7/19/22, 5:30 PM AS090138 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS090138
Reference No.: Issued: 11/3/2009
PC #: Inspector:
Project Title: 1208 & 1210 OAK AV TWO FIRE SPRINKLER INSPECTIONS @
$65/EA
Applicant:
INNOVATIVE FIRE PROTECTION
SUITE 101
8779 COTTONWOOD AV
SANTEE, CA
(619) 593-8200 (619)593-9133
Owner:
BUSBY FAMILY TRUST 10-26-01
1212 OAK AVE
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
S
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 10/21/2009 C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 88.0 82.0 500.0 88.0 31.1 66.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.1 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.1 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 10.0 SOURCE 66.8 31.1
2 10.0 - - - - 53.7
2A 10.0 - - - - 49.7 - - -
3A 0.0 HOSE STREAM 48.9 5.0
3 0.5 - - - - 46.2 - - -
4 3.5 - - - - 43.2 - - -
5 10.5 - - - - 37.8 - - -
6 10.5 - - - - 32.8 - - -
7 20.5 - - - - 24.3 - - -
8 20.5 - - - - 23.0
9 30.5 - - - - 12.1 - - -
10 30.5 - - - - 9.6 - - -
10A 30.0 K= 4.30 9.1 13.0
11 30.5 - - - - 9.6 - - -
hA 30.0 K= 4.30 9.3 13.1
12 20.5 - - - - 23.6 - - -
12A 20.0 - - - - 23.8 - - -
13 20.5 - - - - 23.6 - - -
13A 20.0 - - - - 23.8 - - -
These
7ve ...;etire\;%vetl;rappalttit cortipitance
with the current applicable codes and standards tn fotce
ii the urisdict100 The owl1 or cOflta°1 may uttlt/e
i
,in, es ic n ill pp of an app11catt00 101 a building
pci Oil h o o the espresfi derstaodtt1g that this teVte\V
in ii,
elieveS the owflel 01 contraLtfh or their
...itI ettnitte or archttC for sole respotmtbtlt(Y
mr tull cotflPl ance with sad codes attd siandit 5'
miteIudit the hui1d111g code or for any 'e"'" e5p nsibtltY or
dcIILiCitctC eIrlS. OUU1S5
negligence in
plans whether or nist noted in this review.
I )ate/Q"7 Reviewer
1,71 RECOMMEND APPROVA%.
Lai
0 KFCOMMENDA'RO
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 10/21/2009 1 C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.1 0.995 PL 40.00 PF 13.1
1 10.0 SRCE 66.8 (N/A) 12.9 150 FTG T2LG FE 0.0
2 10.0 0.0 53.7 0.0 0.253 TL 52.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 10.0 0.0 53.7 0.0 4.0 psi, 31.1 gpm
2A 10.0 0.0 49.7 0.0
Pipe: 3 31.1 1.590 PL 165.00 FE' 5.1
2A 10.0 0.0 49.7 0.0 5.0 150 FTG E9L FE 4.3
3A 0.0 H.S. 48.9 5.0 0.026 TL 198.00 PV
Pipe: 4 26.1 1.265 FL 10.00 FE' 2.5
3A 0.0 H.S. 48.9 5.0 6.7 150 FTG E2TC FE -0.2
3 0.5 0.0 46.2 0.0 0.057 TL 44.00 PV
Pipe: 5 26.1 1.049 PL 3.00 PF 1.7
3 0.5 0.0 46.2 0.0 9.7 120 FTG C FE -1.3
4 3.5 0.0 43.2 0.0 0.213 TL 8.00 PV
