Loading...
HomeMy WebLinkAbout703 PALOMAR AIRPORT RD; 3RD FL; FPC2022-0084; Permit:24 F1IrIi1IiJ Print Date: 06/16/2022 Permit No: FPC2022-0084 Job Address: 703 PALOMAR AIRPORT RD, # 3RD FLR, CARLSBAD, CA 92011-1043 Status: Closed - Finaled Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm Parcel #: 2101001500 Track #: Applied: 04/29/2022 Valuation: $0.00 Lot #: Issued: 05/24/2022 Occupancy Group: Project #: Finaled Close Out: 06/16/2022 #of Dwelling Units: Plan #: Bedrooms: Construction Type: Final Inspection: Bathrooms: Orig. Plan Check #: INSPECTOR: Cheung, Nathaniel Plan Check#: Salcedo, Felix Project Title: Description: RAKEN -FIRE ALARM TI TO INSTALL NEW POWER SUPPLY, SMOKE DETECTOR, INPUT MODULES & NOTIFICATION DEVICES & CONNECT TO EXISTING FIRE ALARM SYSTEM (45 DEVICES) Applicant: FPContractor: KELLEY FOULK MAKAI CAPITAL INC 8920 ACTIVITY RD, # STE J 8920 ACTIVITY RD, # STE SAN DIEGO, CA 92126-4458-SAN DIEGO SAN DIEGO, CA 92126-4458-SAN DIEGO (858) 752-6250 (858) 752-6250 FEE AMOUNT FIRE Reinspection (per Inspection) $212.00 FIRE TI Fire Alarm System $682.00 Total Fees: $894.00 Total Payments To Date: $894.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov Submittal Package for: Raken 703 Palomar Airport Road Carlsbad, CA 92011 Pacific Signaling River Fire and Security 8920 Activity Road, Suite J San Diego, CA 92126 Contains Cutsheets and CSFM Listings for: EXISTING Fire Alarm Control Panel Power Supply Input Module Smoke Detector I 2OVAC Duct Smoke Detector by Others Strobe and Horn/Strobe LISTED (E)POTTER I PA-1 00 The Symbol of Protection Fire Alarm Control Panel Features 127 addresses available on this analog addressable system Additional system capacity achieved via multi-point SLC modules 99 software zones NFPA 72 Compliant Smoke Sensitivity Test Built-In System Operates as Class A or Class B for SLC, P-Link and NACs 5 Amp Power Supply, Expandable to 310 amps 2 NACS, Regulated, Rated at 3 Amps each, expandable to 188 2 Input/Output 1/0) Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®, Cooper Wheelock® and System Sensor® strobes Dedicated Alarm, Supervisory and Trouble Relays 4,000 Event History Buffer Cabinet will house up to 18 AH batteries Optional two line DACT with UD-1 000 that can report General, Zone or Point Information Built in IP Communicator Ethernet Port for Programming and Network Connectivity E-Mail System Status, Reports and Event Information Product includes 5 year warranty UUKL Compliance accomplished when using DRy-SO with the Space Age Electronics GL8 Description Technical Specifications The IPA- 100 is an analog/addressable releasing fire alarm system with a total system capacity of 127 addresses. Additional capacity on the system is achieved using multi-point SLC modules. The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC). The [PA- 100 has a 5 Amp power supply with two Notification Appliance Circuits (NACs) and two Input/Output (I/O) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The I/Os are designed for inputs such as manual release stations and abort switches that will not require polling and react nearly instantaneously. The TPA-100 is listed for releasing of fire suppression systems. The software allows cross zones, counting zones, and timers for suppression. The system is capable of multiple release outputs across multiple hazards. In addition, the PSN-1000 may be used to extend releasing capability. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the IPA-loo will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN- I 000E has space to allow the installation of up to six loop expansion cards. The cards mount on a stacker bracket that allows access to all SLC circuit connections. Dimensions 16"W x 17H x 3 7/"D AC Mains 3.0 Amps @ 120 VAC 50/60 HZ 2.0 Amps @ 240 VAC 50/60 HZ Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window Standby Current-130 mA Alarm Current-200 mA 5 Amps power for NACs, I/O, and P-Link Batte 3 Amps per NAC, regulated I Amp per I/O circuit, regulated Battery Charger range 8-55 Ah Battery Charger voltage 27.3 VDC P-Link maximum current of I Amp Temperature and 32° to 1200 (0°C to 49°C) with a maximum Humidity Range humidity of 93% non-condensing. NFPA 12. 12A, 13, IS, 16, 17, 17A, 70, 72, 750, and 2001 ANSI/UL 864 - Local (L). Remote Sta- tion (RS), Central Station (CS), Propriety (PPU). Auxiliary (AUX).Type of Service: Standards Automatic (A), Manual (M), Water flow (WF) Sprinkler Supervisory (SS) Type of Signaling: Digital Alarm Communicator (DAC), March Time (March), Non Coded (NC). Reverse Polarity (Rev Pol). Other Technologies (OT) IBC 2000, 2003, 2006, 2009, 2012 Potter Electric Signal Company, LLC - St. Louis, MO - Phone: 800-325-3936 www.pottersignal.com 8830101- REV B • 05/17 PAGE IOF4 (2,)POTTER The Symbol of Protection IPA-1 00 Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with tip to 127 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PAD 100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PAD1 00-PHD Combination Analog Photo Electric Smoke/Heat Detector - a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135° Fahrenheit heat detector. PADI 00-HD Analog Fixed Temperature Heat Detector that is selectable from 1350 F to 185°F. PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay. PAD 100-DUCT Addressable Duct Smoke Detector. PADI00-6B 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD 100-4B 4" round base that maybe mounted to an electrical box