HomeMy WebLinkAbout417 CARLSBAD VILLAGE DR; ; FPC2016-0018; Permit_____ 1ft Liii1 Print Date: 07/27/2022 Job Address: 417 CARLSBAD VILLAGE DR, CARLSBAD, CA 92008 Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers Parcel #: 2032960700 Track #: Valuation: $451,610.00 Lot #: Occupancy Group: Project #: #of Dwelling Units: Plan #: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check#: Plan Check #: Permit No: FPC2016-0018 Status: Closed - Finaled Applied: 11/22/2016 Issued: 06/13/2017 Finaled Close Out: 03/25/2021 Final Inspection: INSPECTOR: Fieri, Dominic Project Title: Description: BLUE WATER GRILL -SPRINKLER TI -94 HEADS (REVISED) TI -COMM BLUE WATER: 3,346 SF TI RESTAURANT TO SAME FPContractor: VANGUARD FIRE PROTECTION INC 417 CARLSBAD VILLAGE DR CARLSBAD, CA 92008-2302 (760) 727-8540 FEE AMOUNT FIRE Expedited Plan Review Per Hour - Office Hours $132.00 FIRE NFPA 13 or 13R System 7 - 100 heads $536.00 Total Fees: $668.00 Total Payments To Date: $668.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov Ff=~ -r- cg ... Fire Protection by Computer Design VANGUARD FIRE PROTECTION P. 0. Box 1300 Vista, CA 92085 760-727-8540 Job Name : Blue Water Grill Building Location : 417 CARLSBAD VILLAGE DR., CARLSBAD CA System : AREA #1 Contract Data File : Blue Water GriII.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 VANGUARD FIRE PROTECTION Blue Water Grill HYDRAULIC CALCULATIONS for Project name: Blue Water Grill Location: 417 CARLSBAD VILLAGE DR., CARLSBAD CA Drawing no: Date: 8-26-17 Design Remote area number: AREA #1 Remote area location: KITCHEN Occupancy classification: ORD HAZ I Density: .15 - Gpm/SqFt Area of application: 900 - SqFt Coverage per sprinkler: 130- SqFt Type of sprinklers calculated: 5.6K QR-SSP No. of sprinklers calculated: 11 In-rack demand: N/A - GPM Hose streams: 250 - GPM Total water required (including hose streams): 484.834 - GPM Type of system: WET Volume of dry or preaction system: N/A - Gal Page 1 Date 5-13-17 @ 81.6888-Psi Water supply information Date: 7-17-16 Location: HYDRANT DIRECTLY ADJACENT TO SITE Source: CARLSBAD FIRE DEPARTMENT Name of contractor: VANGUARD FIRE PROTECTION Address: P. 0. Box 1300 I I Vista, CA 92085 Phone number: 760-727-8540 Name of designer: S. B. Authority ha ving jurisdiction: CARLSBAD FIRE DEPARTMENT Notes: (Include peaking information or gridded systems here.) A 10% REDUCTION TAKEN PRIOR TO DAT ENTRY Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 VVdLI OUJpI %-,Ul vw I#) VANGUARD FIRE PROTECTION Page 2 Blue Water Grill Date 5-13-17 City Water Supply: Demand: Cl - Static Pressure : 91 Dl - Elevation : 5.847 C2 - Residual Pressure: 51 D2 - System Flow : 233.984 C2 - Residual Flow : 3175 D2 - System Pressure : 69.898 Hose ( Demand) : 250 D3 - System Demand : 483.984 Safety Margin : 19.869 150 - 140 130 p120 R° E10° ci 90 80 U 70 R 60 C2 E ° 40 30 20 ___ 10 -- ____ _____ _______ .Qi_ ________ ___________ . 400 800 1200 1600 2000 2400 2800 3200 3600 FLOW (NA 1.85) Comouter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087 Flow Diagram VANGUARD FIRE PROTECTION Page 3 Blue Water Grill Date 5-13-17 19.7 SI -. A 19.9 S2 4-B 1 343 194 S3 - C 14.7 194 S4 D t I 4.9 19. S5 E t I 24.4 19. S6 4-F 1 144.1 20. ST - G t 164.5 21. S8 4-H t I 85.6 22. S9 4-I 25.7 Sb4- J 26 SIIi- J 19.7 34.3 4.9 44.1 85.6 42.9 A 4-bO-,B -.0 _,D 4-E 4-F +-G 4-H (-I II-.I2 54.2 14.7 24.4 64.5 108.3 151.3 II - MI I 42.9 , 75.4 I2-+J -+13 23. I 50.3 32.5 I 12 +-14 I 50. 73.4 I 82.7 234 234 234 10 .- 13 +-14 +- Ml - TR - BR - BFI BF2+- UG4- SRC 50.3 234 234 234 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 ILL11 19b USU OUItIIIIdI VANGUARD FIRE PROTECTION Page 4 Blue Water Grill Date 5-13-17 Fitting Legend Abbrev. Name % % 1 1% 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPAI39O' Standard Elbow I 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 II 13 T NFPA139O' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with * The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Comouter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087 Pressure I Flow Summary - STANDARD VANGUARD FIRE PROTECTION Page 5 Blue Water Grill Date 5-13-17 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. Si 9.5 5.6 12.36 na 19.68 0.15 130 7.0 S2 9.5 5.6 12.63 na 19.91 0.15 130 7.0 S3 9.5 5.6 12.28 na 19.62 0.15 130 7.0 S4 9.5 5.6 12.21 na 19.56 0.15 130 7.0 S5 9.5 5.6 12.13 na 19.5 0.15 130 7.0 S6 9.5 5.6 12.35 na 19.68 0.15 130 7.0 S7 9.5 5.6 13.27 na 20.4 0.15 130 7.0 S8 9.5 5.6 14.19 na 21.09 0.15 130 7.0 S9 9.5 5.6 16.5 na 22.75 0.15 130 7.0 SIO 9.5 5.6 21.13 na 25.74 0.15 130 7.0 Sli 9.5 5.6 21.63 na 26.04 0.15 130 7.0 A 10.0 13.13 na 10 13.67 13.5 na B 13.67 12.62 na C 13.67 12.22 na D 13.67 12.14 na E 13.67 12.15 na F 13.67 12.4 na G 13.67 13.35 na H 13.67 14.38 na 13.67 17.0 na 11 10.0 32.91 na 12 13.67 27.98 na J 13.67 23.12 na 13 13.67 22.29 na 14 13.67 28.59 na Mi 12.0 57.01 na TR 7.5 63.11 na BR 2.5 65.83 na BF1 -4.0 69.01 na BF2 -4.0 69.49 na UG -4.0 69.82 na SRC -4.0 69.9 na 250.0 The maximum velocity is 23 and it occurs in the pipe between nodes 11 and Ml Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams VANGUARD FIRE PROTECTION Page 6 Blue Water Grill Date 5-13-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ** Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn SI 19.68 1.08 iT 5.762 1.000 12.356 K Factor = 5.60 to 120.0 1E 2.305 8.067 -0.217 A 19.68 0.1096 0.0 9.067 0.994 Vel = 6.89 0.0 19.68 13.133 K Factor = 5.43 S2 19.91 1.08 2T 11.524 4.500 12.635 K Factor= 5.60 to 120.0 0.0 11.524 -1.806 B 19.91 0.1119 0.0 16.024 1.793 Vel= 6.97 0.0 19.91 12.622 K Factor = 5.60 S3 19.62 1.08 2T 11.524 4.500 12.280 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 C 19.62 0.1090 0.0 16.024 1.747 VeI= 6.87 0.0 19.62 12.221 K Factor = 5.61 S4 19.57 1.08 2T 11.524 4.500 12.206 K Factor= 5.60 to 120.0 0.0 11.524 -1.806 D 19.57 0.1085 0.0 16.024 1.738 Vel= 6.85 0.0 19.57 12.138 K Factor = 5.62 S5 19.50 1.08 2T 11.524 5.500 12.125 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 E 19.5 0.1078 0.0 17.024 1.835 Vel= 6.83 0.0 19.50 12.154 K Factor = 5.59 S6 19.68 1.08 2T 11.524 5.500 12.346 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 F 19.68 0.1096 0.0 17.024 1.865 Vel = 6.89 0.0 19.68 12.405 K Factor = 5.59 S7 20.40 1.08 21 11.524 4.500 13.274 K Factor= 5.60 to 120.0 0.0 11.524 -1.806 G 20.4 0.1172 0.0 16.024 1.878 Vel = 7.14 0.0 20.40 13.346 K Factor = 5.58 S8 21.09 1.08 2T 11.524 4.500 14.188 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 H 21.09 0.1246 0.0 16.024 1.997 Vel= 7.39 0.0 21.09 14.379 K Factor = 5.56 S9 22.75 1.08 2T 11.524 4.500 16.505 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 22.75 0.1433 0.0 16.024 2.296 Vel = 7.97 0.0 22.75 16.995 K Factor = 5.52 S10 25.74 1.08 2T 11.524 9.580 21.127 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 J 25.74 0.1801 0.0 21.104 3.801 Vel= 9.01 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams VANGUARD FIRE PROTECTION Page 7 Blue Water Grill Date 5-13-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. UC" or Ftng's Pe Pv ***** Notes *** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 25.74 23.122 K Factor = 5.35 SI 1 26.04 1.08 2T 11.524 6.420 21.626 K Factor = 5.60 to 120.0 0.0 11.524 -1.806 J 26.04 0.1840 0.0 17.944 3.302 VeI= 9.12 0.0 26.04 23.122 K Factor = 5.42 A 19.68 1.08 2E 4.61 13.250 13.133 to 120.0 0.0 4.610 -1.589 10 19.68 0.1096 0.0 17.860 1.958 Vel = 6.89 10 -73.87 1.639 IT 8.727 0.670 13.502 to 120.0 0.0 8.727 0.0 B -54.19 -0.0936 0.0 9.397 -0.880 Vet = 8.24 B 19.90 1.639 0.0 10.000 12.622 to 120.0 0.0 0.0 0.0 C -34.29 -0.0401 0.0 10.000 -0.401 Vel = 5.21 C 19.63 1.639 0.0 10.000 12.221 to 120.0 0.0 0.0 0.0 D -14.66 -0.0083 0.0 10.000 -0.083 Vel = 2.23 0 19.56 1.639 IT 8.727 6.000 12.138 to 120.0 0.0 8.727 0.0 E 4.9 0.0011 0.0 14.727 0.016 VeI= 0.75 E 19.50 1.639 IT 8.727 3.000 12.154 to 120.0 0.0 8.727 0.0 F 24.4 0.0214 0.0 11.727 0.251 Vel = 3.71 F 19.68 1.639 IT 8.727 6.000 12.405 to 120.0 0.0 8.727 0.0 G 44.08 0.0639 0.0 14.727 0.941 Vet = 6.70 G 20.40 1.639 0.0 8.000 13.346 to 120.0 0.0 0.0 0.0 H 64.48 0.1291 0.0 8.000 1.033 Vel = 9.81 H 21.10 1.639 0.0 12.000 14.379 to 120.0 0.0 0.0 0.0 85.58 0.2180 0.0 12.000 2.616 Vel = 13.01 22.75 1.639 2E 8.727 33.750 16.995 to 120.0 0.0 8.727 1.589 II 108.33 0.3372 0.0 42.477 14.325 VeI= 16.47 11 -151.26 1.639 2T 17.453 28.670 32.909 to 120.0 2E 8.727 28.180 -1.589 12 42.93 -0.0609 0.0 54.850 -3.338 Vel = 6.53 0.0 -42.93 27.982 K Factor= -8.12 II 151.25 1.639 1E 4.363 26.830 32.909 to 120.0 IT 8.727 13.090 -0.866 MI 151.25 0.6253 0.0 39.920 24.963 Vel = 23.00 0.