Pipe: 6 26.1 1.101 FL 11.50 FE' 2.3
4 3.5 0.0 43.2 0.0 8.8 150 FTG E2R FE -3.0
5 10.5 0.0 37.8 0.0 0.112 TL 20.50 PV
Pipe: 7 26.1 1.101 PL 16.50 PF 5.1
5 10.5 0.0 37.8 0.0 8.8 150 FTG 2E3T PE 0.0
6 10.5 0.0 32.8 0.0 0.112 TL 45.50 PV
Pipe: 8 26.1 1.101 FL 14.00 FE' 4.1
6 10.5 0.0 32.8 0.0 8.8 150 FTG 3E2R FE -4.3
7 20.5 0.0 24.3 0.0 0.112 TL 37.00 PV
Pipe: 9 20.5 1.101 FL 12.00 PP 1.4
7 20.5 0.0 24.3 0.0 6.9 150 FTG T2R PE 0.0
8 20.5 0.0 23.0 0.0 0.071 TL 19.00 Pv
Pipe: 10 26.1 1.101 FL 27.50 PP 6.5
8 20.5 0.0 23.0 0.0 8.8 150 FTG 3ET5R PE -4.3
9 30.5 0.0 12.1 0.0 0.112 TL 58.50 PV
Pipe: 11 11.1 1.101 FL 68.00 PP 2.5
9 30.5 0.0 12.1 0.0 3.7 150 FTG 4ET9R FE 0.0
10 30.5 0.0 9.6 0.0 0.023 TL 110.00 PV
Pipe: 12 13.0 1.101 FL 8.00 PP 0.6
10 30.5 0.0 9.6 0.0 4.4 150 FTG ETR FE 0.2
10A 30.0 4.3 9.1 13.0 0.031 TL 21.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 10/21/2009 C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -1.9 1.101 PL 9.50 FE 0.0
10 30.5 0.0 9.6 0.0 0.6 150 FTG R PE 0.0
11 30.5 0.0 9.6 0.0 0.001 TL 10.50 PV
Pipe: 14 13.1 1.101 FL 3.50 PF 0.5
11 30.5 0.0 9.6 0.0 4.4 150 FTG 2TR PE 0.2
hA 30.0 4.3 9.3 13.1 0.031 TL 14.50 PV
Pipe: 15 -15.0 1.101 FL 47.00 FE' 2.5
11 30.5 0.0 9.6 0.0 5.1 150 FTG 2T6R FE 0.0
9 30.5 0.0 12.1 0.0 0.040 TL 63.00 PV
Pipe: 16 -5.6 1.101 FL 72.00 PF 0.7
8 20.5 0.0 23.0 0.0 1.9 150 FTG 4T9R FE 0.0
12 20.5 0.0 23.6 0.0 0.007 TL 101.00 PV
Pipe: 17 0.0 1.101 FL 7.50 PF 0.0
12 20.5 0.0 23.6 0.0 0.0 150 FTG 2ETR FE 0.2
12A 20.0 0.0 23.8 0.0 0.000 TL 27.50 PV
Pipe: 18 -5.6 1.101 FL 1.00 FE' 0.0
12 20.5 0.0 23.6 0.0 1.9 150 FTG ---- FE 0.0
13 20.5 0.0 23.6 0.0 0.007 TL 1.00 PV
Pipe: 19 0.0 1.101 PL 2.00 PF 0.0
13 20.5 0.0 23.6 0.0 0.0 150 FTG ETR FE 0.2
13A 20.0 0.0 23.8 0.0 0.000 TL 15.00 PV
Pipe: 20 -5.6 1.101 PL 85.00 FE 0.7
13 20.5 0.0 23.6 0.0 1.9 150 FTG 4T FE 0.0
7 20.5 0.0 24.3 0.0 0.007 TL 105.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.0 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.030 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 10/21/2009, C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
(4) PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: A MATERIAL: SCH40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
0
44
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 10/21/2009 C:\HASS74\C4211—L3.SDF JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC—REC ROOM 0 0. 00 WCl 0OU D I.i a) D " • H D J_) -i a) Ow 04 'J Z o0Ow ill a) .1 00) 4 r-1'.D-.-10>, a% 0cCflU) >r- afl.O
CQ
co
rn
0 0 0 0 0 0
• • .
