423443)**
(Optional) 3.0 Gal. Additional Tank
3.0 Gal. Reg. Actuator 101-30 (423443)***
3.0 Gal. Additional Tank
45-49 5 Multiple 1.5 Gal. Reg. Release 101-30 (423443)
3.0 Gal. Additional Tank
3.0 Gal. Reg. Actuator N/A
Double 3.0 Gal. Tank Box
45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439)
(Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)***
3.0 Gal. Additional Tank
3.0 Gal. Reg. Actuator 101-30 (423443)***
3.0 Gal. Additional Tank
Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system.
If tanks are manliolded, only a "double tank"nitrogen cartridge (Part No. 423493) can be used.
If tanks are manifotded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used.
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-5
10-1-02 REV,4
NOZZLES
There are twelve types of discharge nozzles each designed to dis-
tribute the liquid agent in a uniform pattern throughout the hazard
area:
' 1. 1W Nozzle 7. 245 Nozzle
2. 1 N Nozzle 8. 260 Nozzle
3. 1/2N Nozzle 9. 290 Nozzle
4. 3N Nozzle 10. 2120 Nozzle
5. 2W Nozzle 11. 1 Nozzle
6. 230 Nozzle 12. 1100 Nozzle
Although these nozzles are similar in appearance and have
certain common parts, the tip of each nozzle is designed for a
specific application and must only be used in those areas See
Nozzle Application Chart in Section IV - System Design, for
individual nozzle usage.
3/8— 18 NPT
FEMALE THREAD
INTERNAL CUP
STRAINER
INSIDE•
RECESS FOR
BLOW OFF
CAP LOOP VENDOR
CODE
NOZZLE (IF PRESENT)
STAMPING
N. FIGURE 13
000002
Nozzle identification Chart
Nozzle
Nozzle Nozzle Nozzle* Flow
iyp e Part No. Stamping No. Nozzle Identification
1W Nozzle 419336 1W 1 Chrome-Plated Body
iN Nozzle 419335 iN 1 Chrome-Plated Body
1/2N Nozzle 419334 1/2N 1/2 Chrome-Plated Body
Metal blow-off caps are not allowed with the 1/2N nozzle
3N Nozzle 419338 3N 3 Chrome-Plated Body
2W Nozzle 419337 2W 2 Chrome-Plated Body
230 Nozzle 419339 230 2 Chrome-Plated Body
245 Nozzle 419340 245 2 Chrome-Plated Body
260 Nozzle 419341 260 2 Chrome-Plated Body
290 Nozzle 419342 290 2 Chrome-Plated Body
2120 Nozzle 419343 2120 2 Chrome-Plated Body
1F Nozzle 419333 1 1 Chrome-Plated Body
1100 Nozzle 430912 1100 1 Chrome-Plated- Body
* Nozzle stamping may Contain an additional letter indicating a vendors code.
SWIVEL ADAPTOR
The Swivel Adaptor Assembly, Part No. 418569, consists of a
swivel nut, swivel body and swivel ball. All are chrome-plated. The
swivel adaptor allows any nozzle to be rotated approximately 300
in all directions. Swivel Adaptors must be ordered as a Swivel
Adaptor Shipping Assembly, Part No. 423572, which contains 25
Swivel Adaptors.
3/8 - 18 NPT
FEMALE THREAD
PT
READ
30 DEG
ROTATI
FIGURE 14
000003
RUBBER BLOW-OFF CAPS
The Rubber Blow-Off Cap, Part No. 77676, help keep the orifice of
the nozzle free of grease or other substances that could interfere
with agent distribution. A retaining strap attaches the blow-off cap
to the nozzle. Rubber Blow-Off Caps must be ordered as a
Shipping Assembly, Part No. 77695, which contains 50 blow-off
caps, or Part No. 77411, which contains 12 blow-off caps.
FIGURE 15
METAL BLOW-OFF CAP
Two types of metal blow-off caps are available as options to the
standard rubber caps. The metal cap can be used in unusually
high heat conditions, generally over 400 °F (204 °C). The metal
blow-off cap is attached to the nozzle by means of a stainless steel
wire which prevents it from falling into the appliance during dis-
charge. Shipping Assembly Part No. 79745 contains 10 metal
blow-off caps for use on standard, non-swivel nozzles and
Shipping Assembly Part No. 415568 contains 10 metal blow-off
caps for use on swivel nozzles,
NOTICE
If metal blow-off caps are required for upright broil-
er or salamander protection, use (2) two 1 noz-
zles (Part No. 56930) instead of 1/2N nozzles.
