SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/6/2009 C:\HASS74\C4211L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW
NODE PRESS PRESS
TAG (PSI) (PSI) (GPM)
SZ 850 810 5000
AVAIL. TOTAL REQ'D
PRESS @- DEMAND PRESS
(PSI) (GPM) (PSI)
850 312. 52.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
S2 0-.0. SOURCE 52. 0' 31.2
2 0.0 - - - - 41.7 - - -
2A 0.0 - - - - 37.7 - - -
3A 0.0 HOSE STREAM 33.7 5.0
3 0.5 - - - - 31.4
4 3.5 - - - - 28.4
5 105 - - - - 195 - - -
6 22.0 - - - - 13.5
7 22.0 - - - - 9.8 - - -
7A 21.5 K= 4.30 9.5 13.2
8 22.0 - - - - 9.8 - - -
8A 21.5 K= 4.30 9.1 13.0
9 22.0 - - - - 10.1
10 10.5 - - - - 15.9
11 10.5 - - - - 17.8 - - -
12 10.5 - - - - 17.8
12A 10.0 - - - - 18.0 - - -
13A 10.0 - - - - 18.0 - - -
coflP1 , %,jewed for Ware
with the current app codes and standar n lorce
the le 0 orcofltT may utili
ill
this review in uprt ol an appliCatiofl %or a uidiig
pertui w'i(h the çp1t
unde dtn that this review
n nO way reV the
r. Oni "clor or their
ptoiessona% neer O
resp011sibility
r ardm or tOk
or u1 coflW' w de% and staiidar
the c C or any C1fl'1' or
deC1efldt errO•
or iiegtet n these
ptalts whet
or ntt otC 'i tit' rVieW
zql° 7
APPROVAL
QREco APPROVAL. AS 46TE
*1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ PT DISC. VEL(FPS HW(C) (FT SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.2. 0.995 PL 30.00 PE 10.3
S2 0.0 SRCE 52 .0 (N/A) 12.9 150 FTG TLG PE 0 .0
2 0.0 0.0 41.7 0.0 0.254 TL 40.50 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 41.7 0.0 4.0 psi, 31.2 gpm
2A 0.0 0.0 37.7 0.0
Pipe: 3 31.2 1.590 PL 130.00 PF 4.0
2A 0.0 0.0 37.7 0.0 5.0 150 FTG 8L PE 0.0
3A 0.0 H.S. 33.7 5.0 0.026 TL 154.00 PV
Pipe: 4 26.2 1.265 PL 1G.00 PF 2.1
3A 0.0 H.S. 33.7 5.0 6.7 150 FTG T3LC PE -0.2
3 0.5 0.0 31.4 0.0 0.057 TL 36.00 PV
Pipe: 5 26.2 1.049 Pi 3.00 PP 1.7
3 0.5 0.0 31.4 0.0 9.7 120 FTG C PE -1.3
4 3.5 0.0 28.4 0.0 0.215 TL 8.00 PV
Pipe: 6 26.2 1.101 PL 34.50 PF 5.9
4 3.5 0.0 28.4 0.0 8.8 150 FTG 2E4R PE -3.0
5 10.5 0.0 19.5 0.0 0.112 TL 52.50 PV
Pipe: 7 13.5 1.101 PL 12.00' PF 1.0
5 10.5 0.0 19.5 0.0 4.6 150 FTG E2T2R PE -5.0
6 22.0 0.0 13.5 0.0 0.033 TL 31.00 Pv
Pipe: 8 13.5 1.101 PL 82.00 PF 3.7
6 22.0 0.0 13.5 0.0 4.6 150 FTG 6T PE 0.0
7 22.0 0.0 9.8 0.0 0.033 TL 112.00 PV
Pipe: 9 13.2' 1.101 PL 6.50' PP 0.6
7 22.0 0.0 9.8 0.0 4.5 150 FTG 2TR PE 0.2
7A 21.5 4.3 9.5 13.2 0.032 TL 17.50 PV
Pipe: 10 0.3 1.101 PL 8.50 PP 0.0
7 22.0 0.0 9.8 0.0 0.1 150 FTG R PE 0.0
8 22.0 0.0 9.8 0.0 0.000 TL 9.50 PV
Pipe: 11 13.0 1.101 FL 8.50' PP 0.9
8 22.0 0.0 9.8 0.0 4.4 150 FTG 2ETR PE 0.2
8A 21.5 4.3 9.1 13.0 0.031 TL 28.50 PV
Pipe: 12 -12.7 1.101 PL 8.50 PP 0.3
8 22.0 0.0 9.8 0.0 4.3 150 FTG R FE 0.0
9 22.0 0.0 10.1 0.0 0.029 TL 9.50 PV
I
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR
PIPE TAG Q(GPM) DIA(INY LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe 13 -12.7 1.101 PL 14.50 PF 0.8
9 22.0 0.0 10.1 0.0 4.3 150 FTG ET2R PE 5.0
10 10.5 0.0 15.9 0.0 0.029 TL 28.50 PV
Pipe: 14 -12.7 1.101 PL 47.50 PP 1.
