HomeMy WebLinkAbout6125 PASEO DEL NORTE; 100; FPC2017-0004; PermitPER]CT REPORT Fj[eiPnmjt Print Date: 08/17/2022 Job Address: 6125 PASEO DEL NORTE, # 100, CARLSBAD, CA 92011-1117 Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm Parcel 4*: Track 4*: Valuation: $0.00 Lot 4*: Occupancy Group: Project 4*: #of Dwelling Units: Plan 4*: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check #: Plan Check 4*: City of Carlsbad Permit No: FPC2017-0004 Status: Closed - Finaled Applied: 01/05/2017 Issued: 01/24/2017 Finaled Close Out: 03/08/2021 Final Inspection: INSPECTOR: Wong, Cindy Fieri, Dominic Project Title: Description: PASEO DEL NORTE MULTI TENANT -ALARM TI FPContractor: THE STEINHILBER CORPORATION 533 S VINEWOOD ST ESCONDIDO, CA 92029-1924 (760) 747-3050 FEE AMOUNT FIRE TI Fire Alarm System $601.00 Total Fees: $601.00 Total Payments To Date: $601.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 I 760-602-8561 1 I www.carlsbadca.gov .*lc - -0004- 'c,o-ooto vpqrqp EHUEIRFIRMES FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS PASEO DEL NORTE LLC MUILTI-TENANT IMPROVEMENTS 6125 PASEO DEL NORTE CARLSBAD, CA 92011 FIRE ALARM SYSTEM MATERIAL DATA SHEETS BILL OF MATERIALS NOTIFIER FCPS-24S6 6.0 AMP REMOTE NAC POWER SUPPLY CSFM# 7315-0028:0225 NOTIFIER NP-100 ADDRESSABLE SMOKE DETECTOR CSFM# 7272-0028:0231 NOTIFIER NMM-100P ADDRESSABLE MONITOR MODULE CSFM# 7300-0028:0230 NOTIFIER NC-baR ADDRESSABLE RELAY MODULE CSFM# 7300-0028:0230 SYSTEM SENSOR PC2W HORN/STROBE, SELECTABLE CANDELA - CEILING MOUNTED CSFM# 7125-1653:0188 SYSTEM SENSOR P2RK HORN/STROBE - OUTDOOR WALL MOUNTED CSFM# 7125-1653:0188 SYSTEM SENSOR SCM STROBE MULTI-CANDELA CEILING MOUNTED WHITE CSFM# 7125-1653:0186 DN-6927:A2 FCPS-24S6(CIE) & FCPS. 24S8(CIE) 6. & 8-Amp 24-Volt Remote Power Supplies LII11I_IIIII1 General NOTIFIER® by Honeywell The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are remote power supplies with battery charger. The FCPS-24S6/- 24S8 may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may be used as stand-alone supplies. Pri- mary applications include notification appliance circuit (NAC) expansion (to support ADA requirements and NAC synchroni- zation) or auxiliary power to support 24 volt system accesso- ries. The FCPS-24S6/-24S8 provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either four Class B (Style Y) or Class A (Style Z, with ZNAC-4 option module). Alternately, the four outputs may be config- ured as all non-resettable, all resettable or two non-resettable and two resettable. The FCPS-24S6/-24S8 also contains a battery charger capable of charging up to 18 AH batteries. FCPS-24S6C & FCPS-24S8C are ULC-listed. NOTE: Unless otherwise specified, the terms FCPS-24S6 and FCPS-24S8 used in this document refers to the standard FCPS- 24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the FCPS-24S6E and FCPS-24S8E Features UL-Listed NAC synchronization using System Sensor, Wheelock, or Gentex "Commander2" appliances. Operates as a "sync-follower" or as a "sync-generator" (default). See note on page 2. Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma- nently "ON" (stand-alone mode). Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4 module) NACs. 6-amp (FCPS-2456) or 8-amp (FCPS-24S8) full load out- put, with 3 amps maximum/circuit, in NAC expander mode (UL 864). 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous output in stand-alone mode (UL 1481). Compatible with coded inputs; signals passed through. Optional power-supervision relay (EOLR-1). In stand-alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two, Fully regulated and filtered power output - optimal for pow- ering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power. Power-limiting technology meets UL power-limiting require- ments. Form-C normally-closed trouble relay. Fully supervised power supply, battery, and NACs. Selectable earth fault detection. AC trouble report selectable for immediate 2-hour delay. Works with virtually any UL 864 fire alarm control which uti- lizes an industry-standard reverse-polarity notification cir- cuit (including unfiltered and unregulated NAC power). Requires input trigger voltage of 9 - 32 VDC. Self-contained in compact, locking cabinet - 15"H x 14.5W x 2.75"D (cm: 38.1 H x 36.83W x 6.985D). I - .- - ...- - -- -- Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. Battery charger may be disabled via DIP switch for applica- tions requiring larger batteries. Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1mm2) wire. Specifications Primary (AC) Power: FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum. FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum. Wire Size: minimum #14 AWG (2.0mm2) with 600 V insula- tion. Control Input Circuit: Trigger Input Voltage: 9 to 32 VDC. Trigger Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mA maximum. Output Circuits: +24 VDC filtered, regulated. 