LESS
t1000
STEEL WIRE
METAL CAP
FIGURE 16
000152
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-28
REV.3 10-1-02
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct, plenum,
or appliance.
NOTICE
This chart is for general reference only. See
complete details for each type of hazard.
Minimum
Maximum Hazard Nozzle
Hazard Dimensions Quantity
Duct or Transition Length - Unlimited 1
(Single Nozzle) Perimeter - 50 in. (127 cm)
Diameter— 16 in. (40.6 cm)
Duct or Transition Length - Unlimited 1
(Single Nozzle) Perimeter— 100 in. (254 cm)
Diameter - 31 7/8 in. (81 cm)
Duct or Transition Length - Unlimited 2
(Dual Nozzle) Perimeter— 150 in. (381 cm)
Diameter-48 in. (122 cm)
Electrostatic Precipitator Individual Cell 1
(At Base of Duct)
Plenum Length - 10 ft. (3.1 m) 1
(Horizontal Protection)
Plenum Length - 6 ft. (1.8 m) 1 (Horizontal Protection) Width - 4 ft. (1.2 m) 1
Plenum Length - 4 ft. (1.2 m) 1 (Vertical Protection) Width —4 ft. (1.2 m)
Fryer/Split Vat Fryer** Maximum Size
(without drip board)
15 in. (38 cm) x
14 in. (36 cm)
High Proximity 1
Medium Proximity 1
Maximum Size
(without drip board)
19 1/2 in. (49.5 cm) x
19 in. (48.2 cm)
High Proximity 1
Low Proximity 1
Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 in. (45.7 cm)
High Proximity 1
Nozzle Tip
Nozzle Nozzle Stamping - Heicihts Part No. FlQw No.
- 430912 1100
- 419337 2W
- 419337 2W
- 419334 1/2N
- 419335 iN
- 430192 1100
- 419336 1W
- 419336 1W
27-47in. 419339 230
20-27in. 419340 245
21-34 in. 419338 3N
13—l6in. 419342 290
25-35 in. 419338 3N
(64-89 cm)
For multiple nozzle protection of single fryers, see detailed information on Pages 4-12 through 4-14.
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-29
p. 10-1-02 REV. 3
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights Part No. Flow No.
Fryer/Split Vat Fryer** Maximum Size
(with drip board)
21 in, (53 cm) x
14 in. (36 cm)
(Fry Pot must not exceed
15 in. x 14 in.
(38 cm x 36 cm))
High Proximity 1 27-47 in. 419339 230
Medium Proximity 1 20-27 in. 419340 245
Maximum Size
(with drip board)
25 3/8 in. (64.4 cm)
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2 cm)
High Prdximity 1 21-34 in. 419338 3N
Low Proximity 1 13—l6in. 419342 290
Maximum Size
(with drip board)
18 in. (45.7 cm)
x 27 5/8 in. (70.2 cm)
High Proximity 1 25-35 in. 419338 3N
(64-89 cm)
Range Longest Side 1 30-50 in. 419333 1
28 in. (71 cm) (76 - 127 cm)
Area - 336 sq. in. 40-48 in.
(2168 sq. cm) (102— 122 cm)
(With Backshelf)
Longest Side (High Proximity) 1 40-50in. 419340 245
28 in. (71 cm) (102— 127 cm)
Area-6725q. in.
(4335 sq. cm)
Longest Side
(Medium Proximity) 1 30-40in. 419341 260
32 in. (81 cm) (76 - 102 cm)
Area - 768 sq. in.
p (4955 sq. cm)
Longest Side (Low Proximity) 2 15-20in. 419342 290
36 in. (91 cm) (38-51 cm)
Area - 1008 sq. in.
(6503 sq. cm)
For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11.
Nozzle Application Chart (Continued)
Minimum
Maximum Hazard Nozzle Nozzle
Hazard Dimensions Quantity Heights
Griddle Longest Side (High Proximity) 1 30 - 50 in.
48 in. (122 cm) (76— 127 cm)
Area - 1440 sq. in. (perimeter
(9290 sq. cm) located)
Longest Side (High Proximity) 1 30 - 50 in.
