HomeMy WebLinkAboutCD 2020-0022; THE BEACON PHASE 3; FINAL SOILS REPORT; 2023-09-075710 Ruffin Road | San Diego, California 92123 | p. 858.576.1000 | www.ninyoandmoore.com September 7, 2023 Project No. 108375004 Mr. Will Dukes Asana Partners 11752 San Vicente Boulevard Los Angeles, California 90049 Subject: Second Update to Final As-Graded Report The Beacon Phase 3 7760 and 7770 El Camino Real, Carlsbad, California GR2021-0024 Dear Mr. Dukes: In accordance with your request, Ninyo & Moore has provided compaction testing services during the construction phase of The Beacon Phase 3 project at 7760 and 7770 El Camino Real in Carlsbad, California. Our services included the compaction testing of the earthwork operations performed for this project. This report summarizes our services and presents the results of our field and laboratory testing. PROJECT DESCRIPTION The project included tenant improvements to the existing buildings at 7760 and 7770 El Camino Real along with new exterior site improvements to the surrounding areas of the buildings. The focus of this report are the exterior improvements that included a trach enclosure, new landscaped islands in the parking lot, reconfiguration of the Americans with Disabilities Act (ADA) parking stalls, underground utilities, concrete curbs, sidewalks, landscaping, and a few gravity site walls. FIELD COMPACTION TESTING Our field technician was onsite on an on-call basis between February 6, 2023 and April 14, 2023 and onsite on July 9, 2023 and August 31, 2023 as well to test and retest water line trench backfill, utility trench backfill, subgrade soils, and aggregate base materials. Field density tests were performed by our technician in general accordance with the current version of ASTM International (ASTM) D 6938 (Nuclear Gauge Method). The specified relative compaction for general backfill materials associated with water line trenches and the subgrade soils for sidewalks, curbs, and gravity walls was 90 percent, as evaluated by ASTM D 1557. The specified relative compaction for the upper 1 foot of backfill JVin90 & iy\oore Geotechnical & Environmental Sciences Consultants Ninyo & Moore | 7760 and 7770 El Camino Real, Carlsbad, California | 108375004 | September 7, 2023 2 materials associated with water line and utility trenches beneath pavements along with subgrade soils for the parking lot pavements and the aggregate base materials was 95 percent, as evaluated by ASTM D 1557. The results of our field density tests are presented in Attachment A and the approximate test locations are shown on Figure 1. During the course of the project, failing subgrade tests were recorded for two of the gravity site walls. For the gravity site wall near the roundabout to the northeast of 7760 El Camino Real, the initial compaction test (SG-15) on the subgrade soil indicated a relative compaction of less than 90 percent, primarily due to the over optimum moisture content of the soil. Retests SG-16 and SG-17 were performed on subsequent days, which also indicated relative compactions of less than 90 percent. After performing the second retest, the contractor elected to proceed with the concrete placement for this gravity site wall. Subsequent to construction further retesting of this area was performed on June 9, 2023. The