3.0 A maximum for any one circuit. Total continuous current for all outputs (stand-alone mode): - FCPS-24S6: 4.0 A maximum. - FCPS-24S8: 6.0 A maximum. Total short-term current for all outputs (NAC expander mode): - FCPS-24S6: 6.0 A maximum. - FCPS-24S8: 8.0 A maximum. Secondary Power (Battery) Charging Circuit: Supports lead-acid batteries only. DN-6927:A2 • 5/17/13 - Page 1 of 2 Float-charge voltage: 27.6 VDC. Maximum current charge: 1.5 A. Maximum battery capacity: 18 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP notification appliance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24- volt system power up to 4.0 A (FCPS-2456) or up to 6.0 A (FCPS-24S8). Both resettable and non-resettable power options are available. Resettable outputs are created by con- necting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications. For example, an addressable control module is used to acti- vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module. NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 12,500 feet (3,810 meters). Sync Follower/Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP When installed at the end of a NAC wire run, the FCPS-2456/-2458 can track (i.e. "follow") the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS-2456/-2458 is configured (via DIP switch set- tings) as a "sync follower," the FCPS's NAC outputs track the strobe synchronization pulses present at the FCPS's sync input terminal. The pulses originate from an upstream FACP or other power supply. When the FCPS-2456/-24S8 are configured (via DIP switch settings) as a 'sync generator," the FCPS's sync input termi- nals are not used. Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS's NAC outputs. In "sync generator' mode, the sync type (System Sensor, Whee- lock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS-2456 and FCPS-2458 comply with the following standards: NFPA 72 National Fire Alarm Code. UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). UL 1481 Power Supplies for Fire Alarm Systems. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S635, S674 ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C) CSFM Approved: 7315-0028:225 MEA: 299-02-E FM Approved Ordering Information FCPS-24S6: 6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS-24S6C: Same as above, ULC-listed. FCPS-24S6R: Same as FCPS-24S6 with red enclosure. FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8: 8,0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8C Same as above, ULC-listed. FCPS-24S8R: Same as FCPS-24S8 with red enclosure. FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. ZNAC-4: Class A (Style Y) NAG option module. EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power, BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT Series data sheet DN-6933). System Sensor® and NOTIFIER® are registered trademarks of Honeywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I so 9001 We try to keep our product information up-to-date and accurate. -r2T3TqM We cannot cover all specific applications or anticipate all requirements. ENGINEERING & MANUE&CIURINR All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 - DN-6927:A2 • 5/17/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. CATEGORY: LISTEE: DESIGN: RATING: INSTALLATION: MARKING: 7315-0028:0225 Page 1 of 1 7315-- POWER UNITS NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com Models FCPS-24S6 and FCPS-24S8 are power limited power supply/battery chargers used for supervision and expanded power driving capability of up to four Notification Appliance Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed product description and operational considerations. 120 VAC, 24 VDC In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating and UL label APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm control units. XLF: 7315-0075:0206 1-24-O3KK This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires June 30, 2017 - Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DN-6995:D • Al -320 NP-I 00(A) Series Addressable Photoelectric NOTIFIER® Detectors by Honeywell General The NP-100(A), NP-100T(A) and NP-iOOR(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the-art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with NOTIFIER's FireWarden Series (FireWarden-1 00-2 and FireWarden-50) and Spartan (NSP-25) Addressable Fire Alarm Control Panels (FACPs). The NP-i OOT(A) adds thermal sensors that will alarm at a fixed temperature of 135°F (570C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory, PN RA100Z(A). The NP-100R(A) is a remote test capable detector for use with DNR(A)/DNRW duct smoke detec- tor housings. Features SLC LOOP Two-wire loop connection. Unit uses base for wiring. ADDRESSING Addressable by device. Rotary, decimal addressing: 01 - 99 with FireWarden-100-2 and NSP-25, and 01 - 50 with FireWarden-50. ARCHITECTURE Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires. Sleek, low-profile design. Integral communications and built-in type identification. Built-in tamper-resistant feature. Removable cover and insect-resistant screen for simple field cleaning. OPERATION Withstands air velocities up to 4,000 feet-per-minute (20 m/ sec.) without triggering a false alarm. Factory preset at 1.5% nominal sensitivity for panel alarm threshold level. Visible LED "blinks" when the unit is addressed (communicat- ing with the fire panel) and latches on in alarm. MECHANICALS Sealed against back pressure. Direct surface mounting or electrical box mounting. Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring - included). OTHER SYSTEM FEATURES Fully coated circuit boards and superior RF/transient protec- tion. 94-VU plastic flammability rating. Low standby current. NP-100(A) in B2IOLP(A) Base OPTIONS Remote LED output connection, PN RA1 OOZ(A). Applications Use photoelectric detectors in life-safety applications to provide a broad range of fire-sensing capability, especially where smol- dering fires are anticipated. Ionization detectors are often better than photoelectric detectors at sensing fast, flaming fires. Construction These detectors are constructed of off-white fire resistant plas- tic. NP-100(A) series plug-in, low-profile smoke detectors are designed to commercial standards and offer an attractive appearance. Installation NP-100(A) series plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60054. NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring '7-taps" or branches are permitted for Style 4 (Class B) wiring. NP-100R(A) mounts in a DNR(A)/DNRW duct detector housing. Operation Each NP-100(A) series detector uses one of 99 possible addresses on the FireWarden-100-2 and NSP-25, or one of 50 possible addresses on the FireWarden-50 Signaling Line Circuit (SLC). It responds to regular polls from the system and reports its type and status. The addressable photoelectric sensor in the NP-100(A) series has a unique unipolar chamber that responds quickly and uni- formly to a broad range of smoke conditions. It can withstand wind gusts up to 4,000 feet-per-minute (20 rn/sec.) without sending an alarm level signal. Because of its unipolar chamber, the NP-100(A) series is approximately two times more respon- sive than most photoelectric sensors. This makes it a more sta- ble detector. DN-69950 • 2/11/2015 - Page 1 of 2 Detector Sensitivity Test Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/connected to a FireWarden-100-2 or FireWarden-50 addressable fire alarm control panel. The results of the sensitiv- ity test can be printed off the FireWarden-100-2 or FireWarden- 50 for record keeping. Specification Voltage range: 15- 32 VDC (peak). Standby current: 300 pA @ 24 VDC. LED current: 6.5 mA @ 24 VDC (latched ON"). Air velocity: 4,000 ft/mm. (20 rn/sec.) maximum. Size: 2.1" (5.33 cm) high; base determines diameter - B21OLP(A): 6.1 (15.5 cm) diameter. - B501 (A): 4.1 (10.4 cm) diameter. - B200SR(A): 6.875 (17.46 cm) diameter. - B224RB(A): 6.2' (15.748 cm) diameter. Weight: 3.6 oz. (102 g). Operating temperature range: for NP-100(A): 0°C to 49°C (32°F to 120°F); for NP-IOOT(A): 0°C to 38°C (32°F to 100°F). NP-IOOR(A): installed in a DNR(A)/DNRW -20°C to 70°C (-4°F to 158°F). Temperature: 0°C - 49°C (32°F - 1200F). Relative humidity: 10% - 93%, non-condensing Listings Listings and approvals below apply to the NP-100(A), NP- 100T(A), and NP-100R(A) detectors. In some cases, certain modules may not be listed by certain approval agencies, or list- ing may be in process. Consult factory for latest listing status. UL Listed: S1 115. ULC Listed: SillS. CSFM: 7272-0028:0231. MEA: 243-02-E Vol. 2. Maryland State Fire Marshal: permit 2173. FM approved. Product Line Information NOTE: "A" suffix indicates ULC Listed model. NP-100: Addressable photoelectric detector; B21OLP base included. NP-100A: Sames as NP-100 with ULC Listing; B21OLPA base included. NP-lOOT: Same as NP-100 but with thermal element; B21OLP base included. NP-i OOTA: Same as NP-100T with ULC Listing; B21OLPA base included. NP-100R: Remote test capable addressable photoelectric detector for use with a DNRA/DNRW duct detector housing; B21OLP base included. NP-100RA: Same as NP-baR with ULC Listing for use with a DNRA duct detector housing; B21OLPA base included. INTELLIGENT BASES NOTE: "A" suffix indicates ULC Listed model. NOTE: For details about intelligent bases and their mounting, see DN-60054. B21OLP(A): Plug-in detector base (included); standard U.S. flanged low-profile mounting base. B21OLPBP: Bulk pack of B21OLP; package contains 10. B501(A): Standard European flangeless mounting base. B501 BP: Bulk pack of B501; package contains 10. B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Replaces B501 BH series bases in retrofit applications. B224RB(A): Plug-in System Sensor relay base. Screw termi- nals: up to 14 AWG (2.0 mm2). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. B224B1(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases (see DN-6994). ACCESSORIES F110: Retrofit flange to convert B21OLP(A) to match the B71OLP(A) profile, or to convert older high-profile bases to low- profile. F110BP: Bulk pack of Fl 10; package contains 15. F210: Replacement flange for B21OLP(A) base. RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501 (A) and B21OLP(A) bases only. SMB600: Surface mounting kit M02-04-00:Test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applications. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections. T55-127-010: Detector removal tool without pole. BCK-200B: Black detector covers for use with NP-100(A) only; box of 10. WCK-200B: White detector covers for use with NP-100(A) only; box of 10. NOTIFIER® and FireWarden® are registered trademarks of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved, unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. °I lb I I 1 .1 We cannot cover all specific applications or anticipate all requirements. ENGINEERING & MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2- DN-69950 • 2/11/2015 IN CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0028:0231 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: NotiflerOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev©honeywell.com DESIGN: Models NP-100, NP100R* and NP-100T photoelectric type smoke detectors. Model NP-lOOT has a 135°F supplement integral heat sensor which only assists in a fire situation. The purpose of this thermal circuitry is to increase the sensitivity of the detector. This thermal circuitry is NOT approved for use as a heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 24VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm control units and bases. All models are suitable for open areas and inside duct installations with air velocities between 0 -4000 FPM. *Models NP-100 and NP-100R are also approved for installations inside Notifier duct detector housing ND-200 (OSFM Listing No. 3242-0028:236) and System Sensor duct detector housing DNRW (OSFM Listing No. 3242-1653:210). Refer to listee's Installation Instruction Manual for details. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires, which smolder for hours before bursting into flames. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. XLF: 7272-0075:0194 *Rev. 01-27-10 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires June 30, 2017 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DN-6999:E Monitor Modules N MM-I 00(A), NMM-I OOP(A), NZM-I 00(A), and NDM.I00(A) for FireWarden Series NOTIFIER® hi Hnnin wall r. j • I %# I U %_ V V UI General Four different monitor modules are available for Notifier's FireWarden Series intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-con- tact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (NZM-100(A)). NMM-100(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. NMM-IOOP(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.65' (1.651 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the NMM-100P(A) to be mounted in a single-gang box behind the device it monitors. NZM-100(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. NDM-100(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (lDCs) at two separate, consecutive addresses in intelligent, two-wire sys- tems. LiteSpeedTM is a communication protocol that greatly increases the speed of communication between analog intel- ligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor- mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other communication protocols. NMM-100(A) Monitor Module Built-in type identification automatically identifies this device as a monitor module to the control panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry of address: 01 —99 on FireWarden-100- 2, 01 - 50 on FireWarden-50. LED flashes during normal operation and latches on steady to indicate alarm. The NMM-100(A) Monitor Module is intended for use in intel- ligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. NMM-100(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used NMM-100(A) (Type H) to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. NMM-100(A) OPERATION Each NMM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). NMM-100(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 375 pA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. NMM-I00P(A) Mini Monitor Module Built-in type identification automatically identifies this device as a monitor module to the panel. DN-6999:E • 07/30/2015— Page 1 of 4 Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. Tinned, stripped leads for ease of wiring. Direct-dial entry of address: 01-99 on FireWarden-100-2, 01 - 50 on FireWarden-50. 1415 0 1 ADDRESS 0 1 LOOP I 10 0~~8 7 6 8 7 TENS ONES I.— O Lu Q () -4 Lu • - 0 uco The NMM-100P(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The NMM-100P(A) is intended for use in intelli- gent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two- wire initiating device circuit for normally-open-contact fire alarm and security devices. NMM-100P(A) NMM-IOOP(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with spe- cial supervisory indication at the control panel. Monitored cir- cuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the circuit. NMM-IOOP(A) OPERATION Each NMM-100P(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). NMM-IOOP(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 pA, I communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 450 pA. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. NZM-100(A) Interface Module Supports compatible two-wire smoke detectors. Supervises IDC wiring and connection of external power source. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry entry of address:, 01 —99 on FireWarden- 100-2, 01 —50 on FireWarden-50. LED flashes during normal operation. LED latches steady to indicate alarm on command from control panel. The NZM-100(A) Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It trans- mits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. NZM-100(A) APPLICATIONS Use the NZM-100(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Cir- cuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across termi- nals 8 and 9 for Style D application. NZM-100(A) OPERATION Each NZM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). NZM-100(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 Ohms. Average operating current: 270 pA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K Ohms. External supply voltage (between Terminals TIO and T11): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. Page 2 of 4— DN-6999:E • 07/30/2015 NDM-100(A) Dual Monitor Module The NDM-100(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two- wire initiating device circuits (lDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel- controlled LED. NOTE: The NDM-100(A) provides two Style B (Class 8) /DC cir- cuits ONLY. Style 0 (Class A) /DC circuits are NOT supported in any application. NDM-100(A) SPEcIFIcATIONs Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 pA (LED flashing). Maximum IDC wiring resistance: 1,500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 pA EOL resistance: 47K Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25 (3.175 cm) deep. Mounts to a 4° (10.16 cm) square x 2.125" (5.398 cm) deep box. NDM-100(A) AUTOMATIC ADDRESSING The NDM-100(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the NDM-100(A) is set to address 26", then it will automati- cally assign itself to addresses "26" and '27". NOTE: "Ones" addresses on the NDM-100(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: Avoid duplicating addresses on the system. Installation NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and instal- lation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and reg- ulations. These modules are intended for power-limited wir- ing only. The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electri- cal box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S635. ULC: S635. FM Approved. CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM- 100); 7300-0028:0237 (NDM-100). MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); 227-03-E Vol. 3 (NDM-100). Product Line Information NOTE: "A" suffix indicates ULC-listed model NMM-100(A): Monitor module. NMM-IOOP(A): Monitor module, miniature. NZM-100(A): Monitor module, two-wire detectors. NDM-100(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 52304. DN-6999:E • 07/30/2015 - Page 3 of 4 Notifierlf and FireWardeniEi are registered trademarks and LiteSpeedTM and FireWatchTM are trademarks of Honeywell International Inc. 02015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I so 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENGINEERING MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information, contact Notifier. Phone: (203)484-7161, FAX: (203) 484-7118. www.notifier.com Page 4 of 4— ON-6999:E • 07/30/2015 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0028:0230 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: NotiflerOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com DESIGN: Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-100R and NC-100 control modules; and *NzM..100..6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 15-32 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7300-0075:0185 08-23-11 rev. mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires .June 30, 2017 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division dn-60383:A2 NC-1 OOR(A) NOTI Fl ER® Relay Module for 0 FireWarden Series Panels by Honeywell General The NC-100R(A) Addressable Relay Module provides NOTI- FIER's FireWarden Series intelligent control panels with two isolated sets of Form-C dry-contact outputs for activating a variety of auxiliary devices, such as fans, dampers, door hold- ers, control equipment, etc. Addressability allows the dry con- tact to be activated, either manually or through panel programming, on a select basis. Features Built-in type identification automatically identifies these devices to the control panel. Internal circuitry and relay powered directly by two-wire SLC loop. Integral LED blinks" green each time a communication is received from the control panel and turns on in steady when activated. High noise immunity (EMF/RFI). Wide viewing angle of LED. SEMS screws with clamping plates for wiring ease. Direct Decade entry of address: 01 - 99 with the FireWar- den-100-2(C) and 01 —50 with the FireWarden-50(C). Applications The NC-100R(A) may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire smoke detector power. Construction The face plate is made of off-white heat-resistant plastic. Controls include two rotary switches for direct-dial entry of address setting. The NC-100R(A) provides two Form-C dry contacts that switch together. Operation Each NC-1 OOR(A) uses one of the addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status. The LED blinks with each poll received. On command, it activates its internal relay. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel. NC-i OOR(A) Specifications Normal operating voltage: 15 to 32 VDC. Maximum SLC current draw: 6.5 mA (LED). Average operating current: 230 pA direct poll (CLIP mode), 255 pA group poll with LED flashing. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 490C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5' (11.43 cm) high x 4' (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4° (10.16 cm) square x 2.125" (5.398 mm) deep box. Relay Contact Ratings Load Description Application Maximum Current Voltage Rating Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9A Resistive Non-Coded 125 VAC 0.9 A Inductive (L/R=5ms) Coded 30 VDC 0.5 A Inductive (L/R=2ms) Coded 30 VDC 1.0 A Inductive (PF=0.35) Non-Coded 125 VAC 0.5 A dn-60383:A2 • 06/17/10 - Page 1 of 2 Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. ULIULC Listed: S635. CSFM approved: file 7300-0028:230. FM approved. MEA approved: file 72-01-E, Vol. 2. Product Line Information NC-i OOR: Intelligent addressable relay module. NC-i OORA: Intelligent addressable relay module, ULC listed model. SMB500: Optional surface-mount backbox. NOTE: For installation instructions, see document /56-2593-001 and refer to the SLC Wiring Manual, document 52304. NOTIFIER® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved, unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I so ooi We try to keep our product information up-to-date and accurate. , We cannot cover all specific applications or anticipate all requirements. ENGINEERING & MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the u.S.A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 - dn-60383:A2 • 06117/10 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. CATEGORY LISTEE: DESIGN: RATING: 7300-0028:0230 Page 1 of 1 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyevhoneywell.com Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-100R and NC-100 control modules; and NZM-100-6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. 15-32 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7300-0075:0185 08-23-11 rev. mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires June 30, 2017 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division E \ L 1 SPECTRIert S Indoor Selectable. Output Strobes and Horn Strobes for Ceiling Applications SpectrAlertO Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. Features Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela Field-selectable candela settings on ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and three volume selections Universal mounting plate for ceiling units Mounting plate shorting spring feature checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert devices Compatible with MDL3 sync module Listed for ceiling or wall mounting The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and RRE-printed devices, SpectrAlert Advance can meet virtually any application requirement. Like the entire SpectrAlert Advance product line, ceiling-mount strobes and horn strobes include a variety of features that increase their application versattity while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify instaiation, SpectrAlert Advance u:ilizes a universal mounting plate so you can mount theml to, a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easi y adapt devices to a suit a wide range of application requiremerts using field-selectable candala settings, automatic selection of 12- or 24-volt operation, ad a rotary switch for horn tones with three volume selections. Aaencv Listinas SIGNALING & <~> MEA LISTED APPROVED approved 7125-1663.0186 (indoor strobes) 7125-16530168 horn strobes. S401 1 )ch,rnes, horn strobes, horns) 3023572 M60452-05-E chime strobes) S5512 (strobes) 7135.1653:0189 horns, chimes) SpectrAlert Advance Specifications General SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync.Circuit° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts, Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model ______ listed to UL 1971 and shall be approved for fire protective service The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model ______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. 4 Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens) 6.8" diameter x 251 high (173 mm diameter x 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) (SBBCR, SBBCW) Notes: Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. F, 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS 10101 UL Current Draw Data 1Fj) 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Standard Candela Range 15 123 126 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 III DC Input 8-17.5 Volts 15 15/75 16-33 Volts 15 15175 30 75 - 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 DC Input 16-33 Volts 135 150 177 185 FWR Input 16-33 Volts 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Strobe Tones and Sound Output Data 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 Coded High 82 82 88 88 93 92 101 101 Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7, 8, and 9 are not available on 2-wire horn strobes. AV 0 S 10 10 1 I— 2.5" 6.8" a. SpectrAlert Advance Dimensions Ceiling-mount horn strobes Ceiling back box surface mount