o 0 0 0 0 0• 0 co W
010Cll 0.cNU)U)DCII '-0.U)-H--
0 -1 0 0 0
0 0
co
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 10/21/2009 : C:\HASS74\C4211-L3.SDF
JOB TITLE:OAKAVE. LOT :fl TWO HEAD CALC-REC ROOM: -
WATER SUPPLY CURVE
96+
880\\\\\
I \\\\\\
\\\\\\
* <-82.0 psi @ 500 gpm
80+ Flow Test Point
72+
x
P 64+
R
E I
S I
S 56+
U I
R I
E I
48+
( I
P
S I
IL 40+
32+
24+
4
16+ LEGEND
I,
X = Required Water Supply
6680 psi @ 31.1 gpm
8+ 'I
I 0 = Available Water Supply
I 87.96 psi @ 31.1 gpm
+ ------+ --------+ ------------------+ -----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
-'. --•,,,, ',,- •
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 10/21/2009 C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE - PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 88.0 82.0 500.0 88.0 31.3 56.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 1 31.3 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 10.0 SOURCE 56.0 31.3
2 10.0 - - - - 42.8
2A 10.0 - - - - 38.8
3A 0.0 HOSE STREAM 38.0 5.0
3 0.5 35.3
4 3.5 - - - - 32.2
5 10.5 - - - - 26.9 - - -
6 10.5 - - - - 21.8 - - -
7 20.5 - - - - 13.3 - - -
8 20.5 - - - - 12.7 - - -
9 30.5 - - - - 8.4
10 30.5 - - - - 8.4 - - -
10A 30.0 - - - - 8.6 - - -
11 30.5 - - - - 8.4 - - -
hA 30.0 - - - - 8.6 - - -
12 20.5 - - - - 9.8 - - -
12A 20.0 K= 4.30 9.1 13.0
13 20.5 - - - - 9.8 - - -
13A 20.0 K= 4.30 9.5 13.3
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 10/21/2009, C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) FIW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.3 0.995 PL 40.00 PF 13.2
1 10.0 SRCE 56.0 (N/A) 12.9 150 FTG T2LG FE 0.0
2 10.0 0.0 42.8 0.0 0.254 TL 52.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 10.0 0.0 42.8 0.0 4.0 psi, 31.3 gpm
2A 10.0 0.0 38.8 0.0
Pipe: 3 31.3 1.590 FL 165.00 PF 5.1
2A 10.0 0.0 38.8 0.0 5.1 150 FTG E9L FE 4.3
3A 0.0 H.S. 38.0 5.0 0.026 TL 198.00 PV
Pipe: 4 26.3' 1.265 FL 10.00 FE' 2.5
3A 0.0 H.S. 38.0 5.0 6.7 150 FTG E2TC FE -0.2
3 0.5 0.0 35.3 0.0 0.057 TL 44.00 PV
Pipe: 5 26.3 1.049 FL 3.00 PF 1.7
3 0.5 0.0 35.3 0.0 9.7 120 FTG C FE -1.3
4 3.5 0.0 32.2 0.0 0.215 TL 8.00 PV
Pipe: 6 26.3 1.101 FL 11.50 PF 2.3
4 3.5 0.0 32.2 0.0 8.8 150 FTG E2R FE -3.0
5 10.5 0.0 26.9 0.0 0.113 TL 20.50 PV
Pipe: 7 26.3 1.101 PL 16.50 FE' 5.1
5 10.5 0.0 26.9 0.0 8.8 150 FTG 2E3T FE 0.0
6 10.5 0.0 21.8 0.0 0.113 TL 45.50 PV
Pipe: 8 26.3 1.101 FL 14.00 FE' 4.2
6 10.5 0.0 21.8 0.0 8.8 150 FTG 3E2R FE -4.3
7 20.5 0.0 13.3 0.0 0.113 TL 37.00 PV
Pipe: 9 12.7 1.101 FL 12.00 PF 0.6
7 20.5 0.0 13.3 0.0 4.3 150 FTG T2R FE 0.0
8 20.5 0.0 12.7 0.0 0.029 TL 19.00 PV
Pipe: 10 0.0 1.101 FL 27.50 FE' 0.0
8 20.5 0.0 12.7 0.0 0.0 150 FTG 3ET5R FE -4.3
9 30.5 0.0 8.4 0.0 0.000 TL 58.50 PV
Pipe: 11 0.0 1.101 FL 68.00 PF 0.0