retest (RT-1) indicated a relative compaction meeting the specified 90 percent. Additionally, a compaction test (SG-32) was performed on the subgrade soil for a gravity site wall south of 7770 El Camino Real that initially indicated a relative compaction of less than 90 percent. Subsequent to construction further retesting of this area was performed on August 31, 2023. The retest (RT-2) indicated a relative compaction meeting the specified 90 percent. LABORATORY TESTING Laboratory testing was performed on the soil and aggregate base materials used during the earthwork operations to evaluate their modified Proctor and optimum moisture content relationships. The modified Proctor densities and optimum moisture contents were evaluated in general accordance with the ASTM D 1557, and the results are summarized in Table 1. The modified Proctor densities and optimum moisture contents of the aggregate base material represented by Soil Type Numbers 4 and 6, were provided by the material supplier and are also presented in Table 1. SUMMARY The field density tests performed for the earthwork operations associated with the subject project for permit GR2021-0024 indicated the specified relative compactions, after the retests were performed. Based on our observations and the results of our field and laboratory tests, it is the opinion of Ninyo & Moore that the earthwork were performed in accordance with the referenced reports (Ninyo & Moore, 2017 & 2021) and the project drawings (Drawing No. 532-1A), after retesting was performed. Ninyo & Moore | 7760 and 7770 El Camino Real, Carlsbad, California | 108375004 | September 7, 2023 3 LIMITATIONS The compaction testing services outlined in this report have been conducted in accordance with current practice and the standard of care exercised by geotechnical consultants performing similar tasks in this area. No warranty, expressed or implied, is made regarding the observations and conclusions expressed in this report. The reported test results represent the relative compaction and moisture content at the locations tested. It is important to note that the precision of field density tests and the modified Proctor tests is not exact and variations should be expected. The reported locations and elevations of the density tests were estimated from construction staking and the referenced plans (City of Carlsbad, 2022). Further accuracy is not implied. Respectfully submitted, NINYO & MOORE Jeffrey T. Kent, PE, GE Principal Engineer KWK/JTK/mp Attachments: References Figure 1 – Field Density Test Locations Table 1 – Modified Proctor Density Test Results Attachment A – Summary of Field Density Tests Ninyo & Moore | 7760 and 7770 El Camino Real, Carlsbad, California | 108375004 | September 7, 2023 4 REFERENCES City of Carlsbad, 2022, Carlsbad Grading Plans for: The Beacon Phase 3, 7760 & 7770 El Camino Real, Drawing No. 532-1A, Sheets 1 through 8: dated April 20. Ninyo & Moore, 2017, Geotechnical Evaluation, The Beacon Project, 7720 to 7750 El Camino Real, Carlsbad, California, Project No. 108375001: dated September 1. Ninyo & Moore, 2021, Update Geotechnical Evaluation, The Beacon La Costa – Phase 3, 7760 and 7770 El Camino Real, Carlsbad, California, Project No. 108375002: dated September 3. Ninyo & Moore, 2023, Updated Final As-Graded Report, The Beacon Phase 3, 7760 and 7770 El Camino Real, Carlsbad, California, GR2021-0024, Project No. 108375004: dated July 12. SG-36 SUBGRADE FIELD DENSITY TEST LEGEND FIELD DENSITY TEST LOCATIONS NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: BLUE PEAK ENGINEERING, 4/20/22. 