HomeMy WebLinkAbout4073 AIDAN CR; ; FA070051; PermitFIL [ CO PY fAOt<ffi( Submittals Specification Section 16715 F ire Alarm System . \ • ' for Encina Waste Water Authority Operation and Maintenance Facility UBMITTED Roc k Electric 7950 Silverton Ave., Suite 211 San Diego, California 92126 (858) 566-4449 Fax (858) 536-8931 <e) Fire-uTet Alarms MS-9200UDLS Battery Calculation Note 1: You can edit all current draws and are fully responsible for verifying these calculations. Note 2: You only need to make entries in the yellow cells Regulated Load in Standby 11111 11:.l ''.SitM II • 11111. .... u:.1,1•1• •·=· Main Circuit Board X 00 = 0.255000 ACM-BRF 0 X .03 000 = ACM-16ATF 0 X 0.040 ACM-32AF 0 X 0.040000 = AEM-16ATF 0 X 0.002000 = AEM-32AF 0 X 0.002000 = AFM-16ATF X 0.040000 = AFM-32AF 0 0.040000 = AFM-16AF 0 X .0250 - UDACT-F 0 X 0.040000 = LDM-32F X 0.040000 = LDM-E32F 0 X 0.002000 = LCD-B0F 0 X 0.025000 = 4XTMF 0 X 0.005000 = 4-Wire Smoke Detectors 0 X 0.000000 = Power Supervision Relays 0 X 0.025000 = !Addressable Devices BEAM355 and BEAM355S 0 X 0.002000 = BEAM 1224 0 X 0.017000 .. = CP355 0 X 0.000300 ' = SO355 0 X 0.000300 = SD355T 0 X 0.000300 = AD355 0 X 0.000300 = H355 0 X 0.000300 = H355R 0 X 0.000300 = H355HT 0 X 0.000300 = D350P 0 X 0.000300 = D350RP 0 X 0.000300 = MMF-300 0 X 0.000400 = MMF-300-10 0 X 0.003500 = MDF-300 0 X 0.000750 = MMF-301 0 X 0.000375 = MMF-302 0 X 0.000270 = MMF-302-6 0 X 0.002000 = BG-12LX 0 X 0.000230 = CMF-300 0 X 0.000390 = CMF-300-6 0 X 0.002250 = CRF-300 0 X 0.000270 = CRF-300-6 0 X 0.001450 = 1300 0 X 0.000400 = 8501 BH & 8501 BHT (see note 3) 0 X 0.001000 = 8224RB Relay Base 0 X 0.000500 = 822481 Isolator Base 0 X 0.000450 = 1c.;urrent uraw trom I t:!3 (nonalarm) o.uuuuuu Total Standby Load 0.255000 Page 1 of 4 Notes: 1) Refer to the Device Compatibility Document for standby current 2) Must use compatible listed Power Supervision Relay 3) Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source. 4) Current limitations of TB3 and TB4 circuits is 2.5 amps per NAC output and 0.5 amps per aux. power output 5) Total current draw listed cannot exceed 6.0 amps Page 2 of 4 @Fire·LITe" Alarms MS-9200UDLS Battery Calculation Note 1: You can edit all current draws and are fully responsible for verifying these calculations. Note 2: You onl need to make entries in the ellow cells Regulated Load in ALARM Device Type ain c· ·t -F ACM-16AT ACM-32AF AEM-16ATF AEM-32A AFM-16ATF AFM-32AF -A UDACT-F LDM-32F LDM-E32F LCD-80F 4XTMF 4-Wire Smoke Detectors Power Supervision Relays ALL Addressable Devices -Maximum draw NAC #1 NAC#2 NAC#3 NAC#4 nona arm Notes: Numoer of Devices 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 X X X X X X X X X X X X X X X X X X X I Current (Amps) I I 0.3250 mllllllllEI •a 0.158000 0.056000 = .056000 = 0.018000 = 0.018000 = 0.056000 = 0.056000 = 0.065000 = 0.075000 = 0. 560 0 = 0.018000 0.064000 = 0.011000 = 0.000000 = 0.0 00 0.400000 ' = 0.000000 = 0.000000 = 0.000 00 0.000000 = = Total Alarm Load 1) Current limitations for NAC circuits TB3 & TB 4 is 2.5 amps per circuit 2) ACM 8RF current based on all eight relays activated on a single module 3) Annuciator current based on all LED's lit 4) LDM-32F current with all LED's on 5) MMF 302 current limited to 90mA in alarm 6) Total alarm current cannot exceed 6.0 amps Page 3 of 4 1 otal l;Urrent (Amps) 0.325000 0.400000 0 @)Ftre·LITe·ALarms MS-9200UDLS Battery Calculation Note 1: You can edit all current draws and are fully responsible for verifying these calculations. Note 2: You onl need to make entries in the ellow cells Calculation in Total Sheet Use the total standby and alarm load currents calculated in tables A-2A and A-2B for the following battery calculations Standb Load Current Am s 0.255000 X Alarm Load Current Am s) 0.725000 X Total Current Load the Deratin Factor 1.2 = The MS 9200UDLS can charge this size battery The batteries can be stored in the cabinet Current Draw Check NAC#1 current is within the limitations of the circuit. NAC#2 current is within the limitations of the circuit. NAC#3 current is within the limitations of the circuit. NAC#4 current is within the limitations of the circuit. MS 9200UDLS without XRM-24 transformer Total Ampere Hours Re uired The required output current is within the panel's limitations MS 9200UDLS with XRM-24 transformer The re • ut current is within the anel's limitations Page 4 of 4 6.181 AH X 1.20 7.417 AH Index Of Submittals ISpec # Item Description Manufacturer t Part# 16715-2.1 B Fire Alarm Control Panel FireLite MS-9200UDLS 16715-2.1 B Batteries FireLite PS-695 16715-2.2 A Remote Annunciator FireLite LCD-B0F 16715-2.3 A Manual Pull Station FireLite BG-12LX 16715-2.3 B Photoelectric Smoke Detector FireLite SD355 16715-2.3 C Automatic Heat Detector FireLite H355 16715-2.3 D Duct Smoke Detector FireLite D350PL 16715-2.3 E Monitor Module FireLite MMF-300 16715-2.3 F Control I Relay Module FireLite CRF-300 16715-2.31 Hom/Strobe FireLite P1224MC 16715-2.3 L Alarm Bell FireLite KMS-6-24 16715-2.3 M Waterflow Switch Potter VSR-F 16715-2.3 M Supervisory Switch Potter OSYSU-1 16715-2.3 P Network Cables West Penn 980 16715-2.3 P Network Cables West Penn 994 MS-9200UDLS(E) Intelligent Addressable FACP with Built-In Communicator GENERAL The Fire•Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/ Transmitter) all on one circuit board. This compact, cost effec- tive, intelligent addressable control panel has an extensive list of powerful features. While the MS-9200UDLS may be used with an SLC configured in the CLIP (Classic Loop Interface Protocol) mode, it can also operate in LiteSpeed™ mode--Fire•Lite's latest polling technol- ogy--for a quicker device response time. LiteSpeed's patented technology polls 1 o devices at a time. This improvement allows a fully-loaded panel with up to 198 devices to report an inci- dent and activate the notification circuits in under 1 o seconds. With Litespeed polling, devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. (Consult the wire table on page 3 for specific installation instructions.) The MS-9200UDLS's quick-remove chassis protects the elec- tronics during construction. The backbox can be installed allowing field wiring to be pulled. When construction is com- pleted, the electronics can be quickly installed with just two bolts. Available accessories include LED, graphic and LCD annunci- ators, and reverse polarity/city box transmitter. The panel is programmed through the FACP's keypad or via a standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board. This permits easy typing of address labels and other programming information. NOTE: Unless otherwise specified, the term MS-9200UDLS is used in this document to refer to both the MS-9200UDLS and the MS-9200UDLS(E) FACPs (Fire Alarm Control Panels). FEATURES • On-board DACT. • Four Class B or two Class A NAG circuits. -6.0 amps total NAG power with optional XRM-24. • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices. • Complies with UL 864 9th Edition requirements. • Remote Acknowledge, Silence, Reset and Drill via address- able monitor modules. • Up to 32 ACM Series (ACM-16AT or ACM-32 series) annunciators or LCD-B0F remote annunciators via EIA-485. • EIA-232 printer/PC interface (variable baud rate) on main circuit board. • Integral BO-character LCD display with backlighting. • Real-time clock/calendar with automatic daylight savings control. • Detector sensitivity test capability (NFPA 72 compliant). • History file with 1,000-event capacity. • Maintenance alert warns when smoke detector dust accu- mulation is excessive. • Automatic device type-code verification. • One person audible or silent walk test with walk-test log and printout. • Point trouble identification. • Waterflow (nonsilenceable) selection per monitor point. • System alarm verification selection per detector point. DF-52422 • A 1-40 @) F1re·uTe·ALarms by Honeywell Addressable • PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant). SLCLOOP: • SLC can be configured for NFPA Style 4, 6, or 7 operation. • SLC supports up to 198 addressable devices per loop (99 detectors and 99 monitor, control, or relay modules). • SLC loop maximum length 10,000 ft. (3,000 m.). See wire table on page 3. NOTIFICATION APPLIANCE CIRCUITS (NACS): • Four onboard NACs with additional NAG capability using output control modules (CMF-300 or CMF-300-6). • Silence Inhibit and Auto Silence timer options. • Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability. • Selectable strobe synchronization per NAG. • 2.5 amps maximum per each NAG circuit. NOTE: Maximum or total 24VDC system power shared between all NAG circuits and auxiliary power outputs is 3. 6 amps. PROGRAMMING AND SOFTWARE: • Autoprogram (learn mode) reduces installation time. • Custom English labels (per point) may be manually entered or selected from an internal library file. • Two programmable Form-C relay outputs. • 99 software zones. • Continuous fire protection during online programming at the front panel. • Program Check automatically catches common errors not linked to any zone or input point. DF-52422 • 09/20/06 -Page 1 of 4 USER INTERFACE LED INDICATORS • AC POWER (green) • FIRE ALARM (red) • SUPERVISORY (yellow) • ALARM SILENCED (yellow) • SYSTEM TROUBLE (yellow) • MAINTENANCE/PRESIGNAL (yellow) • DISABLED (yellow) • BATTERY FAULT (yellow) • GROUND FAULT (yellow) KEYPAD CONTROLS • ACKNOWLEDGE/STEP • ALARM SILENCE • DRILL • SYSTEM RESET (lamp test) • 16-key alpha-numeric pad (similar to telephone keypad) • 4 cursor keys • ENTER ORDERING OPTIONS MS-9200UDLS(E): 19S-point addressable Fire Alarm Control Panel, one SLC loop. Includes SO-character LCD display, sin- gle printed circuit board mounted on chassis, and cabinet. 4XTMF Reverse Polarity Transmitter Module: Provides supervised output for local energy municipal box transmitter, alarm, and trouble. DP-9692: Optional dress panel for MS-9200UDLS. TR-CE: Trim Ring for semi-flush mounting. BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-75. BB-55F: Battery box, houses two 55 AH batteries. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. CHG-120F: Remote battery charging system for lead-acid batteries with a rating of 55 to 120 AH. Requires additional BB- 55F for mounting. BAT Series: Batteries, see data sheet DF-52397. XRM-24(E): Optional transformer. Increases system power to 6.0 amps. Use XRM-24E with MS-9200UDLS(E). PAT/PK-CABLE: Cable printer/personal computer interface cable. PRN-6F: UL listed compatible event printer. Uses tractor-fed paper. COMPATIBLE ANNUNCIATORS ACM-8RF: Relay module provides 8 Form-C 5.0 amp relays. ACS-LED Zone Series: LED-type fire annunciators capable of providing up to 99 software zones of annunciation. Available in increments of 16 or 32 points to meet a variety of applica- tions. LDM Graphic Series: Lamp Driver Module series for use with custom graphic annunciators. LCD-S0F (Liquid Crystal Display) point annunciator: SO-character, backlit LCD-type fire annunciators capable of displaying English-language text. NOTE: For more information on Compatible Annunciators for use with the MS-9200UDLS, see the following data sheets (document numbers) ACM-BRFACM-BR (DF-51555), ACSIACMSeries (DF- 52378), LDM Series (DF-51384), LCD-B0F (DF-52185). L/TESPEED COMPATIBLE ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. Page 2 of 4 -DF-52422 • 09/20/06 CP355: Addressable low-profile ionization smoke detector. SD355: Addressable low-profile photoelectric smoke detector. SD355T: Addressable low-profile photoelectric smoke detec- tor with thermal sensor. H355: Fast-response, low-profile heat detector. H355R: Fast-response, low-profile heat detector with rate-of- rise option. AD355: Low-profile, intelligent, "Adapt" multi-sensor detector (B350LP base included). CLIP MODE ONLY BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitivity test. D350PL: Photoelectric low-flow duct smoke detector. D350RPL: Photoelectric low-flow duct smoke detector with relay option. MMF-300: Addressable Monitor Module for one zone of nor- mally-open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of- line resistor. Module may be configured for either a Style B (Class B) or Style D (Class A) IDC. MDF-300: Dual Monitor Module. Same as MMF-300 except it provides two Style B (Class B) only IDCs. MMF-301: Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF-302: Similar to MMF-300, but may monitor up to 20 con- ventional two-wire detectors. Requires resettable 24 VDC power. Consult factory for compatible smoke detectors. CMF-300: Addressable Control Module for one Style Y/Z (Class BIA) zone of supervised polarized Notification Appli- ances. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance Circuit option requires external 24 VDC to power notification appliances. CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. BG-12LX: Addressable manual pull station with interface module mounted inside. 1300: This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). SMB500: Used to mount all modules except the MMF-301 and M301 . MMF-300-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six mod- ules on a CHS-6 chassis in a BB-SF. MMF-302-6: Six-zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six mod- ules on a CHS-6 chassis in a BB-SF. CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-SF. CRF-300-6: Six Form-C relay control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-SF. NOTE: 1) For more information on Compatible Addressable Devices for use with the MS-9200UDLS, see the following data sheets (document numbers): AD355 (DF-52386), BG-12LX (DF- 52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374), CMFI CRF Series (DF-52130), CP355 (DF-52383), D350PUD350RPL (DF-52398), H355 Series (DF-52385), 1300 (DF-52389), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF- 302-6 (DF-52356), SD355/SD355T (DF-52384). 2) Legacy 300 Series detection devices such as the AD355, CP300/CP350, SD300(T)ISD350(T) and older modules such as the M300, M301, M302, C304, and BG-10LX are not compatible with LiteSpeed polling. If the SLC contains one of these devices, polling must be set for standard CLIP protocol. Please consult tac- tory for further information on previous 300 Series devices. WIRING REQUIREMENTS While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical inter- ference. Wire size should be no smaller than 18 AWG (0.78 mm•) and no larger than 12 AWG (3.1 mm•). The wire size depends on the length of the SLC circuit. Use the table below to determine the specific wiring requirements for the SLC. SLC Wire Requirements Distance in Feet Wire Size Wire Type Protocol (m) Twisted-pair, shielded 10,000 feet(3,Q48 m) 12 AWG (3.31 mm2) Belden 9583, Genesis 4410, Signal 98230, WPW D999 Twisted-pair, shielded 8,000 feet (2,438 m) 14 AWG (2.08 mm2) Belden 9581 , Genesis 4408, Signal 98430, WPW D995 CLIP Twisted-pair, shielded 4,875 feet (1,486 m) 16 AWG (1.31 mm2) Belden 9575, Genesis 4406, & 4606, Signal 98630, WPW D991 Twisted-pair, shielded 3,225 feet (983 m) 18 AWG (0.78 mm2) Belden 9574, Genesis 4402 & 4602, Signal 98300, WPW D975 Untwisted, unshielded wire, 3,000 feet (914 m) 12 -18AWG in or out of conduit (3.31 mm2-0.821 mm2) SLC Wire Requirements Distance in Feet Wire Size Wire Type Protocol (m) Non-Plenum (FPLR): Twisted-pair, unshielded 10,000 feet (3,048 m) 12 AWG (3.31 mm2) Genesis 4315, Belden 5020UL Plenum (FPLP): Genesis 4515, Belden 6020UL Non-Plenum (FPLR): Twisted-pair, unshielded 8,000 feet (2,438 m) 14 AWG (2.08 mm2) Genesis 4313, Belden 5120UL Plenum (FPLP): LiteSpeed Genesis 4513, Belden 6120UL Non-Plenum (FPLR): 16 AWG (1.31 mm2) Genesis 4311 , Belden 5220UL Twisted-pair, unshielded 4,875 feet (1,486 m) Plenum (FPLP): Genesis 4511, Belden 6220UL Non-Plenum (FPLR): 18 AWG (0.821 mm2) Genesis 4306, Belden 5320UL Twisted-pair, unshielded 3,225 feet (983 m) Plenum (FPLP): Genesis 4506, Belden 6320UL MS-9200UDLS Wire Requirements DF-52422 • 09/20/06 -Page 3 of 4 SYSTEM SPECIFICATIONS SYSTEM CAPACITY • Intelligent Signalling Line Circuits ....................................... 1 • Addressable device capacity .......................................... 198 • Programmable software zones ......................................... 99 • Annunciators .................................................................... 32 ELECTRICAL SPECIFICATIONS AC Power: MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps. MS- 9200UDLSE: 240 VAC, 50 Hz, 1.5 amps. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Battery: Two 12 V 18AH lead-acid batteries. Battery charger capacity: 7 -18 AH. MS-9200UDLS cabinet holds maximum of two 18 AH batteries. Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Each terminal block pro- vides connections for two Style Y (Class B) or one Style Z (Class A) for a total of four Style Y (Class B) or two Style Z (Class A) NACs. Maximum signaling current per circuit: 2.5 amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer to Fire•Lite Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). Form-C relays. Special Application Power (24 VDC Nominal): Jumper selectable (JP4) for conversion to resettable power output. Up to 0.5 amps total DC current available from each output. Power-limited. Four-Wire Resettable Special Application Smoke Detector Power (24 voe nominal): Up to 0.5 amps for powering four- wire smoke detectors. Power-limited. Refer to Fire•Lite Device Compatibility Document for listed compatible devices. Remote Sync Output: Remote power supply synchronization output. Nominal special application power: 24 VDC. Maximum current: 40 mA. End-of-Line Resistor: 4.7K ohm. Output linked to NAC 1 control. Supervised and power-limited. Telephone Interface: Requires dedicated business tele- phone number with a minimum of 7 volts DC. Obtain dedicated phone line directly from your local phone company. Do not use shared phone lines or PBX (digital) type phone line extensions. CABINET SPECIFICATIONS Door: 19.26" (48.92 cm.) high x 16.82' (42.73 cm.) wide x 0.12' (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65' (49.91 cm.) wide. SHIPPING SPECIFICATIONS Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 - 49°C/32 -120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme tempera- ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27°C/60 -80°F. NFPA STANDARDS The MS-9200UDLS complies with the following NFPA 72 Fire Alarm Systems requirements: -LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). -AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). -REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) -PROPRIETARY (Automatic, Manual and Waterflow). -CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). -AUTO DETECTOR SELF TEST AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic MS- 9200UDLS control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL: S624 • FM approved • CSFM: 7165-0075:208 LiteSpeed™ is a trademar1<; and Firelite® Alarms is a registered trademar1< of Honeywell International Inc. Microsoft® and Windows® are registered trademar1<s of the Microsoft Corporation. ©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. ~ i➔=i ·iil=il=l •J lNCINllllNC I MANIIACTIIINC QllLITY SYSTEMS We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (Bn ) 699-4105. www.firelite.com Page 4 of 4 -DF-52422 • 09/20/06 Made in the U.S. A. LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: NOTE: CALIF ORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7165-0075:208 Control Unit (Non High-Rise) Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653 Contact: Brian Reynolds (203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Models MS-9200UD and *MS-9200UDLS addressable control units. Local, auxiliary, remote station, central station and proprietary (protected premise). Refer to listee's data sheet for detailed product description, operational considerations and required/optional accessories. When required, accessories shall be CSFM listed. 120 VAC, 60 Hz, 2.06 A Primary, 24 voe Secondary In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating and UL label. Listed as an addressable fire alarm control panel for use with separately listed compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual for details. This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition. For Fire Alarm Verification Feature (delay of fire alarm signal). the maximum Retard/ReseURestart period shall not exceed 30 seconds. *Rev./Recert. 04-04-2006 jew This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: AUGUST 17, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 BAT Series Batteries Sealed Lead-Acid General DF-52397:A • D-500 @) Flre·UTe~ALarms by Honeywell Power Supplies/Accessories BAT Series Batteries feature a new part-numbering/listing sys- tem -providing an improved method of delivery for Fire•Lite- approved sealed lead-acid batteries for all your fire alarm sys- tem needs. Multiple brands of batteries are now offered under generic part numbers, reducing backorder situations and per~it- ling us to deliver these products in a more timely fashion. Fire•Lite has approved the multiple brands listed below as pos- sible product shipped for a given part number. Please note that any incoming orders for "PS Series" batteries will be converted to the equivalent BAT Series part numbers. -- Features Provide secondary power for control panels. Sealed and maintenance-free. Overcharge protected. Easy handling with leakproof construction. 6933cov.~ Agency Listings and Approvals • Ruggedly constructed, high-impact case (ABS, polystyrene, or polypropylene, depending on models). The listings and approvals below apply to BAT Series Batteries. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Recognized Components: files MH1 9884 (B & B Bat- tery), MH20727 (UPG, previously Jolt), MH20845 (Power- Sonic). • Long service life. • Compact design. Part Number Reference 6933key1.lbl BATTERY ALTERNATES APPROVED: PREVIOUS CURRENT manufacturers and P/Ns Part Number Part Number DESCRIPTION shipped under BAT P/Ns PS-612 Discontinued NIA NIA PS-695 Discontinued NIA. NIA PS-1242 BAT-1250 12 V, 5 AH, sealed. BP5-12 (B&B Battery); PS-1250 (Power-Sonic); SA1250 (Jolt) to be replaced with UB1250 (UPG). PS-1250 BAT-1250 12 V, 5 AH, sealed. BP5-12 (B&B Battery); PS-1250 (Power-Sonic); SA1250 (Jolt) to be replaced with UB1250 (UPG). PS-1270 BAT-1270 12 V, 7 AH, sealed. BP7-12 (B&B Battery); PS-1270 (Power-Sonic); SA1272 (Jolt) to be replaced with UB1270 (UPG). PS-12120 BAT-12120 12 V, 12 AH, sealed. BP12-12 (B&B Battery); PS-12120 (Power-Sonic); SA12120 (Jolt) to be replaced with UB12120 (UPG). PS-12170 BAT-12180 12 V, 18 AH, sealed. PS-12180 (Power-Sonic); SA12180 (Jolt) to be replaced with UB12180 (UPG). PS-12180 BAT-12180 12 V, 18 AH, sealed. PS-12180 (Power-Sonic); SA12180 (Jolt) to be replaced with UB12180 (UPG). PS-12250 BAT-12260 12 V, 26 AH, sealed. BP26-12 (B&B Battery); PS-12260 (Power-Sonic); SA12260 (Jolt) to be replaced with UB12260 (UPG). PS-12550 BAT-12550 12 V, 55 AH, sealed. PS-12550 (Power-Sonic); XSA 12550 (Jolt) to be replaced with UB12550 (UPG). PS-12600 BAT-12550 12 V, 55 AH, sealed. PS-12550 (Power-Sonic); XSA12550 (Jolt) to be replaced with UB12550 (UPG). PS-12750 Discontinued NIA NIA PS-121000 BAT-121000 12 V, 100 AH, gell cell. PS-121000 (Power-Sonic); XSA121000A (Jolt) to be replaced with UB121000 (UPG). DF-52397:A • 12/29/06 Page 1 of 10 POWER-SONIC 1109!1 lbf Nominal Discharge DIMENSIONS Capacity Current Height over Nominal @ @ Width Depth Height terminal Weight Voltage 20 hr. rate 20 hr. rate MODEL V A.H. mA in. mm. in. mm. in. mm. in. mm. lbs. kg. PS-1250 12 5.0 250 3.54 90 2.76 70 4.02 102 4.21 107 4.1 1.9 PS-1270 12 7.0 325 5.94 151 2.56 65 3.70 94 3.86 98 5.7 2.6 PS-12120 12 12 600 5.94 151 3.86 98 3.70 94 3.86 98 8.8 4.0 PS-12180 12 18 875 7.13 181 2.99 76 6.57 167 6.57 167 12.8 5.8 PS-12250 12 25 1300 6.89 175 6.54 166 4.92 125 4.92 125 18.7 8.5 Ps-12550 12 55 3000 10.25 260 6.60 168 8.20 208 9.45 240 39.7 18.0 PS-121000 12 100 5000 12.00 305 6.60 168 8.20 208 9.45 240 65.7 29.8 Characteristic Discharge Curves Effect of Temperature on Capacity 120% ----------------~ 6.5 13 ~ 6.0 12 ., "' ~ 5.5 11 :g ~ 5.0 10 ., "" .. ~ r-----~ -._ ---"\ \ \ ' a, 4.5 9 4.0 8 : : 3C ~2c-- 0 --..:::-- '\ , , n.•r / I 1C --~ .... \"\ \ \ ., .. o~7sf·~.sc o.," 'I! I 100% 20% ••----0.5 C ••--• -0.1 C 2 3 5 10 20 30 60 2 3 5 10 20 30 t---minutes ---t---hoo,, ---j Discharge Time @ 2o·c (68°F) -20° -10' o· 10· 20· 30• 40• so• so• Temperature (Degrees C.) 90% Charging Is NOT necessary unless 100% of capacity :8 is required, & BO% 1----\J-,.+-"'k:-+--~--t--+------1----=""'1"'-...-Hr-------1 5 'E 70% i-----t-~--t--~u--r"-::'t----t---t---t--r---'i 2 Charging before use Is necessary to help recover flJI capacity. &_ 60% ~ r-----t-----f' ... --j-~"i.c----t---~-...----j--+--t-r-------, ·o [ 50% t---+---+---t->~+--t-=--+--+--~·+--+----1 8 4o•c 3o•c 2o·c 40% f---+--+---'-(1+04_ 0_F'-+) --'-(8+-6-"F-'-)-+--➔ __,_(6-+B"_F.c..) -+----l 0% 0 2 4 6 8 10 12 14 16 18 20 Standing Period (Months) 14.0V I I I I I I 1 1 I Ambient Temperature 2o•c (68°F) 13.0V ·········'· :::::·::·• r--.. --... -....... .... Charge may fail to restore ful capacity, DO NOT l let batteries reach this state. J at left: at left: PS-121000 Shelf-Life and Storage ~ 12.0V .l!I g 11.0V ~ .§ 10.0V ··--r---I -"-. \ ' I'\ \ '"'\ \ I I--::' __,!---_.10A 5.0A PS-1210000 Discharge Characteristics {! 9.0V 8.0V v 20A I V ~50A Final v "1f0~ Voltage 200A I 1.2 2.4 6 12 24 36481 4 6 8 10 20 40 MINUTES --X--HOURS Discharge llme Page 2 of 10 -OF-52397:A • 12/29106 B & B BATTERY Terminal Dimensions Nominal Capacity (AH) Weight Model V Standard Optional L w H TH 20 hr 10 hr 5 hr 1 hr kg lbs Type Pos. Type Pos. mm In mm In mm In mm In BPS-12 12 5.00 4.75 4.25 3.00 1.86 4.10 T1 3 T2 90 3.54 70 2.76 102 4.02 106 4.17 BP7-12 12 7.00 6.65 5.95 4.20 2.60 5.73 T2 5 T1 151 5.94 65 2.56 93 3.66 98 3.86 BP12-12 12 12.00 11.40 10.20 7.20 4.03 8.89 B1 5 T1 151 5,94 98 3,86 94 3.70 98 3.86 BP26-12 12 26,00 24.70 22.10 15.60 9.40 20,73 B1 7 T2.I1 9 175 6.89 166 6.54 125 4.92 125 4.92 Charging Procedure 6933bbch.tb4 Temperature Maximum Charging time 0.1 CA, Charging compensation charging 20°c (hi Application Charging method voltage at coefficient of Temp (°C) current 20°c (V/cell) charging voltage (CA) 100% 50% (mVrC/cell) discharge discharge For standby Constant voltage and 2.25 -2.30 -3 power source constant current 0,3 24 20 o -4o•c For cycle charging (with current 2.40 -2.50 -4 0,3 16 10 (32-104°F) seNice restriction) Temperature compensation of charging voltage is not needed w,en using the batteries wfhin s•c to 35•c range. Discharge Time: for Model BPS-12 Final 5 min 10 min 15 min 30 min 1 hr 3 hr 5 hr Voltage Battery Output Power (W}: for Model BPS-12 10.80 V 180.8 133.1 106.6 63.5 36.39 14.57 10.05 10.50 V 209.2 144.2 111.5 65.9 37.48 14.87 10.20 10.20 V 222.3 149.4 115.0 67.4 38.16 15.00 10.26 9.90 V 232.3 152.9 117.6 68.3 38.61 15.10 10.29 9.60V 240.0 156.0 120.0 69.0 39.00 15.20 10.32 Discharge Time: for Model BP7-12 Final 5 min 10 min 15 min 30 min 1 hr 3 hr 5 hr Voltage Battery Output Power (W): for Model BP7-12 10.80 V 253.1 186.3 149.3 88.8 50.95 20.40 14.07 10.50 V 292.9 201.8 156,2 92.2 52.47 20,81 14.28 10.20 V 311.2 209.1 161.0 94.3 53.42 21 .00 14.36 9.90 V 325.2 214.1 164.7 95.6 54.06 21.15 14.41 9.60 V 336.0 218.4 168.0 96.6 54.60 21.27 14.45 Discharge Time: for Model BP12-12 Final 5 min 10 min 15 min 30 min 1 hr 3 hr 5 hr Voltage Battery Output Power (W): for Model BP12-12 10.80 V 433.9 319.4 256.0 152.3 87.34 34.98 24.12 10.50 V 502.2 346.0 267.7 158.1 89.96 35.68 24.48 10.20 V 533.6 358.5 276.0 161.7 91.57 36.00 24.61 9.90 V 557.5 367.1 282.4 164.0 92.67 36.25 24,70 9.60V 576.0 374.4 288.0 165.6 93.60 36.47 24.77 Discharge Time: for Model BP26-12 Final 5 min 10 min 15 min 30 min 1 hr 3 hr 5 hr Voltage Battery Output Power (W): for Model BP26-12 10.80 V 940.0 692.0 554.6 330.0 189.23 75.79 52.25 10.50 V 1088.0 749.7 580.0 342.5 194.91 77.30 53.04 10.20 V 1156.0 776.7 598.0 350.3 198.41 78.00 53.33 9.90V 1208.0 795.3 611.8 355.2 200.79 78.54 53.52 9.60V 1248.0 811.2 624.0 358.8 202.80 79.01 53.68 10 hr 5,62 5.70 5.73 5.75 5.75 10 hr 7.86 7.98 8.02 8.04 8.04 10 hr 13.48 13.68 13.75 13.79 13.79 10 hr 29.20 29.64 29.79 29.88 29.88 20 hr 2.94 3.00 3.01 3.02 3.02 20 hr 4.11 4.20 4.22 4.23 4.23 20 hr 7.05 7.20 7.23 7.25 7.25 20 hr 15.26 15.60 15,67 15.71 15.71 i 11 I 11 I Constant Power Discharge Characteristics at 25•cn1°F for BP5-12 Constant Power Discharge Characteristics at 2s•cn 1°F for BP7-12 Constant Power Discharge Characteristics at 2s•cn1°F for BP12-12 Constant Power Discharge Characteristics at 2s•cn1°F for BP26-12 DF-52397:A • 12129/06 -Page 3 of 10 B & B BATTERY 13.0 12.0 w ('J 11.0 ~ S2 10.0 'if. z ~ 9.0 a: w I-ao 7.0 13.0 12.0 BP5-12 Battery Discharge Characteristics (25°Cf77°F) I I -c-..... --......_____ '"' ~ -' ' \ \ , , , l.'JA / I I ---15A tOA SA I --........ -----.. ........_ '- I\ \ \ \ / 0.8SA-0.475A-0 .2SA V .2SA 1 2 3 5 10 20 30 60 2 3 5 hours 10 20 30 I minutes I DISCHARGE TIME BP12-12 Battery Discharge Characteristics (25°C/77°F) --,___ r---.. I BPOSdls.tt --........ -----.. I".... r---L'-s ---.,_ I\ \ ~ \ \ \ r--r----. w <!) 11.0 ~ g 10.0 :;j_ z :jj 9.0 a: w I-80 7.0 1 \ I\ ... -~O<A-1.1<A--0.6A , , , 7.2A I I I I i24A --12A 2 3 5 10 20 30 60 2 3 5 ,o 20 30 minutes I hours BP12di&.tif I DISCHARGE TIME BP05-12 BP12-12 Page 4 of 10 -DF-52397:A • 12/29/06 13.0 12.0 w ('J 11.0 ~ g 10.0 'if. z :jj 9.0 a: w I-8.0 7.0 13.0 12.0 w St 11.0 ~ g 10.0 ...J < z j 9.0 a: ~ ao 7.0 BP7-12 Battery Discharge Characteristics (25°C/77°F) -----r--......_____ "' "' -' ' \ \ ........_ r----. -----.. " " \ \ \ \ / 1.fs,,-0.665>.-o.:is, 1.75'1 , ---21A t•A I 7A 2 3 5 10 minutes 20 30 , , ◄2A I I I 60 I DISCHARGE TIME BP26-12 Battery Discharge Characteristics (25°C/77°F) -,___ r--r--1----. ~r--'"' ~ \ \ 2 3 5 10 20 30 8P07d■.tif I hours --.;::: r---.. -------'- I\ \ \ \ t/•.•2A-2hii-1.JA ,,, .SA , , 15.6A / I I 78A-52A -26A I 2 3 5 10 minutes 20 30 60 2 3 5 I hours DISCHARGE TIME BP26-12 10 20 30 BP26dlS.llt I UPG BATTERY UB1250 has the same specifications as previous Jolt SA 1250; SA 1272 to be replaced with UB1270 (specs/diagrams pending). UB1250 (previously SA1250) Diagrams UB1250/SA1250 discharge current vs. time I r I '" I ltC(32'F) "'\ ' 40'C{1CWF) - '-"' ' "' '" .... 0 llllO 1 2 3 5 10 ):) 30 $3 100 200 6933up01 tif ~-"'11)-+M-----fl>J-----.i Currlt!t UB1250/SA 1250 discharge characteristics (25"Cl77°F) 1l ----'--t-... ' r-.. r-----... ,, \,'\ \ '\ "'r-- ~ \ \ --.... '6.i\02~ L _ 1. j :t 1"tT lS!I 1$1\ lo.\ 0 1 2 3 5 10 20 )."I «> 2 3 5 10 )) 30 i---~---~·-h---~ 6933up02.tif UB 1250, SA 1250 Specifications • Nominal voltage: 12 V. • Nominal capacity (20 hr): 5.0 AH. • Dimensions: total height 107 mm (4.21"); container height 101 mm (3.98"); length 90 mm (3.54"); width 70 mm (2.76"). • Weight: approximately 1.83 kg (4.03 lbs). • Container material: UL94HB ABS, UL94V-0 ABS. • Internal resistance (25°C, 77°F): -32 m. • Discharge capacity under different temperatures: 4o•c: -102% 25°c: -100% o•c: -as% • Capacity 25°C/77°F: 20 hr@ 0.25 A: 5.0 AH. 5 hr@ 0.8 A: 4.0 AH. 1 hr@ 3.0 A: 3.0 AH. 1 C@ 5.0 A: 2.5 AH. • Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. • Maximum discharge current: 60 A (5 sec). • Maximum charging current: 1.5 A • Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. SA 1272 Diagrams SA1272 discharge current vs. time I I ,'I. 1'' I I I O'c{l2l') ~ .WC{10-4"F) '" '' '' ' 0 ·MO 1 2 3 S 10 20 )."I SO 100 lC>l i,.-,,,AI --------911----.! 6933up03 lif C'U'lffl SA 1272 discharge characteristics (25°Cl77°F} 11 -. ·-~ ~ :::::: .... -i-.. ' i-... -........ I\ ""-; '"" ' '\ -i-.. '~, \ \ I., 1 ~;.. i.3 I\ L -I~ l ,;: t"'" l ~ 1,,,,. ~ 21 I.U. I I 0 Z 3 5 10 ))I))~ 23 5 10 20~ ---rn'----1-h---~ 6933up04.tif D11¢haf91' Tiffl,e SA 1272 Specifications Nominal voltage: 12 V. Nominal capacity (20 hr): 7.2 AH. Dimensions: total height 100 mm (3.94"); container height 94 mm (3.70"); length 151 mm (5.95"); width 65 mm (2.56"). Weight: approximately 2.66 kg (5.85 lbs). Container material: UL94HB ABS, UL94V-0 ABS. Internal resistance (25°C, 77°F): -22 m. Discharge capacity under different temperatures: 4o•c : -102% 25•c: -100% o•c: -as% • Capacity 25°C/77°F: 20 hr@ 0.36 A: 7.2 AH. 5 hr@ 1.15 A: 5.76 AH. 1 hr @ 4.32 A: 4.32 AH. 1 C@7.2A: 3.6AH. Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. Maximum discharge current: 90 A (5 sec). Maximum charging current: 2.16 A. • Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. DF-52397:A • 12/29/06 -Page 5 of 10 UPG BATTERY Same specifications as previous Jolt models; packaging and part numbers are the only changes. UB12120 (was SA12120) Diagrams UB12120/SA 12120 discharge current vs. time I l I I I I i... '-I I I O'C{32'F) " , .O'C{10C"F) " "" ;'I. ~ r : (•) 2 i , ,n L: 0 500 1 2 3 S 10 20JO SO 100 ))0 l+-<""l------(N----~ 6933up05.tif c...,..n1 UB12120/SA 12120 discharge characteristics (25°Cfl7°F} - --..r~ ' "\. r-----.. ' " '\ \ \ -i---. " I\ ' \ \ \ -"" -... 'f~o.e,. ~ ~~ / _.,_ "" -· l2AI II I 0 6933up06,ti1 I 2 3 5 ,0 ~ 3J ao l l 5 10 20)) ---n)l, 1..---,----.1 ~.n..,. UB12120, SA12120 Specifications Nominal voltage: 12 V. Nominal capacity (20 hr): 12.0 AH. Dimensions: total height 100 mm (3.94"); container height 94 mm (3.70"); length 151 mm (5.95"); width 98 mm (3.86"). Weight: approximately 4.10 kg (9.04 lbs). Container material: UL94HB ABS, UL94V-0 ABS. Internal resistance (25°C, 77°F): -14 m. Discharge capacity under different temperatures: 4o•c: -102% 25•c : -100% o•c: -85% • Capacity 25°Cn7°F: 20 hr@ 0.6 A: 12.0 AH. 5 hr@ 1.92 A: 9.6 AH. 1 hr@ 7.2 A: 7.2 AH. 1 C@ 12.0 A: 6.0 AH. • Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. Maximum discharge current: 120 A (5 sec). Maximum charging current: 3.6 A. Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. Page 6 of 10 -DF-52397:A • 12/29106 UB12180 (was SA12180) Diagrams UB12180/SA12180 discharge current vs. time r : (ll} 2 1..., t : ,I I .. (lrt,I) 10 L: I I I I I ~ I I~ I I I O'C(321') ~ ,IO'C(104'F) .~ "-: ·"-'" ~ " ' 0 $lO 1 2 3 5 10 20:,:, $l ,oo 200 f-.-<,.,AJ------/J\1----,>1 6933up07.lif cu.,.nt UB12180/SA 12180 discharge characteristics (25°Cn7°F) :::::=------ ~,-, :---r...... ' '\ ' '\ 'I \ ---- "" \ \ \ --,., 1ev.o~ L -~ te,. , \.!AA •.;JI\ ' IOI\ ~ !A I I I I I 2 l 5 10 '.)))) ol<l 2 3 5 10 2>30 ---.,, _______ ---- 6933up08.lif UB12180, SA 12180 Specifications Nominal voltage: 12 V. Nominal capacity (20 hr): 18.0 AH. • Dimensions: total height 167 mm (6.58"); container height 167 mm (6.58"); length 181 mm (7.13"); width 76 mm (2.29"). Weight: approximately 6.06 kg (13.36 lbs). • Container material: UL94HB ABS, UL94V-0 ABS. Internal resistance (25°C, 77°F): -13 m. Discharge capacity under different temperatures: 4o•c: -102% 25•c: -100% o•c : -85% Capacity 25°C/77°F: 20 hr@ 0.9 A: 18.0 AH. 5 hr@ 2.88 A: 14.4 AH. 1 hr@ 10.8 A: 10.8 AH. 1 C@ 18.0 A: 9.0 AH. • Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. Maximum discharge current: 300 A (5 sec). Maximum charging current: 5.4 A. • Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. UPG BATTERY Same specifications as previous Jolt models; packaging and part numbers are the only changes. UB12260 (was SA12260) Diagrams UB12260/SA12260 discharge current vs. time T ! t"' ~ J :n,ll,l 10 l : I I I I I I \\ I I :\. I I I I O"C(32'Fj '\. \ .olO'C{10<l'F) ' .:\. "\I\. I\\ 0 5.)0 I 2 3 5 IO 20 )O SO 100 .a:>G j.-twAi------(~----- 6933up09,lJI' UB12260/SA 12260 discharge characteristics (25"Cfl7"F) 13 ~ 12 • J II f 10 t--t-H--t--H+-t-t--,-1nr.m'"7'7'.m---,--,---1 j it--t--t----t-----t--t-t--t---t--t---t---t--t-t--~ 1 2 3 5 10 313> eo 2 3 5 10 »30 --------·!-;---... 6933up10 tif Diaehar!1" r .... UB12260, SA12260 Specifications Nominal voltage: 12 V. Nominal capacity (20 hr): 26.0 AH. Dimensions: total height 125 mm (4.92"); container height 125 mm (4.92"); length 166 mm (6.54"); width 175 mm (6.89"). Weight: approximately 8.80 kg (19.40 lbs). Container material: UL94HB ABS, UL94V-0 ABS. • Internal resistance (25°C, 77°F): -10 m. Discharge capacity under different temperatures: 40°C: ~ 102% 25•c : -100% o•c: -85% • Capacity 25"Cf77°F: 20 hr@ 1.3 A: 26.0 AH. 5 hr@4.16 A: 20.8 AH. 1 hr@15.6A: 15.6AH. 1 C@ 26.0 A: 13.0 AH. Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. Maximum discharge current: 300 A (5 sec). • Maximum charging current: 7.8 A. Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. UB12550 (was SA12550) Diagrams UB12550/SA12550 discharge current vs. time I ' I I I '~ I I I 0'C(32'F) ~ •O'q104'f) ,~ I\."\. ' '\'\. ' 6933up11 tJ1 0 $lO 1 2 3 S 10 30 30 &) !Oil a>O !+-f11A>------w----- cum111t UB12550/SA12550 discharge characteristics (25°Cfl7°F) tl -----..,-.._ ,~ .... -'"'r----[\ ~'\ \ 'I 1 \ \ -~ 1~ 'U&> - L ..1 ,. "" I .,.,.4lll\ !$SI\ 11llll w j I I I 6933up12.tif 1 2 3 $ 10 20)) tlO 2 3 $ IO :))3,') ---:r.i,----1-~----ol Dise!laiv-Time UB12550, SA12550 Specifications Nominal voltage: 12 V. Nominal capacity (20 hr): 55.0 AH. Dimensions: total height 234.5 mm (9.23"); container height 216.5 mm (8.52"); length 229 mm (9.02"); width 138 mm (5.43"). Weight: approximately 19.0 kg (41 .8 lbs). Container material: UL94HB ABS, UL94V-0 ABS. • Internal resistance (25°C, 77°F): -8 m. • Discharge capacity under different temperatures: 40°c: -102% 25•c : -100% 0°c: -85% Capacity 25°Cf77°F: 20 hr@ 2.75 A: 55.0 AH. 5 hr @ 8.8 A: 44.0 AH. 1 hr@ 33.0 A: 33.0 AH. 1 C@ 55.0 A: 27.5 AH. Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. Maximum discharge current: 600 A (5 sec). Maximum charging current: 16.5 A. • Self-discharge residual capacity (25°C, 77°F): After 3 months: -90%. After 6 months: -82%. After 12 months: -70%. DF-52397:A • 12129/06 -Page 7 of 10 UPG BATTERY Same specifications as previous Jolt models; packaging and part numbers are the only changes. UB121000 (XSA121000A) Diagrams UB121000/XSA121000A discharge current vs. time I I ' I " -40'C{104 'F) ., O'C{l2'F) ~ ~ " ;,\. ,, O 500 t 2 '.I 5 10 :))30 &> IOO 2ro 300 6933up13.bf fc-<l'IIAl------w------ cu!l'•n1 U8121000/XSA121000A discharge characteristics (25°C/77°F) 13 ~ . -.._;;;:: I""-. ..... I\ '\ r\ ' ~ I\ L _ b.,-1 r""/1. ~j'"' 1"' "i 0 t l l S 10 JD ,:> «I 2 3 ,5 10 ll 30 6933up1◄.tit UB121000 (XSA121000A) Diagrams Nominal voltage: 12 V. Nominal capacity (20 hr): 100.0 AH. • Dimensions: total height 221 mm (8.70"); container height 214 mm (8.43"); length 329 mm (12.95"); width 172 mm (6.77"). Weight: approximately 34.00 kg (74.8 lbs). • Container material: UL94HB ABS, UL94V-0 ABS. • Internal resistance (25°C, 77°F): -6.5 m. • Discharge capacity under different temperatures: 4o•c: -102% 25•c: -100% o•c : -85% • Capacity 25°C/77°F: 20 hr@ 5.0 A: 100.0 AH. 5 hr@ 16.0 A: 80.0 AH. 1 hr@ 60.0 A: 60.0 AH. 1 C@ 100.0 A: 50.0 AH. • Charging voltage (25°C, 77°F): Standby use: 13.65 V ± 0.15 V. Cycle use: 14.7 V ± 0.3 V. • Maximum discharge current: 600 A (5 sec). • Maximum charging current: 30 A. Self-discharge residual capacity (25°C, 77°F): After 3 months: ~ 90%. After 6 months: -82%. After 12 months: -70%. Page 8 of 10 -DF-52397:A • 12/29/06 UPG Summary Diagrams Summary discharge characteristics UJ ,:,.o ... (.0 ~ 12.0 I.O g 11.0 u l--+-+""-l-~~,--+.,:~__:lr--+4~r-4.-----:l-i-! :;;! ,.. •• l---+-+----1---'°'....4--+--1--11--====c=-1---'--1 ,; ~ W,G; 4,1 I---+-+--+--~ u •• l---+-+----l---+--l-+--l-----+-+---1--1--+-l 2, 5 ,o 20,0 eo '----minutes 6933up1S.wmf O/SCHARGE TII.IE Summary discharge current vs. time curve (25"C/77"F) 1 20 ~ ~'\ ~ "" ~ I!? 10 ~ ~ I\~ I\ l ~ ~ • ~ i\['\ f\ i'\ ~~ ~ ~ \~ t\ I\. .. I'. \. \. \. .. 30 r-._ '\ \ ,\ '\. '\. \. 20 ' .... .... ~.,.--:= ,. ' '\ \. I'. '\ l~'ffl i 10 ~ \['\ I\."\ '\~ ·, t. ~'& <t\,~·~.1"~ L l~i~~i~i 30 50 100 200 "" 1 2 ' ' 10 15 20 30 ,. 100 200 33u 1 :wmf mA Amperes 69 p O/SCHARGE CURRENT UPG BATTERY Same specifications as previous Jolt models; packaging and part numbers are the only changes. Charging Procedure: UPG Battery Charging Application Charging method voltage at 2s•c (Vlcell) For stardby Constant voltage ard 2.25-2.30 power source constant current For cycle charging (with current 2.40 -2.50 service resbiction) Temperature compensation coefficient of charging voltage (mV/"Clcell) -3.3 (-1.8 mVfF/cell) -5 (-2.8 mVfF/cell) 6933ubch.tbl Maximum Charging time 0.1 CA, charging 2s·c (h) current Temp (°C) (CA) 100% 50% discharge discharge 0.3 T .e: 24 T .e: 20 0-40°C 0.3 16 < T < 24 10 < T < 24 (32 -104°F) Temperature compensation of charging voltage is not needed vJ1en using the batteries wthin S'C to 35'C range. OF-52397:A • 12/29/06 -Page 9 of 10 ISO 9001 19 ¥1; ii I =I I ¥i ·I ll'ICINUIINI l MMIIACTIRINC QUlllTY SYSTEMS Flre•Llte® Alarms is a registered trademark of Honeywell International Inc. Batteries display trademarks of the manufacturer. IC2006 by Honeywell lntemational Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•LiteAlarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 10 of 10 -DF-52397:A • 12/29/06 @) F1re·L1Te' Alarms www.firelite.com GENERAL The LCD-SOF is a compact, cost-effective, BO-character, backlit LCD remote Fire Annunciator for use with the Fire•Lite MS-9200UD and MS-9600 Fire Alarm Control Pan- els (FACPs). The LCD-80F displays complete system point status information and includes control switches for remote control of critical system functions. Up to 32 LCD-80Fs may be connected onto the EIA-485 terminal port (TB?) of each FACP. The LCD-80F requires no programming, which saves time during system commis- sioning. FEATURES • BO-character Liquid Crystal Display. • Mimics all display information from the host panel. • Control switches for System Acknowledge, Signal Silence, Drill and Reset with enable key. • System status LEDs for Power, Alarm, Trouble, Supervisory and Alarm Silenced. • No programming necessary -LCD-80F con- nects to the terminal port (TB?) on the FACP. • Displays device type identifiers, individual point alarm, trouble or supervisory, zone and custom alpha labels. • Time-and-date display field. • Aesthetically pleasing design. May be powered by 24 VDC from the host FACP or by remote power supplies (requires 24 VDC). • Up to 32 LCD-80F annunciators per FACP. • Plug-in terminal blocks for ease of installation and ser- vice. • Can be remotely located up to 6,000 feet (1828.8 m) from the FACP. • Local piezo sounder with alarm and trouble resound. • Semi-flush mounts to 2.188" (5.556 cm) minimum deep, three-gang electrical box (Fire•Lite P/N 10103) or three- gangable electrical switchbox. • Surface-mounts to Fire•Lite SBB-3 surface backbox. OPERATION The LCD-80F annunciator provides the FACP with point annunciation with full display text on an BO-character LCD display. The LCD-80F also provides an array of LEDs to indicate system status, and includes control switches for remote control of critical system functions. Flre•Lite® Alarms Is a Honeywell company. January 26, 2005 DF-52185 • 8-150 LCD-SOF 80-Charader Liquid Crystal Display Remote Fire Annunciator Section: Annunciators @(@ LISTED CS635 S2424 MEA 72-01-E Mtt&thi¼¥iJMQ-!#Milt&4!i444 ' LCD-BOF I California State Fire Marshal 7120-0075:190 <@> APPROVED ¥1Wfil&£ !£$ [2 The LCD-80F provides the FACP with up to 32 remote se- rially connected annunciators. All field-wiring terminations on the LCD-80F use removable, compression-type termi- nal blocks for ease of wiring and circuit testing. Communication between the FACP and the annunciators is accomplished over an EIA-485 serial interface, which greatly reduces wire and installation cost over traditional systems. Six wires total are required: four for the EIA-485 communications (two in and two return); and two for the 24 VDC regulated power. Dip switches control local functions such as: piezo disable, control switches/key-switch disable, transmiUreceive mode. INSTALLATION The LCD-80F can be semi-flush mounted to a 2.188" (5.556 cm) minimum deep, three-gang electrical box (Fire•Lite P/N 10103) or three-gangable electrical switchboxes. Alter- nately, an SBB-3 surface backbox is available for surface- mount applications. This document is not Intended to be used for installation purposes. We try to keep our product Information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENGINEEIINli I MANUfACTUIINli QUALITY SYSTEMS For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. Made in the U.S.A. DF-52185 • 01/26/05 -Page 1 of 2 PRODUCT LINE INFORMATION LCD-80F 80-character, backlit, LCD Fire Annunciator with 10103 control switches for remote control of system functions, and key-switch lock. Three-gang electrical box, minimum 2.188" (5.556 cm) deep, for semi-flush mount applica- tions. S88-3 Three-gang surface backbox for surface-mount applications. LCD-80F TERMINAL MODE WIRING EXAMPLE Up to 6,000 ft. (1828.8 m) between EACH DEVICE in the EIA-485 loop Terminal Mode /, LCD-80F LCD-80F EIA-485 (2-wires) 24 VDC (2-wires) LCD-80F Up to 6,000 ft. (1828.8 m) / back from last device to end of EIA-485 loop Addressable Fire Alarm Control Panel Notes: 1) EIA-485: Maximum of6,000 feet (1828.8 m) cable length from FACP to LCD-80F annunciators, 6,000 ft. cable length between each LCD-80F and 6,000 ft. from the last LCD-80F back to the FACP. Circuit is power-limited. 2) Up to 32 LCD-80F annunciators may be used on the EIA-485 circuit. When multiple LCD-80Fs are used, the FACP will re- quire additional power supplies (refer to panel documenta- tion). MOUNTING TO BACKBOX(ES) The LCD-80F annunciators can be semi-flush mounted in a three-gang electrical box with a minimum depth of 2.188" (5.556 cm) (Fire•Lite P/N 10103). The LCD-80F annunciators can be mounted in three- gangable electrical switchboxes connected together. NOTE: Alternately, LCD-B0F annunciators can be mounted to the SBB-3 surface backbox for surface-mount applica- tions. Electrical Installer's Note: This annunciator may not fit easily into a standard 3-gang electrical box if locking clamps are used to secure wiring entering the rear or side knock- outs. Only use the TOP or BOTTOM knockouts to bring wiring into a standard 3-gang electrical box. 5.813" (14.764 cm) wide x 4.0" (10.16 cm) high x minimum 2.188" (5.556 cm) deep, three-gang electrical box (Fire•Lite PIN 10103, shown at right). Page 2 of 2 -DF-52185 • 01126/05 Terminal Mode EIA-485 return (2-wires) 3) Between each LCD-80F annunciator are four wires: a twisted- shielded pair for data communications and a pair for 24 VDC power. The return circuit only requires two wires (twisted) for data communication supervision, wired from the last LCD- 80F annunciator on the loop. Mounting Holes (4) 52185mnl.wmf LCD-B0F flange 0 FIRE ALARM ANNUNCIATOR FIRE-LITE ALARMS, INC . l2'~'-'i-'.S'0:.""-·,A SYSTEMS ALL NORMAL 11 :06A 032001 • ......... · ... •· •··· .. ' · .. 0 LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: XLF: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING • BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7120-0075: 190 Annunciators Fire-Lite Alarms, One Fire-Lite Place, Northford CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Model LCD-80F remote fire annunciator. Unit is a compact 80-character, backlit LCD fire annunciator. Refer to listee's data sheet for additional detailed product description and operational considerations. In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. Listee's name, product number, electrical rating and UL label. Listed as an annunciator for use separately listed compatible fire alarm control units. 7120-0028:209 *Rev. 05-06-05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 e Flr8·LIT0" Alarms www.firefite.com GENERAL The Fire•Lite Alarms BG-12LX is a state-of-the-art, dual- action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire•Lite's addressable MS-9200, MS- 9200UD, and MS-9600 fire alarm control panels. Because the BG-12LX is addressable, the control panel can dis- play the exact location of the activated manual pull station. This leads fire service personnel quickly to the location of the alarm. FEATURES Aesthetically pleasing, highly visible, dual-action design. • Meets ADA 5 lb. maximum pull force. Easily operated (dual-action). Attractive shape and textured finish. • Mounts, semi-flush, to a standard single-gang (2.125" [5.3975 cm] minimum depth), double-gang, or 4" (10.16 cm) square electrical box. • When the handle latches in down position, the word "AC- TIVATED" appears at the top of the handle in bright yel- low to clearly indicate the station has been operated. • Key/lock reset; needs only a 1/4-turn to lock/unlock. • Includes Braille text on station handle. • Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). Optional trim ring (BG-TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. • Maintenance personnel can open station (for inspection and testing) without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes red in normal operation and latches on steady red when in alarm. CONSTRUCTION Shell, door, and handle are molded of durable LEXAN® (or polycarbonate equivalent) with a textured finish. OPERATION Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word "ACTIVATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; closing the door automatically resets the switch. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Flre•Lite® Alarms Is a Honeywell company. July 14, 2004 DF-52013 • E-500 BG-12LX Addressable Manual Pull Station Section: Addressable Devices Patented, U.S. Patent No. D428,351; 6,380,846 U.S. Patent Pending: 09/686,286 c@us LISTED <8> California State Fire Marshal 7150-0075:184 MEA 67-02-E APPROVED BG-12LX Manual stations connect with two wires to one of the con- trol panel SLC loops. Each manual station, on command from the control panel, sends data to the panel represent- ing the state of the pull station switch. Two rotary decimal switches allow address settings (01-99). PRODUCT LINE INFORMATION BG-12LX SB-1/0 SB-10 BG-lR Dual-action addressable pull station. Includes key lock/reset feature. Surface backbox, indoor/outdoor. Surface backbox. Optional trim ring. This document Is not intended to be used for Installation purposes. We try to keep our product Information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENCll'IIRINC I MMUFAl:TURINC QUUITY SYSTEMS For more information, contact Fire•Llte Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. DF-52013 • 07/14/04 -Page 1 of 2 INSTALLATION The BG-12LX can be semi-flush mounted into a single- gang, double-gang, or standard 4" (10.16 cm) square elec- trical outlet box, or surface mounted to the Model SB-I/0 or SB-10 surface backbox. If the BG-12LX is semi-flush mounted, then the optional trim ring (BG-TR) may be used. The BG-TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). ELECTRICAL SPECIFICATIONS Normal operating voltage: 24 voe. Maximum SLC loop voltage: 28.0 VDC. Maximum SLC loop current: 230 µA. If [ I 0 -Back of station without door. I Ml H8UCI I MWOO JJUCI ~ ~ i ◄ TERMINAL CONNECTIONS 1 SLC (-) 2 SLC (+) ICB Cover open to show easy access to the addressable interface module, rotary switch, and UL label. Page 2 of 2 -DF-52013 • 07 /14/04 ARCHITECTURAL/ ENGINEERING SPECIFICATIONS Manual Fire Alarm Stations shall be non-code, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated station shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored LEXAN® (or polycarbonate equivalent) with clearly visible operating instructions pro- vided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-I/0 or SB-1 O; or semi-flush mount- ing on a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the control panel SLC loops. The manual station shall, on com- mand from the control panel, send data to the panel repre- senting the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. 