30 in. (76 cm) (76— 127 cm)
Area - 720 sq. in. (center located)
(4645 sq. cm)
Longest Side (High Proximity) 1 35 - 40 in.
36 in. (91 cm) (89— 102 cm)
Area - 1080 sq. in. (perimeter located)
(6968 sq. cm)
Longest Side 1 20 - 30 in.
(Medium Proximity) (51 - 76 cm)
48 in. (122 cm) (perimeter
Area— 1440 sq. in. located)
(9290 sq. cm)
Longest Side (Low Proximity) 1 10 —20 in.
48 in. (122 cm) (25— 51 cm)
Area - 1440 sq. in. (perimeter
(9290 sq. cm) located)
Chain Broiler Longest Side - 34 in. (86 cm) 2 10 - 26 in.
(Overhead Protection) Area - 1088 sq. in. (25-66 cm)
(7019 sq. cm)
Chain Broiler Length —43 in. (109 cm) 2 1 - 3 in.
(Horizontal Protection) Width - 31 in. (79 cm) (3 - 8 cm)
Gas-Radiant Char-Broiler Longest Side - 36 in. (91 cm) 1 15 - 40 in.
Area —864 sq. in. (38 - 102 cm)
(5574 sq. cm)
Electric Char-Broiler Longest Side - 34 in. (86 cm) 1 20 - 50 in.
Area —680 sq. in. (51 - 127 cm)
(4388 sq. cm)
Lava-Rock Broiler Longest Side - 24 in. (61 cm) 1 18 - 35 in.
Area —312 sq. in. (46 - 89 cm)
(2013 sq. cm)
Nozzle lip
Nozzle Stamping -
Part No. Flow No.
419341 260
419342 290 1
419335/417332 iN/i NSS
419342 290
419343 2120
419336/417333 1W/i WSS
419335/417332 1 N/1 NSS
419335/417332 1 N/1 NSS
419335/417332 iN/i NSS
419335/417332 iN/i NSS
SECTION IV -, SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-30
REV. 3 10-1-02
Natural Charcoal Broiler Longest Side —24 in. (61 cm) 1 18-40 in. 419335/417332
Area —288 sq. in. (46 - 102 cm)
(1858 sq. cm)
Lava-Rock or Natural Longest Side - 30 in. (76 cm) 1 14-40 in. 419338
Charcoal Char-Broiler Area —720 sq. in. (36 - 102 cm)
(4645 sq. cm)
iN/i NSS
3N
- Minimum chain broiler exhaust opening - 12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size,
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CE747 Page 4-31
10-1-02 REV.5
Nozzle Application Chart (Continued)
Minimum
Maximum Hazard Nozzle Nozzle
Hazard Dimensions Quantity Heights
Wood Fueled Char-Broiler Longest Side - 30 in. (76 cm) 1 14 —40 in.
Area —720 sq. in: (36— 102 cm)
(4645 sq. cm)
Upright Broiler Length - 32.5 in. (82.5 cm) 2 -
Width - 30 in. (76 cm)
Salamander Length - 32.5 in. (82.5 cm) 2 -
Broiler Width - 30 in. (76 cm)
Wok 14 in. —30 in. (36-76 cm) 1 35-45 in.
Diameter (89 - 114 cm)
3.75 - 8.0 in. (9.5 - 20 cm)
Deep
11 in.-24 in. (28-61 cm) .30-40 in.
Diameter (89 - 102 cm)
3.0-6.0 in. (8— 15.2 cm)
Deep
Nozzle Tip
Nozzle Stamping -
Part No. Flow No.
419338 3N
419334 1/2N
419334 1/2N
41934.1 260
419335/417332 1 N/1 NSS
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-7
10-1-02 REV. 4
DETECTORS
The detector consists of three basic Components: the bracket, link-
age, and fusible link. (Fusible links are not included and must be
ordered separately.) The bracket holds the entire assembly to the
mounting surface. The linkage is used to support the fusible link.
The fusible link is designed to separate at a specific temperature
and release the wire rope, thereby actuating the regulated release
mechanism.
There are three styles of detectors available: the clip-on style, the
hinged style, and the scissor style.
The clip-on style allows the wire rope to be strung completely
through the detection system conduit and •, brackets first and the
detector linkage assemblies are then clipped on later.