9 30.5 0.0 8.4 0.0 0.0 150 FTG 4ET9R FE 0.0
10 30.5 0.0 8.4 0.0 0.000 TL 110.00 PV
Pipe: 12 0.0 1.101 PL 8.00 PF 0.0
10 30.5 0.0 8.4 0.0 0.0 150 FTG ETR PE 0.2
10A 30.0 0.0 8.6 0.0 0.000 TL 21.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 10/21/2009 C:\HASS74\C4211-L3.SDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 0.0 1.101 PL 9.50 PF 0.0
10 30.5 0.0 8.4 0.0 0.0 150 FTG R PE 0.0
11 30.5 0.0 8.4 0.0 0.000 TL 10.50 PV
Pipe: 14 0.0 1.101 PL 3.50 PF 0.0
11 30.5 0.0 8.4 0.0 0.0 150 FTG 2TR PE 0.2
hA 30.0 0.0 8.6 0.0 0.000 TL 14.50 PV
Pipe: 15 0.0 1.101 PL 47.00 PF 0.0
11 30.5 0.0 8.4 0.0 0.0 150 FTG 2T6R PE 0.0
9 30.5 0.0 8.4 0.0 0.000 TL 63.00 PV
Pipe: 16 12.7 1.101 PL 72.00 PF 2.9
8 20.5 0.0 12.7 0.0 4.3 150 FTG 4T9R PE 0.0
12 20.5 0.0 9.8 0.0 0.029 TL 101.00 PV
Pipe: 17 13.0 1.101 PL 7.50 PF 0.8
12 20.5 0.0 9.8 0.0 4.4 150 FTG 2ETR PE 0.2
12A 20.0 4.3 9.1 13.0 0.031 TL 27.50 PV
Pipe: 18 -0.3 1.101 PL 1.00 PF 0.0
12 20.5 0.0 9.8 0.0 0.1 150 FTG ---- PE 0.0
13 20.5 0.0 9.8 0.0 0.000 TL 1.00 PV
Pipe: 19 13.3 1.101 FL 2.00 FE' 0.5
13 20.5 0.0 9.8 0.0 4.5 150 FTG ETR FE 0.2
13A 20.0 4.3 9.5 13.3 0.032 TL 15.00 PV
Pipe: 20 -13.6 1.101 FL 85.00 FE' 3.5
13 20.5 0.0 9.8 0.0 4.6 150 FTG 4T PE 0.0
7 20.5 0.0 13.3 0.0 0.033 TL 105.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.0 computer program
under license no. 16080621 granted by
I-IRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.008 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 10/21/2009 C:\HA5S74\C4211-L3.sDF
JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC-REC ROOM
(4) PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: A MATERIAL: SCH40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) B T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
1-4
0
0
00
0
0
LI)
0
0
,31
0
rn
0
0
0
0
0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 10/21/2009 C:\HASS74\C4211—L3.SDF JOB TITLE: OAK AVE. LOT #3 TWO HEAD CALC—REC ROOM 0 0
H (N
0 0 0 0 0 0
• • • • • H
0 0 0 0 0 0
0 (N
-H
Ci)0Lr —O&)-H---
- ---- --- ,-;-- ----.-- -:;--- - -- .-,- - - - -=.--
-. .- SPRINKLER SYSTEM;HYDRAULIC ANALYSIS Page 6
DATE 10/21/2009 C:\HASS74\C4211-L3.SDF
-JOB-TITLE, OAK AVE. LOT #3 TWO HEAD-CALC-REC ROOM - -
WATER SUPPLY CURVE
96+
I \\\\\\
\\\\\\
* <-82.0 psi @ 500 gpm
80+ Flow Test Point
72+
P 64+
R
E I
S I
S 56X
U I
R I
E I
48+
( I
P I
S
I 40+
32+
24+
16+ LEGEND
I X = Required Water Supply
56.03 psi @ 31.3 gpm
8+
I 0 = Available Water Supply
I 87.96 psi @ 31.3 gpm
+ ------+ --------+ --------+ ---------+ -----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
L
Bulletin 006 Rev.A
ble
A Concealed Residential
Sprinkler engineered for a
minimum design density
of 0.05 gpm/ft2 with low GPM
requirements.