0 FEET FIGURE 1 50 1000N 1 1 0 8 3 7 5 0 0 4 F D T A B , S G , W , U . D W G A O B AGGREGATE BASE FIELD DENSITY TESTAB-5 7760 AND 7770 EL CAMINO REAL CARLSBAD, CALIFORNIA 108375004 I 9/23 Geotechnical & Environmental Sciences Consultants U-1 UTILITY BACKFILL FIELD DENSITY TEST W-4 WATER BACKFILL FIELD DENSITY TEST U-1 SG-1 SG-2 SG-3 SG-5 SG-6 SG-7 SG-36 SG-4 SG-9 SG-8 SG-22,23 SG-18,19 SG-20,21 SG-10 SG-11 SG-26,27 W-1,2,3,4 SG-12 SG-13 SG-14SG-24,25 SG-28 SG-35 SG-29 SG-33 SG-31 SG-34 SG-30 AB-1,2 AB-3,4 AB-5 RT-2 RETEST OF SUBGRADE SG-15,16,17/RT-1 SG-32/RT-27760 EL CAMINO REAL FF=66.57 ----- r r • • Tf l TI T ~J ~' r: r -------- • • • • ----- ----- -------------------- Ninyo & Moore | 7760 and 7770 El Camino Real, Carlsbad, California | 108375004 | September 7, 2023 1 of 1 Table 1 – Modified Proctor Density Test Results Soil Type Number Description Proctor/Hveem Density (pcf) Optimum Moisture Content (%) 1 Sandy Clay 119.5 12.0 2 Sandy Clay 119.5 13.0 3 Sandy Clay (not used) 115.5 13.0 4 Recycled Aggregate Base 130.5 9.5 5 Silty Sand with Clay 123.5 11.5 6 Recycled Aggregate Base 118.5 11.5 7 Silty Sand (DG Materials) 137.0 8.0 Note: pcf = pounds per cubic foot Ninyo & Moore | 7760 and 7770 El Camino Real, Carlsbad, California | 108375004 | September 7, 2023 ATTACHMENT A Summary of Field Density Tests Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. Relative Compaction (%) TE S T R E S U L T S 7 Initials JVT Test Of Block No. UL 1140 Sand + Bottle Before (lbs) / (DS) 95 8.0 Test Location UTILITY TRENCH IN PARKING LOT EAST OF BUILDINGS Elev. or Depth (ft) 63.5 MOISTURE 95 137.0 129.7 Corrected Maximum Density (pcf) Soil Type Number 7.8 Coarse Fraction (lbs) 139.8 PASS Retest on (if applicable) Coarse Fraction (%) 56 9 SUMMARY OF FIELD DENSITY TESTS 1 ST A N D A R D & T E S T CO U N T S 141 Sand in Cone + Hole (lbs) / (DC) 1711 Permit No.:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 23 Test Date 4/14/23 10 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 784 Project Street Address: Jurisdiction: 690 8 10 Wet Density (pcf) Laboratory Maximum Density (pcf) Dry Density (pcf) Percent Moisture Pass/Fail Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) Tare (lbs) Soil + Rock + Tare (lbs) Sand + Bottle After (lbs) / (MS) NG Test No. Test Of UL WE T D E N S I T Y & RO C K C O N T E N T Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) Test No. 1 2 3 5 9 6 7 4 Finer Fraction (%) Sand in Cone (lbs) / (MC) 5710 Ruffin Road, San Diego, CA 92123 Test Type:UTILITY TRENCH BACKFILL 108375004_FDT_UTILITY_1 Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. PASS Relative Compaction (%) TE S T R E S U L T S 1 Initials JVT Test Of Block No. WM NG 3632029 Sand + Bottle Before (lbs) / (DS) WM WM 90 12.0 92 90 126.6 119.5 7 Test Location IN PARKING LOT OPPOSITE WALKWAY BETWEEN 7760 AND 7760 EL CAMINO REAL IN PARKING LOT OPPOSITE WALKWAY BETWEEN 7760 AND 7760 EL CAMINO REAL Elev. or Depth (ft) 62.5 62.5 107.7 12.0 16.1 1 9590 MOISTURE 90 