10 10.5 0.0 15.9 0.0 4.3 150 FTG 2T7R PE 0.0
11 10.5 0.0 17.8 0.0 0.029 TL 64.50 PV
Pipe 15 0.0 1.101 PL 23.50 PF 0.0
11 10.5 0.0 17.8 0.0 0.0 150 FTG 2T2R PE 0.0
12 10.5 0.0 17.8 0.0 0.000 TL 35.50 PV
Pipe: 16 0.0 1.101 PL 5.00 P? 0.0
12 10.5 0.0 17.8 0.0 0.0 150 FTG ETR PE 0.2
12A 10.0 0.0 18.0 0.0 0.000 TL 18.00 PV
Pipe 17 01.01 1.101 PL 5.00 PF 0.0
12 10.5 0.0 17.8 0.0 0.0 150 FTG ER PE 0.2
13A 10.0 0.0 18.0 0.0 0.000 TL 13.00 PV
Pipe: ia -12.7 1.101 PL 46.50 PP 1.7
11 10.5 0.0 17.8 0.0 4.3 150 FTG E5R PE 0.0
5 10.5 0.0 19.5 0.0 0.029 TL 58.50 PV
NOTES (HASS):
Calculations were performed by the HASS 7.9 computer program
under license no 16080621 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, Gk 30084
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.041 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR
PAGE: A MATERIAL: SCH4 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H. MATERIAL: CPVC. RWC: lSQ
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1590 600 12.00 300 1400 800 200 000 000
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
7
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR
WATER SUPPLY ANALYSIS
Static: 85.00 psi Resid: 81.00 psi Flow: 500.0 gpm
LU U
ii
LEGEND
1
80.
G
A
U
G-
E 60.
2
R
E
S 40.
S
U
R
E
'Ii Available prss.ure
84.98 psi @ 31.2 gpm
Required pressure
51.98 psi @ 31.2 gpm
Source Supply Curve
System Demand Curve
20. ME
p
S
1
-14.71 1 I I I I I 1 I
20C300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page .6
DATE: 5/6/2009 C:\HASS74\C4211-L4.sDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-2nd FLOOR -
WATER SUPPLY CURVE
96+
88+
0
I * <-81.0 psi @ 500 gpm
80+ Flow Test Point
72+
P64+
R
E
S I
S 5.6+
U I
R X
48+
( I
P I
S I
I 40+
) I
32+
24+
16+ LEGEND
I X = Required Water Supply
I 51.98 psi @ 31.2 gpm
8+
I 0 = Available Water Supply
I 84.98 Psi @ 31.2 gpm
0++-+---+-----+-----+------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GEM)
p
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page I
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 9 PRESS. @- DEMAND PRESS
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
S? 850 810 5000 850 311 490
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.1 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.1 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
S2 0.G SOURCE 49.0 31.1
2 0.0 - - - - 38.8 - - -
2A 0.0 - - - - 34.8
3A 0.01 HOSE STREAM 30.8 5.0
3 0.5 - - - - 28.6
4 3.5 - - - - 25.6 - - -
S 10_5 - - - - 167 - - -
6 22.0 - - - - 11.3 - - -
7 22.0 - - - - 9.9 - - -
7A 21.5 - - - - 10.1 - - -
8 22.0 - - - - 9.8 - - -
8A 21.5 - - - - 10.0
9 22.0 - - - - 9.6 - - -
10 10.5 - - - - 14.3
11 10.5 - - - - 13.4 - - -
12 10.5 - - - - 9.5 - - -
12A 10.0 K= 4.30 9.1 13..0
13A 10.0 K= 4.30 9.3 13.1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END E.LE.V. NOZ.. PT DISC. VEL(FPS) HW(C) (FT SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.1 0.995 FL 30.00 FE 10.2.
S2 0.0 SRCE 49.0 (N-/A) 12.8 150 FTG TLG PE 0.0
2 0.0 0.0 38.8 0.0 0.252 TL 40.50 PV
Pipe; 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 38.8 0.0 4.0 psi, 31.1 gpm
2A 0.0 0.0 34.8 0.0
Pipe: 3 31.1 1.50 FL 130.00 PF 4.0
2A 0.0 0.0 34.8 0.0 5.0 150 FTG 8L FE 0.0
3A 0.0 H.S. 30.8 5.0 0.026 TL 154.00 PV
Pipe; 4 26.1 1.265 FL 10.00 FE 2.0
3A 0.0 H.S. 30.8 5.0 6.7 150 FTG T3LC FE -0.2
3 0.5 0.0 28.6 0.0 0.057 TL 36.00 PV
Pipe; 5 26.1 1.049 FL 3.00 FE' 1.7
3 0.5 0.0 28.6 0.0 9.7 120 FTG C FE -1.3
4 3.5 0.0 25.6 0.0 0.213 TL 8.00 PV
Pipe; 6 26.1 1.101 PL 34.50 FE' 5.8
4 3.5 0.0 25.6 0.0 8.8 150 FTG 2E4R PE -3.0
5 10.5 0.0 16.7 0.0 0.111 TL 52.50 PV
Pipe: 7 8.1 1.101 PL 12.00 PF 0.4
5 10.5 0.0 16.7 0.0 2.7 150 FTG E2T2R FE -5.0
6 22.0 0.0 11.3 0.0 0.013 TL 31.00 PV
Pipe; 8 8.1 1.101 FL 82.00 PF 1.4