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 final Calculations - Hazen-Williams VANGUARD FIRE PROTECTION Page 8 Blue Water Grill Date 5-13-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. UCH or Ftng's Pe Pv *** Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 151.25 57.006 K Factor= 20.03 12 -75.40 1.639 0.0 28.170 27.982 to 120.0 0.0 0.0 0.0 J -75.4 -0.1725 0.0 28.170 -4.860 Vel= 11.47 J 51.78 1.639 1E 4.363 28.000 23.122 to 120.0 IT 8.727 13.090 0.0 13 -23.62 -0.0202 0.0 41.090 -0.828 Vel = 3.59 0.0 -23.62 22.294 K Factor= -5.00 12 32.48 1.639 IT 8.727 8.080 27.982 to 120.0 0.0 8.727 0.0 14 32.48 0.0363 0.0 16.807 0.610 Vet = 4.94 0.0 32.48 28.592 K Factor = 6.07 10 73.88 1.639 3T 26.18 26.750 13.502 to 120.0 0.0 26.180 0.0 13 73.88 0.1661 0.0 52.930 8.792 Vet = 11.23 13 -23.63 1.639 3E 13.09 64.250 22.294 to 120.0 0.0 13.090 0.0 14 50.25 0.0814 0.0 77.340 6.298 Vel = 7.64 14 32.48 1.639 13E 56.723 69.750 28.592 to 120.0 IT 8.727 65.450 0.723 Ml 82.73 0.2048 0.0 135.200 27.691 Vel = 12.58 Ml 151.25 2.703 2E 18.651 15.250 57.006 to 120.0 0.0 18.651 1.949 TR 233.98 0.1226 0.0 33.901 4.156 Vel = 13.08 TR 0.0 2.703 0.0 4.500 63.111 to 120.0 0.0 0.0 2.166 BR 233.98 0.1227 0.0 4.500 0.552 Vet = 13.08 BR 0.0 4.1 IT 29.067 1.080 65.829 to 140.0 0.0 29.067 2.815 BFI 233.98 0.0121 0.0 30.147 0.365 Vel = 5.69 BFI 0.0 4.1 2E 29.067 11.000 69.009 to 140.0 0.0 29.067 0.0 BF2 233.98 0.0121 0.0 40.067 0.486 Vel = 5.69 BF2 0.0 4.23 0.0 35.000 69.495 to 150.0 0.0 0.0 0.0 UG 233.98 0.0092 0.0 35.000 0.321 Vel = 5.34 UG 0.0 6.09 IG 4.625 2.500 69.816 to 150.0 IT 46.249 50.874 0.0 SRC 233.98 0.0015 0.0 53.374 0.082 Vet = 2.58 250.00 Qa = 250.00 483.98 69.898 K Factor= 57.89 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Conventional Recessed Pendent/Fl/F2 * Recessed PendentJFP XLH Recessed Pendent l`1/1`2 Pendent Vertical Sidewall Horizontal Sidewall Recessed Horizontal Sidewall - Concealed Pendent Upright XLH Upright XLH Pendent Bulletin 014 Rev. N Model Fl FR Series Quick Response Glass Bulb Sprinklers ou Model Fl FR56 Sprinkler Types Standard Spray Upright Standard Spray Pendent Conventional Upright/Pendent Vertical Sidewall Horizontal Sidewall Model Fl FR56 Recessed Sprinkler Types Standard Spray Pendent Horizontal Sidewall Model Fl FR56 Concealed Sprinkler Types Standard Spray Pendent Model Fl FR42, Fl FRXLH & Fl FR28 Sprinkler Types Standard Spray Upright Standard Spray Pendent Model Fl FR40 Sprinkler Types Standard Spray Pendent Model Fl FR42, Fl FR40, Fl FRXLH & Fl FR28 Recessed Sprinkler Types Standard Spray Pendent Model F1FR56LL & F1FR42LL NSF Certified Low Lead Sprinkler Types Standard Spray Pendent with less than 0.25% Lead Content Listing & Approvals The following organizations provide Listings or Approvals for various Model Fl FR series sprinklers. See the Design and Installation table in this Bulletin for information on specific listings and approvals applicable to each sprin- k!r Underwriters Laboratories Inc. and Certified for Product Description Canada (cULus). Reliable Model F1FR series sprinklers FM Approvals (FM) are quick-response automatic sprin- Loss Prevention Certification Board (LPCB) kiers with a glass bulb thermal element. VcIS Schadenverhutung GmbH (VdS) Model F1FR series sprinklers are Stan- F, MR.P rrtifd tr, MP/AMi t nrkrrI Al Annov r, dard Spray sprinklers, with the excep- tion of the Model F1FR56 Conventional XLH Recessed (NSF) 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- sprinkler which is an Old-style/Conven- Pendent FP tional sprinkler. CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) The Model F1FR Series automatic sprinklers utilize a 3.0 (EC) mm frangible glass bulb. These sprinklers have demonstrat- UL Listing Category ed response times in laboratory tests which are five to ten Sprinklers, Automatic & Open (VNlV) times faster than standard response sprinklers. This quick Quick Response Sprinkler response enables the Model El FR Series sprinklers to apply water to a fire faster than standard-response sprinklers of the same temperature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely man- ufactured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid in boffi the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the Liq- uid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distrib- ute the discharging water. Model Fl FR Series sprinklers provide a wide range of op- tions where quick-response, glass bulb sprinklers are used: Pendent, recessed pendent, upright, horizontal side- wall, and vertical sidewall deflectors K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 metric), and 5.6 (80 metric) Flush, recessed, and concealed installations See the Design and Installation Information table in this Bulletin for information on the approvals and availability of specific Model Fl FR series sprinkler configurations. Model El FR Recessed Pendent and Recessed Horizon- tal Sidewall sprinklers are required to be used with Reliable Model Fl F2, or FP recessed escutcheons. See the Re- cessed Escutcheon Data table in this Bulletin for listing and approval information with each specific Model Fl FR series sprinkler. Model Fl and F2 recessed escutcheons, shown in Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch (19mm) and 1/2-inch (12.7mm) of adjustment, respectively. Model FP recessed escutcheons, shown in Fig. 2, provide a 1/2-inch (12.7mm) threaded adjustment. Model El FR56 Concealed Pendent and Model El FR56LL Concealed Pendent sprinklers are required to be used with Model CCP cover plates. A standard profile Model CCP cov- er plate is available that provides up to 1/2-inch (12.7mm) of cover plate adjustment. In addition, a low profile Model CCP cover plate is also available that provides up to 5/16-inch (8.0mm) of cover plate adjustment. See the Design and In- stallation Information and Listed and Approved Temperature Ratings tables in this Bulletin for further information on ap- proved cover plate options. Application Model F1FR Series sprinklers are intended for use in accordance with NFPA 13, FM Property Loss Prevention Data Sheets, and the requirements of the Authority Hav- ing Jurisdiction. Care must be exercised that the k-factor, temperature rating, deflector style, and sprinkler type are in accordance with the requirements of the applicable design and installation standards. In addition, Model El ER Series sprinklers must be used in accordance with their listings and approvals, as well as the information provided in this Bulletin. Installation Glass bulb sprinklers have orange bulb protectors or pro- tective caps to minimize bulb damage during shipping, han- dling and installation. Reliable sprinkler installation wrench- es are designed to install sprinklers with bulb protectors in place. Remove the bulb protector at the time when the sprin- kler system is placed in service for fire protection. Removal of the bulb protector before this time may leave the bulb vul- nerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Model El FR Series sprinklers must be installed with the Reliable sprinkler installation wrench identified in the Design and Installation Information table in this Bulletin. Any other wrench may damage the sprinkler. A leak tight sprinkler joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not tighten sprinklers over the maximum recommended installation torque. Exceeding the maximum recommended installation torque may cause leakage or impairment of the sprinkler. Recessed Sprinklers Model El FR Series Recessed sprinklers are to be installed as shown in Fig. 1, Fig. 2, or Fig. 3, as applicable to the spe- cific model being installed. The Recessed Escutcheon Data table in the Bulletin identifies the only recessed escutcheons that are permitted to be used with each Model Fl FR Series Recessed sprinkler. The use of any other recessed escutch- eon will void all approvals and negate all warranties. Concealed Sprinklers Model El ER Series Concealed Pendent sprinklers are to be installed as shown in Fig. 4 or Fig. 5, as applicable to the selected cover plate. Model Fl ER56 Concealed Pendent and Model Fl FR56LL Concealed Pendent sprinklers have a factory-installed Model CCP cup. A protective cap is in- stalled at the factory that should remain on the sprinkler until the sprinkler is installed and should then be reinstalled on the sprinkler until the cover plate is installed. The concealed sprinkler assemblies are completed by the installation of a Model CCP push-on/thread-off cover plate assembly. The cover plate and sprinkler cup assemblies are joined using a cover plate skirt with flexible tabs for threaded engage- ment. A choice of two Model COP cover plate assemblies provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover adjustment. Do not install Model F1FR Series Concealed Pendent sprinklers in ceilings which have positive pressure in the space above. Model Fl FR Series Concealed Pendent sprinklers require a 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The Model RC1 wrench is used to engage the sprinkler wrenching surfaces and to install the sprinkler in the fitting. Remove the protective cap to install the sprinkler, then reinstall the protective cap until the cover plate is installed. When inserting or remov- ing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. Do not wrench any other part of the sprinkler/cup assembly. Installation is com- pleted by removing the protective cap from the sprinkler and pushing the cover plate onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning the cover plate in the counter clockwise direction. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any concealed cover plate/cup assembly other than the Reliable Model CCP with Model Fl FR56 Concealed Pendent and Model Fl FR56LL Concealed Pendent sprinklers or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Technical Data: Sensitivity: Quick-response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar) SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar) Design and installation Information Model Nominal K-factor Nominal Orifice Diameter Deflector/ Orientation Nominal Sprinkler Height _____ Installation Wrench SIN mm Listings and Approvals Approval Notes US Metric inches mm inches F1FR28 2.8 40 3/8 10 Pendent 2.25 57 D RA1411 cULus 2 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2 Upright 2.25 57 D RA14211 cULus 1,2 FIFR40 4.0 57 3/8 10 Pendent 2.25 57 D RA1418 VdS Recessed Pendent 2.25 57 GFR2 RA1418 VdS F1FR42 4.2 60 7116 10 Pendent 2.25 57 D RA1413 cULus 2 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 D RA14231 cULus 1,2 F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D RA1410 cULus, NSF Recessed Pendent 2.25 57 GFR2 RA1410 cULus, NSF F1FRXLH (F1FR42 with Pintle) 4.2 60 7/16 10 Pendent 2.25 57 D RA1413 cULus 2 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 D RA1423 cULus 1,2 F1FR56 5.6 80 112 15 Pendent 2.25 57 0 RA1414 cULus, FM, LPCB, VdS, EC 1,2,3,4 Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, LPCB, VdS, EC 1,2,3,4 Concealed Pendant 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6 Upright 2.25 57 D RA1425 cULus, FM, LPCB, VdS, EC 1,2,3,4 Conventional 2.25 57 (Pendent or Upright)" D RA1475 LPCB, VdS, EC 4 F1FR56LL 5.6 80 1/2 15 Pendent 2.25 57 0 RA1415 cULus, NSF 1 Recessed Pendent 2.25 57 GFR2 RA1415j cULus, NSF Concealed Pendent 2.25 57 RC1 RA1414 cULus, NSF 6 F1FR56 5.6 80 1/2 15 Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7 Recessed Horizontal 2.63 67 Sidewall GFR2 RA1435 cULus, FM 8 F1FR56 5.6 80 1/2 ______ 15 - Vertical Sidewall (Pendent or Upright) 2.25 57 D RA1485 cULus, FM, LPCB 1,2,3,9 " cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. Available with FM approved Polyester coating in black or white. (°) Available with LPCB and VdS approved Polyester coating. ' VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F (68°C) temperature rated sprinklers only. VdS approved sprin- klers must use Norbulb brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only. (6) Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment. ' cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori- zontal Sidewall sprinkler is for Light Hazard occupancies only. cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. )) The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil- ing distance shalt be 4 inches to 12 inches (102mm to 305mm). LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. Listed and Approved Temperature Ratings Model Deflector/ OrientatIon Ordinary Temp. Classification 100°F (38°C) Max. Ambient Temp. Intermediate Temp. Classification 150°F (65°C) Max. Ambient Temp. High Temp. Classification 225°F (107°C) Max. Ambient Temp. 135°F (57°C) Temp. Rating 155°F (68°C) Temp. Rating 175°F (79°C) Temp. Rating 200°F (93°C) Temp. Rating 286°F (141°C) Temp. Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1FR28 Recessed Pendent cULus I -- _________ Upright cULus F1FR40 Pendent VdS Recessed Pendent VdS -- Pendent cULus F1FR42 Recessed Pendent cULus I -- __________ Upright cULus F1FR42LL _________ Pendent Recessed Pendent -- -- cULus, NSF cULus, NSF -- -- Pendent cULus F1FRXLH Recessed Pendent cULus I -- _________ Upright cULus Pendent cULus, FM, LPCB, VdS, EC Recessed Pendent cULus, FM, LPCB, VdS, EC -- F1FR56 Concealed Pendent* cULus I cULusVdS,EC I cULus -- Upright cULus, FM, LPCB, VdS, EC 'Conventional (Pendent or Upright)" LPCB VdS EC Pendent -- cULus, NSF -- F1FR56LL Recessed Pendent -- cULus, NSF -- _________ Concealed Pendent* -- cULus, NSF -- Horizontal Sidewall cULus, FM F1FR56 _________ Recessed Horizontal Sidewall cULus, FM ________________________________________________________________________________ -- Fl FR56 Vertical Sidewall (Pen- dentor_Upright) cULus, FM, LPCB * Model Fl FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Model Fl Model F2 Model FP Deflector/ Model (Fig. 1 & 3) (Fig. 1 & 3) (Fig. 2) SIN Orientation 3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-Inch (12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA 1413 F1FR42LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1410 F1FR42XLH Recessed Pendent cULus cULus cULus RA1413 F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus, FM, LPCB, cULus, VdS, EC RA1414 EC VdS,EC F1FR56LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 4. TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS -\ Ft ESCUTCHEON 3/4719mm] ADJUSTMENT F2 ESCUTCHEON 1/2712.7mm] ADJUSTMENT 2 1/4 HOLE OH. (57.2mm) 1 15/16" 014 ' [49.2mm) •- L---4---1 F I (1 I 1" X 1/2" REDUCER FACE OF FITTING TO FACE OF CEILING DIMENSION Fl ESCUTCHEON AT MAXIMUM RECESS = 1 "[25.4mm] AT MINIMUM RECESS = 3/879.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 3/4 '[19mm] 1-7 ---1-7 / / 1 I AT MINIMUM RECESS = 3/879.5mm] Fl ESCUTCHEON AT MAXIMUM RECESS = 7/8"[22.2mmJ AT MINIMUM RECESS = 1-5/8741.3mm] (3.2mmJ F2 ESCUTCHEON AT MAXIMUM RECESS = 1-1/8728.6mm] AT MINIMUM RECESS = 1-5/8741.3mm] 2 27/32" OH. (72.2mm) Fig. 1 Model El ER56, Fl FR56LL, El FR42, Fl FR40, El ER421-L, El FRXLH & Fl FR28 Recessed Pendent sprinkler with Model El or F2 escutcheon L—_—_—_-------==- r I I.- ----------- 2 5/8" 0/A. (66.7mm] HOLE IN CEILING / 2 5/16'" 0/A. [58.7mm] CUP LJ CEILING 1" X 1/2" REDUCER FACE OF FITTING TO FACE OF CEILING DIMENSION AT MAXIMUM RECESS = 1-1/2738mm] AT MINIMUM RECESS 1725.4mm] !12"[12.7mm] AT MINIMUM ADJUSTMENT AT MAXIMUM ; = - 3 1/4"DIA. [82.6mm] Fig. 2 Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. FACE OF FITTING TO FACE OF CEILING DIMENSION Fl ESCUTCHEON AT MAXIMUM RECESS = 1 "[254mm] AT MINIMUM RECESS = 3/8 [9.5mm] F2 ESCUTCHEON AT MAX/MUM RECESS = J14 "(19mm] AT MINIMUM RECESS = 3/8"[9.5mm] 2 1/4" HOLE DIA. [57.2mm] 1" X 1/2" REDUCER F? ESCUTCHEON 14 AT I IAIsJana nr.n .4 7 /.., IJT ._ 7 /if WII1.IMVM I —.,/a AT MINIMUM RECESS = 2-1/16752.4mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8'141.3mm] AT MINIMUM RECESS 2- 1/16'152.4mm] q 1 15/16" /wi [49.2mm] -7 -! II "l I 11111 L_ L_ TURN COLLAR UNTIL —' TIGHT AGAINST SPRINKLER WRENCH SOSS. Lff 2 27/32" DIA. [72.2mm] ll Fl ESCUTCHEON 3/4"[l9mmj ADJUSTMENT F2 ESCUTCHEON 1/2 '112.7mm] ADJUSTMENT T (1) 4"-12" [101. 6mm-304.8mm] CEILING TO DEFLECTOR ol.v= RECESSED HSW w/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig.3 Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon 1" x 1/2" REDUCING TEE OR ELBOW -- 2 5/16 0/A ____ CUP - ri CEILING —J 1/2" MAX. COVER ADJUSTMENT COVER PLATE ASSEMBLY 3 5/16" 0/A SPRINKLER —2 5/8" 0/A. HOLE IN CEILING 1 1/2" MAX, FACE OF FITTING ,TO FACE OF CEILING DIME/VS/ON / 15/16" .1 CONCEALED. 1/2" ADJUSTMENT Fig. 4 Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch (12.7mm) adjustment - Model COP cover plate I" x 1/2" REDUCING TEE OR ELBOW 2 5/16" CEILING -.---- 5/16" MAX. J i COVER ADJUSTMENT COVER PLATE ASSEMBLY SPRINKLER 11 DIA. CEILING 1 1/2" MAX. FACE OF FlU/NC TO FACE OF CElL/NC DIMENSION - 3/4" CONCEALED, 5/16" ADJUSTMENT O17FCO2A Fig. 5- Model Fl FR561F1 FR56LL Concealed Pendent sprinkler with low profile 5/16-inch (8.0mm) adjustment - Model CCP cover plate Maintenance The Model Fl FR Series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Replace any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Finishes (1) Standard Finishes Sprinkler Escutcheon Cover platet11 Bronze Brass Chrome Chrome Plated Chrome White Polyester Plated Coated (4)(5)(6) White Painted Special Application Finishes Sprinkler Escutcheon Cover platet1 Electroless Nickel PTFE17 Electroless Nickel PTFE Bright B rig Brass Bright Brass(3) Bright Brass Black Plating Black Plated Black Plated Black Paint Black Paint(2116) Black Paint Off White Off White(21t6) Off White Satin Chrome Chrome Dull Chrome Dull Other finishes and colors are available on special order. Consult the factory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi-gloss, unless specified otherwise. cULus Listed only. 200°F (93°C) maximum. cULus listed "corrosion resistance" applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendant) and RA1415 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. ) FM Approvals finish as Polyester coated" applies to SIN Number RA1414, RA1435 and RA1425 in standard black or white. LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418 (VdS) and RA1475. cULus listed Corrosion Resistant 7 Material Data Frame: DZR Brass, OM Brass, or Low Lead Brass Deflector: CDA Alloy 220, 260, or 510 Load Screw\Plntle: CDA Alloy 360 or 544 Cup: CDA Alloy 651 or 693 Washer: Nickel Alloy 440 or 360, coated with PTFE Adhesive Tape Bulb: Glass Ordering Information Specify: Sprinkler Model: [Fl FR28][F1 FR40][F1 FR42] [Fl FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] Sprinkler Deflector/Orientation: [Pendent] [Recessed Pendent][Upright] [Conventional] [Horizontal Sidewall] [Recessed Horizontal Sidewall][Vertical Sidewall] Sprinkler threads: [1/2-inch NPT][ISO 7-191/2] Sprinkler Temperature Rating: [135°F (57°C)][155°F (68°C)] [175°F (79°C)][200°F (93°C)] [286°F (141°C)] Sprinkler Finish Escutcheon Model: [F1][F2][FP] Escutcheon Finish (where applicable) Cover plate Model: [standard profile CCP 1/2-inch (12.7mm) adjustment][low profile CCP 5/16-inch (8.0mm) adjustment] Cover plate Temperature Rating: [135°F (57°C) for use with Ordinary Temperature sprinklers][ 165°F (74°C) for use with Intermediate Temperature sprinklers] Cover plate Finish Note: When Model Fl FR Series Recessed sprinklers are ordered, the sprinklers and escutcheons are packaged separately. i-'age : 1 01 1 SENJU SPRINKLER CO.,LTD. Commercial Flat Concealed Sprinkler, Pendent,, Quick Response, Standard Coverage, Model: RC-QR, K-Factor; 5.6, SIN: SS9561 . GENERAL DESCRIPTION The Model RC-OR Commercial Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These are decorative and quick/standard response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is in turn concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate. Therefore, the Model RC-QR should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. They are to be used in wet pipe sprinkler systems per NFPA 13. The Model RC-QR has a 5.6 (80.6 LPM/bar112) K-factor. For extended installation flexibility, the Model RC-QR provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-QR allows for an increased chance of occupants escape or evacuation in case of fire. However, fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. WARNINGS The Model RC-QR must be Installed and maintained In accordance with the rules stated herein as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities ha ving jurisdiction. In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so may Impair the integrity of these devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices In proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. Document No.U036886 Date Oct/06/2016 TECHNICAL DATA Approvals: Listed /as Quick Response FM Approved /as Standard Response Sprinkler Identification Number (SIN): 5S9561 Maximum Working Pressure: 175ps1 (12.1bar) Discharge Coefficient (Nominal K-Factor): K=5.6 GPMIpsi112 (80.6 LPM!bar1 ) Temperature Rating: 162'F / 72°C Sprinkler 140F / 60°C Cover Plate Vertical Adjustment: 1/2 Inch (12.8 mm) Cover Plate Finishes: Standard Finishes- White, Ivory, Beige, Brown, Black, Nickel, Wood Grain Custom Finishes- Custom color and custom pattern cover plates are available on special order. Contact a Senju Sprinkler representative with any custom orders. Please see chart on page 7 for more detail. Physical Characteristics: Ref. Figure 1 Page :2 of 7 2-1/16 Marking Lot of Manufactwe i oYear N. HTatutm2l62F,72C onvol No. : 171R 7 UL Mark T —FM Mark Zi) Body (Copper Alloy) - 2 Deflector (Phosphorus Bronze) Gasket (PTFE) Marking (Deflector) Fusible Metal (Solder) l Heat Collector (Capper) 2-5/8' (68mm) I Cover Plate Assembly or 3-1/4" (083nm) j ,Marking (Deflector) or UL only 2-5/8-square (068mm) K-factor: K5.6 1-Temperature Rating: 162 'F/72 'C - UL Marl, FM Mark FIGURE 1. Model RC-OR K5.6 OPERATION In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then, the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is recorded, internal components of the sprinkler to fall apart. This leads to allow the water flow to be distributed on the affected by fire area. (Ref. Figure 2) Normal Condition Cover Plate Operation Sprinkler Operation Water Discharge FIGURE 2. OPERATION PROCESS (The figure is for illustrative purpose only) DESIGN CRITERIA The Model RC-QR sprinklers are listed by UL and C-UL as quick response I standard coverage for use in accordance with NFPA standard, also the model is FM Approved as a Standard Response, No-Corrosive Atmospheres. The herein stated rules for use and installation of the Model RC-QR are provided by the manufacturer and must be strictly implemented for safe and full results. Document No. U036886 Date : Oct/06/2016 Page : 3 of 7 NOTES Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design, Installation procedures, and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it Is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not coverage by the following instructions, should be submitted to Contact Company. Include sketches and technical details as appropriate. In some Instances, the requirements of this document may concern specifications which are more stringent and which take precedence over those specified In NFPA 13 or by the authority having jurisdiction. The Model RC-QR must not be used in applications where the air pressure above the ceiling Is greater than that below. The Model RC-QR must not be used In applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup are open and free from any airflow impediment The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector. Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment (as defined by NFPA 13) must be kept as small as possible. Do NOT use more sprinklers than necessary to cover a particular space. Use only the Cover Plate provided with the Model RC-QR. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13. General Service Conditions The Model RC-QR must only be utilized in WET PIPE sprinkler systems per NFPA 13. Operational Sensitivity Criteria For proper operational sensitivity, the Model RC-OR must be installed beneath a solid ceiling having a smooth or textured surface. Heat Source Criteria Refer to NFPA 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-QR, due to exposure to a heat sources other than an actual fire. Precautionary Warnings for Corrosive Environments The Model RC-QR should not be installed where they may be subjected to a corrosive environment including the following: Chlorine ion and Chloride environment. Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. Sprinkler system piping with Copper. Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for the copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association) - Solder Joint) All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system. INSTALLATION The Model RC-QR must be installed in accordance with the following instructions. NOTES Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Document No. U036886 Date : Oct/06/2016 Page :4 of 7 Prior to Installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The Protective Cap must be removed to place the sprinkler In service. Use a torque of 7 to 14 ft.lbs (9.5 to 19.0111m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum torque, this could result in damage to the sprinkler Inlet, which may lead to leakage from the sprinkler. In case of insufficient adjustment In Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit. Do not force to rotate the Cap Remover RC to the left when placing the two hook arms into place. The installed sprinkler may become loosened, which may cause water leakage. Installina Procedure Step I The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inch (50.8mm) as shown in Figure 3. Step 2 With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Sprinkler Socket or Wrench & Socket Combination (Ref. Figure 4). The grooves of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation (Ref. Figure 4). Step 3 If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with the 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Tolerance Limit of Ceiling Level" indicator on the Protective Cap to check for proper installation height (Ref. Figure 3). Step 4 Use the Cap Remover RC Toot to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just comes In contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has come in contact with the ceiling. If the ceiling has been lifted from its normal position in the process of tightening of the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover Plate Assembly cannot come in contact with the ceiling sufficiently, readjust the sprinkler fitting as necessary. When property installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6 Make a Space He a Do Not Mmif8(a2mm Tolerance Limit Protective Cap E of Ceili. Level ve, 4 J.Groove .. o t n 41 __ Groove 2a the Socket E Socket Mountmg Surface Wrench LM..rnt.. 2-3'8' (460mm) Ceiling Hole Diameter [àRRECT4 I INCORRECT I FIGURE 3. INSTALLATION FIGURE 4 Document No.U036886 Date : Oct/06/2016 Page : 5 of 7 Hook up I, DVBQ /1 /\ \ I I / d Pull down Step I Step 2 Step 3 FIGURE 5. PROTECTIVE CAP REMOVAL Cup Mmogie Cover Plate Assembly [_2-5/8 (68mm) or 3-1/4 (83mm) or UL only: 2-5/8-square (068mm) FIGURE 6 INCOTI RRECT R6CTI FIGURE 7. INSTALLATION (CORRECT OR INCORRECT) Document No.U036886 Date : Oct/06/2016 Page 6 of 7 CARE AND MAINTENANCE The following instructions must be implemented for the maintenance and service of the Model RC-QR. NOTES Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F/4°C to prevent freezing and bursting of the pipe and/or sprinklers. Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result. Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire. Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may cause Improper operation or non-operation. If the ceiling Is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover plates. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire. Do not pull the Cover Plate. Separation may result. In preparation for maintenance of the fire protection system, permission to close the main control valve must be obtained from the proper authorities and all affected by this action parties must be Informed before the maintenance session can commence. Do NOT enclose any sprinklers within drapes, curtains, or valances. Do NOT hang anything from the sprinklers. Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle (i.e., dusting) brush attachment. Exercise suitable safely precautions in the use and storage of highly flammable materials. The rapid rate of fire development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire involving such hazards. Leaking or corroded sprinklers must be replaced. Automatic Sprinklers must never be shipped or stored where the temperature exceeds 100'F/38'C. Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the sprinklers have been in any way modified, they must be replaced. Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged units, as a result of dropping, hithng, over-tightening, or wrench slippage, must be replaced. When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations. The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this documents, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with NFPA 25. Document No. U036886 Date : Oct/06/2016 ORDER PROCEDURE Page 7 of 7 When placing an order, please contact a local distributor with the following information (Model Name, Specify, Temp. and Finish). Sprinkler; Model: RC-QR (SS9561, Quick & Standard Response, Standard Coverage, Flat Concealed Sprinkler, Pendent, 1(5.6) Cover Plate Assembly; rUlLoUsted :2-5/8 inch (68mm) or 3-1/4 inch ( 83mm) or 2-5/8 inch square (068mm), Order Separately from Sprinkler FM Approved :2-5/8 inch ( 68mm) or 3-1/4 inch (4 83mm) , Order Separately from Sprinkler Please refer to the chart below for available sizes, and finishes. Standard Finishes Custom Finishes White I Ivory Beige Brown Black Nickel Wood grain Custom Color Custom Pattern 2-5/8" Round, 140°F 0 0 - - - 0 - 0 0 3-1/4" Round, 140°F 0 0 0 0 0 0 0 0 0 2-5/8" Square, 140°F' 0 - - - - - - 0 0 1:cULus listed only Tools for Installation of Model: RC-QR Socket for Model RC-QR Wrench & Socket for Model RC-QR Cap Remover RC Document No. U036886 Date : Oct/06/2016 FM Approved and Fully Listed Sprinkler Pipe Wheatland's Mega-Flow steel fire sprinkler pipe is FM Approved for roll-grooved, plain-end and welded joints for wet systems; and UL, C-UL and FM Listed for use with roll-grooved, plain- end couplings and welded joints for wet, dry preaction and deluge systems. Mega-Thread is FM Approved for use in wet systems and is UL, C-UL and FM Listed for wet, dry and preaction sprinkler systems. Approvals and Specifications Both products meet or exceed these standards: ASTM A795, Type E, Grade A NFPA 13 and NFPA 14 Mega-Thread is approved for standard hanger spacing Manufacturing Protocols Mega-Flow and Mega-Thread are subjected to the toughest possible testing protocols to ensure the highest quality and long-lasting performance. Finishes and Coatings Mega-Flow and Mega-Thread black steel fire sprinkler pipe receive a proprietary mill coating to ensure a clean, corrosion-resistant surface that outlasts standard lacquer coatings. This coating allows the pipe to be easily painted without special preparation. Product Marking Each length of Wheatland fire sprinkler pipe is continuously stenciled to show the manufacturer, type of pipe, grade, size and length. Barcoding is acceptable as a supplementary identification method. MEGA-FLOW SPECIFICATIONS NPS NON OD NON ID UL CRR* MEGA-FLOW Mega-Flow Schedule Schedule 10 Schedule Schedule Nominal Pcc./Lift 40 1% 1.660 1.0 1.442 1.380 1.80 100 1.168 61 iVa 1.900 1.740 1.682 1.610 2.6.1 1.00 1556 61 2 2.375 2.715 7.157 2.06/ 7.14 100 1.961 37 2% 2.875 2.707 2.635 2.469 1.43 1.00 2.504 30 3 3.500 3.316 3.260 3.068 134 1.00 3.349 19 4 4.500 4.316 4.260 4.026 1.00 1.00 4.331 19 6 6,625 6.395 6.357 6.065 .75 1.00.8.000 10 Calculated using Standard UL CRR fo,mula, UL Fire Protection Directory, Category VIZY. The CRR Is ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). MEGA-THREAD SPECIFICATIONS NPS NOM OD NOM ID (IL CRR MEGA-THREAD Mega-Thread Schedule Mega-Thread. Schedule L.W.T. Pipe NominalPcs./LItt 1 1,315 1.049 1.00 1.00 .61 1.462 70 11/4 1.660 1.416 1380 100 1.00 39 1,989 51 1½ 1.900 1.650 160 1.00 1.00 .31 2.370 44 2 2.315 2.117 206/ 1.00 1.00 .25 309.1 30 Calculated using Standard UL CRR formula UL Fire Protection Directory, Category VIZY. The CRR Is ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark (value of 7.0). (9) C& APPROVED PROJECT: CONTRACTOR: DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: O MEGA-FLOW-BLACK J MEGA-THREAD-HOT-DIP GALVANIZED 700 South Dock Street into a't'eattani.com Sharon, PA, ata'd.com N1ieat aii Tube P 800,25Z8182 Fotlovv us onTl4ter: A DIVISION OF ZEKEIJIAN INDUSTRIES Description Designed for use in grid systems or any sprinkler system where pressure relief is required. The Adjustable Pressure Relief Valve can be adjusted from 75-175 psi. Adjustment to the desired pressure is achieved with the use of an approved fire sprinkler system pressure gauge. The adjustment cap is "diamond" knurled for easy adjustment. The body is cast bronze* and marked with directional arrows for proper flow indication. The pressure markings on the adjustment cap are for reference only. Use the system gauge for proper relief setting. Directions Installation of the Adjustable Pressure Relief Valve is accomplished with tools readily available on the job site utilizing approved installation methods. Do not install outlet piping until relief pressure has been set. To set relief pressure, rotate adjustment cap clockwise until seated. Pressurize sprinkler system to the pressure that you wish to provide relief Once system pressure has been set slowly turn pressure relief valve adjustment cap counter clockwise until the valve outlet starts to "spit" water from the system (bleed off pressure). Once the valve starts to "spit" then slowly close the valve cap until the valve stops "bleeding off" pressure. Check the system pressure gauge to make sure pressure is maintained at the relief pressure. Repeat steps until proper relief pressure has been set. Make sure to test setting by pressurizing system above relief setting to verify proper relief valve function. Use an appropriate thread sealant such as PipeFit or PipeFit AS to prevent leakage of the threaded connections. Refer to Authority Having Jurisdiction or NFPA13 for proper installation location in the sprinkler system. Specifications Type: Angle pattern, ½" IPS Material: Body: Cast Bronze* Cap: Brass* Seat packing: Rubber Sizes ½" lPS Finish: Rough:BraSs* Dimensions: 3.05" x 1.540" x 1.10" *Contains lead. Not for use in water systems intended for human consumption. 3198 UONSHEAD AVE CARLSBAD, CA 92010 TEL + 1760 599-1168 +1800344-1822 FAX + 1 800 344-3775 0 2012 Fire Protection Products, Inc. VSR ® POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Specifications subject to change without notice. Ordering Information Nominal Pipe Size Model Part Number 2" DN50 VSR-2 1144402 2 1/2 DN65 VSR-2 1/2 1144425 3" DNSO VSR-3 1144403 3 1/2' - VSR-3 1/2 1144435 4" DNIOO VSR-4 1144404 5" - VSR-5 1144405 6' DNI50 VSR-6 1144406 8" DN200 VSR-8 1144408 Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 UL, CUL and CSFM Listed, FM Approved, LPCBApproved, For CE Marked (EN12259-5) IVdS Approved model use VSR-EU Service Pressure: 450 PSI (31 BAR) - UL Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at I25/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps mm. at 24VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: NEMA 4/1P54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA- 13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 A WARNING Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. Shock hazard. Disconnect power source before servicing. Serious injury or death could result. Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. - CAUTION Waterfiow switches that are monitoring wetpipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterfiow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Important: This document contains important information on the installation and operation of the VSR waterfiow switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site. General Information Enclosure The Model VSR is a vane type waterfiow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose, systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, die-cast housing. The cover is held in place with two tamper resistant sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; screws which require a special key for removal. A field installable schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC cover tamper switch is available as an option which may be used approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering to indicate unauthorized removal of the cover. See bulletin number Information chart. 5401103 for installation instructions of this switch. The VSR may also be used as a sectional waterflow detector on large systems. The VSR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG. #54Ol146- REV M PAGE I 0F4 11115 azD APPROVED Approval Detas ai Leeater.s atwww or sAnv5Sales Represeeatee. CsF*~~F;L DUCTILE IRON THREADED FITTINGS •rANVIL FIG. 3201 9Q0 Elbow FIGURE 3201 Ii ELBOW Nominal Size Maximum Working Pressures Dimension A Approx. WI. Each In. (mm) PS! (kPa) Ia. (mm) ths (kg) 1 500 1.50 0.62 1!4 500 1.75 0.90 11/2 500 1.94 1.20 2 500 2.25 1.85 A - Working Pressure Ratings are for reference only and based an Scls. 40 pipe. For the latest UI/ULC, and FM pressure ratings versus pipe schedule, please visit onvilinticam or contact your local Anvil Representative. Dimensions: ASME 816.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UI/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. SPFJDl-1.15 DUCTILE IRON THREADED FITTINGS FIG, 3221 Coupling CE APPROVED For UsliqstApproval Detas and Um4atens. stIow webste a wwasvLn5 corn cr contact an AnvSes Repcesanlabve. FIGURE 3221 COUPLING Nominal Size MaximumDimension A Approx. WI. Each Working Pressurea In. (mm) PSI (kh) In. (mm) 1k (kg) 1 500 1.67 0.40 Ph 500 1.93 0.57 1½ 500 2.15 0.75 2 500 2.53 115 A - Working Pressure Ratings are for reference only and based on Sch. 40 pipe. For the latest IJL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. [Project: - 0 Approved Address: {jJ Approved as noted Contractor: 0 Not approved Engineer: Remarks: Submittal Date: Notes 1: rNotes 2: SPF/Dl- 1. 