119.5 107.9 Corrected Maximum Density (pcf) Soil Type Number 16.9 Coarse Fraction (lbs) 126.1 90 95 PASS Retest on (if applicable) Coarse Fraction (%) 129.6 8.0 8.4 137.0 7.9 7 8.0 137.0 5 140 6 249 233 NG 690 1711 NG 690 9 IN PARKING LOT OPPOSITE WALKWAY BETWEEN 7760 AND 7760 EL CAMINO REAL IN PARKING LOT OPPOSITE WALKWAY BETWEEN 7760 AND 7760 EL CAMINO REAL SUMMARY OF FIELD DENSITY TESTS 1 ST A N D A R D & T E S T CO U N T S 226 Sand in Cone + Hole (lbs) / (DC) 1714 Permit No.:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 63.0 1705 1711 23 63.5 Test Date 4/13/23 4/14/23 4/12/23 10 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 784 WM Project Street Address: Jurisdiction: 699 8 10 208 143 PASS Wet Density (pcf) 687 Laboratory Maximum Density (pcf) Dry Density (pcf) Percent Moisture Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) 125.0 137.2 Tare (lbs) Soil + Rock + Tare (lbs) Sand + Bottle After (lbs) / (MS) NG Test No. Test Of WM WE T D E N S I T Y & RO C K C O N T E N T Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) Test No. 1 2 3 5 9 6 7 4 4/14/23 Finer Fraction (%) Sand in Cone (lbs) / (MC) WM WM WM JVT JVT JVT 139.8 5710 Ruffin Road, San Diego, CA 92123 Test Type:WATER TRENCH BACKFILL 108375004_FDT_WATER_1 Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 5710 Ruffin Road, San Diego, CA 92123 Test Type:SUBGRADE 126.6 130.6132.0 NORTHSIDE OF 7760 EL CAMINO REAL NORTHSIDE OF 7760 EL CAMINO REAL 63.5 NORTHSIDE OF 7760 EL CAMINO REAL NORTHSIDE OF 7760 EL CAMINO REAL CURB AREA EAST OF 7760 EL CAMINO REAL JVT JVT JVT 2/6/23 Finer Fraction (%) Sand in Cone (lbs) / (MC) SW2/6/23 PD PD SW JVT JVT JVT JVT Test No. 1 2 3 5 9 6 7 4 JVT Sand + Bottle After (lbs) / (MS) 63.5 63.5 2/6/23 2/6/23 63.5 63.5 CG SW NG CG Test No. 2/6/23 Test Of PD WE T D E N S I T Y & RO C K C O N T E N T Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) 613 NG 1890 613 1656 146 1632 180 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) 127.5 128.4 Tare (lbs) Soil + Rock + Tare (lbs) PASS PASS PASS PASS Wet Density (pcf) 613613613 1464 613 Laboratory Maximum Density (pcf) Dry Density (pcf) Percent Moisture Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 784 SW 2/6/23 Project Street Address: Jurisdiction: 613 8 10 124 178 Permit No.:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 63.5 1890 CURB AREA EAST OF 7760 EL CAMINO REAL 1890 23 SW 63.5 63.5 Test Date 2/6/23 2/6/23 2/6/23 1890 10 NG 1890 1890 1890 9 TRASH ENCLOSURE NORTHSIDE OF 7760 EL CAMINO REAL SUMMARY OF FIELD DENSITY TESTS 1 2/6/23 ST A N D A R D & T E S T CO U N T S 101 Sand in Cone + Hole (lbs) / (DC) 1890 JVT 1441 1334 NG 613 1890 NG 613 5 126 120 180 172 NG 1890 NGNG 6 SW SW 1432 169 1500 1369 613 123.0122.9128.0 128.6 11.4 5 91 94 123.5 119.5123.5 123.5 11.5 107.1 110.4112.6 123.5 55 13.0 92 11.5 11.5 11.5 90 90 PASSPASSPASS 14.2 13.6 12.9 121.4 11.5 13.8 123.5 8.76.7 Coarse Fraction (lbs) 128.6 95 98 PASS Retest on (if applicable) Coarse Fraction (%) MOISTURE 98 123.5 120.5 Corrected Maximum Density (pcf) Soil Type Number 117.2 11.5 8.8 5 9090 Test Location TRASH ENCLOSURE TRASH ENCLOSURE Elev. or Depth (ft) 63.5 63.5 CG CG 90 11.5 91 90 112.8 123.5 5 90 90 55 NG 14781447 Sand + Bottle Before (lbs) / (DS) PD PD SW NG Initials JVT Test Of Block No. PD SW SW 