6 22.0 0.0 11.3 0.0 2.7 150 FTG 6T FE 0.0
7 22.0 0.0 9.9 0.0 0.013 TL 112.00 PV
Pipe: 9 0.0 1.101 FL 6.50 FE' 0.0
7 22.0 0.0 9.9 0.0 0.0 150 FTG 2TR FE 0.2
7A 21.5 0.0 10.1 0.0 0.000 TL 17.50 PV
Pipe; 10 8.1 1.101 FL 8.50 PF 0.1
7 22.0 0.0 9.9 0.0 2.7 150 FTG R FE 0.0
8 22.0 0.0 9.8 0.0 0.013 TL 9.50 PV
Pipe: 11 0.0 1.101 FL 8.50 PF 0.0
8 22.0 0.0 9.8 0.0 0.0 150 FTG 2ETR FE 0.2
8A 21.5 0.0 10.0 0.0 0.000 TL 28.50 PV
Pipe: 12 8.1 1.101 PL 8.50 FE' 0.1
8 22.0 0.0 9.8 0.0 2.7 150 FTG R FE 0.0
9 22.0 0.0 9.6 0.0 0.013 TL 9.50 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/6/2009 C:\HASS74\C4211-L4.sDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe; 13 8.1 1.101 FL 14.50 PF 0.4
9 22.0 0.0 9.6 0.0 2.7 150 FTG ET2R PE 5.0
10 10.5 0.0 14.3 0.0 0.013 TL 28.50 PV
Pipe; 14 8.1 1.101 PL 47.50 PF 0.8
10 10.5 0.0 14.3 0.0 2.7 150 FTG 2T7R PE 0.0
11 10.5 0.0 13.4 0.0 0.013 TL 64.50 PV
Pipe; 15 26.1 1.101 FL 23.50 PF 4.0
11 10.5 0.0 13.4 0.0 8.8 150 FTG 2T2R FE 0.0
12 10.5 0.0 9.5 0.0 0.111 TL 35.50 PV
Pipe; 16 13.a 1. 101 PL 5.00- PF 0.6
12 10.5 0.0 9.5 0.0 4.4 150 FTG ETR FE 0.2
12A 10.0 4.3 9.1 13.0 0.031 TL 18.00 PV
Pipe 17 13.1 1.101 FL 5.00 FE' 0.4
12 10.5 0.0 9.5 0.0 4.4 150 FTG ER PE 0.2
13A 10.0 4.3 9.3 13.1 0.031 TL 13.00 PV
Pipe; 18 -18.0 1.101 FL 46.50 PF 3.3
11 10.5 0.0 13.4 0.0 6.1 150 FTG ESR PE 0.0
5 10.5 0.0 16.7 0.0 0.056 TL 58.50 PV
NOTES (HASS);
Calculations were performed by the HASS 7.9 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker GA. 30084.
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.039 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.8 ft/sec at pipe 1.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
a-
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM
PAGE A MATERIAL: SCH40 HWC 120
Diameter' Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGR: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.0'O 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1590 600 12.00 3.00 1400 8..00 200 000 000
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM
WATER SUPPLY ANALYSIS
Static: 85.00 psi Resid: 81.00 psi Flow: 500.0 gpm
100-0
LEGEND
1
80.0
G
A
U
G
E 60.0
F
R 2
E
S 400
S
U
R
E
Available pressure.
84.98 psi @ 31.1 gpm
Required pressure
48.99 psi @ 31.1 gpm
Source Supply Curve
System Demand Curve
20.0
p
S
1
-14.71 I 1 I I I I 1 I
20(300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/6/2009 C:\HASS74\C4211-L4.SDF
JOB TITLE: OAK AVE. LOT #4 TWO HEAD CALC-REC ROOM -
WATER SUPPLY CURVE
96+
88+
*\\\\\\\\
0 \\\\\\\\\
I * <-81.0 psi @ 500 gpm
80+ Flow Test Point
72+
P 64+
R
E
S I
S S+
U I
R I
48X
( I
P I
S I
I 40+
) I
32+
24+
16+ LEGEND
'7
I X = Required Water Supply
I 48.99 psi @ 31.1 gpm
8+
I 0 = Available Water Supply
I 84.98 psi @ 31.1 gpm
0++-+---+----+-----+------+--------+--------+-----
200 300 400 500 600 700 800
FLOW (GPM)
--+-----------+
900 1000
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
SOURCE STATIC
NODE PRESS.
TAG (PSI)
Si 85.0
RESID. FLOW
PRESS. @.
(PSI) (GPM)
81.0 500.0
AVAIL. TOTAL REQ'D
PRESS. DEMAND PRESS.
(PSI) (GPM) (PSI)
85.0 31.3 52.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.3 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION
(FT)
SI 0.01
2 0.0
2A 0.0
3.A 0.01
3 0.5
4 3.5
5 10..S
6 10.5
7 10.5
7A 10.0
BA 10.0
9 22.0
10 22.0
11 22.0
hA 21.5
12A 21.5
NODE TYPE PRESSURE DISCHARGE
(PSI) (GPM)
SOURCE 52.0 31.3
- - - - 41.6 - - -
- - - - 37.6 - - -
HOSE STREAM 36.3 5. 0
- - - - 34.0 - - -
- - - - 31.0 - - -
- - - - 25.6 - - -
- - - - 24.5 - - -
- - - - 24.9 - - -
- - - - 25.1 - - -
- - - - 25.1 - - -
- - - - 17.1 - - -
- - - - 14.5 - - -
- - - - 9.9 - - -
K= 4.30 9.5 13.3
K= 4.30 9.1 13.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END E.LEV NOZ.. PT DISC.. VEL(FPS) HW(C) (FT SUM..