15 c® usun APPROVED For Lo pnrvol Detas andLftUt*rS. sst our WGbSIIO at wows inLcom ci contact an AnvdSaios RepresentaSIae. EP F! IPIWN v L: >1 DUCTILE IRON THREADED FITTINGS WANVIL FIG, 3221R Reducing Coupling lJj FIGURE3221R - REDUCING ICOUPLING Nominal Size Maximum. Working PressureA Dimension A Approx. Wt. Each In. (MM) PSI (APO) InJmm) .Lbsjkg) X 'Ii 500 1.69 0.39 I x4 500 1.69 0.53 A - Working Pressure Ratings are for reference only and hosed on Sch. 40 pipe. For the latest UL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. MATERIAL SPECIFICATIONS Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Block Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. SPF/Dl-1.15 TFPIBOO Pane 3 of 8 Figure Nominal Size ches Nominal Size MM Pipe Schedule Rated Pressure ® Figure 772 Patented 11k 11h, 2 42A, 48.3,60.3 8th 5, ID, Ut, WST 175 175 175 - - 1/4 42,4 Sch 10, Sch 4D 300 300 _QQ - - 1/2,2,22/2,3,4 48.3,60,3,73.0,88.9,114.3 8th 10, 8th 40 500 500 500 - - 5,6 141.3,168.3 Sch 10 300 300 300 - - 8 219.1 8th 10 400 400 400 - 5 141.3 Seh40 300 300 1 300 6 168.3 Sch 40 400 400 400 - 8 219.1 Sch 40 450 450 450 - 10,12 273.0,323.9 Sch 10, 8th 40 250 250 250 - - V/4, V/2,2, 272,3 42.4,48.3,60.3,73.0, 88.9 MF 300 300 300 - - 4 114.3 EZ, MF 250 250 300 - - 3 88.9 EZ 300 300 300 - 6 168.3 EZ 250 250 300 - - 1'12,2,2'I2,3,4 48.3160.3,73.0,88.9,114.3 DF,STF 300 300 300 - - 11/4,1/;,2,2Iz,3 42.4,48.3,60.3,73.0,88.9 FIF 300 300 4 114.3 Ft.F 250 250 - - VIz, 2,21h,3 48.3,60.3,73.0,88.9, FF 300 300 300 - - 4 114.3 FF 250 250 300 - - V14, 11h, 2 42.4,483,6(k3 EZI, MT, MIT, WLS 300 300 300 - - 11/4, 112, 2 42.4,48.3,60.3 GL Gal 7, GalRo 300 300 300 - - VIz, 2 48.3,60.3 BIT, DI 300 300 300 - 11/2,2 48.3, 60.3 IL, XL 300 300 - - - 76.1,165.1 881387 300 300 300 - - 4Z4 48.3,60.3,76J,88.9,114.3 8S1387, ISO 4200 - - - 1 16 20 139.7 8S1387, ISO 4200 - - - 16 - 165.1 8S1387, ISO 4200 - - - - 20 168.3— 219.1,273.0,323.9 1804200 - 16 20 O Figure 716 2x 11/2,21/2x 2, 3x2 60.3 x48.3, 73.0x60.3, 88.9x60.3 Sch 5 175 175 .j,. 3X21hr42,4x211z 88.9 x 73.0,114.3 x 60.3,114.3 x 73.0 Sth5 175 175 ,1, 2X11/2,2V2X2,3X2 60.3x48.3,73.0x60.3,88.9x6113 Sch 10, Sch 40 350 350 350 - - 3X2112,42,4X2/z 88.9 x 73.0,114.3 x 60.3,114.3 x 73.0 Sch 10, Sch 40 350 350 350 4x3,5x4 114.3 x 88.9,141.3,114.3 Sch 10, Sch 40 350 350 300 - - 6x4,6x5 168.3x114.3x163&3x141.3 Sch10, Sch 40 ,.,., .350 QQ. 8x6 219.1 x168.3 8th 40 350 350 300 - - 2x11l2,21Izx2,3X2 60.3 x 48.3,73.0 x 60.3,88.9 x60.3 DF,EZT, FF, GL, MF 300_ QQ 300_ 2X1Y2,21/2X2,3X2 60,3x48.3,73.0x60.3,88.9x60,3 MI, MIT, SF, STh1'L 300 300 300 - - 4x2 114.3 x60.3 OF, EZI, FF, GL, MF 300 300 300 - - 42 114.3x60.3 MT, MLT SF, STF,Th 300 300 300 - - U21/2,W'12,03 88.9x73.0,114.3x73.0,114.3X88.9 DF MF, SF aoo 300 QQ 4x21/2,4x3 114.3x73.0, 114.3xBB.9 FFSTF 300 300 300 - - 5x4,6x4 141.3x114.3,16&3x114.3 OF, FF, SF, STF 300 300 3W ..__ 3x2301I2 88.9x60.3,88.903.0 EZ 300 300 300 - 20/a 60.3x48.3 Gall, Gal Flo 300 300 300 - - 60.3x48.3,73.0x60.3,88.9x60.3 JS1387, ISO 4200 300 - 300 16 20 88,9x76,1,114.3x60.3,114.3x76.1 - 881387,I904200 300 300 . j... ...9_ 114.3x88.9 8S1387, ISO4200 300 - 300 16 20 168.3x114.3,219.1x168.3 1804200 300 - 300 16 20 139.7x114.3 B81387, 1804200 300 - 300 16 - 165.1 x114.3 881387,1504200 300 - 300 - 20 _______ ____________ Im Figure 40-5. 1V4,11Iz,2X/z,314,1 424,4&3,60.3x21.3,26.7,33.7 Sth5Sth10,Sth40 im 175 175 - - 11/4,1112.2 x1/z, s/i, 1 42.4,48.3, 60.3x21.3, 26.7, 33.7 BLI, OF, DI, 61, IS, MF 175 175 175 - - V/4,1V2,2MV2,3/4,1 42.4,48.3,60.3x21.3,26.7,33.7 MT, MLI.TLWLS,XI. 175 175 175 - - 4Z4,4&3,60.3x21.3,28.7,33.7 Gal 7, Gal Flo 175 175 175 1114, 11/2x 2/2,3/4,1 4Z4,48.3 x 21.3,26.7,33.7 EZI 175 175 175 - - 12/2X1/2,3/4, 1 48,3x21.3,26.7,33.7 FF 175 175 175 - - 21/zx 2/4,3/4,1 73.0 x 21.3,26.7,33.7 Sch 10, Sch 40 175 175 2VzxVz,b, 1 73.0 x21.3, 26.7,33.7 OF, MF, ST XL 175 ~175 2x2/2,3/4 1 48,3,60.3x21.3, 26.7,33.7 175 V/i, SIF 175 175 - - Figure 40-5 Straps are UL and ULC Listed and FM Approved with NPT and ISO threaded outlets as specified in the chart. Product Features -No pre-drilling required. Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. Saves time from traditional methods. Reduces installation cost. Made in the U.S.A. Not 5 than Toniwlth (t.1oW ow, nelesstisn 3' (2'12) remittal width 4' & 5- No 4 I t Mmmrom 2- 117 frocr bottom f bthhn Miti3nom3 f'nm I ballots for main fines. Exception: Ths requite'renaj not apply b2'nv thicker nang ships resting on top n' steal bean's ilm IN FJW. Joint 114 8018957 SWGIOO.. 114x? 62.2 (Fit) 25 125 114' 8019957 $WG 200 114 x2' 1725 (Fir) 25 125 - 3(8 8020957 SING 10 114 xl 622 (Fir) 300 25 125 - 3/8' 8021957 SING 20 114x2' 1725 (Fir) 1050 25 125 . 3/8 8013925 SWG 20-58 114 x 2' 1725 (Fir) 850 25 125 414 SW Red IT 8022925 SING 25-380 3/8 tt 2112" 2249 (Fir) 1500 25 125 Nut Driver 3/8' 8023925 SWG 30 1(4 a 3 1884 (Fir) 25 125 Part#8114910 - Insert the appropriate nut driver into a 318" or 112" portable drift. Insert the SAMMYS into the #14 (black) nut driver (pIn 8113910). Drill should be in a vertical position. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, slop drill and remove. The SAMMYS is now ready to receive 1/4', 3/8', 112'ormefrio all thread rod, bolt stock. (The 1/2"requires the#I4SWred nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout inpurlin steel. HORIZONTAL Insert the appropriate nut driver info a 318" or 112' portable drill. Insert the SAMMYS into the #148W (red) nut driver (fin 8114910). With drill unit in a horizo fuel position and at right angle to the structural member, begin installation. When the nut driver spins free on the SAMMYS, stop the drill and remove. The unit is now ready to receive 114", 3180r metric all thread rod or bolt stock Nate: When installing SWDR, follow the above Instructions, then add retainer nut and torque 1o20 foot lbs. for maximum pullout in punt/n steel. SPECIAL NUT DRIVER SYSTEM: The nut drivers were dest9ned with a unique spin-off feature which provides a fast and safe Installation each time. When the face of the driver comes into contact with the material you are installing Into, continue drilling until nut driver spins tree. Installaton is then complete. Warranty requires the use of the appropriate nut driver for installations. C®US LISTED Fig. 25 - Surge Restrainer Size Range - One size fits 3/4" thru 2' pipe. Material - Pre-Galvanized Steel Function - Designed to be used in conjunction with TOLCO® Band Hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficient- ly installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals - Underwriters' Laboratories Listed qnly when used with TOLCO band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and Canada (cUL). Finish - Pre-Galvanized Order By - Figure number and TOLCO band hanger, size from 3/4" thru 2'. Patent #5,344,108 OFFICE/MANUFACTURING FACIUTY • 1375 SAMPSON AVE.' CORONA, CA 92879 • FF4: 951.737.5599 • FAX: 951.737.0333 CUSTOMER SERVICE • 800.785.5265 ©3' an MT /c Double Check Detector Assembly Application Designed for installation on water lines in fire protection systems to protect against both backsiphonage and backpressure of polluted water into the potable water supply. Model 350ADA shall provide protection where a potential health hazard does not exist. Incorporates metered by-pass to detect leaks and unauthorized water use. Standards Compliance (Horizontal & Vertical) ASSE® Listed 1048 AMA Compliant C510 (with gates only), and C550 CSA® Certified UL® Classified C-UL® Classified FM® Approved Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California NYC MEA 221-04M-2 (2 1/2° - 8") NSF® Listed-Standard 61, Annex G" *(025% MAX. WEIGHTED AVERAGE LEAD CONTENT) Materials Main valve body Ductile Iron ASTM A 536 Grade 4 Access covers Ductile Iron ASTM A 536 Grade 4 Coatings FDA Approved electrostatic epoxy finish Internals Stainless steel, 300 Series NORYLTM, NSF Listed Fasteners & springs Stainless Steel, 300 Series Elastomers EPDM (FDA approved) Buna Nitrite (FDA approved) Polymers NORYLTM, NSF Listed Features Sizes: 2 1/211*, 3", 4", 611, 81;, 10" (with OS&Y gates) •..... .., (with BGVIC valves) Options (Suffixes can be combined) O - with flanged end OS & Y gate valves (standard) O L - less shut-off valves (grooved body connections) O LM - less water meter O - with remote reading meter O - with gallon meter (standard) O CFM - with cu ft meter U CMM - with cu meter meter O G - with grooved end OS&Y gate valves U FG - with flanged inlet gate connection and grooved outlet gate connection U P1 - with Post Indicator Gate Valves (4'-10") OBGVIC - with grooved end butterfly valves valves with integral supervisory switches Accessories U Repair kit (rubber only) O Thermal expansion tank (Model XT) U OS & V Gate valve tamper switch (OSY40) Maximum working water pressure 175 PSI Maximum working water temperature 140°F Hydrostatic test pressure 350 PSI End connections (Grooved for steel pipe) AWWA C606 (Flanged) ANSI 816.1 Class 125 *2 112" & 3" sizes use 4" body & reducer couplings Dimensions & Weights (do not include pkg.) WEIGHT ___________ MODEL WITH 350AL)A wrmour NTH os&v WITH OS&Y BUTTERFLY SIZE GATES GATES (GXF) GATES (GXG) VA&SIES(GXG) in. mm lbs. I kg lbs. kg lbs. kg lbs. kg 21/2 65 1 105 47.5 207 94 199 90.3 123.8 56.2 3 80 104 47 224 101.5 214 97 124.4 56.5 4 100 91 41.3 245 111 219 99.4 123 55.8 6 P 10 150 141 64 377 171 347 158 193 87.6 8 200 302 137 778 353.2 754 342.3 410 186 250 1 355 161 1040 472.7 918 416.5 527 239.3 MODEL 350ADA with OS&Y option rflJF C 0 Flow Characteristics MODEL 350ADA 2 112", 3" & 4" (STANDARD & METRIC) FLOW RATES (Us) 