The hinged style detector requires the wire rope to be strung to the
detector bracket, and then 'threaded" through the linkage assem-
bly before continuing to the next detector bracket.
The scissor style allows the wire rope to be strung completely
through the detection system conduit and brackets first and the
detector linkage assemblies are then clipped on later.
Each style of detector consists of two types of assemblies:
The Terminal Detector (Part No. 56838, 15375, or 417368)
includes a test link and is placed last in a series of detectors. This
detector is sometimes referred to as the end-of-line detector and
is thus named because it is at the point at which the wire rope "ter-
minates," or is anchored at the detector bracket. Only one termi-
nal detector is required per detection system.
The Series Detector (Part No. 56837, 15373, or 417369) is any
detector located in-line between the regulated release assembly
and the terminal detector.
When using Part No. 56837 and 56838 style detectors, a total of
12 detectors can be in one detection system: 11 series detectors,
Part No. 56837-and 1 terminal detector, Part No. 56838.
When using Part No. 15373 and 15375 style detectors, a total of
5 detectors can be in one detection system: 4 series detectors,
Part No. 15373 and 1 terminal detector, Part No. 15375.
When using Part No. 417368 and 417369 style detectors, a total
of 15 detectors can be in one detection system: 14 series detec-
tors, Part No. 417369 and 1 terminal detector, Part No. 417368.
CLIP-ON STYLE - PART NO. 56837 AND 56838
/ LINKAGE f
F,
U
SK1BLjBRACKET
000157
HINGED STYLE - PART NO. 15373 AND 15375
000155
SCISSOR STYLE -PART NO. 417368 AND 417369
000159
FIGURE 21
PULLEY ELBOWS
There are two types of pulley elbows used to change the direction
of the wire rope by 90°. Ansul recommends for temperatures not
in excess of 700 °F (371 00) Part No. 415670 has socket ends
with set screws for 1/2 in, conduit, and Part No. 423250 has com-
pression ring ends also for 1/2 in. conduit. Pulley elbows must be
ordered in quantities of 50 as Shipping Assembly Part No. 415671
(socket end type) and Part No. 423251 (compression end type).
PART NO. 415670 PART NO. 423250
rTT
ve, VO) 0
005150 000961
FIGURE 22
BRACKET
/
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-10
REV. 1 10-1-02
REGULATOR TEST KIT
The Test Kit Assembly (Shipping Part No. 56972) is required to
test the regulator setting and nitrogen flow during 12-year mainte-
nance examinations. This will ensure that the regulator is func-
tioning properly.
BURSTING DISC
The R-102 Bursting Disc is installed in the tank adaptor assembly.
The bursting disc eliminates the siphoning of the agent up the pipe
during extreme temperature variations. The bursting discs are
available in packs of 10, Part No. 417911,
(5
NOZZLE AIMING DEVICE
FIGURE 32
000172
FIGURE 30
000169
FUSIBLE LINK
Select correct UL Listed fusible link(s) for installation in detector(s)
according to the temperature condition chart below:
Fusible Link To Be Used
Fusible Shipping Where
Link Assembly Temperature Temperature
Part No. Part No. Rating Does Not Exceed
415739(1) 415739(1) 165°F (74°C) 100°F (38°C)
415740(l) 415740(l) 212 °F (100 00) 150 °F (66 °C)
415741 (1) 415744(25) 280°F(138°C) 225°F(107°C)
415742(l) 415745 (25) 360 °F (182 °C) 290 °F (143 °C)
415743(l) 415746 (25) 450°F (232 °C) 360 °F (182 °C)
56816(l) 73867 (25) 500°F (260 °C) 400 °F (204 °C)
0J5UL.
(5)c
0' TEMPERATURE
RATING STAMPED ON
FUSIBLE LINK BODY o
__
The Nozzle Aiming Device, Part No. 551265, is required to prop-
erly aim each nozzle to the correct aiming point. The device
clamps to the nozzle and emits a small laser light that reflects on
the surface that it is aiming at. The nozzle can then be rotated to
point at a predetermined aiming point and then tightened to hold
that angle. The aiming device requires an adaptor, Part No.
431186, to attach it to the nozzle. The adaptor must be ordered
separately.