Features
1. Very low water flow requirements.
2.112" (13mm) Total adjustment.
Push-On/Thread-Off
cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and
black plated or painted finishes.
Listings & Approval
Listed by Underwriters Laboratories,
and certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Model RFC43 Concealed
Residential Sprinkler
(SIN RA061 2) CD
Product Description
Model RFC43 Concealed Residential Sprinklers are fast
response residential fusible solder link automatic sprinklers.
Residential sprinklers differ from standard sprinklers primarily
in their response time and water distribution patterns.
Model RFC43 sprinklers discharge water in a
hemispherical pattern below the sprinkler deflector.
Residential distribution patterns are higher and generally
contain a finer droplet size than standard sprinkler patterns.
The combination of speed of operation and high discharge
pattern required for residential sprinklers has demonstrated,
in fire testing, an ability for controlling residential fires, and
thereby providing significant evacuation time for occupants.
The RFC43 Sprinkler provides the best form of fire
protection by combining an attractive appearance and 1/2
(13mm) of cover adjustment for ease of installation. The
small diameter cover plate is easily and positively attached
and blends into the ceiling, concealing the most dependable
fire protection available, an automatic sprinkler system.
The RFC43 is a UL Listed Residential Sprinkler to be
installed in the residential portions of any occupancy in
accordance with NFPA 13, 13R, & 13D.
The RFC43 can reduce the need for precise cutting of drop
nipples The threaded cover plate assembly can be adjusted
without tools to fit accurately against the ceiling. The fire
protection system need not be shut down to adjust or remove
the cover plate assembly.
Application and Installation
The RFC43, for residential installations, uses a 165°F (74°C)
fusible solder link in a tuning fork style sprinkler frame with a
drop-down deflector. This assembly is recessed into the
ceiling and concealed by a flat cover plate. The cover plate is
attached to the skirt, using 135°F (57°C) ordinary temperature
classification solder. When the ceiling temperature rises, the
solder holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
Thc RchhIø hiOnmnfie qnrinklar ('rb Inr cc f\Irrth tA flu uctc'n PrktA,\, tArupnt \Icrncun NOW Yrrk incc
inside to ceiling temperature. The subsequent operation of
the solder link opens the waterway and causes the deflector
to drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover plate
and cup will assure that the drop-down deflector is properly
located below the ceiling. The residential distribution pattern
contains a finer droplet size than a standard sprinkler, and the
pattern produces significantly higher wall wetting.
After a 2 5i8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench. When
installing a sprinkler, the wrench is first positioned into the
sprinkler/cup assembly and around the hexagonal body of
the sprinkler frame. The Wrench must bottom out against the
cup in order to ensure proper, safe installation. The sprinkler
is then tightened into the pipe fitting. When inserting or
removing the wrench from the sprinkler/cup assembly, care
should be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP
ASSEMBLY. MODEL RFC43 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COVERS.
Cover assemblies provide up to /2" (13mm) of adjustment
Turn the cover clockwise until the flange is in contact with the
ceiling. The optional push-on cover plate may require a final
adjusting turn to contact the calling. Cover removal requires
turning in the counter-clockwise direction.
In callings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative
pressurization but must not be positively pressurized. Inspect
all sprinklers after installation to ensure that the gap between
the cover plate and calling and the 4 slots in the cup are all
open and free from any air flow impediment
Temperature Rating
Sprinkler Cover Plate Max. Ambient
Temp.