0.0 12.6 252 37.9 10 0 Rated Flow (established by approval agencies) 50.5 104 69 35 goo 252.4 104 - 69 35 4000 200 400 600 FLOW RATES (OPM) MODEL 350ADA 6", 8" & 10" (STANDARD & METRIC) FLOW RATES fl/s) 63.1 1262 189.3 1000 2000 3000 FLOW RATES (GPM) Typical Installation Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum of 12" (305mm) and a maximum of 30" (762mm) above adequate drains with sufficient side clearance for test- ing and maintenance. The installation shall be made so that no part of the unit can be submerged. MODEL 350ADABGVIC (Vertical Installation) Capacity thru Schedule 40 Pipe (GPM) Pipe size 5 ft/sec 7.5 ft/sec 110ft1sec 15 ft/sec 21/2" 75 112 149 224 3" 115 173 230 346 4- 198 298 397 595 6" 450 675 900 1351 8" 780 1169 1559 2339 10" 1229 1843 2458 3687 12" 1763 2644 3525 5288 PROTECTIVE MODEL 350ADA (Outdoor Installation) Specifications The Double Check Detector Backflow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be NorylTM (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM. The first and second check valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector Backflow Prevention Assembly shall be a WILKINS Model 350ADA. Zurn Industries, LLC I Wilkins 1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada I Zum Industries Limited 3544 Nashua Drive, Mississauga, Ontario L4V 11_2 Ph. 905405-8272, Fax 905-405-1292 Page 2 of 2 0.200 0.003 0.212 0.10 4.071 0.212 SECTION UL/FM IMueller Cal N.R.S. RESILIENT WEDGE B-i GATE VALVES Rev. 9-05 FIRE PROTECTION PRODUCTS FLANGED ENDS Shaded are:0 indicates change P-2360-6 FLANGED ENDS Indicator Post Style Stuffing box 2" Square Operating Nut 4", 6", 8", 10" AND 12' SIZES MEETS OR EXCEEDS ALL APPLICABLE REQUIREMENTS OF UL 262 AND FM 1120/1130 SPECIFICATIONS AND COMPLIES WITH NSF-61 CAST IRON BODY WITH MUELLER® PRO.GARDTM . FUSION EPDXY COATED INTERIOR & EXTERIOR SURFACES NON-RISING BRONZE STEM RUBBER ENCAPSULATED IRON WEDGE Options STAINLESS STEEL FASTENERS: TYPE 316 ASTM 1398-C6610011-102 STEM PARTS LIST 200 PSIG (1379 KPA) MAXIMUM WORKING PRESSURE, 400 PSIG (2758 KPA) STATIC TEST TRIPLE 0-RING SEAL STUFFING BOX (2 UPPER & 1 LOWER 0-RINGS) EPDXY COATING MEETS OR EXCEEDS ANSI/AWWA C550 AND COMPLIES WITH NSF-61 Catalog Part No. Description Material Material Standard G-16 Bonnet Bolts & Nuts Stainless Steel Type 304 G-27 Wrench Nut Cast Iron ASTM A126 CL.B G-41 Stuffing Box Bolts &Nuts Stainless Steel . Te3. 0-49 Stem 0-rings (3) Rubber ASTMD2000 G-152 Stuffing Box Cast Iron ASTM A126 CL.B 0200 Wrench Nutçperew Stainless Steel Typ_____ 0-201 Stuffing Box Seal Rubber ASTM D2000 G-203 Stem Bronze ASTM B138 G-205 Stem Nut Bronze ASTM B62 - 0-206 Guide Cap Bearings Thermal Plastic 0-208 Anti-friction Washers (2) Thermal Plastic 0-209 Wedge, Rubber Encapsulated Cast Iron** ASTM A 12 CL.B 0-210 Bonnet Cast Iron ASTM AI26CL.B 0-211 Bonnet Gasket Rubber ASTM D2000 0-212 Body Cast Iron ASTM A126 CL.B DIMENSIONS Dimension 4° 6° i 8° 110. 12° A 1 14.19" 18.00" 121.50" 25.50" r 2862 R 1 9.00" 11.00" 113.50° j 16.00" 19.00" FF 9.00" ] 10,50' 111.50" 13.00" 14.00" E 12.00" 12.00" 12.00" 12.00" 12.00" Q(Booe) UU 4.30" 7.50" 6.30" 9.50" i 8.30" 11.75" 10.30" 12.30" 1 14.2511 17.00" B (number and size of boles) 8--.75" 8--.88" j 8--.88" 12-I" 12--I" Turns to open - 1 20.5 26.5 33 38.5 Weight (Ibs.)* 1 113 1172 263 1398 520 Se page B.-t-22for ordering insturctions. NOTE: Flanged ends have 125 lb. American Standard End Flange Drilling, ANSI B16.1. *All dimensions are in inches. All weights are in approximate pounds. Fully encapsulated in molded rubber with no iron exposed. Page B-i-i i ~O-~ JiA - ~gle r~'LUE BRUTE ~J":; Pipe Size (IN) Ave OD (IN) Nom ED (IN) D9 - Approx. Bell Outside Diameter (IN) Mm T (IN) Ref. El ±1/4 (IN) Ref. E2 ±1/4 (IN) Approx. Weight (LBSIFT) PRESSURE CLASS 165 psi (DR 5) 4 4.80 4.39 5.57 0.192 4.50 5.50 1.9 6 6.90 6.31 8.00 0.276 5.25 6.25 3.9 8 9.05 8.28 10.50 0.362 6.25 7.25 6.7 10 11.10 10.16 12.88 1 0.444 7.25 1 8.25 10.1 12 13.20 12.08 1 15.31 1 0.528 8.25 9.25 14.4 PRESSURE CLASS 235 psi (DRI8)* 4 4.80 4.23 5.87 0.267 4.50 5.50 2.6 6 6.90 6.09 8.43 0.383 5.25 6.25 5.3 8 9.05 7.98 11.06 0.503 6.25 7.25 9.2 10 11.10 9.79 13.57 0.617 7.25 8.25 1 13.9 12 1 13.20 11.65 1 16.13 0.733 8.25 9.25 19.7 PRESSURE CLASS 305 psi (DR14)* 4 4.80 4.07 6.17 0.343 4.50 5.50 3.2 6 6.90 5.86 8.87 0.493 5.25 6.25 6.7 8 9.05 7.68 11.63 0.646 6.25 7.25 111.6 10 11.10 9.42 14.27 0.793 7.25 8.25 17.6 12 j 13.20 11.20 16.97 0.943 8.25 9.25 25.1 Cnsu J -ag.!s GSA c,her Us:in avaab p o mpnen:. Note: ?oorcas Pessue C!ass 's R 220 o csc: v3u J 'c cca:ci a:abit:. - Assembly Mark rodi;ct Strdard: S/A"/.VA C903 -pe CovpcL.rd: AS v*Di 78L Cs Cass 12L5L Gasket: 7- L77 'teoc 3e ort:AS-I! J3159 Celctior5: AiS \SF Stardd 61 US:rdard 1265 pe _ert'r: 20 feet yrg ergth A'I!iA C635 cstd'aficr Guide -irc; s:''ear -s.s;'s. Thcc: c sri'i c_:r. Th s Tr-s pr:cs UL -;:sc!r; e p c h "akei Fcr:Ei S' c f:s hE E:m 2k Wt. of Gland, Pipe Bolt Bolt Bolt Torque Bolts and Barrel Size No. Size length Ft/Lbs. Gasket, Lbs. O.D. °2 2 /s 3 45-60 5 2.50 3 4 ½ 3 45-60 7 3.96 4 4 Y4 3½ 75-90 10 4.80 6 6 3/-- 31/ 75-90 16 6.90 8 6 3A 4 75-90 25 9.05 10 8 ~ 4 75-90 30 11.10 12 8 2/4 4 75-90 40 13.20 14 10 3/4 4112 75-90 45 15.30 16 12 :?/4 41/2 75-90 55 17.40 18 12 314 4½ 75-90 65 19.50 20 14 :114 4'/2 75-90 85 21.60 24 16 a14 5 75-90 105 25.80 30 20 1 6 100-120 220 32.00 36 24 1 6 100-120 301 38.30 42 28 1'.4 6½ 120-150 389 44.50 48 32 11/4 6'/2 120-150 477 50.80 - Not included in AWWA CiIO. 2 2.50 2.50 3.39 3.50 2.61 3 3.96 2.50 4.84 4.94 4.06 4 4.80 2.50 5.92 6.02 4.90 6 6.90 2.50 8.02 8,12 7.00 8 9.05 2.50 10.17 10.27 9.15 10 11.10 2.50 12.22 12.34 11.20 12 13.20 2.50 14.32 14.44 13.30 14 15.30 3.50 16.40 16.54 15.44 16 17.40 3.50 18.50 18.64 17.54 18 19.50 3,50 20.60 20.74 19.64 20 21.60 3.50 22.70 22.84 21.74 24 25.80 3.50 26.90 27.04 25.94 30 32.00 4.00 33.29 33.46 32.17 36 38.30 4.00 39.59 39.76 38.47 42 44.50 4.00 45.79 45.96 44.67 48 50.80 4.00 52.09 52.26 50.97 -Not included in AWWACI1O. ACCESSORIES AND WEIGHTS 28° 3/4 4.75 6.25 6.25 .75 .62 1.12 .31 .63 .44 28" 3/4 6.19 7.69 7.69 .94 .62 1.37 .31 .63 .52 28" /s 7.50 9.12 9.12 1.00 .75 1.50 .31 .75 .65 28° 7/ 9.50 11.12 11.12 1.06 .88 1.63 .31 .75 .70 28° % 11.75 13.37 13.37 1.12 1.00 1.75 .31 .75 .75 28° Y8 14.00 15.69 15.62 1.19 1.00 1.75 .31 .75 .80 28° 7/ 16.25 17.94 17.88 1.25 1.00 1.75 .31 .75 .85 28° Va 18.75 20.31 20.25 1.31 1.25 2.00 .31 .75 .89 28" Va 21.00 22.56 22.50 1.38 1.31 2.06 .31 .75 .97 28" 7/ 23.25 24.83 24.75 1.44 1.38 2.13 .31 .75 1.05 28" Va 25.50 27.08 27.00 1.50 1.44 2.19 .31 .75 1.12 28° /t 30.00 31.58 31.50 1.62 1.56 2.31 .31 .75 1.22 20" 1'/a 36.88 39.12 39.12 1.81 2.00 2.75 .38 1.00 1.50 20" 1'/a 43.75 46.00 46.00 2.00 2.00 2.75 .38 1.00 1.80 20° 13'4 50.62 53.12 53.12 2.00 2.00 2.75 .38 1.00 1.95 20° 1% 57.50 60.00 60.00 2.00 2.00 2.75 .38 1.00 2.20 14THRU 48 GLANDS MAY BE TAPERED DUCTILE IRON Cli 0 FULL BODY MECHANICAL JOINT DIMENSIONS Sizes 3" thru 12' UL Listed for Fire Main Equipment TYLER UNION SAMPLE SPECIFICATION (Current ANSI/AWWA revision apply) Mechanical joint wotermain fittings with accessories, 2° through 48" shall be produced of ductile iron in accordance with and meet all applicable terms and provisions of standards ANSI/AWWA CI 10/A2 1.10 and ANSI/AWWA Cli 1/A2 1.11. Ductile iron mechanical joint fittings 3" through 24° shall be rated for 350 PSI working pressure. All ductile iron mechanical joint fittings 30 through 48° shall be rated for 250 PSI working pressure. Flanged ductile-iron fittings in 24-in. (610mm) and smaller sizes may be rated for 350 psi (2,413 kPa) with the use of special (annular ring or comparable) gaskets. NOTE - EXCEPTIONS: Mechanical Joint Fittings with flanged branches and 14" and larger caps and plugs are rated for water pressure of 250 PSI. NOTE. Installation per AWWA C600-10 NOTE: Fittings are cement lined and seal coated in accordance with ANSI/AWWA C104/A21.4. Fittings are also available double cement lined, bare or epoxy coated. Coated and lined fittings meet requirements of NSF-61, NSF-372, & Annex G.. NOMINAL JOINT DIMENSIONS IN INCHES - MECHANICAL JOINT FITTINGS DIMENSIONS IN INCHES Size A B C 0 F ½ X J K' K2 L M N 0 P S ANSI/AWWA Cl 10/A21.1O. ANSI/AWWA C111/A21 .11 13 2$6772_Ui4ity Catalog par 13 17115203 024721 DUCTILE IRON C1 10 FULL BODY MECHANICAL JOINT FITTINGS TYLER UNION Mi TAPPED TEE Mi Tapped Tee (2Tap) Dimensions Size I Max. Top Weights 3 8 2 40 4 8 2 51 6 8 2 73 8 8 2 104 10 8 2 130 12 8 2 180 TEES Size Dimensions Weights Run Run Branch X '1 Z Mi "MJxFExMJ "MJxMJxFE 2 2 2 3.25 3.25 ... 21 3 3 2 3.25 3.25 ... 45 3 3 3 55 55 135 58 -- 4 4 2 4.8 4.8 14.5 68 ... 49 .L_)(." 4 4 3 6.5 6.5 14.5 77 4 4 4 6.5 6.5 14.5 78 75 76 Straight Tees and 4 4 6 8.0 8.0 ... 112 Reducing on Branch Tees *6 6 2 8.0 8.0 ... 78 6 6 3 8.0 8.0 16.0 112 6 6 4 8.0 8.0 16.0 110 ... 109 6 6 6 8.0 8.0 16.0 119 120 141 6 6 8 9.0 9.0 ... 158 8 8 3 9.0 9.0 17.0 155 8 8 4 9.0 9.0 17.0 157 ... 150 8 8 6 9.0 9.0 17.0 175 170 182 180 194 ldz~ 10 10 11.0 19.0 10 10 6 11.0 11.0 19.0 258 ... 264 Bullhead 10 10 8 11.0 11,0 19.0 268 ... 