0'.1,\
ADAPTOR (ORDER
SEPARATELY
NOZZLE -
AIMING
DEVICE FIGURE 33
006520
STAINLESS STEEL ACTUATION HOSE
The Stainless Steel Actuation Hose is used to connect the actua-
tion line compression tees between each pneumatic actuator and
P. can also be connected end to end. The hose has the same thread,
7/16-20, as the fittings. The actuation hose allows flexibility
between the AUTOMAN and each regulated actuator.
K STYLE ML STYLE Hose
505170
500 F (260 'C) ONLY Part No. Length
FIGURE 31 31809 16 in. (41 cm)
32335 20 in. (51 cm)
MAXIMUM REGISTERING THERMOMETER 32336 24 in. (61 cm)
430815 42 in. (107 cm) The Maximum Registering Thermometer, Part No. 15240, is used
to indicate the highest normal temperature for the protected area. Fitting
Once this is established, the correct rated fusible link can be Part No. Description
chosen. 31810 Male Elbow (7/16-20 x 1/4 in. NPT)
31811 Male Tee (7/16-20 x 7/16-20 x 1/4 in. NPT)
32338 Male Straight Connector (7/16-20 x 1/4 in. NPT)
FIGURE 34
000433
MECHANICAL GAS VALVES
The mechanical gas valves are designed to shut off the flow of gas
to the appliances upon actuation of the regulated release assem-
bly. The valves are available in sizes of 3/4 in., 1 in., 1 1/4 in., 1
1/2 in., and 2 in. Ansul style; and 2 1/2 in. and 3 in. Asco style. The
valves are rated for natural and LP gas. Both styles are UL Listed.
Maximum Part Operating No. Description Pressure
55598 3/4 in. Gas Valve (ANSUL) 10 psi (69 kPa) 55601 1 in. Gas Valve (ANSUL) 10 psi (69 kPa) 55604 1 1/4 in. Gas Valve (ANSUL) 10 psi (69 kPa) 55607 1 1/2 in. Gas Valve (ANSUL) 10 psi (69 kPa) 55610 2 in. Gas Valve (ANSUL) 10 psi (69 kPa) 25937 2 1/2 in. Gas Valve (ASCO) 5 psi (34.5 kPa) 25938 3 in. Gas Valve (ASCO) 5 psi (34.5 kPa)
ANSUL STYLE ASCO STYLE 000164 000165
FIGURE 25
I
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-8
REV. 5 104-02
PULLEY TEE
The Pulley Tee (Part No. 427929) is used to change the direction
of two wire ropes by 900. It must be used in areas where the tem-
peratures are within the range of 32 OF to 130 OF (0 °C to 54 0C). Pulley tees can be used in mechanical gas valve actuation lines
and remote manual pull station lines. Pulley tees cannot be used
within a detection line.
V
FIGURE 23
000447
STAINLESS STEEL CABLE
The 1/16 in. stainless steel cable is run from the terminal detector,
through conduit, all series detectors and pulley elbows, and into
the regulated release mechanism trip lever. When any fusible link
separates, the tension on the cable is relaxed, and the trip lever
actuates the regulated release mechanism. The cable can also be
used for mechanical gas valves and remote manual pull stations.
The cable is available in 50 ft. (15 m) (Part No. 15821) and 500 ft.
(152.4 m) (Part No. 79653) lengths.
REMOTE MANUAL PULL STATION
The remote manual pull station (Part No. 4835 or Part No. 54011)
is required for manual actuation of the regulated release assem-
bly. The remote manual pull station should be mounted at a point
of egress and positioned at a height determined by the authority
having jurisdiction. Trim rings, Part No. 427074 (pack of 10), are
available.
PART NO. 4835 (WITHOUT CABLE)
PART NO. 54011 (WITH 50 FT. OF CABLE)
9
0)
METAL STAMPED
000163
FIGURE 24
1
a
a
I:
0
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-9
10-1-02 REV. 2
ELECTRICAL GAS VALVES
The electrical gas valves are designed to shut off the flow of either
natural or LP gas to the appliances upon actuation of the regulat-
ed release assembly. The valves are available in sizes of 3/4 in.,
1 in., 1 1/2 in., 2 in., and 3 in. The valve is held open by an ener-
gized solenoid and upon system actuation, the switch contacts in
the regulated release assembly open, thus de-energizing the cir-
cuit to the gas valve solenoid, causing the valve to close. Valves
are available in 120 VAC and are UL Listed.