165°FR4°C 135°F/5C 100°F/38°C I
Installation Data
Minimum Required
Thread Size K Sprinkler Maximum Minimum Sprinkler Discharge
Spacing Distance Distance between inch (mm) Factor ft. (m) to Wall ft. (m) sprinkler ft. (m) Flow Press.
gpm (Lpm) psi (bar)
1/2' (15mm) 4.3 12 x 12 (3.60.6) 6(1.83) 8 (2.43) 12(45) 7.8 (0.54)
l/2 (15mm) 4.3 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63)
1/2" (15mm) 4.3 16 x 16 (4.9x4.9) 8(2.43) 8(243) 13(49) 9 1(0.63)
'/2': (15mm) 4.3 18 x 18 (5.5x5.5) 9(2.74) 8(243) 18(68) 17.5 (1.21)
½"(l5mm) 4.3 20x20(6.0x6.0) 10(3.05) j8(243) 21(79) 23.8(1.64)
Note: 1 bar = 100 Kpa
Model RFC 43 Pendent Flat Concealed installed below Sloped Ceiling.
Tkrrit flt
Thread Sprinkler [Temp.
Si I Temp. Rating I Temp. Rating Pri
F kçL
½" NPT ( L IJZL I 135(57) --
lax. Max. Actual 1 Sprinkler
ssure Ambientlemp. K Factor M
Ad
' ti Identification
Number J (bar) ._çL_... Jc
5(.)
Table 3 - Anolication
Max Sprinkler Spacing Along Slope
(1
(W) Width x ( L) Length ft (m) Mm. Flow Per Sprinkler Head
Pitch I Slope of' 18.4° Pitch
Pressure I Mm. Flow Per Sprinkler Head Pressure
12 x 12(3,6 x 3,6) - L!15 (1,21) 13(49) 9.1 0.63_...j
14 x 14(4.3 x 4,3) 18(68)-
18(68)...__j
L 17.5(1,21) 13(49) 9.1 0,63 -.
16 x 16(4.9 x 4,9) ITS (121) 13(49)
18 x 18(5.5 x 5,5) I 21(79)
20x20(6,1 x6,1) __________ 21 (79) 23.8 1,64
2.
Maintenance
Model RFC43 Concealed Sprinklers should be inspected
quarterly and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
cover plate assembly which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-operation.
135°F (57°C). Cover plate assembly shall consist of a brass
cover plate and copper alloy retainer flange having a
[thread-on] [push-on] and thread-off design, allowing a /2"
cover plate adjustment Any secure engagement between
the cover plate and the cup will assure that the drop-down
deflector is properly located below the ceiling. A plastic
protective cap shall be provided and factory installed inside
the sprinkler cup to protect the drop-down sprinkler deflector
from damage, which could occur during construction before
the cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty - specify]. Residential concealed sprinklers
shall be Reliable Model RFC43, SIN RA0612 (Bulletin 006).
Model RFC43 Residential Concealed
Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential
concealed sprinklers with drop-down deflector and
adjustable flat cover plate engineered for a minimum design
density of 0.05 gprrt2. Sprinkler frame and deflector shall be
of bronze frame construction having a ½" NPT thread.
Thermal element shall consist of an approved black-painted
beryllium-nickel fusible solder link with symmetric lever
mechanism, maintaining a Teflon-coated Belleville spring
washer and machined brass cap water seal assembly
containing no plastic parts. Sprinkler K-factor shall be nominal
4.3 (62.4), having a 7/16" orifice. Temperature rating shall be
Ordinary 165°F (740C); cover plate temperature rating to be
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On cover
Cover Plate Finishes n
Standard Finishes
Chrome
White
Special Application
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
" Other colors and finishes
available. Consult factory
for details.
Note: Paint or any other
coatings applied over the
factory finish will void all
approvals and warranties.
- x 112 ' REDUCING
TEE OR ELBOW -...
C f (66.7mm] DA.
2?6 - (58.7mm] 0/A - •..- I-I0LE IN CEILING
CUP
1
2 [50.8mm] U4X.
