7/27/22,1:27 PM AS160057 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 5115 CARLSBAD BL
Permit Type: SPRINK
Parcel No: 2100320700
Lot #: 0
Permit No: AS160057
Status: ISSUED
Applied 3/3/2016
Approved: 4/19/2016
Reference No.: Issued: 4/19/2016
PC #: Inspector:
Project Title: J SQUARED CONDOS CONDO: INSTALL NEW FIRE
PROTECITON SYSTEM IN NEW RESIDENCE. 2,162 SF LIV, 438
SF GARAGE, 21 SF PATIO, 173 SF DECK
Fees ($) Add'I Fees Total Balance($)
460.5 -- 0 460.5 0
about:blank 1/1
[o03§aXGfiV1Cu7%GF0 Lubrizol
FIRE SPRINKLER SYSTEMS
BlazeMaster® Fire Sprinkler Systems AS160057_5115 Carlsbad BL
Submittal Specification - North America
A5160058_5117 Carlsbad BI
SCOPE:
This specification covers the material requirements for BlazeMaster® CPVC SDR 13.5 pipe and
socket fittings. Both the pipe and fittings are manufactured in North America and meet or
exceed the requirements set forth by the appropriate ASTM standard (F437, F438, F439, F442),
and NSF/ANSI Standards 14 and 61.
CPVC MATERIALS:
BlazeMaster CPVC pipe and fittings are extruded/molded from Lubrizol CPVC compounds. The
pipe compound meets cell class 23547 and the fitting compound meets cell class 24447 as
defined by ASTM Dl 784. Both the pipe and the fitting compounds are certified by NSF
International for use with potable water.
As manufactured by Tyco Fire Protection Products, The Viking Corporation, Georg Fischer
Harvel LLC., Nibco Inc. and IPEX Inc.
DIMENSIONS AND PROPERTIES:
Dimensions, tolerances and physical properties meet or exceed the requirements of the
appropriate ASTM standard (F437, F438, F439, F442).
COMPATIBILITY:
Ancillary products (including, but not limited to fire stops, thread sealants, leak detectors, etc.)
coming into contact with pipe and fittings must be chemically compatible with BlazeMaster
CPVC pipe and fittings (reference the Lubrizol FBCTM System Compatible Program).
SOLVENT WELDING:
All socket type joints shall be assembled employing solvent cements that meet or exceed the
requirements of ASTM F493. The standard practice for safe handling of solvent cements shall
be in accordance with ASTM F402. Solvent cement shall be certified by NSF International for
use with potable water, and approved by the BlazeMaster pipe and fittings manufacturers.
BASIC USE:
BlazeMaster Pipe and fittings are Listed by UL for use in Light Hazard Occupancies as defined
by NFPA 13,13R and 13D.
BlazeMaster is permitted to protect ordinary hazard rooms of otherwise light hazard
occupancies where the room does not exceed 400 square feet (i.e. Laundry room) as defined in
NFPA 13 and NFPA 13R.
MARKING:
The marking on the CPVC pipe and fittings shall meet the requirements of UL 1821 and the
appropriate ASTM standard (F437, F438, F439, F442), and state the pipe/fitting manufacture's
name or trademark, the material designation, the size, the NSF mark for potable water and the
ASTM designation ASTM (F437, F438, F439, F442).
BlazeMaster® is a registered trademark of The Lubrizol Corporation. June 2015.
JB FIRE PROTECTION
P0 BOX 1111
FALLBROOK,CA 92028
HYDRAULIC CALCULATIONS
FOR
J SQUARED CONDOS
5115-5117 CARLSBAD BLVD CARLSBAD, CA 92008
FILE NUMBER:
DATE: MAR 25, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: NFPA 13D RESIDENTIAL
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 2 REMOTE HEADS
COVERAGE PER SPRINKLER: 16 X 16
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 26.7 gpm
TOTAL WATER REQUIRED (including hose) : 31.7 gpm
FLOW AND PRESSURE (@ BOR) : 26.7gpm @ 33.5psi
SPRINKLER ORIFICE SIZE: 7/16" inch
NAME OF CONTRACTOR: JB FIRE PROTECTION
DESIGN/LAYOUT BY: TL
AUTHORITY HAVING JURISDICTION: NORTH COUNTY FIRE
CONTRACTOR CERTIFICATION NUMBER: 911081
*STATIC PRESSURE REDUCED BY 10% AT INPUT
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 50100268
HRS SYSTEMS, INC.
AS160057_5115 Carlsbad BL
A5160058_5117 Carlsbad BL
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
C:\PROGRAM FILES\HRS SYSTEMS\HASS\CONDOS. SDF DATE: 3/25/2016
JOB TITLE: condo
WATER SUPPLY DATA
SOURCE STATIC
NODE PRESS.
TAG (PSI)
SOURCE (N/A)
RESID. FLOW
PRESS. @
(PSI) (GPM)
67.5 (N/A)
AVAIL. TOTAL REQD
PRESS. @ DEMAND PRESS.