and wired for connection to the above sensors. PAD 100-TB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PADIOO-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125 VAC. PAD 100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. PAD 100-CD Addressable CO gas detector. PADIOO-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. Modules Device Description PADIOO-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD 100-PSSA Single Action Addressable Pull Station. PAD 100-PSDA Dual Action Addressable Pull Station. PADIOO-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box. PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD 100- TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2 amps at 30VDC or 0.5 amps at I 25VAC. Also provides two contact inputs. PADIOO-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PADIOO-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PADIOO-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD loo-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PADl00-LED Module provides a single addressable LED that is controlled by the control panel. PA.DIOO-SM Speaker Module provides switching for two audio channels. PAD loo-LEDK Addressable LED and key switch that mounts in a single gang box. PAD IOO-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. PAD 100-ORO1 One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 - www.pottersignal.com 8830101- REV B • 05/17 PAGE 2 OF 4 ® POTTER The Symbol of Protection IPA-100 Fire Alarm Control Panel SLC Features The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The system does not require special cable or conductors for connection of the Signaling Line Circuit as long as the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations as well as "T-Taps", with a max wiring distance of 10.000 Ft. Sensor Features The sensors through the fire alarm control panel provide a real time status as to the condition of the system. The smoke detector sensitivity, heat detector temperature level and drift compensation are all programmable options. The system also allows for a day/night mode where the panel automatically adjusts the sensitivity depending on the time of day. To assist in the reduction of false alarms, the smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. User Interface The fire alann control panel has a 2 x 16 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs: AC Power - Green Alarm - Red Earth Fault - Amber Supervisory -Amber Silenced - Amber Trouble - Amber Pre-Release -Amber Release - Red The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened. P-Link The IPA-100 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 64 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: PADIOO-SLCE-Analog/Addressable loop expansion module RA-6075R —2 x 16 LCD annunciator with a key pad in a locked metal enclosure. RA-6500R(F) —4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F)— 16 LED annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) - 10 amp, remote intelligent power supply with 6 NACs, 2 I/Os and a P-Link repeater. This panel is listed in conjunction with the IPA- 100 as releasing circuits. CA-6500 - Class A convertor that converts the SLC, NACs and P-Link connection UD-1000 - UL listed, Dual line telephone alarm communicator DRY-SO - LED driver expander, used to connect up to 50 LEDs in a graphic display FCB-1000 - Fire communication bridge, provides remote mounting of the Ethernet connection FIB-11 000 - Fiber interface module, used to extend P-Link to multi- mode fiber (2 required) RLY-5 - Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/l25AC SPG-1000 - Serial parallel gateway, allows for the connection to a serial or parallel printer The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi-Connect allows up to sixty-three IPA series panels to share a single reporting technology. AE-2 —Two card expansion cabinet AE-8 - Eight card expansion cabinet AE-14 - Fourteen card expansion cabinet Ethernet/I.P. Connection The IPA-100 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test. Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the Ethernet connection is UL listed as an [P communicator. The IP communicator is listed to report to the UL listed Sur-Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station. Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com 8830101-REVB • 05/17 PAGE 3OF4 ® POTTER I PA-1 00 The Symbol of Protection Fire Alarm Control Panel Dimensions P 0 of TOP DEPTH = 3.75 40 oJ DOOR = 16.07 BACKBOX= 15.77 DEPTH =3.84 0 0 0 0 0 LEFT SIDE RIGHT SIDE BOTTOM OWG #593-1 Ordering Information Model Description I Stock No. IPA-100 Fire Alarm Releasing Control Panel 13992715 Compatible Releasing Devices Note: For releasing applications please order the Potter EOLD (3005012) for circuits connected to a releasing solenoid or actuator. Brand Description Skinner 7321 8BN4UNLVNOC 11 2CZ 732 I2BN4TNLVN0C322C2 Victaulic 753-E Series Mini Max MX 123 & MX200 w/ 8876677 & 889323 Viking 11591, 11601, 11602, 13843,& 13844 TLX IPA0036 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 . www.pottersignal.com 8830I01-REVB • 05/17 PAGE 4OF4 (R)POTTER PSN Series The Symbol of Protection Power Supplies Features PSN-64 has 6 amps regulated with 4 outputs PSN-106 has 10 amps regulated with 6 outputs May be configured as up to three class "A" Style "Z" notification circuits Two Trouble relays (5A at 30VDC) General System Trouble (programmable