90 118.0 96 123.5 11.5 119.5 90 13.0 90 2 90 2 111.4 8.5 14.7 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 115.7 PASS Relative Compaction (%) TE S T R E S U L T S 5 108375004_FDT_SUBGRADE_1 Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 119.4 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 113.5 116.5119.7 123.5123.5 97 119.5 94 119.5 119.5 125.0 121.7 119.8 103 119.5 98.7 109.8 119.5 106 99 NG 1656 NG 109134 Sand in Cone + Hole (lbs) / (DC) 1890 2/17/23 Test No. 1676 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) Test Of Block No. CG CG CG CG JVT JVT JVT JVT Initials 90 13.0 Test Location CURB AREA EAST OF 7760 EL CAMINO REAL CURB AREA EAST OF 7770 EL CAMINO REAL Elev. or Depth (ft) 63.5 63.5 90 83 1 CG 90 92 5 11.5 11.5 123.5 92 119.5 110.5 10.3 Coarse Fraction (lbs) 121.9 Percent Moisture 2 Coarse/Finer Fraction in Max (%) 63.5 63.5 66.0 WB2/15/23 2/15/23 2/15/23 WB JVT MOISTURE JVT JVT JVT JVT JVT SW WB WB 8.0 6.7 94 119.5 92 101.0 5 90 90 1 100 12.0 9090 1 90 1115 90 90 11.5 12.0 12.0 12.0 12.0 12.0 8585 17.8 112.0 16.5 15.3 13.4 101.7 7.77.3 20.5 115.0 126.6 WB WB WB NG 1895 SW 180192227 201 188 1895 Test No. Laboratory Maximum Density (pcf) 1892 613 18 SIDEWALK BETWEEN 7760 AND 7770 EL CAMINO REAL 1892 12 13 20 612 WB 1916 WB WB Wet Density (pcf) 15 5710 Ruffin Road, San Diego, CA 92123 Test Type:SUBGRADE 2/16/23 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 63.5 65.0 14 Test Date 2/7/23 63.5 SUMMARY OF FIELD DENSITY TESTS 610 14441470 1505 NG 606 1892 610 13831746 1962 1497 CG CG NG 606 612 11 12 606 CURB AREA EAST OF 7770 EL CAMINO REAL CURB AREA EAST OF 7770 EL CAMINO REAL 1880 20 NG 1895 NG 17 1814 CG 1671 2/6/23 11 2/16/23 ST A N D A R D & T E S T CO U N T S Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG Corrected Maximum Density (pcf) Optimum Moisture (%) PASS Specified Relative Compaction (%) PASS FAIL FAIL FAIL PASS PASSPASS PASSPass/Fail Retest on (if applicable) PASS RT-116 17 TE S T R E S U L T S Soil Type Number Relative Compaction (%) Dry Density (pcf) Soil + Rock + Tare (lbs) 122.6 127.7 13 WE T D E N S I T Y & RO C K C O N T E N T Tare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 2/7/23 2/7/23 Coarse Fraction (%) Test Of GRAVITY WALL FOOTINGS NEAR NORTH ENTRANCE GRAVITY WALL FOOTINGS NEAR NORTH ENTRANCE 65.0 GRAVITY WALL FOOTINGS NEAR NORTH ENTRANCE GRAVITY WALL FOOTINGS BETWEEN 7760 AND 7770 EL CAMINO REAL GRAVITY WALL FOOTINGS BETWEEN 7760 AND 7770 EL CAMINO REAL 63.5 Finer Fraction (%) 609 128.6 NG 612 1890 NG 1890 127.0 108375004_FDT_SUBGRADE_1 Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 26 27 SIDEWALK EAST OF 7770 EL CAMINO REAL 25 2/21/23 604 NG 28 CURB FOR PARKING STALLS SOUTH OF 7770 EL CAMINO REAL 1877 22 23 30 30 SW NG NG 1877 2926 CG CG NG 27 2824 NG SW SW Test No. 21 22 23 25 2/21/23 66.0 66.0 SW2/21/23 JVT JVT 2/21/23 66.0 66.0JVT Test Of 2/21/23 119.5 1877 18771877 1877 612612 15.3 118.5 116.8 2051 124.2 124.3 13.0 12.012.0 1 119.5 PASS PASS PASS PASS Wet Density (pcf) Laboratory Maximum Density (pcf) 124.5 123.7 9.0 90 606 Percent Moisture 130.9 128.7 8.4 Sand in Cone + Hole (lbs) / (DC)1408 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 66.024 Test Date 2/20/23 2/20/23 2/21/23 WALL FOOTINGS NORTHWEST OF 7770 EL CAMINO REAL SIDEWALK EAST