(PSI) (GPM) (PSI)
67.5 31.7 53.9
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.7 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.7 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION
(FT)
1 24.0
2 27.2
3 28.5
4 18.0
5 18.0
6 18.0
7 8.5
TR 5.0
Fl 4.6
F2 4.6
BR 4.8
DS 1.0
A -3.0
Ml -3.0
M2 -3.0
SOURCE -3.0
NODE TYPE PRESSURE DISCHARGE
(PSI) (GPM)
K= 4.90 7.8 13.7
K= 4.90 7.0 13.0
- - - - 8.3 - - -
- - - - 14.6 - - -
- - - - 15.8 - - -
- - - - 21.8 - - -
- - - - 27.6 - - -
- - - - 30.2 - - -
- - - - 30.5 - - -
- - - - 33.5 - - -
- - - - 33.5 - - -
HOSE STREAM 36.5 5.0
- - - - 39.7 - - -
- - - - 40.6 - - -
- - - - 44.6 - - -
SOURCE 53.9 31.7
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 3/25/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS\CONDOS.SDF
JOB TITLE: condo
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -13.7 1.101 PL 13.50 PF 0.6
1 24.0 4.9 7.8 13.7 4.6 150 FTG L BE -1.4
2 27.2 4.9 7.0 13.0 0.034 TL 18.50 PV
Pipe: 2 -26.7 1.101 PL 5.58 PF 1.8
2 27.2 4.9 7.0 13.0 9.0 150 FTG 2L PE -0.6
3 28.5 0.0 8.3 0.0 0.116 TL 15.58 PV
Pipe: 3 -26.7 1.101 PL 10.50 PP 1.8
3 28.5 0.0 8.3 0.0 9.0 150 FTG L PE 4.5
4 18.0 0.0 14.6 0.0 0.116 TL 15.50 By
Pipe: 4 -26.7 1.101 PL 5.25 PP 1.2
4 18.0 0.0 14.6 0.0 9.0 150 FTG T BE 0.0
5 18.0 0.0 15.8 0.0 0.116 TL 10.25 PV
Pipe: 5 -26.7 1.101 PL 37.17 PP 6.0
5 18.0 0.0 15.8 0.0 9.0 150 FTG 3L BE 0.0
6 18.0 0.0 21.8 0.0 0.116 TL 52.17 PV
Pipe: 6 -26.7 1.101 PL 9.50 PP 1.7
6 18.0 0.0 21.8 0.0 9.0 150 FTG L PE 4.1
7 8.5 0.0 27.6 0.0 0.116 TL 14.50 By
Pipe: 7 -26.7 1.101 PL 4.00 PP 1.0
7 8.5 0.0 27.6 0.0 9.0 150 FTG L PE 1.5
TR 5.0 0.0 30.2 0.0 0.116 TL 9.00 By
Pipe: 7A -26.7 1.049 PL 0.42 PP 0.1
TR 5.0 0.0 30.2 0.0 9.9 120 FTG ---- BE 0.2
Fl 4.6 0.0 30.5 0.0 0.222 TL 0.42 By
Pipe: 7B FIXED PRESSURE LOSS DEVICE
P2 4.6 0.0 33.5 0.0 3.0 psi, 26.7 gpm
Fl 4.6 0.0 30.5 0.0
Pipe: 8 -26.7 1.049 PL 0.42 PP 0.1
P2 4.6 0.0 33.5 0.0 9.9 120 FTG ---- BE -0.1
BR 4.8 0.0 33.5 0.0 0.222 TL 0.42 PV
Pipe: 9 -26.7 1.101 PL 3.83 PP 1.4
BR 4.8 0.0 33.5 0.0 9.0 150 FTG C BE 1.7
DS 1.0 H.S. 36.5 5.0 0.116 TL 11.83 By
Pipe: 10 -31.7 1.101 PL 4.00 PP 1.4
DS 1.0 H.S. 36.5 5.0 10.7 150 FTG L BE 1.7
A -3.0 0.0 39.7 0.0 0.159 TL 9.00 By
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 3/25/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS\CONDOS.SDF
JOB TITLE: condo
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 11 -31.7 1.598 PL 29.42 PF 0.9
A -3.0 0.0 39.7 0.0 5.1 150 FTG L PE 0.0
Ml -3.0 0.0 40.6 0.0 0.026 TL 36.42 PV
Pipe: 12 FIXED PRESSURE LOSS DEVICE
M2 -3.0 0.0 44.6 0.0 4.0 psi, 31.7 gpm
Ml -3.0 0.0 40.6 0.0
Pipe: 13 -31.7 0.995 PL 21.50 PF 9.3
M2 -3.0 0.0 44.6 0.0 13.1 150 FTG 4ET PE 0.0
SOURCE -3.0 SRCE 53.9 (N/A) 0.261 TL 35.50 PV
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 50100268 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.007 gpm and a maximum
imbalance at any node of 0.100 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 13.1 ft/sec at pipe 13.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node SOURCE under full flow conditions is
67.50 psi compared to the minimum required pressure of 20.00 psi.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 3/25/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS\CONDOS.SDF
JOB TITLE: condo
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEii ChkVlv BfyViv GatVlv AimChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E L T R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 5.00 5.00 1.00 1.00 8.00 2.00
1.598 2.00 7.00 8.00 1.00 1.00 14.00 3.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Eli TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
I&wi1
70.0
G
A
U 60.0
G
E
50.0 P
R
E
S 40.0
S
30 .0
p 20.0
S
j
10.0
-14.
WATER SUPPLY ANALYSIS
20 30 40 50 60 70 80 90 100
FLOW (GPM )
(Note: Dashed Lines indicate extrapolated values from Test Results)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 3/25/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS\CONDOS.SDF
JOB TITLE: condo
WATER SUPPLY CURVE
72+
66+
60+
54X
P 48+
R
E I
S I
S 42+
U
R
E
36+
P
S
I 30+
24+
18+
12+ LEGEND
I X = Required Water Supply
I 53.88 psi @ 31.7 gpm
6+
I 0 = Available Water Supply
67.50 psi 8 31.7 gpm
'I
0++-+---+----+-----+ ------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)