for AC delay) Low AC Trouble with optional delay settings Diagnostic LED's Status LED's for Active NAC and NAC Trouble conditions. Quadrasync feature synchronizes strobes from AMSECO, Gentex, Cooper-Wheelock and System Sensor. Configurable output circuits (DIP switch sets options for each circuit) Reference EOL allows 2K - 27K EOL value to be used Pass Thru mode allows the outputs to match the input signal from FACP SIGNAIJNG II&I ___Ji LISTED Description The PSN series of notification power supplies offers reliable notification power with unprecedented versatility. The power supplies offer either 6 or 10 amps of continuous power through 4 or 6 outputs respectively. Each output is rated at 3 amps and it may be used continuously without any derating. The power supply operates on either 120 VAC or 220 VAC power input and has a regulated 24 VDC output. In addition, the power supply can charge up to 55 AU batteries and leads the industry in housing up to 18 AM batteries. The cabinet is constructed out of 18 gauge cold rolled steel and has a durable red powder coat finish. In addition, a key lock is provided for securing the door. Ample electrical knockouts are provided on the sides and the top, allowing the installer options for running wires and maintaining the correct separations. The power supply offers an industry leading Quadrasync function that allows for multiple strobe circuits of different brands to he synchronized to flash at the same time. The power supply can have four different brands each connected to its own circuit and all the strobes flash together. Each output can independently be configured to provide one of four synchronizations or steady power. This provides unequivocal flexibility in new and retrofit installations. The power supply can be configured to synchronize AMSECO®, Gentex®, Wheelock® and System Sensor® strobe devices. Each output can be configured to the same sync protocol or set independently. In addition, the power supply has an input Pass Thru mode which allows the outputs to follow the input signal from a non-supported synchronization protocol. The power supply will recognize the type of input being supplied and pass this through to the outputs with the same pattern. This input pass through can be selected on each output independently. The power supply contains simple dipswitch programming and LED indicators providing the installer the ability to correct any possible faults. A Trouble Memory is provided to allow an installer to review past troubles and make the necessary repairs. Each output has an LED to pinpoint the exact circuit where a trouble may have occurred. Relays are provided for monitoring the general system and AC failure. Each output and be independently configured for various applications and installations. Each output can be independently configured for Class A or Class B operation, constant power. ANSI Temporal Code 3, Single, Multiple or Combo Inputs or Door Holder Power. Technical Specifications Size (HxWxD) I61/8"WxI6%"Wx3W'D Enclosure Eighteen (18) gauge sheet steel with hinged, locked door 120 VAC @60Hz Power Input 2201240 VAC @50Hz 5.1 Arrips P 120 VAC 2.5Anips@24OVAC Current 751 nA Standby & Alarm (no external load) Input Voltage I 5mA @8-33 VDC Trigger Terminals 18-12 AWG Temperature 32° F to 120°F (0°C to 49°C) with a maximum humidity of 93% non-condensing NAC Output 3 Amp max per NAC, Regulated Battery Charging 27.3 @ IA, can support 7— 55Ah batteries Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8910013- REV E • 05/21 PAGE I 0F3 NC COSt NO NC COSt NO Battery + Common relays are {— Battery - non-power limited. (R)POTTER The Symbol of Protection PSN Series Power Supplies GND FAULT DETECT ENABLE ON OFF Black White —Ground ZZ Status LED's NACI NAC2 NAC3 NAC4 NACS NAC6 DC PWR 0, • • • S S 5 0 ,S7 S8 El st LII S2 t Factory Installed 0 0 0 '' Interconnect. AC Power El El D El El S5 Low Battery Gad Fault Contra S6 EEDEEE 91 ED = o NACt, NAC2 NAC3 NAC4 NACS NACS DCPWR IREF Ni IN2 0 Optional H.O.L. Rn term cm O.L DC Power Trigger -1 -+ PSN-106 Wiring Diagram 120/24OVAC n Jumper Position 120 VAC 50Hz-60Hz 240VAC 50Hz-60Hz Connect to separate unswitched AC circuit Battery connection (non-power Smiled) Use two (2) I2V batteries connected in series Note: PSN-64 and PSN- 106 draw 15 mA when polarity reverses and the power supply is triggered. There is no current draw in Standby Mode. Ordering Information Model Description Stock No. PSN-106 10 A Power Supply, 6 NAG Circuits, 3006437 Red Enclosure PSN- 106B 10 A Power Supply, 6 NAG Circuits, 3006446 Black Enclosure PSN-64 6 A Power Supply, 4 NAG Circuits, 3006436 Red Enclosure Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 . www.pottersignal.com 8910013- REV E • 05/21 . PAGE 2OF3 ()POTTER PS N Series The Symbol of Protection Power Supplies Engineering Specifications The contractor shall supply and install the Potter PSN power supply. The power supply shall operate on either 120 or 240 VAC input. The panel shall be capable of continuous load power without any degradation to the main supply or the distribution board. The cabinet shall be capable of housing up to I 8AH batteries and the panel shall be capable of charging up to 55 AH batteries in an external cabinet. The panel shall have dip switches for simplistic configuration of the system and LEDs to provide visual indication to the installer of the status of the system. The dip switches shall allow for AC power delay selection, Class