FACE OF FITTING ro FACE OF CEILING
1-' DIMENSION
CEILING'
-
[12.7mm] MAX.
COVER ADJUSTMEJ
.- DJA_
rE
_[I
COVER PLA (84.1mm] [4.8mm]
ASSE/,I&LY SPRINKLER-'
COVER PLATE, 1/2 ' (12.7mm] ADJUSTMENT
3.
Ila*. ble
Bulletin 136 Rev.O w Model FIFR
Model FIFR Recessed
Quick Response
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council (LPC, UK)
NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
Upright Pendent
Vertical Sidewall Conventional
UL Guide Number
VNIV
Patents: US Patent No. 6,374,920 Applies to
Model F1FR Vertical Sidewall Sprinklers.
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the anractive low profile of a decorative
sprinkler.
The Models F 1 FR and F 1 1R Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response tines in laboratory tests which are
five to ten times faster than standard response sprinklers. This
quick response enables the Model F 1 FR and F 1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is Specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble As heat is applied, the liquid ex-
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model FP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push Out against the bIb causing the glass to shatter,
opening the waterway ann allowing the deflector to distrib-
ute the discharging water
Application
Quick response sprinKers are used in fixed lire protec
tion systems: Wet, Dry. Deiuge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data
Sheet 2-8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
Conventional
H
CJE
R(OCf 4
,&u',ST cP.'i( socc
-
—1
P rcc 01 70
wus1±'-- co
r 21-
,/8
I 2 I1/32' N, [12.2,,..,,1
(') REFER ,o r r2 (sCu'C..(O LM r r( fog 4PPRO',4 S 4'O O44.5,OgS
Model FIFR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
infIlfinn flith
Sprinkler Type
K Factor Sprinkler
Height
Approval
Organization
Sprinkler identification
Number (SIN)
US Metric
Standard-Upright (SSU and Pendent (SSP) Defiectors Marked to Indicate Position
)" (15mm) Standard Orifice with )" NPT (R,) Thread 5.6 1 80 2.2" (56mm) 1.2,3.4.5.6.7 R3625 R3615
; (20mm) Large Orifice with 3" NPT (R3/4)Thread 8.0 115 2.3' (58mm) 1,2,3,4,7,8 8362201 83612
<' (17mm) Srnafi Orifice with )" NPT (R.) Thread 4.2 60 2.2" (56mm) 1,2,8 R3623t0 R3613
3" (10mm) Small Orifice with X" NPT (RY)Thread 2.8 40 2.2"(56mm) 1,2,8 R362 R361t
l0mmOdfice)QHwfthR%"Thread 4.2 60 56nm 4,6,7 R3624 R3614
Conventional--Install in Upright cx Pendent Position ____
10mm Orifice )QH with R Thread 42 60 56mm ---- R3674
15mm Standard Orifice with ) NPT(RX) Thread 5.6 56mm 4,6,7
I rnn Orifi with 3/4"NPT (R34)Thread
83675
20mm 8.0
4--807
11558mm 4,7 R3672
Polyester coated upright UL and ULC listed corrosion resistant.
Upright Pendent
Model FIFR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
P Nominal - Thread K Factor Sprinkler Approvat1° Sprinkler Identification
Orifice Size Height Organizations Number (SIN) us Metric
(15mm) "NPT(R'/2) 5.6 80 27(56mm) .2,3.4.5,7,8 R3615
(20mm) " NPT (R3%) 8.0 L)5 2.3" (58mm) 12,3.8 R3612 --
{T22L_ NPT(RY7) 4.2 60 27(56mm) 12.8
V (10mm) ;'NPT (R/2) 2.8 -
40 27(56mm) 1,2.8 R3611
10mm -R 4 4.2 - 60 56mm 4.7 83614
Refer to escutcheon data table for approvals and dimensions
2.
Vertical Sidewall
US Patent No. 6,374,920
3.
1 00
I f'EF''COR
OtEDIA.
2-1
2 REDUCER __•7
I t
2
OLLAR UNTIL -
r'c; .104/NSf SPRINKLER : WRENCH BOSS.