0 AD!lRESS LOOP gp).: e a 7 e ROTARY DECIMAL SWITCHES LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: XLF: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE ST ATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7150-0075:184 Page 1 of 1 Boxes/Pull Stations Fire-Lite Alarm Inc., One Fire-Lite Place, Northford CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Models BG-12, BG-12S, BG-12NC, BG-12W, BG-12LW, BG-12WP, BG-12LWP, BG-12L, BG-12LX, BG-12LA, BG-12PS, BG-12LSP, BG-12SP, BG-12LR, BG-12LRA, BG-12LAO, BG-12LAOB, BG-12-LO, BG-12LOB, BG-12LPS, BG-12LPSP, BG-12SL, *UT-PS1 and UT- PS2 fire alarm pull boxes. The BG-12 series is a dual action pull station that has normally open switch contacts. Refer to listee's data sheet for detailed product description and operational considerations. In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having juri sdiction. Listee's name, model number and UL label. Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Models BG-12WP, BG-12W, BG-12LW and BG-12LWP are intended for outdoor use when installed with Model WP-10 back box. Models BG-LAOB and BG-12LOB are intended for outdoor use when installed with Model WBB or WP-1 0 back box. 7150-0028: 199 •Rev. 05-06-05 JEW -~ This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 (2) FlrS·LITe" Alarms www.flrellte.com GENERAL The Fire•Lite Alarms SD355 and SD355T addressable, low-profile plug-in photoelectric detectors use a state-of- the-art photoelectric sensing chamber with communica- tions to provide open area protection and are used exclu- sively with Fire•Lite's MS-9200, MS-9200UD, and MS-9600 Addressable Fire Alarm Control Panels (FACPs). The SD355T adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving pre- cious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (PIN RA400Z). FEATURES SLC/oop: • Two-wire loop connection. • Unit uses base for wiring, detector head plugs-in. Addressing: • Addressable by device. • Direct Decade 01 -99 (MS-9200, MS-9200UD) and 01 -159 (MS-9600) entry of address. Architecture: Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires. • Sleek, low-profile design. • Integral communications and built-in type identification. • Built-in tamper-resistant feature. • Removable cover and insect-resistant screen for simple field cleaning. Operation: • Withstands air velocities up to 1,500 feet-per-minute (7.6 mlsec.) without triggering a false alarm. • Factory preset at 1.5% nominal sensitivity for panel alarm threshold level. Visible LED 'blinks" when the unit is addressed (com- municating with the fire panel) and latches on in alarm. Mechanicals: • Sealed against back pressure. • Direct surface mounting or electrical box mounting. • Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring -included). Fire•Lite® Alarms is a Honeywell company. July 14, 2004 DF-52384 • E-160 SD355(A)/ SD355T(A) Addressable Photoelectric Smoke Detectors Section: Addressable Devices @(@ LISTED S1059 MEA SD355Twith B350LP base Other system features: California State Fire Marshal 7272-0075:194 <8> APPROVED • Fully coated circuit boards and superior RF/transient pro- tection. • 94-V0 plastic flammability rating. • Low standby current. Options: • Remote LED output connection (PIN RA400Z). APPLICATIONS Use photoelectric detectors in life-safety applications to pro- vide a broad range of fire-sensing capability, especially where smoldering fires are anticipated. Ionization detec- tors are often better than photoelectric detectors at sens- ing fast, flaming fires. This document Is not intended to be used for Installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENGlrlEIINli I MANUFACTIIIINli QUALITY SYSTEMS For more Information, contact Flre•Lite Alarms. One Fire-Lite Place, Northford. Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. DF-52384 • 07/14/04 -Page 1 of 2 CONSTRUCTION These detectors are constructed of off-white LEXAN®. SD355(T) plug-in, low-profile smoke detectors are designed to commercial standards and offer an attractive appear- ance. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. INSTALLATION SD350(T) plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base on box which is at least 1.5 inches (3.81 cm) deep. Suitable boxes include: • 4.0" (10.16 cm) square box with plaster ring. • 4.0" (10.16 cm) octagonal box. • 3.5" (8.89 cm) octagonal box. • Single-gang box. NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring •r-taps• or branches are permitted for Style 4 (Class B) wiring only. OPERATION Each SD355(T) uses one of 99 possible addresses on the MS-9200 and MS-9200UD Signaling Line Circuit (SLC), or up to 318 (159 on each loop) on the MS-9600 SLC. It re- sponds to regular polls from the system and reports its type and status. The SD355(T) addressable photoelectric sensor's unique unipolar chamber responds quickly and uniformly to a broad range of smoke conditions and can withstand wind gusts up to 1,500 feet-per-minute (7.6 m/sec.) without sending an alarm level signal. Because of its unipolar chamber, the SD355(T) is approximately two times more responsive than most photoelectric sensors. This makes it a more stable detector. DETECTOR SENSITIVITY TEST Each detector can have their sensitivity tested (required per NFPA 72, Chapter 7 on Inspection, Testing and Main- tenance) when installed/connected to an MS-9200, MS- 9200UD, or MS-9600 addressable fire alarm control panel. The results of the sensitivity test can be printed off the MS- 9200, MS-9200UD, or MS-9600 for record keeping. SPECIFICATIONS Voltage range: 15 -32 VDC (peak). Standby current: 300 µA@ 24 VDC. LED current: 6.5 mA@ 24 VDC (latched 'ON'). Air velocity: 1,500 ft./min. (7.6 m/sec.) maximum. Diameter: 6.1" (15.5 cm) installed in B350LP base. Height: 2.1" (5.33 cm) installed in B350LP base. Weight: 3.6 oz. (102 g). Operating temperature range: for SD355: o•c to 49°C (32°F to 120°F) SD350; for SD355T: o•c to 38°C (32°F to 100°F). Temperature: o•c -49•c (32°F -120°F). Relative humidity: 10% -93%, non-condensing. Page 2 of 2 -DF-52384 • 07/14/04 PRODUCT LINE INFORMATION NOTE: 'A" suffix indicates ULC-Usted model. SD355 Addressable photoelectric detector (B350LP base included). SD355A Same as SD355 with ULC Listing (B350LPA base included). SD355T Same as SD355 but with thermal element (B350LP base included). SD355TA Same as SD355T with ULC Listing (B350LPA base included). RA400Z(A) Remote LED. Mounts to a single-gang box. B350LP(A) Plug-in detector base (included). Dimen- sions: 6.1" (15.5 cm). Mounting:4.0" (10.16 cm) square box with or without plastic ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm) octagonal box, or single-gang box. All mount- ing boxes have a minimum depth of 1.5" (3.81 cm). B224RB(A) Plug-in System Sensor relay detector base. Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square box with or without plastic ring, 4.0" (10.16 cm) octagonal box, or 3.5" (8.89 cm) octagonal box. All mounting boxes have a minimum depth of 1.5" (3.81 cm). B224Bl(A) Intelligent isolator base, isolator SLC from shorts on the loop. B501BH(A) Plug-in System Sensor sounder detector base. Diameter: 6.0" (15.24 cm). Mounting: 4.0" (10.16 cm) square box with or without plastic ring. Mounting box has a minimum depth of 1.5" (3.81 cm). B501 BHT(A) Same as B501 BBH(A), but includes tempo- ral sounder. Accessories: RA400Z(A) Remote LED annunciator. 3 -32 voe. Fits U.S. single-gang electrical box. For use with B501(A) and B350LP(A) bases only. SMK400 RMK400 Surface mounting kit provides for entry of surface wiring conduit. For use with B501(A) base only. Recessed mounting kit. For use with 8501(A) base only. M02-04-01 Test magnet. XR-2 Detector removal tool. Allows installation and/ or removal of detector heads from bases in high ceiling applications. XP-4 Extension pole for XR-2. Comes in three 5-ft. (1.524 m) sections. LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: NOTE: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7272-0075:194 Photoelectric Smoke Detector Fire-Lite Alarms Inc., One Fire-Lite Place, Northford, CT 06472 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Models SD350, SD350T, SO355, SD355T and AD355 photoelectric type smoke detectors. Model SO350T and SO355T has a 135°F supplement integral heat sensor which only assists in a fire situation. The purpose of this thermal circuitry is to increase the sensitivity of the detector. This thermal circuitry is NOT approved for use as a heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. 24VDC In accordance with listee's printed installation instructions, applicable codes & ordinances and a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating and UL label. Listed as photoelectric smoke detector for use with separately listed compatible fire alarm control units. All units are suitable for installation inside air duct with a maximum air velocity of 4000 fpm. The photoelectric type detectors are generally more effective at detecting slow, smoldering fires which smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. *Rev. 05-06-05 BH This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 (2) F1re·uTe· Alarms www.firelite.com GENERAL The Fire•Lite Alarm H355 Series thermal detectors are ad- dressable sensors that use a state-of-the-art thermistor sensing circuit for fast response. These sensors are de- signed to provide open-area protection and are intended for use with Fire•Lite's MS-9600 and MS-9200UD Fire Alarm Control Panels (FACPs). Both the H355 and H355R sensors provide fixed tempera- ture alarm detection at 135°F. The H355R sensor responds to rate-of-rise conditions of greater than 15°F/8.3°C per minute. H355HT provides fixed high-temperature detection at 190°F/88°C. These thermal detectors provide cost ef- fective, addressable property protection in a variety of ap- plications. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA400Z). FEATURES SLC loop: • Two-wire SLC loop connection. • Unit uses base for wiring. Addressing: • Addressable by device. • Direct Decade 01 -159 (MS-9600), or 01 -99 (MS- 9200UD) entry of address. Architecture: • Sleek, low-profile, stylish design. • State-of-the-art thermistor technology for fast response. • Integral communications and built-in device-type identi- fication. • Built-in tamper resistant feature. • Built-in functional test switch activated by external mag- net. Operation: • Factory preset at 135°F (57°C). Rate-of-rise model (H355R), 15°F (8.3°C) per minute. 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink green in Normal condi- tion and turn on steady red in Alarm. • Visible LEDs "blink" every time the unit is addressed. Mechanicals: • Sealed against back pressure. • SEMS screws for wiring of the separate base. • Designed for direct-surface or electrical-box mounting. Fire•Llte® Alarms is a Honeywell company. July 14, 2004 DF-52385 • E-710 H355 (A) Series Intelligent Addressable Thermal (Heat) Detectors for MS-9600, MS-9200UD Section: Addressable Devices @(@ I California State Fire Marshal 7270-0075: 195 LISTED S2517 <§> APPROVED :I',,/ 6936pho1.Jpg ¥ H355 in B350LP base • Plugs into separate base for ease of installation and maintenance. • Separate base allows interchange of photoelectric, ion- ization and thermal sensors. Other system features: • Remote test feature from the panel. • Walk test with address display. • Low standby current. 94-5V plastic flammability rating. Options: Remote LED output connection to optional RA400Z re- mote LED annunciator. • Recessed (RMK400) or surface (SMK400) base mount- ing kits. APPLICATIONS Use thermal detectors for protection of property. CONSTRUCTION These detectors are constructed of off-white Bayblend®. The H355 Series plug-in intelligent thermal detectors are designed to commercial standards and offer an attractive appearance. Bayblend® is a registered trademark of Bayer Corporation. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENH~fRINI I MANUFACTURINC QUUITY SYSTEMS For more information, contact Flre•Llte Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-34 73, Toll-Free FAX: (877) 699-4105. DF-52385 • 07/14/04 -Page 1 of 2 INSTALLATION H355 Series plug-in intelligent thermal detectors use a de- tachable base to simplify installation, service and mainte- nance. Installation instructions are shipped with each de- tector. Mount base (all base types) on box that is at least 1.5" (3.81 cm) deep. Suitable boxes include: • 4.0" (10.16 cm) square box. • 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box. • Single-gang box (except relay or isolator base). NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 {Class "B") wiring only. OPERATION Each H355 Series detector uses one of 159 (MS-9600) or 99 (MS-9200UD) possible addresses on a control panel SLC loop. It responds to regular polls from the control panel and reports its type and the status. If it receives a test com- mand from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The H355 Series offers features and performance that represent the latest in thermal detector technology. SPECIFICATIONS Diameter: 6.1" (15.5 cm) installed in B350LP. Height: 2.1" (5.33 cm). Weight: 4.8 oz. (137 g). Installation temperature: -4°F to 100°F (-20°C to 38°C). Humidity range: 10% to 93% relative humidity (non-con- densing). Voltage range: 15 to 32 VDC peak. Standby current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled). LED current: 6.5 mA @ 24 VDC. Mounting: B350LP flanged base, included. Fixed-temperature setpoint: 135°F (57°C). Rate-of-rise detection: responds to greater than 15°F/ 8.3°C per minute. Page 2 of 2 -DF-52385 • 07/14/04 PRODUCT LINE INFORMATION NOTE: "A" suffix indicates ULC-Listed model. H355 H355A H355R H355RA H355HT H355HTA Intelligent thermal sensor (B350LP base in- cluded). Same as H355 but with ULC Listing (B350LPA base included). Same as H355 with rate-of-rise feature (B350LP base included). Same as H355R but with ULC Listing (B350LPA base included). Intelligent high-temperature thermal detector (B350LP base included). Same as H355HT but with ULC Listing (B350LPA base included). RA400Z(A) Remote LED. Mounts to a single-gang box. B350LP(A) Plug-in detector base (included). Dimen- sions: 6.1" (15.5 cm). Mounting: 4.0" (10.16 cm) square box with or without plastic ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm) octagonal box, or single-gang box. All mount- ing boxes have a minimum depth of 1.5" (3.81 cm). M02-04-00 Test magnet. B224RB(A) Plug-in System Sensor relay detector base. Diameter: 6.2" (15.75 cm). Mounting: 4.0" (10.16 cm) square box with or without plastic ring, 4.0" (10.16 cm) octagonal box, or 3.5" (8.89 cm) octagonal box. All mounting boxes have a minimum depth of 1.5" (3.81 cm). B224Bl(A): Intelligent isolator base. Isolates SLC from loop shorts. 8501 BH(A) Plug-in System Sensor sounder detector base. Diameter: 6.0" (15.24 cm). Mounting: 4.0" (10.16 cm) square box with or without plastic ring. Mounting box has a minimum depth of 1.5" (3.81 cm). B501BHT(A) Same as B501 BH(A), but includes temporal sounder. Accessories: RA400Z(A) Remote LED annunciator. 