A/B operation per output, Door Holder Power options, constant auxiliary power, trigger input type, ANSI Code 3 Temporal Code, Pass Thru (input tracking), AMSECO® sync. Gentex® Sync, System Sensor® Sync or Wheelock® sync. The LEDs shall provide indication of communication between the power supply and distribution circuit assemblies. The LEDs shall have distinct flash patterns to provide further indication of the troubles present. The panel shall have selectable Trouble Memory to provide the installer an indication that a past trouble existed on a circuit for diagnostic purposes. Each output of the power supply shall be capable of 3 amps of continuous power without degradation overtime. The power supply shall provide for multiple circuits of strobe appliances. The power supply shall synchronize the flashes of any of the above listed strobe appliances on a per circuit basis. Up to four different strobe circuits may be connected and all the strobes shall flash in unison as required by UL 864. In addition to this Quadrasync feature, the panel shall allow any of the four above mentioned sync patterns as an input and pass this signal through and synchronize the outputs to match the input flash pattern. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8910013- REV E • 05/21 PAGE 3OF3 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL 1 FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7315-0328:0189 Page 1 of 1 CATEGORY: 7315-- POWER UNITS LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 United States Contact: Brad Serangeli (314) 595-6900 Fax (314) 595-6999 Email: brads@pottersignal.com DESIGN: Models PSN-106, PSN-64, PSB-10 Notification Appliance Circuit (NAC) Power Supply Units. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Input 120/240 VAC 50/60Hz Output 24VDC @ 10A INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. For fire alarm use, the unit must provide battery backup suitable for at least 24 hours. MARKING: Listees name, model number, electrical rating and UL label. APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control units and notification appliances. Authority having jurisdiction should be consulted prior to installation. The unit can be programmed to generate the three-pulse temporal fire alarm evacuation signal (for total evacuation) in accordance with NFPA 72, 2002 edition. 01-27-2010 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division (R)POTTER The Symbol of Protection PADI 00-MIM Micro Input Module Features One Class B contact monitoring input Small size allows mounting in most electrical boxes SLC Class A, Class X& Class B 6" Pigtail wiring connections Product includes a 5 year warranty 12 4 9 16 22 64 PAD 100-MIM (SLC Module) Description The PADIOO-MIM is used to monitor the status of an initiating device(s) that contain a normally open set of dry contacts. The module is enclosed in a plastic case to protect against inadvertent shorts and ground faults. The case can be mounted using a single screw. The PAD 100-MIM has a status indicator LED to indicate communication and alarm condition. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate. Application The micro input module (PAD 100-MIM) is compatible with Potter's IPA series addressable fire alarm control panels. Generally the PAD loo-MIM is used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure behind the device being monitored. Technical Specifications Operating Voltage 24.OV Max SLC Standby 200iA Current Max SLC Alarm Current 200tA IDC Input Circuit Wiring Class B Max Wiring Resistance 100 E2 of IDC Max Wiring Capacitance of IDC EOL Resistor 5.1K1 Operating Temperature Range 32 to 120°F (0 to 49°C) Operating Humidity Range 0 to 93% (non-condensing) Max no. of Module Per 127 units Loop Dimensions 1.75" (44.5mm)L x 1.36" (34.5mm)Wx .43" (llmm)D Mounting Options 2-1/2" (64mm) deep single-gang box Shipping Weight 0.3 lbs Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830079- REV B • 12/17 PAGE I OF 2 (E)POTTER PADI OO-MIM The Symbol of Protection Micro Input Module Setting the Address Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD 100-MIM. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device: I. Power to the device is removed. Field wiring is correctly installed. Field wiring has no open or short circuits. Wiring Diagram Fig I 1 2 4 863264 ®JPO1TER PAD100-MIM FROM FACP OR PREVIOUS TO NORMALLY OPEN DEVICE AND TO NEXT DEVICE MONITORED DEVICE 5.1 K OHM REQUIRED Part #3005013 Ordering Information Model Description Stock No. PADIOO-MIM Micro Input Module 3992700 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830079- REV B 2117 PAGE 2 OF 2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0328:0514 Page 1 of 1 CATEGORY: 7300 - FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Potter Electric Signal Co 1609 Park 370 Place, Hazelwood, MO 63042 United States Contact: Brad Serangeli (314) 595-6900 Fax (314) 595-6999 Email: brads@pottersignal.com DESIGN: Model PAD100-DIM Dual Input Module Model PAD100-LED Addressable LED Module Model PAD100-OR0I One Relay-One Input Module Model PAD100-RM Relay Module Model PAD100-SIM Single Input Module Model PAD100-TRTI Two Relay-Two Input Module Model PAD100-ZM Zone Module Model PAD100-IM Isolator Module Model PAD100-NAC Notification Appliance Circuit Module Model PAD100-SM Speaker Module Model PAD100-MlM Micro Input Module Model PAD1---LEDK Key Switch Module Model PAD100-DRTS Duct Remote Test Switch Model SLCE 127 Point SLC Expander Model MC-1000 Multi Connect Model PAD100-DUCTR Model AE-2 Enclosure Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model designation, rating and UL label. APPROVAL: Listed as fire alarm control unit accessories for use with listee's separately listed fire alarm control panels. Refer to listee's Installation Instruction Manual for details. 