HomeMy WebLinkAbout5805 ARMADA DR; ; FS030007; PermitCity of Carlsbad
Fixed Systems Permit
Permit No: FS030007
Job Address: 5805 ARMADA DR
Permit Type: FIXSYS
Parcel No: 2111110109
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 3/12/2003
Approved: 3/19/2003
Issued: 3/19/2003
Inspector:
Project Title: GRAND PACIFIC RESORTS
Applicant: Owner:
HAWKINS WAYNE&PAMELA J
C/O GRAND PACIFIC PALISADES
5900 PASTEUR CT #200
CARLSBAD CA
Fees ($) 1 Add'l Fees ($) Total ($) Balance ($)
100 0 100 0
r0306
City Fire Equipment Inc.
1816 Country Club Drive
Escondido Calif. 92029
C-16 756636
Grand Pacific Resorts
5805 Armada Drive
H Carlsbad,Ca.
CITY OF CARLS51 j FIRE DEPARTME. I APPROVED
Subject to field inspection and requj cg tests fl0t8t1on5 hereon conditions In
Vmftn of my 1417. SCHEDULE FIRE DEPT.
By
pHONE (760) 602-4660
FS030co~-
G/&) O//o3
System shall be installed in accordance with current U.L.300,NFPA17a and 96 Standards
and manufacturers requirements
The system shall have a means of manual actuation from either the system control head
or a remote manual pull station.
The manual actuator shall be in path of egress no higher than 48" above finished floor
All discharge nozzles shall be located within manufacturers minimum and maximum
distance and coverage guideline
All penetrations in exhaust hood shall have a liquid-tight continuous weld or utilize a
U.L. listed seal adapter.
Each exhaust duct with-in the protected hood(s) shall have not less than one nozzle and
one detector located per manufacturer guidelines.
All fuel and power sources below protected exhaust hood(s) shall be interfaced to
automatically shut down upon system activation
Make-up and or supply air fans integral to the exhaust hood(s) being protected shall be
interfaced to automatically shut down upon system activation.
The system shall be interfaced with the building fire alarm system(if applicable) and
annunciate the F.A.C.P. upon system discharge.
A minimum of one (1) 2A1OBC and one (1)K type hand portable fire extinguisher shall
be provided with-in the occupancy locat in the path of egress.. Actual location subj5ct to fire
department approval.
,
ed
()11. Total flow points required for ¶ is / per
manufacturer
Total flow points available with a - is _\_ per
manufacturer
-
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-9
7-1-98 REV. 4
NOZZLE PLACEMENT REQUIREMENTS (Continued)
Plenum Protection (Continued)
For a plenum, either single or "V" bank, with a linear extension
longer than 8 feet (2.4 m), each bank may be protected using one
1 nozzle every 8 ft. (2.4 m) or less depending on the overall
length of the plenum. See Figure 28. The nozzles may point in the
opposite directions as tong as the entire plenum area is protected,
and the 8 ft. (2.4 m) limitation is not exceeded. See Figure 29. The
nozzle positioning shown in Figure 30 is not an acceptable method
of protection because the plenum area directly under the tee is not
within the discharge pattern of either nozzle.
8 FT (2.4 111)
MAXIMUM
8 Ft (2.4 rn)
MAXIMUM
8 FT. (2.4 m)
MAXIMUM
24 FT (7.2 m)
MAXIMUM
Appliance Protection
The following pages detail types of appliance protection. Each
design requires several factors: correct nozzle choice, correct noz-
zle height above hazard, correct nozzle location and correct aim-
ing point.
Fryer - Single Nozzle Protection
1. Design requirements for fryers are broken down into two
types.
FRYERS WITHOUT DRIPBOARDS
If the fryer does not include a dripboard, measure the
internal depth (horizontal dimension from front to back)
and length of the frypot.
FRYERS WITH DRIPBOARDS
If the fryer includes any dripboard areas, measure both
the internal depth (horizontal dimension from front to
back) and length of the frypot portion, and then measure
the internal depth and length of the overall hazard area
including any dripboard areas.
2. Using Table, Maximum Cooking Area Dimension - Single
Nozzle Fryer Protection," determine which nozzle is needed
to protect the fryer based on the maximum dimensions listed.
A. If the fryer does not include a dripboard, use the maxi-
mum dimensions listed in the first column of the table to
select the correct nozzle.
8 FT. (2.4 m)
MAXIMUM
8 FT. (2.4 m)
MAXIMUM
FIGURE 28
0002% B. If the fryer includes any dripboard areas, use both the
maximum frypot dimensions in the first column of the
table, and the maximum overall dimensions in the second
column of the table to select the correct nozzle. None of
the maximum dimensions in either column may be
exceeded.
8 FT. (2.4 m)
MAXIMUM
3. If either the maximum frypot or the overall sizes are exceed-
ed, an additional nozzle(s) will be required. Refer to the mul-
tiple nozzle requirements.