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31..3 0..995 FL 30..00 FE 10..3
Si 0.0 SRCE 52.0 (N-/A) 12.9 150 FTG TLG FE 0.0
2 0.0 0.0 41.6 0.0 0.255 TL 40.50 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 41.6 0.0 4.0 Psi, 31.3 gpm
2A 0.0 0.0 37.6 0.0
Pipe: 3 31.3 1.590 FL 40.00 PF 1.4
2A 0.0 0.0 37.6 0.0 5.1 150 FTG 4L FE 0.0
3A 0.0 H.S. 36.3 5.0 0.026 TL 52.00 PV
Piper 4 26.3 1.265 FL 10.00 PF 2.1
3A 0.0 H.S. 36.3 5.0 6.7 150 FTG T3LC FE -0.2
3 0.5 0.0 34.0 0.0 0.057 TL 36.00 PV
Pipe: 5 26.3 1.049 FL 3-.0,0 FE 1.7
3 0.5 0.0 34.0 0.0 9.8 120 FTG C FE -1.3
4 3.5 0.0 31.0 0.0 0.216 TL 8.00 PV
Piper 6 26.3 1.101 FL 12.00 FE 2.4
4 3.5 0.0 31.0 0.0 8.9 150 FTG E2R FE -3.0
5 10.5 0.0 25.6 0.0 0.113 TL 21.00 PV
Pipe: 7 21.1 1.101 FL 8.00 FE 1.1
5 10.5 0.0 25.6 0.0 7.1 150 FTG TR FE 0.0
6 10.5 0.0 24.5 0.0 0.075 TL 14.00 PV
Pipe 8 -5.1 1.101 FL 42.50 P'F 0.3
6 10.5 0.0 24.5 0.0 1.7 150 FTG ET6R PE 0.0
7 10.5 0.0 24.9 0.0 0.005 TL 60.50 PV
Pipe: 9 0.0 1.101 FL 7.00 FE 0.0
7 10.5 0.0 24.9 0.0 0.0 150 FTG ETR FE 0.2
7A 10.0 0.0 25.1 0.0 0.000 TL 20.00 PV
Pipe: 10 0.0 1.101 FL 4.50 PF 0.0
7 10.5 0.0 24.9 0.0 0.0 150 FTG TR FE 0.2
8A 10.0 0.0 25.1 0.0 0.000 TL 10.50 PV
Pipe: 11 -5.1 1.101 FL 94.50 PF 0.7
7 10.5 0.0 24.9 0.0 1.7 150 FTG E6T FE 0.0
5 10.5 0.0 25.6 0.0 0.005 TL 131.50 PV
Pipe: 12 26.3 1.101 FL 13.00 FE 2.5
6 10.5 0.0 24.5 0.0 8.9 150 FTG E2R FE -5.0
9 22.0 0.0 17.1 0.0 0.113 TL 22.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
PIPE TAG QGPM) DIA(INY LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Piper 13 14.3 1.101 FL 51.50 PF 2.5
9 22.0 0.0 17.1 0.0 4.8 150 FTG 2T8R PE 0.0
10 22.0 0.0 14.5 0.0 0.036 TL 69.50 Fv
Pipe: 14 26.3 1.101 FL 28.00 PF 4.6
10 22.0 0.0 14.5 0.0 8.9 150 FTG 2T3R FE 0.0
11 22.0 0.0 9.9 0.0 0.113 TL 41.00 PV
Piper 15 13.3 1.101 PL 5.50 PF 0.6
11 22.0 0.0 9.9 0.0 4.5 150 FTG ETR FE 0.2
hA 21.5 4.3 9.5 13.3 0.032 TL 18.50 PV
Pipe: 16 13.0 1.101 FL 18.00 PF 1.0
11 22.0 0.0 9.9 0.0 4.4 150 FTG ET2R FE 0.2
12A 21.5 4.3 9.1 13.0 0.031 TL 32.00 PV
Pipe: 17 -12.0 1.101 FL 76.50 PF 2.5
10 22.0 0.0 14.5 0.0 4.0 150 FTG 2T9R FE 0.0
9 22.0 0.0 17.1 0.0 0.026 TL 95.50 PV
NOTES (HASS):
Calculations were performed by the HASS 7.9 computer program
under license no. 160.80.621 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 3004
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.035 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
FIFE FITTINGS TABLE
Pipe Table Name: FSS.PIF
I
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
PAGE: A MATERIAL: SCH40, HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC. HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.0-01 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
159.0 600 1200 300 14.00 8.00 200 000 000
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
WATER SUPPLY ANALYSIS
Static: 85.00 psi Resid: 81.00 psi Flow: 500.0 gpm
100.0
LEGEND
1
80.0
G
A
U
G
E 60.0
2
R
E
S 400
S
U
R
E
Available pressure
84.98 psi @ 31.3 gpm
Required pressure
51.95 psi @ 31.3 gpm
Source Supply Curve
System Demand Curve
20.0
P
S
i
-14.7t I I I I I I I 1 I
20C300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/6/2009 C:\HASS74\04211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-2nd FLOOR
WATER SUPPLY CURVE
96+
88+
0 \\\\\\\\\
I * <-81.0 psi @ 500 gpm
80+ Flow Test Point
72+
P 64+
R
E I
S I
S 56+
U
R X
a
48+
P I.