09-11-18 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct RV' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division (E)POTTER PAD 1 00-PD The Symbol of Protection Photoelectric Smoke Sensor Features Low profile, less than 2 inches with the base Wide selectable sensitivity range of 1.0 to 3.7%/foot 4 s3 Sensor communicates sensitivity to control panel UL listed smoke calibration and sensitivity Optional locking tab to prevent unwanted removal Simple DIP switch address setting, no programming tool required LED alarm indicator Product includes a 5 year warranty UUKL Listed for Smoke Control APPROVED LISTED Description The Photoelectric Smoke Sensor is a listed Analog Addressable smoke sensor compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD 100-PD is a low profile smoke sensor with a wide sensitivity range. The sensor and base (not included) are made of a durable plastic in an off-white color to blend in with the ceiling. The PAD 100-PD has a sensitivity range of 1.0 to 3.7 % per foot and is UL. The PAD 100-PD features drift compensation and has built in dirty detector warning as well as. The PADl00-PD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements. The sensor is compatible with any of the PAD series sensor bases and simply twists on. The PAD 100-PD is addressed using DIP switches in the rear of the sensor and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from I to 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: I. Power to the device is removed Field wiring is correctly installed. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 iA Alarm indicator I LED Alarm set-point range 1.0 to 3.7%/ft 3.6-12 %/m Installation temperature 32 to 120 'F/ 0 to 49 0 C range Operating relative 0% to 93% (Non-condensing) humidity range Start-up time Max. I sec. Maximum number of 12/ addresses per loop Maximum number of lighted indicators in 30 alarm per loop. Color Eggshell White Weight (without base) lOIg (3.56oz) Dimensions (without Height: 1.35 in (34mm) base) Diameter: 3.93 in (100 mm) Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830108-REVD • 2fl8 PAGE IOF2 (E)POTTER PA Dl 00-PD The Symbol of Protection Photoelectric Smoke Sensor Air Velocity Ratings The PAD IOO-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD 100-PD will operate even though the LED may not illuminate. Operation The PAD IOO-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation. The PAD 100-PD with the PAD 100-41313 or PAD 100-61313 has a low profile of less than two (2) inches to blend into the surrounding environment. The sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector. Sensor Sensitivity The PAD 100-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned or replaced. The PAD 100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs. NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service. Spacing The PAD 100-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. Compatible Bases All bases will mount on a single gang, double gang, octagon, 4" square or mud ring electrical box. Device Description Stock No. PAD 100-4DB 4" Standard Base 3992731 PAD 100-6DB 6" Standard Base 3992732 PAD 100-lB 6" base with an isolator module included. 3992730 PAD 100-RB 6" base with one Form-C relay contact. 2A @ 30VDC, 0.5A 125 VAC 3992728 PAD 100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729 PAD 100-SPKB 6" base with speaker included 3992762 Ordering Information Model Description I Stock No. PAD IOO-PD Photoelectric Smoke Sensor 3992733 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignaI.com 8830108-REVD • 2/18 PAGE20F2 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0328:0504 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: Potter Electric Signal Co 1609 Park 370 Place, Hazelwood, MO 63042 United States Contact: Brad Serangeli (314) 595-6900 Fax (314) 595-6999 Email: brads@pottersignal.com DESIGN: Models PAD100-PD, PAD100-DD and PAD100-PHD photoelectric smoke detector heads. Model PAD1 00-PHD has an intergral heat detector. Refer to Listee's data sheet for detailed product description and operational considerations. RATING: 24Vdc INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Models PAD100-PD and PAD100-PHD are listed as photoelectric smoke detector heads for use with listee's detector base Models PAD100-4DB, PAD100-6DB, PAD100-RB, PAD100-SB (CSFM#7300-0328:502) and Model PAD100-IB (CSFM#7300-0328:501). Model PAD100-DD is listed as a photoelectric smoke detector head for use with Model PAD100-DUCT (CSFM#3248-0328:0505). Refer to listee's Installation Instruction Manual for details. 