OF 7770 EL CAMINO REAL Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 65.0 JVT JVT JVT SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type:SUBGRADE CG NG 2302 NG 612 1885 NG 606 112 190 SW 2452 2034 1882 169 612612612 21592045 2063 115 151 125 1885 186171 170 129.4 12.0 1 90 12.0 9090 111 13.2 Coarse Fraction (%) Finer Fraction (%) 120 PASS 15.0 CG CG Sand + Bottle Before (lbs) / (DS) 3/7/23 29 PASS Retest on (if applicable) Corrected Maximum Density (pcf) 90 Soil Type Number 100 119.5 119.4 Pass/Fail Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) TE S T R E S U L T S 108.9 8.8 123.0 Initials Test Location SIDEWALK BETWEEN 7760 AND 7770 EL CAMINO REAL WALL FOOTINGS NORTHWEST OF 7770 EL CAMINO REAL Elev. or Depth (ft) 66.0 65.0 JVT Block No. SW WB 107.2 11.8 111.1 9.5MOISTURE 64.0 21 1880 609Sand + Bottle After (lbs) / (MS) Test No. ST A N D A R D & T E S T CO U N T S WE T D E N S I T Y & RO C K C O N T E N T Tare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) WB SW SW 119.5 SIDEWALK EAST OF 7760 EL CAMINO REAL 66.0 SIDEWALK EAST OF 7760 EL CAMINO REAL ISLAND IN PARKING LOT SOUTHEAST OF 7770 EL CAMINO REAL SOUTH ISLAND IN PARKING LOT 113.9 12.0 11 1 90 91 90 PASS 90 9597 PASS 2/17/23 Test Of SW WB WB Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 1359 1385 CG SW Coarse Fraction (lbs) JVT JVT JVT NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 90 Dry Density (pcf) Relative Compaction (%) 115.6 14.2 95 1 PASSPASS 119.5 107.6 107.8 119.5 119.5119.5 90 12.0 90 113.7 107.7 119.5 90 1 119.5 90 90 93 12.0 12.0 12.012.0 108375004_FDT_SUBGRADE_1 Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 36 37 CUTOUT AT PARKING STALLS SOUTHEAST OF 7770 EL CAMINO REAL 35 3/18/23 38 1895 32 33 40 40 NG 1895 3936 37 3834 NG PL PL Test No. 31 32 33 35 63.0 65.0 PL3/18/23 JVT JVT Test Of 119.5 1895 608 129.4 125.3 1030 125.8 15.5 12.012.0 1 119.5 PASS PASS PASS Wet Density (pcf) Laboratory Maximum Density (pcf) 11.2 604 Percent Moisture 120.2 131.7 13.8 Sand in Cone + Hole (lbs) / (DC)2186 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 63.034 Test Date 3/7/23 3/18/23 3/18/23 PARKING STALLS SOUTH OF 7770 EL CAMINO REAL PARKING STALLS SOUTH OF 7770 EL CAMINO REAL Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 63.0 JVT JVT JVT SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type:SUBGRADE 303 NG 608 1895 NG 608 180 PL 620 608 144 146 1882 220 196 122.2 12.0 1 95 11.5 95 1 20.3 Coarse Fraction (%) Finer Fraction (%) 166 Sand + Bottle Before (lbs) / (DS) 39 PASS Retest on (if applicable) Corrected Maximum Density (pcf) 90 Soil Type Number 90 119.5 107.4 Pass/Fail Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) TE S T R E S U L T S 113.3 14.2 Initials Test Location CURB FOR PARKING STALLS SOUTH OF 7770 EL CAMINO REAL GRAVITY WALL FOOTINGS SOUTH OF 7770 EL CAMINO REAL Elev. or Depth (ft) 64.0 62.0 JVT Block No. CG WB 112.7 11.3 113.0 MOISTURE 31 1882 604Sand + Bottle After (lbs) / (MS) Test No. ST A N D A R D & T E S T CO U N T S WE T D E N S I T Y & RO C K C O N T E N T Tare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) PL PL 119.5 MUCKED OUT PARKING STALLS NORTH OF 7760 EL CAMINO REAL 114.0 12.0 11 6 95 95 95 PASS 95 9584 FAIL 3/7/23 Test Of CG WB PL Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 