HomeMy WebLinkAbout1808 ASTON AVE; 200; AS020100; Permit9/14/22, 3:38 PM AS020100 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 1808 ASTON AV
Permit Type: SPRINK
Parcel No: 2121200700
Lot #: 0
Reference No.:
PC #:
Permit No: AS020I00
Status: ISSUED
Applied 7/19/2002
Approved: 8/6/2002
Issued: 8/6/2002
Inspector:
Project Title: SPEC SUITE #200
Applicant: Owner:
ASTON VIEWS L L C
8799 BALBOA AVE #260
SAN DIEGO CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
100 0 100 -[ 0
about:blank 1/1
-'C
Carlsbad
Office of Fire Protection Services
POLICY
October 25, 2000
SMOKE FIRE DAMPERS
Background - The 1997 California Building Code Section 713.10 has revised the
actuation requirements for smoke dampers. Generally, smoke dampers are require
d
t
o
b
e
actuated by either a smoke detector or a total-coverage smoke-detection system. Deput
y
Fire Marshals, Plan Checkers and Field Inspectors have found that stand-alone smok
e
detectors used to actuate these dampers are not listed with the California State Fir
e
Marshal for that purpose. This complicates and extends the plan review process and
causes delays in final inspection in the field. Therefore, until industry lists stand-alone
smoke detectors for use in actuating smoke-fire dampers, the following policy will be
used in the City of Carlsbad:
Policy - Smoke fire dampers are required to be wired to an approved fire alarm system.
Building plan submittals are required to note that the smoke fire dampers, and smoke
detectors that actuate the dampers comply with the above provision. A separate subm
i
t
t
a
l
to the Fire Department from a licensed fire alarm contractor is required for plan review
o
f
these systems. The submittal shall include floor plans, mechanical details of the dampe
r
s
,
wiring diagrams, permit fees, State Fire Marshal listings and manufacturer's cut shee
t
s
o
n
all devices.
This policy may be reconsidered and modified when the smoke detector manufacture
r
s
have listed these devices with the California State Fire Marshal for this specific purp
o
s
e
.
Building permits including such stand-alone systems will not be issued until it can b
e
demonstrated prior to permit issuance that all components of such systems are listed
f
o
r
their intended purpose by the California State Fire Marshal's Office.
/F t
Fire Marshal Approval Date
- C AV 1-7 Q A%