3 -32 VDC. Fits U.S. single-gang electrical box. For use with B501 (A) and B350LP(A) bases only. SMK400 RMK400 Surface mounting kit provides for entry of surface wiring conduit. For use with B501(A) base only. Recessed mounting kit. For use with B501 (A) base only. M02-04-01 Test magnet. XR-2 Detector removal tool. Allows installation and/ or removal of detector heads from bases in high ceiling applications. XP-4 Extension pole for XR-2. Comes in three 5-ft. (1.524 m) sections. LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7270-0075: 195 Heat Detector Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Models H350, H355, and H355HT fixed temperature heat detectors. Models H350R and H355R rate-of-rise with fixed temperature heat detectors. Refer to listee's data sheet for detailed product description and operational considerations. H350, H355, and H355HT H350R and H355R H355HT 135° F fixed temperature 15° F rate-of-rise 190° F fixed temperature In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating and UL label. Listed as heat detectors for use with separately listed compatible fire alarm control units. Rev. 05-06-0SJEW This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 D350PL(A), D350RPL(A) Intelligent Low-Flow Photoelectric Duct Smoke Detectors General Fire•Lite D350PL(A) and D350RPL(A) Intelligent Photoelectric Smoke Duct Detectors provide low-flow technology that enables duct smoke detection throughout a broad range of air- flow environments in HVAC applications. The low-flow technol- ogy can detect smoke at air speed velocities of 100 feet per minute (0.5 m/sec) or greater, while continuing the same reliable performance to 4,000 feet per minute (20.32 m/sec). The intelli- gent low-flow duct detectors sample air currents passing through a duct and gives dependable performance for shutdown of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke an fire gases through the protected area. D350PL(A) and D350RPL(A) are compatible with all Fire•Lite addressable panels. D350PL(A) and D350RPL(A) provide a remote alarm output for use with auxiliary devices, such as the RA400Z(A) remote LED annunciator, as well as remote test capability with the RTS451 (A) or RTS451 KEY(A) Remote Test Stations. Applications Duct smoke detectors have specific limitations, they are: • NOT a substitute for open area smoke detectors. NOT a substitute for early warning detection. NOT a replacement for a building's regular fire detection sys- tem. Please call Fire•Lite for a copy of System Sensor's application guide, Proper Use of Smoke Detectors in Duct Applications, (A05-1004-00). Features Air velocity rating from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). Patented telescopic sampling tube. • Easily accessible code wheels for addressing detector. Outside mounting tabs. • Mounts to round or rectangular ducts from 1' to 12' (0.3 to 3.7 meters) wide. Transparent cover for convenient visual inspection. Installation Refer to installation manuals for control panel and duct detector for detailed information or to install equipment. Installation man- uals for detectors: I56-1975-003R for D350PL(A), I56-1974- 004R for D350RPL(A). Wiring: For signal wiring (the wiring between detectors or from detectors to auxiliary devices), it is recommended that single conductor wire be no smaller than 18 AWG (0.821 mm2). The duct smoke detector terminals accommodate wire sizes up to 12 AWG (3.31 mm2). Flexible conduit is recommended for the last foot (30.48 cm) of conduit; solid conduit connections may be used if desired. DF-52398:A • E-605 @F1re·LIT8eALarms by Honeywell Addressable Devices D350PL 3242key.jpg 0 RA400Z RTS451 RTS451KEY Smoke detectors and alarm system control panels have specifi- cations for Signaling Line Circuit (SLC) wiring. Consult the con- trol panel specifications for wiring requirements before wiring the detector loop. The D350PL(A) and D350RPL(A) detectors are designed for ease of wiring; their housing provides a termi- nal strip with clamping plates. LED Features: If programmed with the system control panel, two LEDs on each duct smoke detector light to provide local vis- ible indication. Programming specifications/requirements for intelligent system control panels: The number of devices that can have their LEDs programmed to illuminate is limited by the features of the panel and the individual devices. The actual number of devices is determined by the control panel and its ability to sup- ply LED current. Refer to the control panel installation manual for details. DF-52398:A • 12/29106 -Page 1 of 4 Wiring Diagrams for D350PL(A) COMMUNICATION LINE :E :r: :E :E 00 00 £:I :E :E ------~ 0 0 00 On to other Detectors UL Listed Control Panel 1 st Detector in Loop on the Loop. 2nd Detector in Loop 6821wlr1.wmf ........._D350PL(A) Duct Smoke Detector using a UL or ULC Listed control panel. Detector Terminals z 0 :E :E 0 0 I ~------(,' J-----<-~ RA400Z 6821'Mr2 wml 6821'Nlr3.wmf Detector Terminals COMMON TEST s ® Field-Installed JUMPER ~ 1---t--l 1 ® LED RESET RTS451/RTS451 KEY Inlet Tube Selection Outside Duct Width Inlet Tube* Up to 2 feet (0.6096 m) ST-1.5(A) 2 to 4 feet (0.6096 to 1.2192 m) ST-3(A) 4 to 8 feet (1.2192 to 2.4384 m) ST-5(A) 8 to 12 feet (2.4384 to 3.6576 m) ST-10(A) •Inlet tube is required and must be purchased separately. Order One inlet tube for each duct smoke detector ordered. Page 2 of 4 -DF-52398:A • 12/29106 ◄ D350PL(A) Duct Smoke Detector with an optional RA400Z(A). ◄ D350PL(A) Duct Smoke Detector with RTS451 (A)/RTS451 KEY(A). NOTE: For RTS451(A), Terminal 3 is not used. RTS451(A) does not have a Terminal 6. For RTS451KEY(A), Terminals 3 and 6 are not used. Wiring Diagrams for D3SORPL(A) D350RPL(A) Duct Smoke Detector using a UL-Listed control panel: COMMUNICATION LINE l ~ I.______~ UL-LISTED CONTROL PANEL J1 JUMPER 1ST DETECTOR IN LOOP J1 JUMPER 0 □ 2ND DETECTOR IN LOOP 0 NOTE: 1) Jumper J1 shunt must be installed for 2-W applications. J1 shunt must be removed for power PCB supervision. Note that removal of shunt without adding external power will prevent communications to the panel over the SLC. 2) External power of 24 V AC/DC or 1201220 VAC must be connected in order to power all remote hom or strobe accessories. D350RPL(A) Duct Smoke Detector with an optional RA400Z(A): 5 = Alarm Signal 7 =Aux.Power(-) D350RPL(A) Duct Smoke Detector with an optional PA400: RA400Z DO NOT BREAK TAB ONRA400Z PA400 '-----1---+---J i 5 = Alarm Signal 7 =Aux.Power(-) D350RPL(A) Duct Smoke Detector with RTS451 (A)/RTS451 KEY(A): ALARM SIGNAL AUX.POWER(-) TEST+ TEST- ATS 451/ RTS451KEY TEST SWITCH FOR RTS451, TERMINAL 3 IS NOT USED. (RTS451 DOES NOT HAVE A TERMINAL 6.) FOR RTS451KEY, TERMINALS 3 AND 6 ARE NOT USED. DF-52398:A • 12129/06 -Page 3 of 4 Product Line Information NOTE: "A" model suffix is for Canadian models. D350PL: Addressable low-flow duct detector housing with pho- toelectric smoke detector. D350PLA: Same as above with ULC listing. O350RPL: Addressable low-flow duct detector housing with photoelectric smoke detector with DPDT relay. D350RPLA: Same as above with ULC listing. A5053FL: Replacement photoelectric sensor board. A5067: Replacement power board (without relay). A5060: Replacement power board (with relay). ST-1.S(A): Metal sampling tube, duct widths 1' to 2' (see Inlet Tube Selection table on page 2 for metric lengths). ST-3(A): Metal sampling tube, duct widths 2' to 4'. ST-5(A): Metal sampling tube, duct widths 4' to 8'. ST-10(A): Metal sampling tube, duct widths 8' to 12'. RA400Z(A): Remote annunciator alarm LED. RTS451 (A): Remote test station. Mounts in single-gang box. Includes red alarm LED and magnet test switch. RTS451 KEY(A): Key-activated remote test station. F36-09-11: Replacement filters. M02-04-00: Test magnet. M02-09-00: Test magnet with telescoping handle. S0S-39-01: Replacement photo insect screen. P48-61-00: Replacement end cap for plastic sampling tube. P48-21-00: Replacement end cap for metal sampling tube. TB0-71-00: Replacement plastic sampling tube. Specifications FOR D350PL(A) Operating voltage range: 15 to 30 voe. Standby current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled). Operating temperature range: 32° to 131 °F (0° to 55°C). Operating humidity range: 10% to 93% relative humidity (non- condensing). Storage temperature range: -22°F to +158°F (-30°C to + 70°C). Duct air velocity: 100 to 4,000 feeUmin (0.5 to 20.32 mis). Shipping weight: 3.35 lbs. (1.5 kg). Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x 2.75" (7 cm) deep. D350PL(A) accessory current loads @ 24 voe: RA400Z(A): 0 mA standby, 10 mA maximum in alarm. RTS451(A) and RTS451KEY(A): 0 mA standby, 7.5 mA maximum in alarm. FOR D350RPL(A) Operating voltage range: 20 to 30 VDC, 24 VACNDC, 120/ 240 VAC auxiliary power (requires a separate auxiliary source). Standby current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled). Operating temperature range: 32° to 131 °F (0° to 55°C). Operating humidity range: 10% to 93% relative humidity (non- condensing). Storage temperature range: -22°F to +158°F (-30°C to + 70°C). Duct air velocity: 100 to 4,000 feeUmin (0.5 to 20.32 mis). Shipping weight: 3.90 lbs. (1.8 kg). Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x 2.75" (7 cm) deep. D350RPL(A) CONTACT RATINGS Alarm auxiliary contacts (DPDT): 10 A@ 30 VDC; 10 A@ 277 VAC (0.75 power factor); 240 VA @ 249 VAC (0.4 power factor); 1/8 HP@ 120 VAC; 1/4 HP@ 240 VAC. Minimum switching current for auxiliary contact must be 100 mA DC minimum@ 5 voe. Supervisory contact (SPST): 2.0 A@ 30 VDC (resistive). O350RPL(A) accessory current loads @ 24 voe: PA400: refer to PA400 data sheet DF-50727. RA400Z(A): O mA standby, 12 mA maximum in alarm. RTS451(A) and RTS451 KEY(A): 0 mA standby, 10 mA maximum in alarm. D350RPL(A) CURRENT REQUIREMENTS (USING NO ACCESSORIES) 20 -30 voe power supply voltage: 26 mA maximum standby current; 87 mA maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. 24 VAe, 50/60 Hz power supply voltage: 65 mA RMS maxi- mum standby current; 182 mA RMS maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. 120 VAe, 50/60 Hz power supply voltage: 44 mA RMS maxi- mum standby current; 52 mA RMS maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. 220/240 VAe, 50/60 Hz power supply voltage: 25 mA RMS maximum standby current; 30 mA RMS maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. Agency Listings and Approvals The listings and approvals below apply to D350PL(A) and D350RPL(A) Intelligent Low-Flow Photoelectric Smoke Duct Detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: file S1059 (D350PL, D350RPL). • ULC Listed: file CS6963 (D350PLA, D350RPLA). eSFM approved: file 3240-0075:196. • FM approved. MEA approved: file 320-02-E2 (D350RPL). Maryland State Fire Marshal approved: Permit #2144. Fire•Lita® Alanns and System Sensor® are registered trademarks of Hon- eywell International Inc. e:!006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. 19 =I; ii I =i I =I •I IIICIIIEIINC I MMlllCURINC QUALITY SYSTEMS We try to keep our product information up-tMate and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•LiteAlarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 4 of 4 -DF-52398:A • 12/29/06 LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 3240-0075:196 Duct Smoke Detector Housing/Base Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Model D350P, D350PL, D350RP, and D350RPL automatic smoke detector for duct application. The unit consists of a plastic enclosure, relay, electrical components, listed open area detector, and a sampling and exhausted tube. Refer to listee's data sheet for additional detailed product description and operational considerations. In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation, electrical rating, and UL label. Listed as duct smoke detector for use with listee's separately listed compatible fire alarm control units. Suitable for use in ducts where air velocity is between 100 and 4000 fpm. *Rev. 05-06-0SKK This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 (2) Flre·UTe· Alarms www.flrellte.com GENERAL Four different monitor modules are available for Fire•Lite Alarm's MS-9200, MS-9200UD and MS-9600 intelligent fire alarm control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302). MMF-300 (Replaces M300) -The MMF-300 Moni- tor Module is a standard-sized module (typically mounts to a 4" [101.6 mm] square box) that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input de- vices. MMF-301 (Replaces M301 )-The MMF-301 is a Min- iature Monitor Module (a mere 1.3" (33.02 mm) H x 2.75" (69.85 mm) W x 0.5" (12.70 mm) D) used to supervise a Class B (Style B) circuit. Its compact design allows the MMF-301 to be mounted in a single-gang box behind the device it is monitoring. MMF-302 (Replaces M302) -The MMF-302 Inter- face Module is a standard-sized module used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Class A (Style D) or Class B (Style B) circuit. MDF-300 (New) -The MDF-300 Dual Monitor Module is a standard-sized module (typically mounts to a 4" [101 .6 mm] square box) that supervises two Class B (Style B) cir- cuits of dry-contact input devices. MMF-300 MONITOR MODULE • Built-in type identification automatically identifies this de- vice as a monitor module to the control panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct Decade 01 -99 (MS-9200 and MS-9200UD) and 01-159 (MS-9600) entry of address. • LED flashes red during normal operation and latches on steady to indicate alarm. The MMF-300 Monitor Module is intended for use in intel- ligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire Class A or Class B fault-tolerant Initiating Device Circuit (IDC) for normally- open-contact fire alarm and supervisory devices. The MMF- 300 can be used to replace M300 modules in existing sys- tems. MMF-300 Applications -Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterffow devices, or other normally-open dry-contact alarm activation devices. May also be used to monitor normally- open supervisory devices with special supervisory indica- tion at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class D) Initiating Fire•Lite® Alarms is a Honeywell company. July 14, 2004 DF-52121 • E-325 MMF-300(A) Serles/MDF-300 Addressable Monitor Modules @ LISTED Section: Addressable Devices I California State Fire Marshal 7300-0075,185 <y (Q!9 APPROVED csxxxx MDF-300 Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. Maximum IDC resistance is 1,500 ohms. MMF-300 Operation -Each MMF-300 uses one of 99 (MS-9200 and MS-9200UD) or 159 (MS-9600) avail- able module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300 Specifications Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Average operating current: 400 µA (LED flashing). EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49"C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101 .6 mm) wide x 1.25" (31 .75 mm) deep. Mounts to a 4" (101 .6 mm) square x 2.125" (53.975 mm) deep box. This document Is not Intended to be used for Installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENGINHIINli I MANIFAClllllNG QUALITY SYSTEMS For more Information, contact Flre•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. DF-52121 • 07/14/04 -Page 1 of 3 MMF-301 MINI MONITOR MODULE • Built-in type identification automatically identifies this device as a monitor module to the MS-9200, MS- 9200UD or MS-9600. Powered directly by two-wire SLC Loop. No additional power required. • High noise (EMF/RFI) immunity. Tinned, stripped leads for ease of wiring. Direct-dial entry of address (01-99 for MS -9200/MS- 9200UD, 01-159 for MS-9600). The MMF-301 Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301 is intended for use in intelli- gent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-con- tact fire alarm and security devices. The MMF-301 can be used to replace M301 module in existing systems. F MMF-301 Applications -Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally- open supervisory devices with special supervisory indica- tion at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the circuit. MMF-301 Operation -Each MMF-301 uses one of 159 available module addresses on an SLC loop MS- 9600. It uses one of 99 on a MS-9200 or MS-9200UD. It responds to regular polls from the control panel and re- ports its type and the status ( open/normaVshort) of its Ini- tiating Device Circuit (JDC). MMF-301 Specifications Nominal operating voltage: 15 to 32 voe. Average operating current: 375 µA maximum. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (33.02 mm) high x 2. 75" (69.85 mm) wide x 0.5" (12.70 mm) deep. Wire length: 6" (152.4 mm) minimum. Page 2 of 3 -CF-52121 • 07/14/04 MMF-302 INTERFACE MODULE • Supports compatible two-wire smoke detectors. • Supervises IDC wiring and connection of external power source (resettable). • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address (01 -99 for MS-9200/MS- 9200UD, 01-1 59 for MS-9600). • LED flashes during normal operation. • LED latches steady to indicate alarm on command from control panel. The MMF-302 Interface Module is intended for use in intel- ligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and moni- tor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conven- tional detectors back to the control panel. All two-wire de- tectors being monitored must be UL compatible with the module. MMF-302 Applications -Use the MMF-302 to moni- tor a zone of two-wire smoke detectors. The monitored cir- cuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum JDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302 Operation -Each MMF-302 uses one of 159 available module addresses on a MS-9600 SLC loop. It uses one of 99 on a MS-9200 or MS-9200UD. It responds to regular polls from the control panel and reports its type and the status ( open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-302 Specifications Nominal operating voltage: 15 to 32 voe. Maximum current draw: 5.1 mA (LED on). Average operating current: 270 µA (LED flashing). EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 18 to 28 volts power limited. Ripple voltage: 0.1 VRMS maximum. Current: 90 mA per module maximum. Requires regulated, resettable 24 VDC power. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. MDF-300 DUAL MONITOR MODULE • Built-in type identification automatically identifies this de- vice as two monitor modules to the control panel. • Powered directly by the two-wire SLC loop. No addi- tional power required. High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address (01 -159 on the MS-9600, 01-99 for MS-9200/MS-9200UD). • LED flashes red during normal operation and latches on steady red to indicate alarm. The MDF-300 Dual Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides two independant two-wire fault-toler- ant Initiating Device Circuits (IDCs) at two separate, con- secutive addresses. It is capable of monitoring normally open-contact fire alarm and supervisory devices, or either normally open or normally closed devices for non-fire ap- plications. MDF-300 Applications -Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull sta- tions, waterflow devices, or other normally-open dry-con- tact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervi- sory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class 8) Initiating Device Circuit. The 47K ohm End-of-Line Resistors (provided) terminate the Style B circuit. Maximum IDC resistance is 1,500 ohms. MDF-300 Operation -Each MDF-300 uses two of 99 (MS-9200 or MS-9200UD) or 159 (MS-9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in com- munication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MDF-300 Specifications Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Average operating current: 750 µA (LED flashing). EOL resistance: 47K ohms. Maximum IDC wire resistance: 1,500 Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SM8500 electrical box. INSTALLATION MMF-300, MMF-302 and MDF-300 modules mount di- rectly to a standard 4" (101.6 mm) square, 2.125" (53.975 mm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordi- nances, and regulations. These modules are intended for power-limited wiring only. The MMF-301 module is intended to be wired and mounted without rigid connections inside a standard elec- trical box. All wiring must conform to applicable local codes, ordinances and regulations. ARCHITECTS' /ENGINEERS' SPECIFICATIONS Specifications of these and all Fire• Lite Alarms products are available from Fire•Lite Alarms. PRODUCT LINE INFORMATION MMF-300 Monitor Module. MMF-300(A) Monitor Module (Canada). MMF-301 Mini Monitor Module. MMF-301(A) Mini Monitor Module (Canada). MMF-302 Two-Wire Detector Monitor Module. MMF-302(A) Two-Wire Detector Monitor Module (Canada). MDF-300 Dual Monitor Module. SMB500 Optional Surface-Mount Backbox. MOUNTING DIAGRAM for standard-sized modules DF-52121 • 07/14/04 -Page 3 of 3 LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE ST ATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7300-0075:185 Misc. Devices/Control Unit Accessories Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. 15-32 voe In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation, electrical rating, and UL label. Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. *Rev. 05-06-05 JEW This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 (2) F1re·L1Te" Alarms www. fire lite. com GENERAL CMF-300 Control Module (Replaces C304) The CMF-300 Addressable Control Module provides Fire•Lite Alarm's MS-9200, MS-9200UD, and MS-9600 in- telligent control panels a supervised Class B (Style Y) or Class A (Style Z) circuit for Notification Appliances (horns, strobes, etc.). Addressability allows the CMF to be acti- vated, either manually or through panel programming, on a select (zone or area of coverage) basis. CRF-300 Relay Module (Replaces C304 configured as a relay) The CRF-300 Addressable Relay Module provides the MS-9200, MS-9200UD, and MS-9600 systems with two isolated sets of Form-C dry-contact outputs for activating a variety of auxiliary devices, such as fans, dampers, door holders, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis. FEATURES Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. The CMF module requires power (for horns, strobes, etc.). • Integral LED "blinks" green each time a communication is received from the control panel and turns on in steady red when activated. High noise immunity (EMF/RFI). • The CMF may be used to switch 24-volt NAC power. Wide viewing angle of LED. SEMS screws with clamping plates for wiring ease. • Direct Decade 01-99 (MS-9200/MS-9200UD) and 01- 159 (MS-9600) entry of address. APPLICATIONS The CMF is used to switch 24 VDC audible/visual power. The CRF may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc. CONSTRUCTION • The face plate is made of off-white Noryl®. • Controls include two rotary switches for direct-dial entry of address (01-99 on the MS-9200, MS-9200UD, and 01 - 159 on the MS-9600). The CMF is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The CRF provides two Form-C dry contacts that switch together. Noryl® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Flre•Llte® Alarms Is a Honeywell company. July 14, 2004 DF-52130 E-350 CMF (A) and CRF (A) Series Addressable Control and Relay Modules Section: Addressable Devices @ LISTED California <§> State Fire FM Marshal 7300-0075:185 APPROVED S2424 CMF-300 and CRF-300 Module OPERATION Each CMF or CRF uses one of 99 (MS-9200/MS-9200UD) or 159 (MS-9600) possible module addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status. including the open/normal/ short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it acti- vates its internal relay. The CMF supervises Class B (Style Y) or Class A (Style Z) notification or control circuits. Upon code command from the panel, the CMF will discon- nect the supervision and connect the external power sup- ply in the proper polarity across the load device. The dis- connection of the supervision provides a positive indica- tion to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the communication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a mod- ule and a sensor address. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ISO 9001 CERTIFIED ENGINf.fRINS I MMUFACTIIRING QUAllTY SYSTEMS For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toil-Free FAX: (877) 699-4105. DF-52130 • 07/14/04 -Page 1 of 2 SPECIFICATIONS FOR CMF RELAY CONTACT RATINGS Normal operating voltage: 15 to 32 voe. for both CMF and CRF models Maximum current draw: 5.1 mA (LED on). Average operating current: 390 µA (LED flashing). External supply voltage {between Terminals T3 and T4): maximum 80 volts (RMS or DC). Drain on external supply: 2 mA maximum (using internal EOL relay). EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. SPECIFICATIONS FOR CRF Normal operating voltage: 15 to 32 voe. Maximum current draw: 5.1 mA (LED on). Average operating current: 270 µA {LED flashing). EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. PRODUCT LINE INFORMATION CMF-300 Intelligent Addressable Control Module. CMF-300(A) Same as above with ULC listing. CRF-300 Intelligent Addressable Relay Module. CRF-300(A) Same as above with ULC listing. SMBS00 Optional Surface-Mount Backbox. CBS00 Control Module Barrier -required by UL for separating power-limited and non-power lim- ited wiring in the same junction box as CMF-300. DODD D □□□[lll[Ill□ 0 OOIDrnD OOOIDrnD 0 OOIDrnD 0 OOIDrnD mmoornD (O..O = s o O> IBIOOOrnD (0..0 = 2 0 0) IBIOOOrnD (0 0 = 0.35) MOUNTING DIAGRAMS Note CB500 Module Barrier, which creates isolated quadrant. ISOLATED QUADRANT □ □ D [ID□□IJ □ □ 00[1) □□ DDIIDDD 0 00-0 0000 30 00 0 0 0000 30 00 0 0 00-0 0000 110 00 0 0 00-0 0000 125 00 0 0 0000 30 00 0 0 0000 30 00 0 0 00-0 0000 125 00 0 □□mm□ D D□Il □ 3.0 0 2.0 0 0.9 0 0.9 0 0.5 0 1.0 0 0.5 0 6724rate.lbl 4" (101 .6 mm) square x 2.125" (53.975 mm) deep box Page 2 of 2 -DF-52130 • 07/14/04 LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING· BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7300-0075: 185 Misc. Devices/Control Unit Accessories Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653 Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309 Page 1 of 1 Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. 15-32 voe In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation, electrical rating, and UL label. Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. *Rev. 05-06-05 JEW This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 9, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 March 30, 2000 G-250 (2) F1re·L1Te" Alarms GENERAL System Sensor SpectrAlert Serles strobes, horns, and combina- tion horn/strobes are UL listed for primary signaling in life safety systems and meet ADA public mode visible signaling requirements. SpectrAlert products can be connected to the alarm indicating cir- cuit of a fire alarm control panel and are compatible with DC line supervision. The SpectrAlert product line mounts to standard backboxes using a universal mounting plate included with each unit. An optional small footprint mounting plate fits to a single-gang box. An accessory backbox skirt gives a cosmetic finish to a 4" x 4" x 1-1/2' or a 2' x 4' x 1-7/8' surface-mounted backbox. All strobe and horn/strobe mounting options require only one screw attach- ment of product to plate. These products are designed for 12 and 24 VDC and full-wave rec- tified unfiltered power. Full-wave rectified operation requires more current than DC operation. For detailed current draw information, consult the Current Draw Tables (page 2). The horn/strobe com- bination products are factory-assembled with jumper wires for in- tandem operation. For independent wiring of horn and strobe, re- move jumper wires. When wired for independent operation, the strobe will continue to run while the horn can be silenced. How- ever, the strobe must be running for horn to operate. Horns -The SpectrAlert Series horns and horn/strobes pro- vide two different field-selectable/reversible tones, a high-low field- selectable/reversible sound output setting (low setting on 24-volt models only) and a field-selectable/reversible temp 3 pattern or non-temporal continuous pattern. These field-selectable features are accomplished using pins and jumpers located on the back of each SpectrAlert horn and horn/strobe. An accessory module is not needed to make these field selections. The horn on horn/strobe models will operate on a coded power supply. Those horn-only models with "HC" In their part numbers wllf also operate on a coded power supply. The horn and horn/strobe series includes weatherproof models. Strobes -The ADA-compliant SpectrAlert strobes are elec- tronic visible warning signals that flash at 1 Hz over their operating voltage range. These products are available in 24-volt models at 15, 15/75, 75 and 11 O candela intensities and in 12-volt models at 15 and 15/75 candela intensities. The strobe series includes weath- erproof models. SpectrAlert products feature dramatic reductions in current requirements. Sync•Circuit Module (MDL) -The Sync•Circuit Mod- ule is available for synchronization of strobes and horns and can synchronize two Style Y (class B) circuits or one Style Z (class A) circuit. The module can also generate a synchronized temp 3 tone for System Sensor's Multi-Alert™ and PA400 horn products: The synchronization module allows the SpectrAlert horns on combina- tion horn/strobes to be silenced on two-wire systems. SpectrAlert's Sync•Circuit Module can be daisy-chained for multiple zone syn- chronization. The module does not operate on a coded power sup- ply. "For Multi-Alert and PA400: Strobes must be wired to a continuous source of power {non-coded power supply). SpectrAlert TM Series Horns, Strobes, and Horn/Strobes Section: AudioNisual Devices @ ◄ S4011 & S5512 (P1215, P121575, P2415, P241575, P2475, P24110). S5512 (S1215, S121575, S2415, S241575, S2475, S24110). LISTED S4011 (HC12/24). @ ◄ CS549 (P2415A, P241575A, P2475A, P24110A, S2415A, S241575A, S2475A, S24110A). CS548 (H12/24A, HC12/24A). 088A4.AY (P1215, P121575, ► ~ P2415,P241575,P2475,P24110, ~ S1215,S121575,S2415,S241575, S2475, S24110, H12/24). 0D4A7.AY (HC12/24). California State Fire Marshal ◄ 7135-1209:173 (P1215, P121575, P2415, P241575, P2475, P24110). 7125-1209:174 (S1215, S121575, S2415, S241575, S2475, S24110). 7135-1209:143 (H12/24, HC12/24). M EA◄ 319-96-E (P1215, P121575, P2415,P241575,P2475, P24110,S1215,S121575, S2415, S241575, S2475, S24110, H12/24, HC12/24). SpectrAlert™, Sync•Clrcult™, and Multi-Alert™ are trade- marks of System Sensor, a division of Pittway Corporation. This document Is not Intended to be used for Installation purposes. We try to keep our product Information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more Information, contact Flr.,.Llte Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627- 3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299 ISO 9001 CERTIFIED ENCll'IEIINC I MANIFACTIIINC WEB: www.firelite.com DF-51609 -Page 1 of 6 FEATURES • 24-volt strobe models: 15, 15/75, 75 and 11 o candela. • 12-volt strobe models: 15 and 15/75 candela. • Horn models operate on 12 and 24 volts. • Low current draw: reductions as high as 45%. • Two field-selectable/reversible horn tones: -3000 Hz interrupted -electromechanical • Field-selectable/reversible high-low dBA output on horn (low output on 24-volt models only): -101 peak dBA@ 10 ft. high output.• -96 peak dBA @ 10 ft. low output.• • Field-selectable/reversible temp 3 pattern or non-temp 3 con- tinuous pattern on horn. • Horn/strobe can be wired either in tandem or independently. • Weatherproof strobes, horns, and horn/strobes available. • Horns for use with coded power supply available. • Universal mounting plate included with each unit. • One-screw mounting of strobe and horn/strobe to mounting plate. • SpectrAlert strobe and horn/strobe take up no room in the backbox. CURRENT DRAW TABLES Strobe Only • Single-gang mounting without the use of a mounting plate (horn model only). • Self-contained screw covers. • Aesthetically pleasing design. • Synchronize horn and strobe with Sync•Circuit™ module (MDL). • Silence horn on horn/strobe over a single pair of wires using a Sync•Circuit module (MDL). •sound output varies with tone and output options selected; sound levels based upon anechoic room measurements. SPECIFICATIONS Input terminals: 12 to 18 AWG (3.25 mm2 to 0.51 mm2). Dimensions: see diagrams page 3. Weight, horn only: 7.2 oz. (204 g). Weight, strobe and horn/strobe: 8.8 oz. (250 g). Mounting: see diagrams page 4. Operating temperature: 32°F to 120°F (0°C to 49°C). Operating voltage range:•• 12 V: 10.5-17 V. 24 V: 20-30 V. •• These products should be operated within their rated voltage range. UL does, however, test functional integrity to -20% and +10% of manufacturer's stated ranges. AVERAGE CURRENT (mA) PEAK CURRENT (mA) IN RUSH CURRENT (mA) ovu ....... l'l..Moli.. 2~ 2<1'£.MOdola .2Y-MOda• fY...l!.Odeil 10.SV 12V 17V 2r,v UV 3111( 10.SV 12V 17V 2CIV 24V -10.SV 12V 17V 20V 24V SOY c ... -DC FWR DC ..... DC -DC FWR DC FWA DC FWA DC FWR DC .... DC FWA DC FWA DC fWA DC FWA DC fWft DC FWA DC FWR DC-DC -DC'- 15 133 158 114 157 11 12J 58 120 53 IIO .. 79 '80 -450 -'20 -150 270 150 270 140 -110 101 12 124 140 1110 170 230 220 2IIO 270 371 15175 11!111!1 112 142 171 . , .. 78 112 88 83 58 132 -520 480 520 --170 270 170 270 1IIO 27( 78 10. N 128 IIIO Ill!! 170 230 210 270 270 ,_ 75 NA NA NA NA NA NA 14& 170 123 158 102 141 NA NA NA NA NA NA 315() -340 -330 -NA NA NA NA NA NA 1110 240 230 2IIO 290 -110 NA NA NA NA NA NA 1111 220 140 191 115 11• NA NA NA NA NA NA -seo 450 570 '20 NA NA NA NA NA NA 1110 230 220 290 290 37 Horn Only AVERAGE CURRENT (mA) 12y__ModM ~llodell High/low Temp 10.SV 12V 17V 20V 24V 3111( T-VOiume /Non DC FWR DC FWA DC FWA DC FWA DC""" DC FWA Electro-High Torno 10 11 10 10 14 " 11 21 25 18 28 .. moch. Non 10 11 10 18 14 2! 17 29 23 .. 30 .., Low Torno NA NA NA NA NA NA 11 12 13 13 17 15 Non NA NA NA NA NA NA 12 18 ,. 18 17 .. 3000Hz High Torno 11 13 11 11 18 1 24 28 28 23 :IT 3: Interrupt. Non 11 17 11 21 ,. 2 18 .. 27 "" 35 ., Low Torno NA NA NA NA NA NA ,. ,. 17 1S 21 11 .... N• N• N• N• "" 13 1 1 21 22 ., Horn/Strobe -15 cd Horn/Strobe -75 cd AVERAGE CUIUIENT (mA) 1~~ ~Qllek ~ Temp 10..SV 12V 17V 2r,v 24V 31/1( rr-VokJme /Nan DC -DC FWR DC l'WA DC FWA DC FWR DC '- AVERAGE CURRENT (mA) ,v .. ~ 24.v..M .... High/Law Tamp 10.SV 12V 17V 261 24V 30V T-v..-.me /Non DC FW• DC FWA DC'-DC FWA DC FWA DC- Electro-HIit! T...-143 170 124 187 95 142 71 1n1 78 • 7S 141 moch. Non 143 170 124 187 95 142 88 • 78 100 78 1SI! Electro-HIit! Torno NA NA NA NA NA NA 114 111 141 187 131 187 mech. Non NA NA NA NA NA NA 1113 ,. 141 ,. 132 1• Low T...