06-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct VG operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division SYSTEM $ SENSOR : D4120 Duct Smoke Detector The InnovairFlexm Series are the only duct smoke detectors flexible enough to fit configurations from square to rectangular and everything in between. Innow-n- Features 4-Wire Photoelectric, integrated low-flow technology Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32 m/sec) Versatile mounting options: square or rectangular configuration Plug-in sensor offers superb false alarm immunity and the latest sensor technology Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of the detector with no tools required Increased wiring space with a newly added 3/4-inch conduit knockout One easy-access Test/Reset button and improved LED status Patented interconnect feature for multi-fan shutdown New high contrast terminal designations Built-in short circuit protection from operator wiring errors Field selectable settings for configuring the detector Two DPDT Form-C relay contacts 24 VAC/DC or 120 VAC Backward compatibility with existing Innovair products, including remote accessories Agency Listings & <~> 0 LISTED APPROVED SAIl 3033744 3242-1653:0207 The InnovairFIex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of -4°F to 158°F, and a humidity range of 0 to 95 percent (non- condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. The InnovairFIex housing provides ample wiring space, a 3/4-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFIex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source. An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure field selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board has two LEDs that can be used to indicate the status of connected sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm). The InnovairFIex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFIex product line is compatible with all previous Innovair models, including remote test accessories. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information. tab (front locking tab shown below lnnovairFlexTM Duct Smoke Detector Specifications The air duct smoke detector shall be a System Sensor lnnovairFlex° D4120 Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the RTS2-AOS Multi-Signaling Accessory or the RTS151 KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Size: (Rectangular Dimensions) (Square Dimensions) 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 2.5 lbs (1.14 kg) Operating Temperature Range: D4120 & D4S: 4° to 158°F(-20° to 70°C); D4P120: 40° to 158°F(-40° to 70°C) Storage Temperature Range: D4120 & D4S. -22° to 158°F (-30° to 70°C); D4P120: -40° to 158°F (-40° to 70°C) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: 100 to 4000 ft/mm (0.5 to 20.32 m/sec) Electrical Ratings Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz Input capacitance: 270 pF max. 270 pF max. N/A Reset voltage: 3.0 VDC mm. 2.0 VAC mm. 10 VAC mm. Reset time: (with RTS151) .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time: (by power down) 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 35 sec. max. 35 sec. max. 35 sec. max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current: 21 mAO 24VDC 65 mA RMS 0 24VAC 60Hz 20 mA RMS 0 120VAC 60Hz Max. alarm current: 65 mAO 24VDC 135 mA RMS 0 24VAC 60Hz 35 mA RMS 0 120VAC 60Hz Contact Ratings Alarm initiation contacts: (SPST) 2.OA @30 VDC (resistive) Alarm auxiliary contacts: (DPDT) Note: Alarm auxiliary contacts shall iDA @30 VDC (resistive); 10A @250 VAC (resistive); 1/2 HP @240 VAC; ¼ HP 0 120 VAC not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPDT) Accessory Current iLoads at 24 V 2.OA @30 VDC (resistive); 2.OA 0 125 VAC (resistive) III Device Standby Trouble Alarm APA1S1 12.5 mA n/a 30mAMax. MHR/MHW 0 mA n/a 29 mA Max. RA100Z 0 m n/a 12mAMax. RTS151/RTS151KEY 0mN12mA n/a i2mAMax. RTS2/RTS2-AOS 3.0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max Note: Any combination of accessories may be used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output Installing the InnovairFiex Sampling Tube The lnnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be Wiring for 4-wire Duct Smoke Detector and Accessories ------------ I POWER INPUTS (NOTE 1) I 4VAC/D1 120 I I ; VAC I& &I 910 I OR I I AUXILIARY CONTACTS I FOR FAN SHUTDOWN, ETC. (NOTE 2) AUXA AUXB JN IN I SUPERVISORY CONTACTS I (NOTE 3) I SUP N.O. SUP C I POWER INPUTS (NOTE 1) I I r4 I 910 I OR I I AUXILIARY CONTACTS I FOR FAN SHUTDOWN, ETC. (NOTE 2) AUXA AUXB JN 2N I SUPERVISORY CONTACTS I (NOTE 3) I SUP N.Q. SUP C EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER ------------- FIRST DETECTOR IN THE LOOP NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz. 120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to appropriate terminals of each detector. See specifications for additional power supply information. NOTE 2: Auxiliary contacts shown in standby position. Contacts switch during alarm as indicated by arrows. Auxiliary contacts are not to be used for connection to the control panel. See specifications for contact ratings. *Please refer to the corresponding installation manual for accessory wiring diagrams. LAST DETECTOR IN THE LOOP NOTE 3: Supervisory contacts shown in standby position. Open contacts indicate a trouble condition to the panel. See specifications for contact ratings. NOTE 4: Alarm Initiation contacts shown in standby position. Closed contacts indicate an alarm condition to the panel. See specifications for contact ratings. Important Notes on 2:1 Sensor-to-Power Capability 2:1 sensor-to-power capability is not available for all lnnovairFlex models. The feature is only available on the D4120 4-wire conventional models. 2:1 sensor-to-power capability can be enabled using one D4120 and one D4S, or two D4S and one D4P120. Important Interconnect Notes When using the interconnect feature, all interconnected units must be powered using the same independent supply. Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit 1 to the lNT+ terminal on unit 2 and so on. Similarly, connect the INT/AUX— terminal on unit 1 to the INT/AUX- terminal on unit 2 and so on. Up to 50 D4120 units, 50 04P120 units, or 50 units of combination may be interconnected. Up to 10 DH100ACDC units may be interconnected. Please note that each of the 9 DH100ACDC units interconnected may be replaced by three D41P120 units. Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 27 D4120 units. * NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected. APA151 UL S4011 Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation, As with our duct smoke detectors, all duct smoke detector accessories are UL listed. MHR UL S4011 RTS151 UL S4011 RA100Z UL S2522 rT1 L!J RTS151 KEY UL S2522 MIIW UL S4011 SMOKE a 0 - RTS2-AOS UL S2522 r -1 AOS Ordering Information D4120 4-wire photoelectric low-flow duct smoke detector Accessories D4S 4-wire photoelectric sensor component only D4P120 4-wire photoelectric power board component only, 24 VAC/DC, 120 VAC 2D51 4-wire conventional photoelectric sensor head DST1 Metal sampling tube duct width up to 1 f (0.3m) DST1 .5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6t0 1.2m) DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m) DST1 0 Metal sampling tube duct widths 8 ft to 12 ft (2,4 to 3.7 m) APA151 Remote annunciator with piezo alarm ETX Metal exhaust tube duct width 1 f (0.3m) M02-04-00 Test magnet MHR Mini Horn, Red MHW Mini Horn, White P48-21-00 End cap for metal sampling tubes RA100Z Remote annunciator alarm LED RTS151 Remote test station RTS151KEY Remote test station with key lock RTS2 - AOS Multi-signaling accessory with add on strobe "STEM Ohio Avenue • St. Charles, IL 60174 Syse Sensor. Phone 800 SENSOR2 • Fax 630 377 6495 ' Lfor current 01° S echn tr oce '/st r cuct information, including the iatest version of this data r '......Y www.systemsensor.com HVOS00502 • 10/13 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 3242-1653:0207 Page 1 of 1 CATEGORY: 3242 -- DUCT SMOKE DETECTOR, PHOTO. (W/ OR W/O BASE) LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models D4120, D4240, RD4120, P270-3000PL, TD41203, TD41204, LD4S, LD412OX, LD4120H, D4S, D4P120, CD4P120 LD4P120X, LD4P120H, TD4C, PD4120, YD4120, YD4P120, and AD4P120 four-wire conventional photoelectric duct smoke detectors and subassemblies. Unit consists of a duct detector housing, powerboard with electrical components and relays, exhaust tubes, and listed 2D51 detector head (CSFM Listing No. 7272-1653:203). Model AD4S sensor component. Models *TD4C, LD412OX, LD4120H, LD4P120X and LD4P120H do not contain a 120 VAC transformer. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 20-29 VDC, *24 VAC, 120 VAC (except Models *TD4C, LD412OX, LD4120H, LD4P120X and LD4P120H *do not have 120 VAC rating). INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, air velocity and UL label. APPROVAL: Listed as conventional photoelectric duct smoke detector for use with separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. *Rev. 03-27-13 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, ME., F.P.E. Fire Engineering Division Exceder Strobe, HOTnStTobe, and Horn Notification Appliances EATON Powering Business Worldwide Description The Wheelock Exceder Series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. The Wheelock Exceder Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AI-IJ inspection. The Wheelock Exceder Series of wall and ceiling notification appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts. The Contact Cover also acts as a shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed. The UMB allows for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra secure installation, while the ceiling models provide a captivated screw to prevent the screw from falling during installation. Technical Data TD450049EN Effective November 2016 Features Sleek modern aesthetics Finger slide switches Voltage test points Multiple voltages 3 Audible settings 90, 95, 99 dB Industry leading-8 candela settings on 1 device Wall: 1511575/30/75/95/110/135/185 Ceiling: 15/30/60/75/95/1151150/177 Universal mouting base Ceiling and wall Mounts to 5 backbox types: 1 gang, 2 gang, 4" square, 3.5" octal. & 4" octal. (100mm for international customers) Universal mounting base Contact cover (j. 'L Common base for wall and ceiling with 5 mounting options Voltage test points for quick troubleshooting and easy spot checking (wall models only) 2 EATON www.eaton.com HN Series HS Series ST Series Environmentally friendly Low current draw Up to 9 models now in 1 appliance draw® 12/24VDC on a single appliance Easy to remember model numbers ® Patented Note: Please read these specifications and associated installation instruc- tions, before using, specifying, or installing this product. Visit Eaton.com/ massnotification for current installation instructions. General Notes Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range' All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971). Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only). Compatibility and requirements Synchronize using the Wheelock5 Sync Modules or panels with built-in Wheelock® Patented Sync Protocol Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage Strobes produce 1 flash per second over the "Regulated Voltage" range Compliance UL 1971, UL 464, ULC, CSFM, FM ADAJNFPAJANSI/OSHA RoHS HN Series Technical Data TD450049EN HS Series Effective November 2016 ST Series Table 1. Strobe Ratings per UL Standard 1971 UL Max Current® 24VDC/24FWR 12VDC Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Model Range VDC ST 8.0-33.0 0.057 0.070 0.085 - 0.135 0.163 0.182 - 0.205 - - 0.253 0.110 0.140 SIC 8.0-33.0 0.061 - 0.085 0.103 0.135 0.163 - 0.182 - 0.205 0.253 - 0.110 - Table 2. Horn Strobe Ratings per UL 1971 &Anechoic at 24VDC UL Max Current® at Anechoic 99 dBA 24VDC 12VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.082 0.095 0.102 - 0.148 0.176 0.197 - 0.242 - - 0.282 0.125 0159 HSC 8.0-33.0 0.082 - 0.102 0.141 0.148 0.176 - 0.197 - 0.242 0.282 - 0.125 - UL Max Current® at Anechoic 95 dBA 24VDC 12VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.073 0.083 0,087 - 0.139 0.163 0.185 - 0.230 - - 0.282 0.122 0.153 HSC 8.0-33.0 0.073 - 0.087 0.128 0.139 0.163 - 0.185 - 0.230 0.272 - 0.122 - UL Max Current® at Anechoic 90 dBA 24VDC 12VDC Regulated Voltage Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.065 0.075 0.084 - 0.136 0.157 0.184 - 0.226 - - 0.267 0.120 0.148 HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 - 0.184 - 0.226 0.267 - 0.120 - ® Ut man current rating is the maximum RIMS Current within the listed voltage range (1 6-33 VDC for 24 VDC units). For strobes the UL man Currents usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the man Current IS usually at the maximum listed voltage (33 VOC for 24 VDC units). For unfiltered ratings, see installation instructions. Table 3. Horn Ratings per UL Anechoic Model legend Regulated Voltage Model Range VDC 99 dB 95 dB 90 dB HN = Horn R = Red HN 16-33.0 0.064 0.044 0.022 ST = Strobe A = Agent Lettering (strobes only) HNC 16-33.0 0.084 0.044 0.022 HS = Horn Strobe AL = Alert Lettering (strobes only) HN 8.0-17.5 0.047 0.026 0.017 C = Ceiling Mount N = No Lettering (strobes only) HNC 8.0-17.5 0.047 0.026 0.017 W = White Example 1: STRC = Strobe, Red, Ceiling Mount Table 4. Specification & Ordering Information [sample 2: HSR = Horn Strobe, Red, Wall Mount Sync WI DSM or Example 3: HSW = Horn Strobe, White, Wall Mount Wheelock Power 12/24 Mounting [sample 4: SiW-AL = Strobe. White, Wall Mount, Alert Lettering Model Strobe Candela Supplies VDC Options Horn Strobes HSR 15/1575/30/75/95/110/135/185 X X UMB® , HSW 15/1575/30/75/95/110/136/185 X X UMB® .. ' HSRC 15/30/60/75/95/115/150/177 X X UMB® HSWC 15/30/60/75/95/115/150/177 X It LiMB® - t.LI Strobes STIR 15/1575/30/75/95/110/135/185 It X UMB® STW 15/1575/30/75/95/110/135/185 X X UMB® , STRC 15/30/60/75/95/115/150/177 X X UMB® STWC 15/30/60(75/95/115/150/177 X X UMB®100 Horn HNR X X UMB® HNW It X UMB® HNRC X X UMB® HNWC It X UMB® ® 12 VDC models feature 15 & 15/75 settings © UMB = Universal Mounting Bose - Example: HSWC Example: HSR EATON www.eaton.com 3 Technical Data TD450049EN HN Series Effective November 2016 HS Series ST Series Architects and Engineers Specifications The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens, The Series shall be of low current design. Where multi- candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15175, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount, The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (eg., ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies or other manufacturer's panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization protocol. Wall Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal )CSFM), ULC, FM, RoHS Ceiling Appliances: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Eaton standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland, 01144122 United States Eaton .com Eaton Life safety & mass notification solutions 273 Branchport Ave. Long Branch, NJ 07740 Eaton.com/massnotification © 2016 Eaton E All Rights Reserved Eaton is a regetered trademark. Printed in USA Publication No. T0450049EN All other trademarks are property Powering Business Worldwide November 2016 of their respective owners. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-0785:0168 Page 1 of 1 CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: Cooper Wheelock Inc. 7246 16th St. E., Ste. 105, Sarasota, FL 34243 Contact: Thomas Conover (941) 487-2336 Email: thomaslconover@eaton.com DESIGN: Exceder Series: Models ST strobe, HS horn strobe and HN horn. Model ST is a synchronous and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an audible signal appliance. All units followed by R (red) or W (white). Additionally, a 'C' may be added for ceiling models and/or a '-NR' may be added for non-resettable models. For non -NR models and optional '5' for silver fascia may be added*. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Electrical: 12 VDC/24VDCIFWR Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185 Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177 INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. All models are for indoor use and for wall mount only or ceiling mount only* MARKING: Listee's name, model number, electrical/candela rating, and UL label. APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when used with separately listed electrically compatible fire alarm control units. Refer to listee's Installation Instructions Manual for details. *Rev. 9-24-09 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct ?Vl operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division