Maximum
Part Operating
No. Description Pressure
13707 3/4 in. Solenoid Gas Valve (ASCO) 25 psi (172 kPa)
13708 1 in. Solenoid Gas Valve (ASCO) 25 psi (172 kPa)
13709 1 1/2 in. Solenoid Gas Valve 25 psi (172 kPa)
(ASCO)
13710 2 in. Solenoid Gas Valve (ASCO) 25 psi (172 kPa)
17643 3 in. Solenoid Gas Valve (ASCO) 5 psi (34.5 kPa)
FIGURE 26
000166
MANUAL RESET RELAY
The manual reset relay, Part No. 14702 or Part No. 426151, is
required when using an electrical gas valve shut-off system. After
the electric gas valve has closed, either due to system actuation
or power failure, the valve cannot be re-opened, allowing gas to
flow, until the reset relay button is manually pressed, re-energizing
the circuit. The reset relay is available 120 VAC. The manual reset
relay is also recommended for electrical shut down.
FIGURE 27
- 000087
ELECTRICAL SWITCHES
The electrical switches are intended for use with electric gas
valves, alarms, contactors, lights, contractor supplied electric
power shut-off devices and other electrical devices that are
designed to shut off or turn on when the system is actuated.
Switches are available in kits: One Switch Kit, Part No. 423878,
Two Switch Kit, Part No. 423879, Three Switch Kit, Part No.
423880, and Four Switch Kit, Part No. 423881. Each switch has a
set of single-pole, double-throw contacts rated at 21 amp, 1 HP,
125, 250, 277 VAC or 2 HP, 250, 277 VAC. Mounting hardware
and 12 in. (305 mm) long wire leads are provided with each kit.
COMI
FIGURE 28
001612
ALARM INITIATING SWITCH
The Alarm Initiating Switch Kit, Part No. 428311, can be field
mounted within the ANSUL AUTOMAN release, This switch must
be used to close a supervised circuit to the building main fire alarm
panel when the ANSUL AUTOMAN release actuates. This action
will signal the fire alarm panel that there was a system actuation in
the kitchen area. The switch kit contains all necessary mounting
components along with a mounting instruction sheet. The switch is
rated 50 mA, 28 VDC.
SPACER
TOWARD WHEN SPACER AND AUTOMAN SWITCH ARE PROPERLY
MOUNTED, THIS DIVIDER
MUST BE BETWEEN THE / N.O. AND N.C. TERMI-
COM
NO.
NC.
ALARM INITIATING
SWITCH
FIGURE 29
004690
N.C.
SECTION III - SYSTEM COMPONENTS
UL EX. 3470 ULC CEx747 Page 3-6
REV. 4 10-1-02
CONDUIT OFFSET ASSEMBLY
The conduit offset assembly, Part No. 79825, is used to change
direction of the wire rope on detection, mechanical gas valve, and
remote pull station lines. The conduit offset assembly can only be
used in the area where the conduit attaches to the regulated
release assembly. When using the conduit offset assembly, the
maximum number of pulley elbows is still allowed. The Conduit
Offset Shipping Assembly, Part No. 79825, consists of 6 conduit
offsets.
CONDUIT
COUPLING
CONDUIT
OFFSET
CONDUIT
CONNECT(
"QUIK-SEAL" ADAPTOR
The "Quik-Seal" adaptor is a listed mechanical bulkhead fitting that
produces a liquid-tight seal around both distribution piping and
detection conduit which runs through restaurant hoods and ducts.
The "Quik-Seal" adaptor accepts threaded pipe or conduit. The
adaptor is available for 1/4 in. (Part No. 78195), 3/8 in. (Part No.
77284), 1/2 in. (Part No. 77286), or 3/4 in. (Part No. 77288) pipe
or conduit sizes. When using with EMT conduit, a conduit con-
nector must be installed in each end of the adaptor. The "Quik-
Seal" Adaptor Shipping Assembly must be ordered as stated
below:
Shipping
Assembly Hole Size
Size Part No. Qty. Required
1/41n. 78196 24 3/41n.
3/8 in. 77285 24 11/8 in.
1/2 in. 77287 24 1 1/8 in.
3/4 in. 77289 24 1 3/8 in.