S I
I 40+
) I
32+
24+
16+ LEGEND
X = Required Water Supply
I 51.95 psi @ 31.3 gpm
8+
0 = Available Water Supply
I 84.98 psi @ 31.3 gpm
0++-+---+----+-----+------+--------+ --------+---------+ -----------+
200 300 400 500 600 700 1 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS- PRESS. @- PRESS. @- DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
Si 85.0 81.0 500.0 85.0 31.2 38.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
SI 01.01 SOURCE 38.8 31.2
2 0.0 - - - - 28.6 - - -
2A 0.0 - - - - 24.6
3A 0.01 HOSE STREAM 23.2 5.0
3 0.5 - - - - 20.9 - - -
4 3.5 - - - - 17.9 - -
5. 105 - - - - 12-5 - - -
6 10.5 - - - - 12.0
7 10.5 - - - - 9.5 - - -
7A 10.0 K= 4.30 9.1 13.0
BA 10.0 K= 4.30 9.4 13.2
9 22.0 - - - - 7.0 - - -
10 22.0 - - - - 7.0
11 22.0 - - - - 7.0 - - -
hA 21.5 - - - - 7.2 - - -
12A 21.5 - - - - 7.2
4
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELE.V. NOZ. PT DISC.. VEL(FPS HW(C) (FT) SUM..
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
P:Lpe: 1 31.2 0.995 FL 30.00 FE 10.3
51 0.0 SRCE 38.8 (N/A) 12.9 150 FTG TLG PE 0.0
2 0.0 0.0 28.6 0.0 0.253 TL 40.50 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 28.6 0.0 4.0 psi, 31.2 gpm
2A 0.0 0.0 24.6 0.0
Pipe: 3 31.2 1.590 PL 40.00 FE 1.3
2A 0.0 0.0 24.6 0.0 5.0 150 FTG 4L FE 0.0
3A 0.0 H.S. 23.2 5.0 0.026 TL 52.00 PV
Pipe: 4 26.2 1.265 FL 10.00 FE 2.1
3A 0.0 H.S. 23.2 5.0 6.7 150 FTG T3LC PE -0.2
3 0.5 0.0 20.9 0.0 0.057 TL 36.00 PV
Pipe: 5 26.2 1.049 FL 3.00 FE 1.7
3 0.5 0.0 20.9 0.0 9.7 120 FTG C FE -1.3
4 3.5 0.0 17.9 0.0 0.214 TL 8.00 PV
Pipe: 6 26.2 1.101 FL 12.00 PF 2.4
4 3.5 0.0 17.9 0.0 8.8 150 FTG E2R PE -3.0
5 10.5 0.0 12.5 0.0 0.112 TL 21.00 PV
Pipe: 7 15.1 1.101 FL 8.00 PF 0.6
5 10.5 0.0 12.5 0.0 5.1 150 FTG TR FE 0.0
6 10.5 0.0 12.0 0.0 0.040 TL 14.00 PV
Pipe: 8 15.1 1.101 PL 42.50 PF 2.4
6 10.5 0.0 12.0 0.0 5.1 150 FTG ET6R FE 0.0
7 10.5 0.0 9.5 0.0 0.040 TL 60.50 PV
Pipe: 13.0 1.101 FL 7.00 PF 0.6
7 10.5 0.0 9.5 0.0 4.4 150 FTG ETR PE 0.2
7A 10.0 4.3 9.1 13.0 0.031 TL 20.00 PV
Pipe: 10 13.2 1.101 FL 4.50 PF 0.3
7 10.5 0.0 9.5 0.0 4.4 150 FTG TR FE 0.2
BA 10.0 4.3 9.4 13.2 0.032 TL 10.50 PV
Pipe: 11 -11.1 1.101 FL 94.50 FE 3.0
7 10.5 0.0 9.5 0.0 3.7 150 FTG E6T FE 0.0
5 10.5 0.0 12.5 0.0 0.023 TL 131.50 PV
Pipe: 12 0.0 1.101 FL 13.00 PF 0.0
6 10.5 0.0 12.0 0.0 0.0 150 FTG E2R PE -5.0
9 22.0 0.0 7.0 0.0 0.000 TL 22.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe 13 0-.0, 1.101 FL 51 .50 PF &.9
9 22.0 0.0 7.0 0.0 0.0 150 FTG 2T8R FE 0.0
10 22.0 0.0 7.0 0.0 0.000 TL 69.50 PV
Pipe: 14 0.0 1.101 FL 28.00 FE 0-.0-
10 22.0 0.0 7.0 0.0 0.0 150 FTG 2T3R PE 0.0
11 22.0 0.0 7.0 0.0 0.000 TL 41.00 PV
Pipe: 15 0.01 1.101 FL 5.50 PF 0.0
11 22.0 0.0 7.0 0.0 0.0 150 FTG ETR PE 0.2
hA 21.5 0.0 7.2 0.0 0.000 TL 18.50 PV
Pipe: 16 0.0 1.101 FL 18.00 F? 0.0
11 22.0 0.0 7.0 0.0 0.0 150 FTG ET2R FE 0.2
12A 21.5 0.0 7.2 0.0 0.000 TL 32.00 PV
Pipe - 17 0.0 1.101 FL 76.50 FE' 0.0
10 22.0 0.0 7.0 0.0 0.0 150 FTG 2T9R FE 0.0
9 22.0 0.0 7.0 0.0 0.000 TL 95.50 PV
NOTES (HASS):
Calculations were performed by the HASS 7.9 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
The system has been calculated to provide an average
imbalance at each node of 0.005 gpm and a maximum
imbalance at any node of 0.078 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
FIFE FITTINGS TABLE
Pipe Table Name: FSS.PIP
'ft
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
PAGE' A MATERIAL: SCH4O' HWC 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC. HWG: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L .B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.00 0.00'
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1590 600 12.00 300 14..QQ 800 2..00 000 000
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
WATER SUPPLY ANALYSIS
Static: 85.00 psi Resid: 81.00 psi Flow: 500.0 gpm
100-0
LEGEND
1 Available pressure
80.0 84.98 psi @ 31.2 gpm
G
A Required pressure
U 38.82 psi @ 31.2 gpm
G
E 60. )L
A. Source Supply Curve
P B. System Demand Curve
R
E
S 40 )L
S 2
U
R
E
20.