2213 283 PL Coarse Fraction (lbs) NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. RT-2 90 Dry Density (pcf) Relative Compaction (%) 99.9 119.5118.5 95 12.0 108375004_FDT_SUBGRADE_1 Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. PASS Relative Compaction (%) TE S T R E S U L T S 4 95 112.1 95 118.5 11.5 11.5 Initials JVT Test Of Block No. AB NG 15701583 Sand + Bottle Before (lbs) / (DS) AB AB 95 9.5 130.5 96 95 113.6 6 Test Location TRASH ENCLOSURE TRASH ENCLOSURE Elev. or Depth (ft) 63.5 63.5 123.7 130.5 9.5 10.2 4 9595 MOISTURE 95 123.8 Corrected Maximum Density (pcf) Soil Type Number 9.8 Coarse Fraction (lbs) 135.9 95 96 PASS Retest on (if applicable) Coarse Fraction (%) 113.4 11.5 11.2 118.5 10.8 6 11.5 118.5 6 125.0 608 5 142 146 1895 NG 6 AB 606 620 NG 608 1895 NG 608 9 PARKING STALLS SOUTH OF 7770 EL CAMINO REAL PARKING STALLS SOUTH OF 7770 EL CAMINO REAL SUMMARY OF FIELD DENSITY TESTS 1 ST A N D A R D & T E S T CO U N T S 135 Sand in Cone + Hole (lbs) / (DC) 1892 Permit No.:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALFIORNIA 2021-0024 63.5 1892 1895 23 63.5 63.5 Test Date 2/7/23 3/18/23 2/7/23 10 Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 784 AB Project Street Address: Jurisdiction: 606 8 10 141 144 PASS PASS Wet Density (pcf) 606 626 Laboratory Maximum Density (pcf) Dry Density (pcf) Percent Moisture Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) 136.3 126.3 Tare (lbs) Soil + Rock + Tare (lbs) Sand + Bottle After (lbs) / (MS) NG Test No. Test Of AB WE T D E N S I T Y & RO C K C O N T E N T Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) Test No. 1 2 3 5 9 6 7 4 3/18/23 Finer Fraction (%) Sand in Cone (lbs) / (MC) AB3/18/23 AB AB AB JVT JVT JVT JVT PARKING STALLS SOUTHEAST OF 7770 EL CAMINO REAL 125.7 5710 Ruffin Road, San Diego, CA 92123 Test Type:AGGREGATE BASE 108375004_FDT_BASE_1 Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 5710 Ruffin Road, San Diego, CA 92123 Test Type:SUBGRADE - RETEST Finer Fraction (%) Sand in Cone (lbs) / (MC) WBTJW Test No. RT-1 RT-2 Sand + Bottle After (lbs) / (MS) SC Test No. Test Of WB WE T D E N S I T Y & RO C K C O N T E N T Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) 122.6 Tare (lbs) Soil + Rock + Tare (lbs) Wet Density (pcf) 645 10.1 Laboratory Maximum Density (pcf) Dry Density (pcf) Percent Moisture Project Name:ASANA/BEACON/7760 AND 7770 EL CAMINO REAL Project No:108375004 784 Project Street Address: Jurisdiction: 4.89 164 Permit No.:CITY OF CARLSBAD Plan File No.: 7760 AND 7770 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2021-0024 1704 23 Test Date 8/31/23 6/9/23 109 SUMMARY OF FIELD DENSITY TESTS 1 ST A N D A R D & T E S T CO U N T S 2.961 Sand in Cone + Hole (lbs) / (DC) 14.47 56 12.0 Coarse Fraction (lbs) 125.0 90 PASS Retest on (if applicable) Coarse Fraction (%) MOISTURE 93 119.5 111.6 Corrected Maximum Density (pcf) Soil Type Number 107.3 12.0 14.3 1 90 Test Location ADJACENT TO GRAVITY WALL CURB RETAINING WALL FOOTING Elev. or Depth (ft) 63.5 62.0 90 12.0 0.6 119.5 NG 6429.57 Sand + Bottle Before (lbs) / (DS) WB Initials KVT Test Of Block No. WB NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. Relative Compaction (%) TE S T R E S U L T S 1 108375004_FDT_SUBGRADE_RETEST Field Density Test Sheet 2013 v 3.0 I