ADAPTOR BODY
GASKET
LOCK WASH ER
ci
NUT
FIGURE 18
000154
"COMPRESSION-SEAL" ADAPTOR
This adaptor is a mechanical bulkhead fitting that produces a
liquid-tight seal around pipe and conduit when installing distribu-
tion piping and detection conduit through restaurant hoods and
ducts. The "Compression-Seal" adaptor is a straight-through
design requiring no cutting or threading of conduit or pipe. The
adaptor is available for pipe sizes of 1/4 in. (Part No. 79148), 3/8
in. (Part No. 79150), 1/2 in. (Part No. 79146), and EMT conduit
size of 1/2 in. (Part No. 79152). Each "Compression-Seal" Adaptor
Shipping Assembly must be ordered as stated below:
Shipping
Assembly Hole Size
Size Part No. Oty. Required
1/4 in. Pipe / 1/2 in. tube 79149 24 3/4 in.
3/8 in. Pipe / 5/8 in. tube 79151 24 11/8 in.
1/2 in. Pipe 79147 24 1 1/8 in.
1/2 in. EMT Conduit 79153 24 1 1/8 in.
COMPRESSION NUT
ADAPTOR BODY
LOCK WASHER
FIGURE 19
000155
"HOOD SEAL" ADAPTOR ASSEMBLY
This adaptor is a mechanical bulkhead fitting that produces a liq-
uid-tight seal around 1/2 in. EMT conduit when installing the detec-
tion line through restaurant hoods and duct. The adaptor accepts
a high temperature pulley elbow and, when used, correctly posi-
tions the elbow or conduit in line with the conduit adaptor hole in
the detector bracket. The "Hood Seal" eliminates the need for mul-
tiple elbows when penetrating the top of a hood when installing the
detection line. "Hood Seal" Adaptors are available in quantities of
6 as Shipping Assembly Part No. 423253.
SEAL NUT
SEAL çWASHER
ADAPTOR
BODY
GASKET
PULLEY
ELBOW
(NOT PART
OF ASSEMBLY)
USE ONLY PULLEY
ELBOW, PART NO. 423250
FIGURE 20
000156
GASKET
FIGURE 17 NUT
000153
007128
VERTICAL EDGE OF BROILER—'- OPENING
AIM AT CENTER BROILER OPEN
1 NOZZLE .—(PART NO. 419335)
-4--NOZZLE LOCATION ZONE
12 IN. (30 cm)
I
61N.\ (15 CM)
AIM AT CENTER OF
BROILER OPENING
IU.IANSULI
TYCO SAFETY PRODUCTS
ONE STANTON STREET
MARINETTE, \M 54143-2542 Hu-lletin 715-735-7411
wwwansulxom
GENERAL BULLETIN NO. 4927
DATE: February 18, 2005
TO: All Authorized R-1 02 TM Restaurant System Distributors and OEMs
FROM: Mark Neumann - Marketing Manager, Commercial Suppression
SUBJECT: New Salamander Broiler Protection for R-1 02 TM Restaurant Fire Suppression Systems
Salamander broilers are now standard appliances in most commercial restaurants. As such, we are
pleased to offer a convenient new protection design using the R-102 Restaurant Fire Suppression
System.
This new design is UL Listed under UL EX 3470 and ULC CEx747 and will be added to the R-102
Design Manual (Part No. 418087) at next reprint.
Salamander Broiler Protection
The R-102 Restaurant Fire Suppression System uses one iN Nozzle (Part No. 419335) for
salamander broiler protection. The nozzle tip is stamped with iN indicating that this is a one-flow
nozzle.
One 1 nozzle will protect a maximum hazard area (internal broiler chamber) of 16 in. (41 cm) deep
x 29 in. (74 cm) wide.
The single 1 nozzle must be located directly in line with either vertical edge of the broiler opening,
6 in. (15 cm) to 12 in. (30 cm) in front of the broiler, and 0 in. to 12 in. (30 cm) above the top of the
broiler. The nozzle must be aimed at the center of the broiler opening. See Figure.
UL EX3470
General Bulletin No. 4927
February 18, 2005
Page 2
Previous Salamander Broiler protection using two 1/2N nozzles remains an approved method.
Salamander broilers are generally mounted above other types of appliances. See Installation manual
for detailed design information concerning these other appliances.
If you have any questions regarding the material in this bulletin, please contact your U.S. District
Manager or International Area Manager; or call Ansul Technical Services at 1-800-862-6785 or
1-715-735-7415.
UL EX3470