back box SpectrAlert Advance Ordering Information Ceiling Horn Strobes PC2R 2-Wire Horn Strobe, Standard Cd, Red PC2R-P 2-Wire Horn Strobe, Standard Cd, Red, Plain (no "FIRE") marking PC2RH 2-Wire Horn Strobe, High Cd, Red PC2W 2-Wire Horn Strobe, Standard Cd, White PC2W-P 2-Wire Horn Strobe, Standard Cd, White, Plain (no "FIRE") marking PO2W-SP 2-Wire Horn Strobe, Standard Cd, White, "Fuego" PC2WH 2-Wire Horn Strobe, High Cd, White PC2WH-P 2-Wire Horn Strobe, High Cd, White, Plain (no "FIRE") marking PC2WH-SP 2-Wire Horn Strobe, High Cd, White, "Fuego" PC4R 4-Wire Horn Strobe, Standard Cd, Red PC4RH 4-Wire Horn Strobe, High Cd, Red PC4W 4-Wire Horn Strobe, Standard Cd, White EM 12~- Ceiling Strobes SCR Strobe, Standard Cd, Red SCRH Strobe, High Cd, Red SOW Strobe, Standard Cd, White SOW-P Strobe, Standard Cd, White, Plain (no "Fire") marking SOWH Strobe, High Cd, White Accessories SBBOR Surface Mount Back Box, Ceiling, Red SBBOW Surface Mount Back Box, Ceiling, White Notes: All -P models have a plain housing (no "FIRE" marking on cover) All -SP models have "FUEGO" marking on cover "Standard Cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High Cd" refers to strobes that include 135, 150, 177, and 185 candela settings. @20 5 System Sensor, .5')'.cTEIV1 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice, Visit systemsensorcOrn for current product information, including the laest version of this data sheet. %•'_$ Phone: 800-SENSOR2 • Fax: 630-377-6495 A50010102 .03/1 5 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1653:0188 Page 1 of I CATEGORY: 7125 - FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhartsystemsensor.com DESIGN: Models CHSR and CHSW Chime/Strobes. Models P2R, P2W, P2RH and P2WH Horn/Strobes two-wire type, rectangular enclosure. Models PC2R, PC2W, PC2RH and PC2WH Horn/Strobes two-wire type, round enclosure Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure. Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure. All models are intended for indoor use only unless otherwise indicated. Models may be followed by the suffix "K" indicating indoor or outdoor use, or may be followed by suffix P' for plain housing with no lettering. K" suffix models are suitable for outdoor applications at temperatures from -40°F to +151°F (-40°C to +66°C) and are rated NEMA 4X when used with the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall), SA-WBBC (Ceiling) and *SA..WBBCW (Ceiling). Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Standard Horn/Strobes and Chime/Strobes 8 - 17.5 or 16-33 VDC/FWR Hi CD Horn/Strobes 16-33 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling appliances and equipment for the hearing impaired applications when used with separately listed compatible fire alarm control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall mount. Chime section is suitable for private mode and indoor use only. Horn/Strobes or chime/strobes* can generate the distinctive three-pulse audible Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2010 Edition. Refer to listee's Installation Instruction Manual for details. *Corrected 12-15-11 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires June 30, 2017 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Outdoor Selectable. Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. Features Weatherproof per NEMA 4X, 1P56 Listed to UL 1638 (strobe) and UL 464 (horn) Compatible with System Sensor synchronization protocol and legacy SpectrAlert products Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela Rotary switch for horn tone and three volume selections Horn rated at 88+ dBA at 16 volts Rated from —40°F to 151°F Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed Plug-in design with minimal intrusion into the back box Tamper-resistant construction Listed for ceiling or wall mounting Aaencv Listinas SIGNALING <~> wl_~"" FM MEA 300-1 653187 (outdoor strobes) LISTED S401 1 (Chimes, ross strobes, sores) APPROVED approved 7125-1653,188 (horn strobes, cheese strobes) S3593 (outdoor and alert strobes) 3023572 M6A452-05.E 7135.1653:189 (horns, chimes) SpectrAlert Advance offes the broadest I ne of outdoor horns, strobes, and horn strobes in toe industry. Witri white or red plastic housings, wall or ceiling mounting cptions, ard plain or FIRE-printed devices, SpectrAlert Advance ,an meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from —40°F to 15.1°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes fcr wall applications include a variety of features that increase application flexib lily and simplify installation. First, field-selectable settings, inducing candela, aJornatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance de'ices use a urieiersa1 mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installas can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are noun:ed, all SpectAlert Advance devices utilize a 011g-in desigr with a single' ap'ured screw to speed installation and virtually eliminate cosiJ ground faults. Outdoor devices shp with weatherproof plastc back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic bac< boxes feature removable side flarges and improved resistance to