p
S
I
-14.71 I I 1 I I 1 1 I I.
20(300 400 500 600 700 800 900 1000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/6/2009 C:\HASS74\C4211.SDF
JOB TITLE: OAK AVE. LOT #2 TWO HEAD CALC-REC ROOM
WATER SUPPLY CURVE
96+
88+
0 \\\\\\\\\
I * <-81.0 psi @ 500 qpm
80+ Flow Test Point
72+
P 64+
R
E I
S I
S 56+
U
R I
48+
( I
P 1
S I
I 40+
X
32+
24+
164- LEGEND
I X = Required Water Supply
I 38.82 psi @ 31.2 gpm
8+
I 0 = Available Water Supply
I 84.98 psi @ 31.2 gpm U
0++-+---+----+-----+------+--------+ --------+---------+ -----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
A Concealed Residential
Sprinkler engineered for a
minimum design density
of 0.05 gpmlft2 with low GPM
requirements.
Features
1. Very low water flow requirements.
2.112" (13mm) Total adjustment.
Push-On/Thread-Off
cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and
black plated or painted finishes.
Listings & Approval
Listed by Underwriters Laboratories,
and certified by UL for Canada (cULus)
Bulletin 006 Rev.A
Model RFC43 Concealed
Residential Sprinkler 09
(SIN RA0612) .CD
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC43 Concealed Residential Sprinklers are fast
response residential fusible solder link automatic sprinklers.
Residential sprinklers differ from standard sprinklers primarily
in their response time and water distribution patterns.
Model RFC43 sprinklers discharge water in a
hemispherical pattern below the sprinkler deflector.
Residential distribution patterns are higher and generally
contain a finer droplet size than standard sprinkler patterns.
The combination of speed of operation and high discharge
pattern required for residential sprinklers has demonstrated,
in fire testing, an ability for controlling residential fires, and
thereby providing significant evacuation time for occupants.
The RFC43 Sprinkler provides the best form of fire
protection by combining an attractive appearance and ½"
(13mm) of cover adjustment for ease of installation. The
small diameter cover plate is easily and positively attached
and blends into the ceiling, concealing the most dependable
fire protection available, an automatic sprinkler system.
The RFC43 is a UL Listed Residential Sprinkler to be
installed in the residential portions of any occupancy in
accordance with NFPA 13,13R, & 13D.
The RFC43 can reduce the need for precise cutting of drop
nipples. The threaded cover plate assembly can be adjusted
without tools to fit accurately against the ceiling. The fire
protection system need not be shut down to adjustor remove
the cover plate assembly.
Application and Installation
The RFC43, for residential installations, uses a 165°F (74°C)
fusible solder link in a tuning fork style sprinkler frame with a
drop-down deflector. This assembly is recessed into the
ceiling and concealed by a flat cover plate. The cover plate is
attached to the skirt, using 135°F (57°C) ordinary temperature
classification solder. When the ceiling temperature rises, the
solder holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
inside to ceiling temperature. The subsequent operation of
the solder link opens the waterway and causes the deflector
to drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover plate
and cup will assure that the drop-down deflector is properly
located below the ceiling. The residential distribution pattern
contains a finer droplet size than a standard sprinkler, and the
pattern produces significantly higher wail wetting.
After a 2 5/8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench. When
installing a sprinkler, the wrench is first positioned into the
sprinkler/cup assembly and around the hexagonal body of
the sprinkler frame. The Wrench must bottom out against the
cup in order to ensure proper, safe installation. The sprinkler
is then tightened into the pipe fitting. When inserting or
removing the wrench from the sprinkler/cup assembly, care
should be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP
ASSEMBLY. MODEL RFC43 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COVERS.
Cover assemblies provide up to /2" (13mm) of adjustment. Turn the cover clockwise until the flange is in contact with the
ceiling. The optional push-on cover plate may require a final
adjusting turn to contact the calling. Cover removal requires
turning in the counter-clockwise direction.
In ceilings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative
pressurization but must not be positively pressunzed. Inspect
all sprinklers after installation to ensure that the gap between
the cover plate and ceiling and the 4 slots in the cup are all
open and free from any air flow impediment.
Temperature Rating
Sprinkler Cover Plate Max. Ambient
Temp.