-NA NA NA NA NA NA 10 112 88 83 13 "" Low Torno NA NA NA NA NA NA 158 112 138 112 111 15' Non NA NA NA NA NA NA 71 112 87 83 83 IS: Non NA NA NA NA NA NA 157 1112 1"1 112 111 157 3000Hz HIit! T...-144 172 125 188 t7 1 .. a, 101 11 1m 83 1 ... lnlenupt Non 144 173 125 188 .. 1 .. 71 102 110 101 11 142 Low li NA NA NA NA NA NA 73 .. 70 95 87 1"' 3000Hz HIit! Tomn NA NA NA NA NA NA 1811 1N 151 172 138 m lntenupt Non NA NA NA NA NA NA , .. 1112 150 175 137 177 Low Torno NA NA NA NA NA NA 151 114 140 114 123 111 -NA NA NA NA NA NA 72 112 .. .. OI 132 -NA NA NA NA NA NA 151 1• 1"' 1"' 124 18' Horn/Strobe -15/75 cd Horn/Strobe -110 cd AVERAGE CUIUIENT (mA) AVERAGE CURRENT (mA) 1~l ,'"'-.!!Qllll HW>/1.0W Temp 10.SV 12V 17V 2r,v 24V -rr-VokJme /Nan DC -DC ""' DC l'WA DC l'WA DC ,_ DC - ~ ~ High/Lo. Temp 10.SV 12V 17V 20V 24V 30V T-VokJme /Non DC FWA DC FWA DC-DC FWA DC FWR DC'~ Electro-HIit! T""'" 171 183 152 181 113 1& 85 113 81 111 87 153 moch. Non 171 193 152 181 113 , .. 13 110 • 113 Ill 1"' Electro-H"" Temo NA NA NA NA NA NA 1111 241 1115 201 144 ~ mech. Non NA NA NA NA NA NA 1N 238 183 211 14& 202 Low Torno NA NA NA NA NA NA ,, 10. 711 101 75 1 .. Low Tomn NA NA NA NA NA NA 180 232 153 -132 1"' Non NA NII NA NA NA NA Ill 104 _, 108 75 1+ Non NA NA NA NA NA NA 111 232 154 204 132 1• 3000Hz HIit! Torno 1711 195 152 1113 115 1 .. 100 11• M 11111 "", .. lnte,rupt. Non 171 1N 152 1113 113 181 85 114 13 111 83 "" Low Tom• NA NI\ NA NA NA NA 90 108 113 108 .,. "' 3000Hz HIit! Tomn NA NA NA NA NA NA 183 248 1118 214 152 207 lntenupt. Non NA NA NA NA NA NA 1118 242 1'1 217 150 210 Low Torno NA NA NA NA NII NA 183 2S4 157 208 131 183 Non NA NA NA NA NA NA .. 10, 12 107 IIO 14' -NA NA NA NA NA NA 112 232 151 -137 , .. Page 2 of 6 -DF-51609 ENGINEERING SPECIFICATIONS General -SpectrAlert horns, strobes and horn/strobes shall be capable of mounting to a standard 4' x 4' x 1-1/2' (10.16 x 10.16 x 3.81 cm) backbox or a single-gang 2' x 4' x 1-1/2' (5.08 x 10.16 x 3.81 cm) backbox using the universal mounting plate included with each SpectrAlert product. Also, SpectrAlert products, when used in conjunction with the ac- cessory Sync•Circuit Module, shall be powered from a non- coded power supply and shall operate on 12 or 24 volts. 12- volt rated devices shall have an operating voltage range of 10.5 -17 volts. 24-volt rated devices shall have an operating voltage range of 20 -30 volts. SpectrAlert products shall have an operating temperature of 32°F to 120°F (0°C to 49°C) and operate from a regulated DC or full-wave rectified, unfiltered power supply. Horn -Horn shall be a System Sensor SpectrAlert model ____ capable of operating at 12 and 24 volts. Horn shall be listed to UL 464 for fire protective signaling systems. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. The horn-only model shall NOT operate on a coded power supply except those models (model numbers contain "HC") designed to do so. Strobe -Strobe shall be a System Sensor SpectrAlert model ____ listed to UL 1971 and be approved for fire protective service. The strobe shall be wired as a primary signaling notification appliance and comply with the American_s with Disabilities Act requirements for visible signaling appli- ances, flashing at 1 Hz over the strobe's entire operating volt- age range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. DIMENSIONS 5• (127 mm) 5-518" (142.875 mm) I 2-5/16" (58. 7375 mm) OUTER: 5-5/8" (142.875 mm) INNER: 5-5/16" (134.9375 mm) ~ 2-5/16"- (58.7375 mm) Horn/Strobe Combination -Horn/strobe shall be a System Sensor SpectrAlert model ____ listed to UL 1971 and UL 464 and shall be approved for fire protective service. Horn/strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over its entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a tem- poral 3 pattern and a non-temporal continuous pattern. Strobes shall be powered independently of the sounder with the re- moval of factory-installed jumper wires. The horn on horn/ strobe models shall operate on a coded or non-coded power supply. Module -Module shall be a System Sensor Sync•Circuit model ____ listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal 3. Also, the module shall silence the horns on horn/strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 4-11/16' (1 19.0625 mm) square x 2-1/8' (53.975 mm) deep backbox and shall control two Style Y (class B) or one Style Z (class A) circuit. Module shall be capable of multiple zone synchronization by daisy- chaining multiple modules together and resynchronizing each other along the chain. The Module shall NOT operate on a coded power supply. ~ 2-15116" -.j J (74.8125 mm) J 15116' -(23.8125 mm) 5-5116' (134.9375 mm) UPPER LEFT: Horn/Strobe with Small Footprint Mounting Plate (same dimensions for strobe only). LOWER LEFT: Horn/Strobe with Universal Mounting Plate (same dimensions for strobe only). UPPER RIGHT: Horn only (may be mounted with either Small Footprint or Universal Mounting Plate). LOWER RIGHT: Sync•Circuit Module (MDL). 2' 5-1/4' (133.35 mm)+--~ ~50.8 mm) In ::: IL DF-51609 -Page 3 of 6 MOUNTING DIAGRAMS 2" x 4" x 1-7/8" backbox 0 • 0 0 0 0 Horn Direct Mount ~ 4" x 4" x 1-1/2" backbox Horn Surface Mount with accessory Backbox Skirt Horn with Universal Mounting Plate 4" X 4• X 1-1/2" backbox 4-11/16" X 4-11/16" X 2-1/8" (119.0625 x 119.0625 x 53.975 mm) backbox \~~r:::._.~-- A -- (included with each product} T Strobe or Horn/Strobe with Universal Mounting Plate (included with each product} 4• x 4• x 1-1/2" backbox 2" X 4• X 1-7/8" backbox / A Strobe or Horn/Strobe with accessory Small Footprint Mounting Plate Sync•Circuit Module Direct Mount Strobe or Horn/Strobe Surface Mount with accessory Backbox Skirt SOUND OUTPUT GUIDE (dBA) UL Reverberant Room dBA @ Volts DC Anechoic Room Peak d BA @ 10 ft.NOC 10.5 12 17 20 24 30 10.5 12 17 20 24 30 LOW Electromechanical NA NA NA 75 75 79 NA NA NA 94 96 98 TONE 3000 Hz Interrupted NA NA NA 75 79 79 NA NA NA 94 96 98 Temporal Electromechanical 75 75 79 82 82 82 94 95 98 100 101 102 HIGH TONE 3000 Hz Interrupted 75 75 79 82 85 85 94 95 98 100 101 102 LOW Electromechanical NA NA NA 79 82 85 NA NA NA 94 96 98 TONE 3000 Hz Interrupted NA NA NA 82 82 85 NA NA NA 94 96 98 ~on-Electromechanical emporal HIGH 79 79 85 85 88 88 94 95 98 100 101 102 TONE 3000 Hz Interrupted 79 82 85 88 88 90 93 95 98 100 101 102 Page 4 of 6 -DF-51609 WIRING DIAGRAMS NOTE: Do NOT loop wires under terminal screws. Tandem Operation HORN/STROBE COMBO (+) (-) H } EBQM FACP, (-MODULEOR '-<c-+-~_J_• ~';!{)(/;~us HORN/STROBE STROBE ONLY ,------------(+)r------.(+) Two-wire system, any mix of models, wired for TANDEM OPERATION. T Horns silenced over two-wire circuit. • Any mix of horn/strobes or strobe-only devices is acceptable. • Horn control connects to interruptible power source. FACPII {+) -+-•-+-+--0 NAC1 (-)-+---+--0 {+)-+---+--o NAC2 H --+---+--o IIODULE1 IIODULE2 FACJ'f2 i:i}:..o.. {+) -+-f-H-H--0 NAC1 (-)-+--+-4-1-H--O (+) -+-t-H--<o+--0 NAC2 H ---+-+'o-+---+--u ""'"' .. :-a 11IOUILE ~}~ ·~ •[!] T!IIP.AIIIPU°"' DIAGRAM NOTES: > 'IONEXT s'::~ OIi EOL 'IONEXT Spoc:ITAlort IJEVICE OIIEOI. > > All SpectrA/erl hams, ham/strobes, and strobes wit operate In sync. 1) Any mix of SpectrAlert horn/strobe, strobe-only, or horn- only devices is allowable for Zone 1. 2) No devices or horn-only are allowed on Zone 2. If no de- vices are installed on Zone 2, terminate EOL resistor at horn control terminal. (+) H (+) H Independent Operation H 0 A N s T A 0 a E HORN AND STROBE :C :0 :M :a :o H 0 A N s T R 0 a E HORNS H {+) Four-wire system, combo models, wired for INDEPENDENT OPERATION. (Horn can be turned off at the panel while strobes continue to oparate.) T Temp 3 coding of Multi-Alert and PA400 sounders. NOTE: Strobes must be powered from non-coded supply. IIODULE 1 FACJ' o},_ 0 con-. NA_c_1 _1---+--oi:)} r 1 NA_C_z_+---+--0"} r I l11DUk2 {~ u~ ~{§ [OJ TEMP. JUIIJ'EII ON > > 'IONEXT DEVlCE 011 EDI. Homswilbe temporal-coded and In sync. > DF-51609 -Page 5 of 6 z 0 i 0 ... z -Ill z -... ... u ::, A I a. Horn/Strobes Canadian Models, Horn/Strobes Spanish Labeling, HIS Strobes Canadian Models, Strobes Spanish Labeling, Strobes Horns Accessories .... Sync•Circuit Module Small Footprint Mounting Plate for Single-Gang OHL Y Surface-Mount Backbox Skirt Universal Mounting Plate (replacement) Weatherproof Backbox RED WHITE P1215 P1215W P121575 P121575W P2415 P2415W P241575 P241575W P2475 P2475W P24110 P24110W P241575K (weatherprooQ - P2475K (weatherprooQ - P24110K (weatherprooQ - P2415A P2415WA P241575A P241575WA P2475A P2475WA P24110A P24110WA P241575KA (weatherprooQ - P2475KA (weatherprooQ - P24110KA (weatherprooQ - P241575F (FUEGO) S1215 S1215W S121575 S121575W S2415 S2415W S241575 S241575W S2475 S2475W S24110 S24110W S241575K (weatherprooQ - S2475K (weatherprooQ - S24110K (weatherprooij - S2415A S2415WA S241575A S241575WA S2475A S2475WA S24110A S24110WA S241575KA (weatherprooQ - S2475KA (weatherprooQ - S24110KA (weatherprooQ - S241575F (FUEGO) H12/24 H12/24W H12/24K (weatherprooQ - HC12/24 (coded power) HC12/24W (coded power) HC12124K (weatherproof, k>r coded power) - H12/24A H12/24WA H12/24KA (weatherprooij - HC12/24A (coded power) HC12/24WA (coded power) MDL MDLW MOLA MDI.WA S-MP S-MPW BBS BBSW O-MP O-MPW WBB - voltage candela avg. mA*@ avg. mA*@ nom. voe nom.Pw\R 12 15 124 167 12 15175 152 181 24 15 78 98 24 15175 91 111 24 75 148 167 24 110 165 209 24 15175 91 111 24 75 148 167 24 110 165 209 24 15 78 98 24 15175 91 111 24 75 148 167 24 110 165 207 24 15175 91 111 24 75 148 167 24 110 165 209 24 15175 91 111 12 15 114 157 12 15175 142 171 24 15 53 80 24 15175 66 93 24 75 123 149 24 110 140 191 24 15175 66 93 24 75 123 159 24 110 140 191 24 15 53 80 24 15175 66 93 24 75 123 149 24 110 140 191 24 15175 66 93 24 75 123 149 24 110 140 191 24 15175 66 93 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 12 / 23 12 / 21 12/24 NA 16 24 12/24 NA 16 24 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NOTES: 1) Canadian model numbers end in "A". 2) Latin American model numbers end in "F". 3) All weatherproof models must use weatherproof backbox model WBB. 4) All SpectrAlert products are designed for wall-mount only. 5) Installation of less than 75 candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). However, it is the responsibility of the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. 6) All 15ll5 candela strobes or horn/strobes are recommended for 20' x 20' rooms or less. *For a complete listing of SpectrAlert current require- ments, please refer to the Current Draw tables on page 2 of this document, or the Instruction Manual. Horn and horn/strobe current draws assume the horn is set at Temp 3, electromechanical tone, and high audibility. Page 6 01 6 -DF-51609 LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: NOTE: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7135-1653:163 Page 1 of 1 Audible Devices System Sensor, Unincorporated Div. ofHoneywell lnt'I Inc., 3825 Ohio Avenue, St. Charles IL 60174 Contact: Trish Linhart (630) 377-6580 ext. 1185 FAX (630) 377-7245 Models P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW, P1224MCK, and P1224MCWK combination horn/strobes with selectable candela. Refer to listee's data sheet for additional detailed product description and operational considerations. Electrical: 8-33 VDC/FWR 12/24 VDC/FWR 24 VDC/FWR Selectable :15cd, 15/75cd Selectable: 30cd, 75cd, 110cd In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, rating, and UL label. Listed as horn strobes for use with separately listed compatible fire alarm control units. Suitable for the hearing impaired application. For wall mount and indoor use only. *Models with suffix 'K' are suitable for indoor or outdoor use with an operating temperature range of -40°C to + 66°C (-40°F to +150.8°F) when mounted on Model WBB backbox NEMA type 3R enclosure rating. Units can generate the distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition. Refer to manufacturer's Installation Manual for details. Formerly 7135-1209:223 Rev. *02-09-2006 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 26, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 March 1, 1999 G-700 (2) F1re·L1Te" Alarms KMS Series Alarm Bells Section: AudioNisual Devices GENERAL KMS Series bells are low-current, audible signaling devices for use in fire alarm systems or other signaling applications. @(® California State Fire Marshal 7135-0028: 117 LISTED CS47021 S748 <8> FEATURES • Under-dome design. • Available in three gong sizes (6", 8", and 1 O" diameter). • Low operating current. • Low "kick" current. • Indoor/outdoor installation. • Mount to standard 4" square electrical box. • Complies with UL 864. OPERATION The KMS Series bells use a low-current, high efficiency DC motor to drive the striker. All DC models are polar- ized for use with supervision circuitry. The operating mechanism is completely enclosed in a cast aluminum base. APPLICATIONS KMS Series bells are ideally suited for almost any kind of alarm signaling application. They can be used in schools, factories, office buildings, or private residences. Their low current consumption means additional savings on standby power. CONSTRUCTION Each bell gong is made of steel finished in red enamel. The striker is also made of steel, and the mechanism housing is made of cast aluminum. Optional backboxes are of steel finished with red enamel to match the gong. INSTALLATION Bells may be installed on a wall surface or semi-flush. A weatherproof backbox (WBB) also permits installation on an exterior wall surface. This document is not intended to be used for installation purposes. We try to keep our product Information up-to-date and accurate. We cannot cover all specific appllcaUons or anticipate all requirements. All specifications are subject to change without notice. For more Information, contact Flre•Llte Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627• 3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299 WEB: www.flrelite.com BSA 1070-80-SA 0M6A4.AY ISO 9001 CERTIFIED ENClrt.EIINC I MANIFACTIIINC DF-51636 -Page 1 of 2 PRODUCT LINE INFORMATION Model Number Gong Size SPL Measurement Rated Input Rated Current at 10 ft (3.048 m)* Voltage (mA) KMS-6-24 6" (15.24 cm) 85 dB 24 VDC 30 KMS-8-24 8" (20.32 cm) 85 dB 24 VDC 30 KMS-10-24 1 0" (25.40 cm) 85 dB 24 VDC 30 WBB Surface-mount weatherproof backbox, metal, red. BB-A Standard 4" square electrical backbox -red enamel finish. SFP-R Semiflush plate, mounting trim, metal, red. MP-SF/A Semiflush plate, mounting trim, plastic, red. Notes: * Sound Pressure Level (SPL) measured in accordance with UL Standard 464. UL Standard 464 requires that: • The units be measured in a reverberant room qualified for pure tones under the methods for Determination of Sound Power Levels of Small Sources in Reverberation Rooms, ANSI S1.21 - 1972. • The units be capable of providing a sound out- put of not less than the sound level provided by an omnidirectional source having an A-weighted sound pressure level equal to the level speci- fied on the unit marking and not less than 75 decibels in any case. Page 2 of 2 -DF-51 636 ~ I \ ~-\ I \· Minimum Starting Voltage 12 VDC 12 VDC 12 VDC 5163611.tbl 6-inch bells 2-19/32' (6.59 cm) 8-inch and 10-inch bells 3-1/8' (7.94 cm)) LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: NOTE: XLF: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7135-1653:100 Page 1 of 1 Audible Devices System Sensor, Unincorporated Div of Honeywell lnt'I Inc., 3825 Ohio Ave, St. Charles IL 60174 Contact: Trish Linhart (630) 377-6580 ext. 1185 FAX (630) 377-7245 Models KBS-6, -8, -10 with suffix 120AC and SSV120-6, -8, -10 vibrating bells. Refer to listee's data sheet for detailed product description and operational considerations. In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating and UL label. Listed as audible devices for use with separately listed compatible control units. Suitable for outdoor use with weatherproof back box. If this appliance is required to produce a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition, the appliance must be used with a fire alarm control unit that can generate the temporal pattern signal. Refer to manufacturer's Installation Manual for details. Formerly 7135-1209:100 7135-0587:002 06-17-2005 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 24, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 U.S. Pat. No. 3921989 Canadian Pat. No. I 009680 Other Patents Pending Potter Electric, Rd., 1990 GENERAL INFORMATION The Model VSR-F is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules IO through 40. sizes 2" thru 8" (50mm thru 200mm). LPC approved sizes are 2" thru 8" (50mm thru 200mm). The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instn1ctions of this switch. VSR-F VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD UL, ULC and CSFM Listed, FM and LPCBApproved, NYMEA Accepted, CE Marked Service Pressure: Up to 450PSI (3 1 BAR) Minimum Flow Rate for Alarm: l0GPM (38 LPM) Maximum Surge: I 8 FPS (5,5 mis) Contact Ratings: Two sets ofSPDT (Fonn C) 15.0Arnpsat 125/250VAC 2.0Ampsat30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: • Suitable for indoororoutdooruse with factory installed gasket and die-cast housing. • NEMA 4/1 P54 Rated Enclosure -use with appropriate conduit fitting. • Temperature Range: 40°F/l 20°F, 4,5°C/49°C • Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Sizes Available: Steel Pipe schedules IO thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thrn 200mm Note: For copper or plastic pipe use Model VSR-CF. Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code Optional: CoverTamperSwitch Kit, StockNo. 0090018 INSTALLATION: See Fig.2 NFPA-13 NFPA-13D NFPA-13R NFPA-72 These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they wi ll be accessible. The units should not be installed within 6" ( 15cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a hole with a diameter of I 1/4" + 1/8" -l/16" (33mm ±2mm). All other sizes require a hole with a diameterof2" ±1/8" (50mm ±2mm). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft-lbs. (68 n-m) of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8800001 • REV W MFG. #5400761 -7/02 PAGE I OF2 VSR-F VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FIG. 1 FIG. 2 SWlTCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL OPTIONAL TAMPER SWITCH ~ ~~TtOT LEAVE COVER Off FOR ~NOED PERIOD OF TIME RETARD ADJUSTMENT: TO CHANGE TIME TURN KNOB (EITHER DIRECTION) FOR DESIRED TIME DELAY. USE THE MINIMUM AMOUNT OF RETARD NECESSARY TD PREVENT FALSE ALARMS. A •a• SETTING IS USUALLY ADEQUATE FOR THIS. FACTORY IS SET TD •a•. TO INSTALL, DRILL HOLE AS INDICATED: PIPE SIZE HOLE SIZE TIGHTEN NUTS ALTERNATELY TO AN EVENTUAL SOFT. -LBS ( 68 n-m) OF TORQUE MOUNT ON PIPE SO 2" to 2 1/2" 1 1/4" +1/8" -1/16" (50mm to 65mm) (33mm ±2mm) -i..-.::_----::/2'.::.,__.....:,'<---~~~T! ?NN ~~~~N CAtffION: 3· to 5• 2· ±1 /8" OF WATERFLOW An uninsulated section of a single conductor should not be looped around the tenninal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the tenninal. (80mm to 200mm) 50mm ±2mm) 1,r-j~~----\ ~~~~;~o~~E~TION C N.O. N.C. DIRECTIO WATERFL OF WATERFLOW (WIJT) (RED) (BLK) \\ APPROX. RETARD SETTINGS (IN SECS.) DWG. #761-30 FIG. 3 TYPICAL ELECTRICAL CONNECTIONS :? SETS OF NORMALLY OPEN CONTACTS CLOSE ON ALARM TH.EN.C. AND NO. MARKINGS ON THE SWTTCII ARE FOR ANAi.ARM CO'.'IOITIOS WATERFLOW ZONE ON FIRE PANEL POSITIVE DC ORIIOTAC NEGATIVE l>C OR THE CONTACTS ARE REVERSED NEIJfRALAC WHEN THE DEVICE JS IN THE NORMAL CO!-,!DJTION, APPLICATION WARNlNG! EOLR FROM FJRE PANEL NOTES: I. The Model VSR-F has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. A condition of LPC Approval of this product is that the electrical entry must be sealed to exclude moisture. 3. For supervised circuits see "Switch Tenninal Connections" drawing and caution note (Fig. I). 0 A 8 C 0 10-25 20-40 35-55 50-70 60-90 FIG. 4 To remove knockouts: Place screwdriver at edge of knockouts, not in the center. Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches that are monitoring wet pipe sprinkler systems should not be used as tie sole initiating device to discharge AFFI-~ deluge, or chemical suppression systems. TESTING The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. lfthere are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F is not recommended or advisable. A minimum flow of IO gpm (38 Lpm) is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. PRINTED IN USA MKT. #880000 I -REV W MFG. #5400761 -7/02 PAGE 2 Of 2 LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7770-0328:001 Valves/Switches Potter Electric Signal Co., 2081 Craig Road, St. Louis, MO 63146 Contact: *Bill Witherspoon *(314) 878-4321 Fax (314) 878-7264 Page 1 of 1 Vane and pressure type water flow alarm switches listed below. Refer to listee's data sheet for detailed product description and operational considerations. Vane Types: VSR-CF VSR-FE-2 VSR-SFT *VSR-C Pressure Type: WFS-B PS-10A VSR-D VS-SP VSG *VSR-ST WFSR-C PS-100A VSR-F VS-F VSR *VSR-SG WFSPD-B WFSR-F VSR-SF VSR-SFG *VSR-S *PS10 *PS100 In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number and UL or FM label. Listed as waterflow alarm switches for use with fire sprinkler systems. Vane models may be used in wet pipe systems; pressure models may be used in wet or dry systems. Model VSR-CF is for use on K, Lor M copper pipe (2", 2-1/2", 3", 4") and listed CPVC pipe (2", 2-1/2", 3"). Model VSR-SF for use on 1", 1-1/4" and 1-1/2" steel, copper or listed plastic pipe. Model VSG is for low flow rate. Model VSR-SFG and VSR-SFT are for use on 1", 1-1/4" and 1-1/2" plastic pipe. Models VS-F, VSR-F, VSR-FE and VSR-FE-2 is for use on 2", 2-1/2", 3", 3-1/2", 4", 5", 6", 8" and 1 O" pipe. *Model VSR is for use on steel pipe sizes from 2" through 8". Vane type switches may be used outdoors when the outdoor temperature never falls below 40°F. •Rev. 08-22-2006 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: AUGUST 22, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 OSYSU-1 Stock No. 1010106 OSYSU-2 Stock No. I 010206 GENERAL INFORMATION I • The OSYSU is used to monitor the open position of an OS & Y (outside screw and yoke) type gate valve. This device is available in two models; the OSYSU-1, containing one set of SPDT (Form C) contacts and the OSYSU-2, containing two sets of SPDT (Form C) contacts. These switches mount conveniently to most OS & Y valves ranging in size from 2" to 12" (50mm to 300mm). They will mount on some valves as small as 1/2" (12,5mm). The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available. See ordering information on page 4. OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH UL and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked Dimensions: 6. I 9"L X 2.25"W X 5.88"H 15,7cm L X 5,7cm W X 14,6cm H Weight: 2 lbs. (0,9 kg.) Enclosure: Cover -Die-Cast Finish-Red Spatter Enamel Base -Die Cast Zinc All parts have corrosion resistant finishes. Cover Tamper: Tamper resistant screws, Optional cover tamper kit available. Contact Ratings: OSYSU-1: One set of SPOT (Form C) OSYSU-2: Two sets ofSPDT (Form C) 15.00Amps at 125/250YAC 2.50 Amps at 30VDC resistive Environmental Limitations: • NEMA 4 and NEMA 6P Enclosure (IP67) when used with appropriate watertight conduit fittings. • Indoor or Outdoor use (Not for use in hazardous locations. See bulletin no. 5400705 OSYS-U-EX for hazardous locations.) • Tern perature Range: -40°F to I 40°F (-40°C to 60°C) Conduit Entrances: 2 knockouts for 1/2" conduit provided Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code OPTIONAL COVER TAMPER SWITCH NFPA-13 NFPA-130 NFPA-1 3R NFPA-72 A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information on page 4. TESTING The OSYSU and its associated protective monitoring system should be inspected and tested in accordance with applicable NF PA codes and standards and/or the authority havingjurisdiction (manufacturer recommends quarterly or more frequently). Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.ponersignal.com PRINTED IN USA MKT. #8820004 -REV P 12/01 PAGE I OF 4 OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG.1 SMALL VALVE INSTALLATION -1/2" THRU 21/2" (12,5mm THRU 63,5mm) SIZES THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME VALVES AS SMALL AS 1/2" (12,SMM). J-HOOKS MAY BE REQUIRED ON VALVES WlTH LIMITED CLEARANCE. CLAMP BAR CARRIAGE BOLT SMALL VALVE INSTALLATIO I. Remove and discard "C" washer and roller from the trip rod. 2. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, ~ that the trip rod lays against the non-threaded portion of the valve stem. 3. Loosen the locking screw that holds the trip ro<l in place and adjust the rod length (!£e Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bi!'. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the I" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYSU. 5. Mark the valve stem at the center of the trip ro<l. SLOTTED MOUNTING HOLES MAY BE USED FOR FINE ADJUSTMENT OF SWITCH ON BRACKET BRACKET DWG. #979-3 6. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark on the v~ve stem utilizing a 3/16" (4,8mm) round, non-tapered file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated 7. Mount the OSYSU with the trip rod centered in groove. 8. Final adjustment is made by loosening 2 screws (see Fig. 1) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate when the trip rod moves out of the groove. 9. Tighten the adjustment screws and all mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. PRINTED IN USA MKT. #8820004 • REV P 12/01 PAGE 2 OF 4 OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG.2 LARGE VALVE INSTALLATION -3" THRU 12" (76mm THRU 300mm) SIZES 3" THRU 12" (76mm THRU 300mm) VALVES BRACKET CLAMP BAR USE CARRIAGE BOLTS. BOLTS MOUNT ON INSIDE OF YOKE, IF THERE IS SUFFICIENT CLEARANCE. SLOTTED MOUNTING HOLES. MAY BE USED FOR FINE ADJUSTMENT OF SWITCH ON BRACKET. DWG. #979-4 LARGE VALVE INSTALLATION I. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, oo that the trip rod lays against the non-threaded portion of the valve stem. 2. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. 3. Loosen the locking screw that holds the trip rod in place and adjust the rod length (~e Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the lockingscrew and remove the trip rod from the trip lever. Using pliers, break off the one I" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mark the valve stem at the center of the trip rod. 5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark of the valve stem utilizing a 3/8" (9,5mm) round, CARRIAGE BOLTS (2 REQUIRED) YOKE VALVE STEM TRIP ROD non-tapered file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 6. Mount the OSYSU loosely with the trip rod centered in groove. 7. Final adjustment is made by loosening 2 screws (see Fig. 2) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. 8. Tighten the adjustment screws and mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FU LL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCI-I BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. PRINTED IN USA MKT. #8820004 -REV P 12/01 PAGE 30F4 FIG. 3 DIMENSIONS FIG. 4 OSYSU-l, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH PARTS KHOCl<llUlS fOft CU:CTltlCAI. CONN[CllONS MID 01'1DmCD 17 I I l,..J I I I I.a' BREAKlNG EXCESSIVE ROD LENGTH SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL FIG. 5 CAUTION: An uninsulated section of a single conductor should not be looped around the tenninal and serve as two separate connections. The wire must be severed. thereby providing supervision of the connection in the event that the wire becomes dislodged from under the tenninal. ORDERING INFORMATION MODEL OSYSU-1 OSYSU-2 DESCRIPTION Outside Screw & Yoke-Supervisory Switch (Single switch) Outside Screw & Yoke-Supervisory Switch (Double switch) Cover Screw Hex Key for Cover Screws and Installation Adjustments Optional Cover Tamper Switch Kit STOCK NO. 1010106 1010206 5490344 5250062 0090131 For pressure reducer type valve installation kits (if required) contact valve manufacturer. PRINTED IN USA MKT. #8820004 -REV P 12/01 TYPICAL ELECTRICAL CONNECTIONS LOCAL CIRCUIT TO POWER FOR INDICATING DEVICE TO SUPERVISORY CIRCUIT OF CONTROL PANEL N.D. 0 coMpN.C. INDICATING DEVICE END OF LINE RESISTOR DWG. #979-1 Contacts shown in nonnal (valve open) condition. TYPICAL SWITCH ACTION OPEN V/IJ..VE POSITION COM • .r;;:;- SW #t ~ N.C, I I COM.I~ SW 12 b..._1 ... A,V. ~ CLOSED VAL VE POSITION con:. N.o. SW #1 1't'.=- I C~M-~ SW #2'j<1)~"" t=- DWG. #979-2 PAGE 4 OF 4 LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: NOTE: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7770-0328:010 Valves/Switches Potter Electric Signal Co., 2081 Craig Rd., St. Louis MO 63146 Contact: *Bill Witherspoon *(314) 878-4321 Fax (314) 878-7264 Page 1 of 1 Supervisory switches listed below to monitor pressure, OS&Y, gate, globe/gate, PIV, tank temperature or water level valves. Refer to listee's data sheet for detailed product description and operational considerations. HLS-8 PS-120A PTS-8 PIVS-8 WLS WLS-W OSYSU-2 OSYSU-1 TTS-S PTS-C WLS-S OSYS-8 GVS TTS-W *PS40 PS-40A PMS PCVS-1 PCVS-2 *PS120 In accordance with listee's printed instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation and FM or UL label. Listed as sprinkler system supervisory switches. Formerly 7738-0328:010 *Rev. 08-22-2006 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: AUGUST 22, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 Technical Data Sheet Fire Alarm Cables PART NUMBER: 980 WEST PENN WIRE 2833 West Chestnut Street Washington, PA 15301 Toll Free: (800) 245-4964 Fax: (724) 222-6420 www.westpenn-wpw.com DESCRIPTION: NEC RATING: 18/2 Solid bare copper conductors, unshielded with an overalljacket. FPLR, NEC Article 760 APPROVALS: (UL) or (ETL)us Listed APPLICATION: Indoor for (Audio Circuits, Control Circuits, Initiating Circuits, Notification Circuits) Construction Parameters: Conductor Stranding Insulation Material Insulation Thickness Number of Conductors Shield Drain Jacket Material Jacket Thickness Overall Cable Diameter Approximate Cable Weight Flame Rating 18 AWG Bare Copper Solid PVC 0.010" Nom. 2 None None PVC 0.015" Norn. 0.146"Nom. 18 Lbs/IM' Nom. UL 1666 Riser Flame Test Electrical & Environmental Properties: Temperature Rating Operating Voltage Max.Capacitance Between Conductors @ I KHz DC Resistance per Conductor @ 20deg C Insulation Colors • Jacket Color RoHS Compliant Mechanical Properties: Max. Recommended Pull Tension Min. Bend Radius (Install) Specification Issue Date: 7 /06 This document is the property of West Penn Wire. The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire -20deg C to 60deg C 300 V RMS 29 pl7ft Nom. 6.4 Ohms/IM' Norn. Black, Red Red Yes 39.2 lbs. 1.5" Standard Lengths are I OOOfl. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise. LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7161-0859:101 Cables-Fire Protective Signaling West Penn Wire, PO Box 762, Washington PA 15301 Contact: Diane Kelley (724) 222-7060 FAX (724) 229-1151* Page 1 of 1 Types FPL and FPLP power limited fire protective signaling cable. Refer to listee's data sheet for detailed product description and operational considerations. In accordance with listee's printed installation instructions, NEC Article 760, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, type, NEC rating and UL label. Listed as power-limited fire protective signaling cable. *Rev. 05-23-2005 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: Authorized By: JUNE 14, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires June 30, 2007 Technical Data Sheet Fire Alarm Cables PART NUMBER: 994 WESTPENN WINE 2833 West Chestnut Street Washington, PA 15301 Toll Free: (800) 245-4964 Fax: (724) 222-6420 www.westpenn-wpw.com DESCRIPTION: NEC RATING: 14/2 Solid bare copper conductors, unshielded with an overall jacket. FPLR, NEC Article 760 APPROVALS: (UL) or (ETL)us Listed APPLICATION: Indoor for (Audio Circuits, Control Circuits, Initiating Circuits, Notification Circuits) Construction Parameters: Conductor Stranding Insulation Material Insulation Thickness Number of Conductors Shield Drain Jacket Material Jacket Thickness Overall Cable Diameter Approximate Cable Weight Flame Rating 14 AWG Bare Copper Solid PVC 0.012"Nom. 2 None None PVC 0.015" Norn. 0.195"Nom. 41 Lbs/lM'Nom. UL 1666 Riser Flame Test Electrical & Environmental Properties: Temperature Rating Operating Voltage Max.Capacitance Between Conductors@ I KHz DC Resistance per Conductor @ 20deg C Insulation Colors Jacket Color RoHS Compliant Mechanical Properties: Max. Recommended Pull Tension Min. Bend Radius (lnstall) Specification Issue Date: 7/06 This document is the property of West Penn Wire. The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire -20deg C to 60deg C 300 V RMS 32 pf7ft Norn. 2.43 Ohms/IM' Norn. Black,Red Red, Black, Blue, White, Yellow Yes 99.4 lbs. 2" Standard Lengths are 1 0OOfl. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise. LISTING No. CATEGORY: LISTEE: DESIGN: INSTALLATION: MARKING: APPROVAL: CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 7161-0859:101 Page 1 of 1 Cables-Fire Protective Signaling West Penn Wire, PO Box 762, Washington PA 15301 Contact: Diane Kelley (724) 222-7060 FAX (724) 229-1151* Types FPL and FPLP power limited fire protective signaling cable. Refer to listee's data sheet for detailed product description and operational considerations. In accordance with listee's printed installation instructions, NEC Article 760, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, type, NEC rating and UL label. Listed as power-limited fire protective signaling cable. *Rev. 05-23-2005 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: A uthorized By: JUNE 14, 2006 DIANE K. AREND, Senior Deputy Program Manager Listing Expires·June 30, 2007