245 10 10 10 11.0 11.0 19,0 300 250 12 12 4 12.0 12.0 20.0 318 315 323 12 12 6 12.0 12.0 20.0 325 325 335 12 12 8 12.0 12.0 20.0 335 335 372 v 13 12 12 10 12.0 12.0 20.0 392 390 12 12 12 12.0 12.0 20.0 396 396 476 14 14 12 14.0 14.0 22.0 540 560 tr L 14 14 14 14.0 14.0 22.0 585 570 16 16 4 15.0 15.0 23.0 600 580 575 MJxMixFE 16 16 6 15.0 15.0 23.0 615 590 605 16 16 8 15.0 15.0 23.0 625 605 615 16 16 10 15.0 15.0 23.0 645 620 16 16 12 15.0 15.0 23.0 660 640 651 16 16 16 15.0 15.0 23.0 740 720 730 NOTICE: Weights published in this catalog are for shipping purposes only. Actual weights may vary because some fittings are produced in multiple foundries. All fittings meet the AWWA standards to which they are designed. For weights of specific fittings, please contact Tyler Union Waterworks Company. Not included in AWWA Cl 10 *Made to order only. Not Returnable ANSI/AWWA CI1O/A21.lO, ANSI/AWWA C1 1/A21.11 16 255772.y*,lo9pf 76 82422 AM DUCTILE IRON Cl 10 FULL BODY MECHANICAL JOINT FITTINGS TYLER UNION REDUCERS Laying Lengths (L) Weights f- L Size Mi MI-SEB Mi-LEB PExPE FExMJ MixFE Mi Mi-SEB MJ-LEB PExPE FExMJ MixFE p 3x2 6 14 14 42 7 15 15 4x3 7 15 15 *6x2 9 17 17 6x3 9 17 17 hi 6x4 9 17 17 Mi Reducer 8x3 11 19 19 8x4 11 19 19 8x6 11 19 19 10x6 12 20 20 10x8 12 20 20 12x4 14 22 22 12x6 14 22 22 12x8 14 22 22 Mi Small End Bell Reducer 12x10 14 22 22 14x6 16 24 24 14x8 16 24 24 • 1 14x12 16 24 24 lóxó 18 26 26 16x8 18 26 26 16x10 18 26 26 16x12 18 26 26 1604 18 26 26 Mi Large End Bell Reducer 18x8 19 27 27 18x10 19 27 27 ________ _________ 18x12 18x14 19 19 27 27 27 27 18x16 19 27 27 2000 20 28 28 20x12 20 28 28 20x16 20 28 28 20x18 20 28 28 24x12 24 32 32 Plain End-Plain End Reducer 24x16 24 32 32 24x18 24 32 32 -L--1 2420 24 32 32 • 30x16 30 38 38 30x18 30 38 38 30x20 30 38 38 30x24 30 38 38 • 36x20 36 44 44 36x24 36 44 44 FExMJ Reducer 36x30 36 44 44 42x24 42 50 50 42x30 42 50 50 42x36 42 50 50 9 48x30 48 56 56 4806 48 56 56 48x42 48 56 56 24 24 24 31 30 31 23 7 7 37 38 37 34 46 43 47 25 ... 9 55 50 55 25 9 9 56 60 59 57 27 ... ... 84 77 70 27 11 11 84 82 84 27 11 11 94 90 93 96 28 12 12 115 116 117 28 12 12 142 135 130 135 30 ... ... 139 131 30 14 12 148 150 153 30 14 12 173 168 165 168 30 14 12 194 190 178 185 32 ... 16 ... 32 ... 16 .. 32 ... 16 ... 34 ... ... 250 34 ... ... 288 248 34 ... ... 300 34 18 18 330 304 325 34 ... ... 370 35 .. 19 320 35 ... ... 388 35 ... 19 380 355 35 ... ... 450 35 .. 19 476 36 ... ... 410 36 ... ... 515 420 36 ... 20 578 525 510 36 ... ... 575 40 ... 24 610 570 40 ... ... 705 665 753 40 ... .. 789 720 40 ... ... 815 775 804 46 ... .. 1150 1040 ... 1015 46 ... ... 1160 1050 ... 1025 46 ... ... 1225 1120 ... 1090 46 ... ... 1360 1255 1320 1215 52 ... ... 1495 ... 1466 52 ... ... 1580 ... 1535 1389 52 .. .. 1919 1721 ... 1585 58 ... ... 2060 ... 58 .. ... 2370 ... 58 ... ... 2695 ... 64 ... ... 3005 ... 64 ... ... 3370 .. 64 ... ... 3750 .. 34 35 50 53 62 ;:i ;s 84 80 100 105 130 130 145 130 170 175 188 190 195 215 270 305 325 300 405 445 510 455 (,-•- 1 * Not included in AWWA Cl 10 MixFE Reducer ANSI/AWWA C1 10/A21.10, ANSI/AWWA C111/A21.11 19 Tol-Brace Seismic Calculations VANGUARD FIRE PROTECTII Project Address: BLUE WATER GRILL 925 POINSETTIA AVE B-Line VISTA, CA 92081 477 CARLSBAD VILLAGE DRIVE 760-7274540 by o[] CARLSBAD, CA 487475 Job# 16-142 Calculations based on 2013 NFPA Pamphlet 913 Brace Information Tolco Brace Components Maximum Spacing 10' 0' (3.05 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length =(?-. (2.13 m) Fig. 1001 Clamp 1131 lbs (513 kg) Bracing Material 1' Sth.40 Fig.980 Universal Swivel 1425 lbs (646 kg) Angle from Vertical 450 Mm. Calculation Based on CONCENTRIC Loading Please Note: These calculations are for Tolco components only. Use of any other Least Red. of Gyration 0.42" (11 mm) components voids these calculations and the listing of the assembly. Assembly Detail L/R Value 200 Max Horizontal Load 1310 lbs (594 kg) TOLCO FIG. 98 UNIVERSAL SWAY BRACE ATTACHMENT Force Factor (Cp) 0.5806 oil STEEL PIPE Fastener Information Fastener Orientation NFPA Type __ Maximum Load jj(g)_•_ 4 Diameter .n. TOLCO FIG. 1001 Length 3-1l2in. FAST CLAMP Type Lag-Screw Orientation of Brace Lateral Size and Type of Pipe Total Length Total Calculated Load 2.50 Sch.7 Steel Pipe (83.5 mm) lOft (3 m) 130 lbs (14 kg) Percentage added for Fittings and Sprinklers 115% 14 lbs (1.81 kg) Total Adjusted Load of all pipe within Zone of Influence 34 lbs (15 kg) (Tol.Brace Veñzon 8) Tol-Brace Seismic Calculations BLUE WATER GRILL 477 CARLSBAD VILLAGE DRIVE Brace Identification Brace Type (Per NFPA#13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 16-142 A/B NFPA Type E 2.5° Sch.7 Steel Pipe 10'0" (3.05 m) Lateral 1" Sch.40 70° (2.13 m) 200 45° 3/8in. x 3-1/21n. Lag-Screw 3-1/2in. B-Line by 17.,ffoM Summary of Pipe within Zone of Influence 2.5° Sch.7 Steel Pipe (63.5 mm) I loft (3m) G-Factor Used 0.5806 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 34 lbs (15 kg) Material Capacity 1310 lbs (594 kg) Fastener Capacity 220 lbs (100 kg) Fig. 1001 Clamp 1131 lbs (513 kg) Fig.980 Universal Swivel 1425 lbs (646 kg) Structural Member WOOD WALL STRUCTURE Calculations prepared by SB * The description of the Structural Member is for informational purposes only. Tol-Brace software calculates the brace assembly only, not the structure it is attached to. Calculated with tel-Brace 8 Visit us at w.toIco.ccur Tol-Brace Seismic Calculations VANGUARD FIRE PROTECTh Project Address: BLUE WATER GRILL 925 POINSETTIA AVE B-Line VISTA, CA 92081 477 CARLSBAD VILLAGE DRIVE 760-727-8540 by o[J CARLSBAD, CA 4.87475 Job# 16-142 Calculations based on 2013 NFPA Pamphlet #13 Brace Information Tolco Brace Components Maximum Spacing 20' 0" (ç.j) - - Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7' 0" (2.13 m) Fig. 1001 Clamp 1386 lbs (629 kg) Bracing Material 1" Sch.40 Fig.980 Universal Swivel 1745 lbs (792 kg) Angle from Vertical 60° Min._ - *Calculation Based on CONCENTRIC Loading "Please Note: These calculations are for Tolco components only. Use of any other Least Red. of Gyration 0.42" (11 mm) components voids these calculations and the listing of the assembly. Assembly Detail L/R Value 200 ___.._ Max Horizontal Load 1604 lbS(j g)_ -. TOLCO FIG. 98 UNIVERSAL SWAY BRACE ATTACHMENT Force Factor (Cp) 0.5806 o21 STEEL PIPE Fastener Information Fastener Orientation NFPA Type F Maximum Load 310 lbs (141kg) + Diameter 3/8ur._ TOLCO FIG. 1001 / Length 3-1/2in. FAST CLAMP Type Lag-Screw Orientation of Brace Lateral Size and Type of Pipe Total Length 1 59 Total Calculated Load 2.5" Sch.7 Steel Pipe (63.5 mm) 20ft (6.1 m) lbs (27 kg) Percentage added for Fittings and Sprinklers 15% 9 lbs (4.08 kg) Total Adjusted Load of all pipe within Zone of Influence 68 lbs (31 kg) (101-Brace Venzon 8} Tol-Brace Seismic Calculations BLUE WATER GRILL 477 CARLSBAD VILLAGE DRIVE Brace Identification Brace Type (Per NFP013) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 16-142 C NFPA Type F 2.5° Sch.7 Steel Pipe 20'0" (6.1 m) Lateral 1 Sch.40 7'0" (2.13 m) 200 60° 3/8in. x 3-1/2in. Lag-Screw 3-1/2in. B-Line by [7,,,'JoPJ Summary of Pipe within Zone of Influence 2.5 Sch.7 Steel Pipe (63.5 mm) _r20ft (6.1 m) G-Factor Used 0.5806 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 68 lbs (31 kg) Material Capacity 1604 lbs (728 kg) Fastener Capacity 310 lbs (141 kg) Fig. 1001 Clamp 1386 lbs (629 kg) Fig.980 Universal Swivel 1745 lbs (792 kg) Structural Member IN BEAM Calculations prepared by SB * The description of the Structural Member is for informational purposes only. Id-Brace software calculates the brace assembly only, not the structure it Is attached to. Calculated with Id-Brace 8 Visit us at www.tolco.com Tol-Brace Seismic Calculations VANGUARD FIRE PROTECTII Project Address: BLUE WATER GRILL 925 POINSETTIA AVE B-Line VISTA, CA 92081 477 CARLSBAD VILLAGE DRIVE 760.7274540 by [j(o[J 4 c4p,c4 87475 Job # 16-142 Calculations based on 2013 NFPA Pamphlet #13 Brace Information Tolco Brace Components Maximum Spacing 80 0" (24.38 m)____ Tolco Component Fig. Number Adjusted Load Maximum Brace Length !0_(?!!.!PL_._ * Fig. 4LA Clamp 707 lbs (321 kg) Bracing Material 1' Sch.40 Fig.980 Universal Swivel 1425 lbs (646 kg) Angle from Vertical 4 !L *Calculation Based on CONCENTRIC Loading *please Note: These calculations are for Tolco components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42"(11 mm) Assembly Detail L/R Value 200 Max Horizontal Load Co R*A,T*a(Mua Force Factor (Cp) 0.5806 Fastener Information Fastener Orientation NFPA Typ_E_ Maximum Load 23(104kg) Diameter 1/2n Li Length 1-1/2in. ROtA VOl.0 rpm Type Through-Bolt Orientation of Brace Longitudinal Size and Type of Pipe Total Length Total Calculated Load 1.5" Sch.40 Steel Pipe (38.1 mm) 80ft (24.4 m) 168 lbs (76 kg) Percentage added for Fittings and Sprinklers 115% 25 lbs (11.34 kg) Total Adjusted Load of all pipe within Zone of Influence 193 lbs (88 kg) (Tol.8race Venzon 8) Tol-Brace Seismic Calculations BLUE WATER GRILL 477 CARLSBAD VILLAGE DRIVE Brace Identification Brace Type (Per NFPA#13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 16-142 D NFPA Type E 1.5 Sch.40 Steel Pipe 80'0" (24.38 m) Longitudinal 1 Sch.40 7'0" (2.13 m) 200 450 1/2in. x 1-1/2in. Through-Bolt 1-1/2in. B-Line by o[ Summary of Pipe within Zone of Influence 1.5" Sch.40 Steel Pipe (38.1 mm) 80ft(24.4 m) G-Factor Used 0.5806 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 193 lbs (88 kg) Material Capacity 1310 lbs (594 kg) Fastener Capacity 230 lbs (104 kg) Fig. 4LA Clamp 707 lbs (321 kg) Fig.980 Universal Swivel 1425 lbs (646 kg) Structural Member ROOF JOISTS Calculations prepared by SB * The description of the Structural Member is for informational purposes only. Tot-Brace software calculates the brace assembly only, not the structure it is attached to. Calculated with Tot-Brace 8 Visit us at www.tolco.com