165°Fft4°C 135°F/57C - 100°F/38°c
Installation Data
Thread Size
Inch (mm)
K
Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance
to Wall ft. (m)
Minimum
Distance between
sprinkler ft. (m)
Minimum Required
Sprinkler Discharge
Flow Press.
gpm (Lpm) psi (bar)
'/2" (15mm) 4.3 12 x 12 (3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8 (0.54) '/2" (15mm) 4.3 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63)
1/2 (15mm) 4.3 16 x 16 (4.9x4.9) 8(2.43) 8(2.43) 13(49) 9,1 (0.63) ½" (15mm) 4.3 18 x 18 (5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(l.21) 15Qj 4.3 20 x 20 (6.0x6.0) 10 (3.05) 8(2.43) 21(79)
Note: 1 bar = 100 Kpa
Maintenance
Model RFC43 Concealed Sprinklers should be inspected
quarterly and the sprinkler system maintained in accordance
with NFPA 25. Do not dean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
cover plate assembly which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-operation.
135°F (570C). Cover plate assembly shall consist of a brass
cover plate and copper alloy retainer flange having a
[thread-on] [push-on] and thread-off design, allowing a ½"
cover plate adjustment. Any secure engagement between
the cover plate and the cup will assure that the drop-down
deflector is properly located below the ceiling. A plastic
protective cap shall be provided and factory installed inside
the sprinkler cup to protect the drop-down sprinkler deflector
from damage, which could occur during construction before
the cover plate is installed. Standard cover finish: [Chrome]
(White] [Specialty -specify]. Residential concealed sprinklers
shall be Reliable Model RFC43, SIN RA0612 (Bulletin 006).
Model RFC43 Residential Concealed
Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential
concealed sprinklers with drop-down deflector and
adjustable flat cover plate engineered for a minimum design
density of 0.05 gprMt2. Sprinkler frame and deflector shall be
of bronze frame construction having a ½' NFl thread.
Thermal element shall consist of an approved black-painted
beryllium-nickel fusible solder link with symmetric lever
mechanism, maintaining a Teflon-coated Belleville spring
washer and machined brass cap water seal assembly
containing no plastic parts. Sprinkler K-factor shall be nominal
4.3 (62.4), having a 7/16" orifice. Temperature rating shall be
Ordinary 165°F (740C); cover plate temperature rating to be
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On cover
Cover Plate Finishes
Standard Finishes
Chrome
White
Special Application
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
" Other colors and finishes
available. Consult factory
for details.
Note: Paint or any other
coatings applied over the
factory finish will void all
approvals and warranties.
- x (/2 REDUCING
TEE OR ELBOW
-
----i- I1L_)
(66.7mm] 0/A.
_____ HOLE IN CEILING
CUP
2" [50.8mm] MAX.
FACE OF FITTING
TO FACE OF CEILING
DIVENSION
I 1
CE/LING
" [12. 7mm] MAX.
COVER ADJUSTMENT 34 , DA Jlf6- COVER PLATE [84.1mm] [4.8mm]
ASSE4IBLY I
SPRINKLER1
COVER PLATE: 1/2" [12.7mm] ADJUSTMENT
3.
Bulletin 136 Rev.O
Model FIFR
Model FIFR Recessed
Quick Response
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewal
- HSW 1 Deflector
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention council (LPC, UK)
S. NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
Upright Pendent
Vertical Sidewall conventional
UL Guide Number
VNIV
Patents: US Patent No. 6374,920 Applies to
Model FIFR Vertical Sidewall Sprinklers.
-
Product Description
Reliable Models F1FR and F1FA Recessed Sprinklers are
quick response spnnklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F 1 FR and F 1 FR Recessed automatic spnnklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response trees in laboratory tests which are
five to ten times faster than standard response sprinklers. This
quick response enables the Model F 1 FR and F1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. fhis glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model PP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulh. causing the glass to shatter,
opening the waterway ano allowing the deflector to distrib-
ute the discharging water
Application
Quick response sprinklers are used in fixed lire protec
tion systems: Wet. Dry, Deluge or Preaction. Care must he
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction,
Quick response sprinklers are intended for installation as
specified in NFPA 13. FM Global Loss Prevention Data
Sheet 2-8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
Conventional
Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
InctiIHr,n flt
Sprinkler Type
K Factor S
Height
prinkler roval App
Organization
Sprinkler Identification
Number SIN
US Metric SSP
Standard-Upright (SSU) and Pendent (SSP) Deft tors Marked to Indicate Position
y" (15mm) Standard Orifice with ,t" NPT(R,) Thread 5.6 80 2.2"(56mm) 1.23,4,56,7 R3625 R3615
(20mm) Large Orifice with 3'" NPT(R3/4)Thread 8.0 115 2.3"(58mm) 1,2,3,4,7,8 R3622 63612
" (17mm) Small Orifice with 1" NPT (R) Thread 4.2 60 2.2" (56mm) 128 R36231 63613
3" (10mm) Small Orifice with%" NPT(RY2) Thread 2.8 40 2.2- (.56mm) 1,2,8 R362 R3611
10mm Orifice XLH with R%" Thread 4.2 60 56mm 4,6,7 R3624 63614
Conventional-Instal in Upriqhtor Pendent Position
10mm Orifice XLHwithRThread 4.2 60 56mm ----- 63674
15mm Standard Orifice with ,t NPT(RY) Thread 5.6 80 56mm 4,6,7 R3675
20mmLargeOriflcewith/4"NPT(R3%)Thread 8.0 115 58mm 4.7 R3672
Polyester coated upright UL and ULC listed corrosion resistant.