saltwater corrosion. Knock-outs located on the back el mirate the need to drill holes for screw-in mounting. Plastic and meta weatherproof back boxes come with 3%-inch top a,-:d bcttom conduit entries and 3,4-inch knock-outs at the back. A screw-in NPT plug ith an 0-ring gasket for a watertight sea is include': with each ba: k box. SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync.Circuie° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between -40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Operating Temperature -40°F to 151°F (-40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/F\NR or regulated 24 DC/FWR1 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6-L x 47"W x 2.5"D (142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D (142 mm Lx 119 mm x 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7"L x 5.1"W x 2.0"D(145 mm Lx 130 mm W x 51 mm 0) Notes: Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs F, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDSO1 201 UL Current Draw Data iTiftFJt.: 1 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard Candela Range High Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 8-17.5 Volts 16-33 Volts Temporal High 57 55 69 75 Temporal Medium 44 49 56 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures listed n . gra W. raT. I candela ratings must be reduced in accordance with 8-17.5 16-33 24-Volt Nominal this table. ..- . Switch Sound Volts Volts Reverberant Anechoic I.-1Tn'.1vIl1j .1 D, + 14P fl(' FWR fli' (' fl FWR fl(' FWR Listed Candela Candela rating at —40°F 15 Do not use below 32°F 30 15/75 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- High 82 82 88 88 93 92 100 100 Temporal 5 Non- Medium 78 78 85 85 90 90 98 98 Temporal 6 Non- Low 75 75 81 81 88 84 96 92 Temporal 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7, 8, and 9 are not available on 2-wire horn strobe. AvDS01201 Wall-Mount Horn Strobes rproof Back Box SpectrAlert Advance Diagrams Wail-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Wall Horn Strobes P2RK*t 2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*t 2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*f 2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*t 2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*t Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*i Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*t Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*t Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRKt Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box Notes: * Add "-F" to model number for plain housing (no "FIRE" marking on cover), e.g., P2RK-P, t Add "-R" to model number for weatherproof replacement device (no back box included), Only for use with weatherproof outdoor flush mounting plate, WTP and WTPW "Standard cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd" refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. f"I SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 Product specrtrcahOns subje020 ct to12 System Sensor change sithout notice. Visit systemsensor.corn S'Ei'I.ScI?' Phone' 800-SE NSOR2 • Fax' 630-377-6495 br current product information, including the latest version 01 this data sheet. AVDS01201 .3/12 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1653:0188 Page 1 of 1 CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Intl lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhart@systemsensor.com DESIGN: Models CHSR and CHSW Chime/Strobes. Models P2R, P2W, P2RH and P2WH Horn/Strobes two-wire type, rectangular enclosure. Models PC2R, PC2W, PC2RH and PC2WH Horn/Strobes two-wire type, round enclosure Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure. Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure. All models are intended for indoor use only unless otherwise indicated. Models may be followed by the suffix "K" indicating indoor or outdoor use, or may be followed by suffix "P' for plain housing with no lettering. "K" suffix models are suitable for outdoor applications at temperatures from -40°F to +151°F (-40°C to +66°C) and are rated NEMA 4X when used with the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall), SA-WBBC (Ceiling) and *SAWBBCW (Ceiling). Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Standard Horn/Strobes and Chime/Strobes 8 - 17.5 or 16-33 VDC/FWR Hi CD Horn/Strobes 16-33 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model number, electrical rating, and UL label. APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling applianqes and equipment for the hearing impaired applications when used with separately listed compatible fire alarm control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall mount. Chime section is suitable for private mode and indoor use only. Horn/Strobes or chimelstrobes* can generate the distinctive three-pulse audible Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2010 Edition. Refer to listee's Installation Instruction Manual for details. *Corrected 12-15-11 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2016 Listing Expires June 30, 2017 Authorized By: DAVID CASTILL.O, Program Coordinator Fire Engineering Division