- SruE,vr
REFER To ESCUTHCEON DATA TARt C FOR APPROVALS AND DIMENSIONS
'.t' '-1 L
Horizontal Sidewall
Model F1 FIR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Positlori Upright or Pendent
Approval Type: Light Hazard Occupancy
I ncfllfitn flf
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Approval
Organizations
Sprinkler
Identification
Number (SIN)
__________
us Metric
1/2 NPT(RY2) 5.6 80 2.2(56mm) 1,23,6.8
R3685
15mm W'NPT(R½) 5.6 80 2.2(56mm) 4
LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
Dimension (Mm. - Max.)
Upright 4" - 12 (102mm - 305mm)
Pendent 6 - 12 (152mm .305mm) I
Model FIFR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor and Type of Approval Sprinkler
Nominal Thread Sprinkler Identification
Number (SIN) I Light Ordinary
Orifice Size US Metric Length Hazard Hazard
ic' (15mm) )'' NPT(R'/7) 5.6 80 263(67mm) 1,2,3.5.8 1.2.5.8 R3635
NOTE: UL. ULC and MEA Listing permits use with Fl Of F2 recessed escutcheon.
H 1
OF F/TI/NO r ----H WALL DIMENSION
.-. __J .. IJI,
tie vacuuming. Remove an'sprinkier. which has: been
painted (other than factory applied) 'ordàmaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes (1)121
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated (3)
White Polyester Coated (4) White Painted t31
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
(I) Other finishes and colors are available on special order.
Consult the factory for details.
(2) FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
131 FP Push-on/Thread-off escutcheon.
( 4) UL and ULC listed corrosion resistance.
SIN numbers: R362 1. R3622, R3623, R3625.
Note: For )'" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify:
Sprinkler Mode)
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
-Installation -.
Quick response spnnklers are intended for ,nstallaUon as
specified hi NFPA 13, FM Global Loss PrêñtithDätaSbeét.
2-8N or. other applicable standards; ,Quick responsesprin-
kters and standard response sprinklers should not be inter-
mixed.'
The Model Fl FIR Recessed Quick Response Sprinklers are to
be installed as shown. The Model Fl or F2 Escutcheons illus-
trated are the only recessed escutcheons to be used with the
Model Fl FR Sprinklers. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
When installing Model F1FR Sprinklers, use the Model D 5pm-
kier Wrench. When installing Model Fl FR Recessed Pendent or
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re-
moval of the protectors before this time may leave the bulb vul-
nerable to damage. RPSCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
Sprinkler
Clfficbon Max Ambient
Temp.c
PBuIb
E
Ordinary 57 135 1O3°F(38°C)
Ordinary 68 155 ltfl°F(38"C)
Intermediate 79 175 150F(66"C) Yellow
Intermediate 93 2(K) 150°F(66C) Green
High 141 286 1 225F(107°C) Blue
Not available for recessed sprinklers.
Escutcheon Data
Escutcheon "A" Face of Fithng
Model Approvals kment Drnenston to Ceding or
Wad Dimension
1/2
Fl 12.4,8 Max Recess (38.1mm) i6 6
Min Recess X (5mm - 24mm)
(19.1mm)
1/2
F2 1.2,3,4,5,7.8 Max Recess (38.1mm) 4" -
Min Recess -' (5mm- l7rrni)
(24mm)
FP 1.2 Max Recessed X 6"1"(38.1m)
______ _______ (11mm) PuSh-orV
Thread-off 1.2 Min Recessed 16 1" (25 4rrm)
__ (24mm) __________
No Dimensional Figure for FP
Maintenance
The Models F1FR and FlEA Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
Corporation. or other similar Organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Recycled
(800)431-1588 Sales Offices Reliableo (800)848-6051 Sales Fax RevisiDn lines indicate updated or new data
(914)829-2042 Corporate Offices
ww.reliableslx 1klor.COhi Internet Address CC. Piinicd in U.S.A.3,V7 P/49999570027