Upright Pendent
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Approval11t Sprinkler Identification
Orifice Size Height Organizations Number (SIN) us Metric
(15mm) ';NPT(6½) 5.6 80 2.2" (56mm) 1.2.3,4.5,7,8 63615
(20mm) i" NPT(R3%) 8.0 -
115 23(58mm) 1.2.3.8 R3612
iJLL22L_ 'NPT(6½) 4.2 60 22" (56mm)
2.2 (56mm)
1.2.8
128
R3613
.J±L " (10mm) ;'NPT(R½) 2.8 40
10mm R: 4.2 60 56mm 4,7 63614
Refer to escutcheon data table for approvals and dimensions
, ,/'' '.091 DK
L...
r'H 1/2 10,01
..c'.,S1 cpaw..qrft
..'.l".C" 8055 \H -I
I05iV8
1;2-
------------
(fi R(9'IR 10 9" & (2 (9Cu'C"(O". (&&( FOR &.PPR0'.'5 ".0 0&9(NS,0.'09
H
r
H ('"V"
.'
T (,i
n)_.' ('er, ......... .. -
icr '(1 rI' £ C)'I9
2.
Vertical Sidewall
US Patent No. 6,374,920
Model FIFR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
lnctillfirn nnfq.
Nominal
Orifice
Thread
Size
K Factor . Sprinkler
Height
Approval
Organizations
Sprinkler
Identification
Number (SIN) us Metric
1/2-NFl (R½) 5.6 80 2.2" (56mm) 1,2,3,6,8
P3685
15mm '/NPT(R½) 5.6 80 2.2"(56mm) 4
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling I
Dimension (Mm. - Max.) I
Upright 4" - 12" (102mm - 305mm)
Pendent 8" -12" (152mm -305mm) I
Model FIFR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor and Type of Approval Sprinkler
Nominal Thread Sprinkler Identification
Number (SIN) I Light Ordinary
Orifice Size US . I Metric Length Hazard Hazard
.t" (15mm) Y" NPT(8½) 1 5.6 80 2.63" (67mm) 1,2,3.5.8 1.2,5.8 P3635
NOTE: UL, ULC and MEA Listing permits use with Ft or F2 recessed escutCfleon.
J
..,CE or FITTING
WALL DIMENSION
I WIN,
"OLE 0/A. -
'G'
'2 REDUCER
HA l
I(
1',.'.') :OLLAR UNTIL
TIG*Ii AGAINST SPRINKLER , WRENCH BOSS.
, 'I
H "/'JjSIME,vr
() REFER TO ESCUTHCEON DATA rABLE fOR APPROVALS AND OIMENSIONS
Horizontal Sidewall
3,
Installation ..
Quick response sprinklers are intended for installation as
specified inNFPA 13, FM Global Loss Prevention Data Sheet
2-8N or other applicable standards. Quick response sprin-
klers and standard response sprinklers should not be inter-
mixed.
The Model El FR Recessed Quick Response Sprinklers are to
be installed as shown. The Model Fl or F2 Escutcheons illus-
trated are the only recessed escutcheons to be used with the
Model Fl FR Sprinklers. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
When installing Model El FR Sprinklers, use the Model D Sprin-
kler Wrench. When installing Model El FR Recessed Pendant or
Sidewall Sprinklers, use the Model Gffi 1 Spnnkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re-
moval of the protectors before this time may leave the bulb vul-
nerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp.
Bulb
Color
Ordinary 57 1 135 1 00rF(38C) Orange
Ordinary 68i 155 1001F(38°C) Red
Intermediate 79 175 150-F (66-C) Yellow
Intermediate 93 I 200 150-F (66-C) Green
High 141 j286 225°F(107°C) Blue
Not available for recessed sprinklers.
Escutcheon Data
Escutcheon "A" Face of Fitting
ModelApprovals A4-trnent 0nenson to Ceding or
Wed Dimension
1y -
Fl 1.2.4.8 Max Recess (38.1mm) /16 6
Min Recess X" (Eimm - 24i'rn)
(19.1mm) I
F2 1,23,4.5,7.8 Max Recess (38.1mm) X6
Min Recess <6 (5iiim - 17m)
(24mm) _________
FP 1.2 Max Recessed '6 1y'(38.1ni)
______ _______ (11mm) Pueh >1_ Thread-off 1,2 Min Recessed '6 1'4ffm) (24mm)
No Dimensional Figure for FP
Maintenance
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tie vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes ff1121
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated
White Polyester Coated (4) White Painted 131
Speclal Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
Ill Other finishes and colors are available on special order.
Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push -onflhread-off escutcheon.
UL and ULC listed corrosion resistance.
SIN numbers: R3621, R3622, R3623, R3625.
Note: For ," orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model FlEA Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
Corporation. Of other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable nave been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
Rel
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
ia e (800)431-1588 Sales Offices
(9 14)829-2G42 Corporate Offices
(800)848-6051 Sales Fax Revision tines indicate updated or new data
ww.reliablesprhkte(.COffl Internet Address €0. pena6i iri uS. W p49999970027