Example: A fryer with a dripboard. The inside of the frypot without
the dripboard measures 18 in. in depth x 18 in. in length (46 cm x
46 cm) and the inside of the overall area including the dripboard
measures 18 in. in depth x 24 in. in length (46 cm x 61 cm). From
the Table "Maximum Cooking Area Dimension - Single Nozzle
Fryer Protection," either the 3N or the 290 nozzle should be select-
ed to protect the fryer, depending on the maximum nozzle height
above the fryer and the positioning requirements allowed. Refer to
appropriate Figures.
24 FT. (7.2 m(
MAXIMUM
FIGURE 29
000207
FIGURE 30
0002%
SECTION W SYSTEM DESIGN
UL-EX. 3470 ULC CEx747 Page 4-6
7-1-98 REV. 2
NOZZLE PLACEMENT REQUIREMENTS (Continued
Duct Protection (Continued)
9. Multiple-Nozzle Duct Protection:
For ducts larger than 150 in. (254 cm) perimetei, the total
perimeter of the duct must be divided by 75. It the answer con-
tains a decimal (or fraction), it must be rounded-up to the near-
est whole number. This answer signifies the number of equal-
ly-sized modules in which the duct must be divided. The diag-
onal dimension of each module must not exceed 35.5 in.
(90.2 cm). If diagonal dimension is exceeded, additional mod-
ule divisions must he added until the diagonal dimension is not
exceeded. A nozzle must then he centered in each module.
Example: Figure 20 shows a duct opening of 270 in.
(686 cm) perimeter. By dividing 270 in. (686 cm) by
75, it is determined that the duct must be divided
Into 4 equally-sized modules. Because the diago-
nal dimension of each module is 33.54 in,
(85.2 cm), It is within the maximum limb Ut 35.5 in.
(90.2 cm) and therefore acceptable as shown in
Figure 21. One nozzle is then centered in each
module as shown in Figure 22.
FIGURE 20
3354 IN
- (65.2rim
33.S4 IN.
165.2 ml
—S3.54IN.
33.5415
(76.3
- (76.1 cm)
FIGURE 21
ii(llilimfl
FIGURE 22
The chart below shows the maximum protection available from
each duct nozzle
Part 3.0 Gallon 1.5 Gallon
escbption No. Syrn . .Sy.iom.........
1W Nozzle 419336 Maximum Maximum
27 in. (69 cm) 27 in. (69 urn)
Perimeter Perimeter
2W Nozzle 419337 Maximum Maximum
75 in. (191 cm) 75 in, (191 cm)
Perimeter Perimeter
2WH Nozzle 78078 Maximum
75 in. (191 cm)
Perimeter
Electrostatic Precipitator Protection
Some restaurant ventilating ducts have an electrostatic precipita-
for installed at or near the base. These precipitators are used to
aid in the cleaning of exhaust air.
Normally electrostatic precipitators do not require protection but
shoulct the 'authority having jurisdiction" require protection, use
the following guidelines.
Ducts with precipitators located at or near the base can be pro-
tected using duct nozzle(s) above the precipitator and 1/2N noz-
zle(s) (Part No. 419334) for the precipitator. One 1/2N nozzle must
be used for each cell being protected. This nozzle tip is stamped
with 1/2N, indicating that it is a 1/2-flow nozzle and must be count-
ed as 1/2 flow number.
When protecting ducts equipped with precipitators, the duct noz-
3/IN
- 7' ' " zle(s) must be installed above the precipitator and aimed to dis-
(74 .. in) charge downstream. If the area above the precipitator is a duct,
the nozzle(s) must be positioned according to duct protection
guidelines. If the area above the precipitator is a transition, the
transition guidelines must be followed. See Figure 20,
SECTION 1V - SYSTEM DESIGN
UL-EX. 3470 ULC CEx747 Page 4-34
7-1-98 REV.4
TANK AND CARTRIDGE REQUIREMENTS
Once the hazard analysis is completed and the total nozzle flow
numbers are established, the quantity and size of agent tanks and
cartridges needed to supply the nozzles with the proper volumes
of agent at the proper flow rates can be determined. For cartridges
used in the regulated release mechanism, flow capacities, tank
quantities and sizes, and regulated release cartridge options are
given in the table below.
Total Quantity and Regulated Release
Flow Size of Cartridge Options
Numbers* Tank(s) Nitrogen Carbon Dioxide
1— 5 (1) 1.5 Gallon LT-20-R (7032) 101 -10 (15850)
6-11 (1) 3.0 Gallon LT-30-R (5373) 101-20 (17492)
11 —16 (1) 1.5 Gallon Double (73022) 101-30 (15851)
(1) 3.0 Gallon
16-22 (2) 3.0 Gallon Double (73022) 101-30 (15851)**
When one or more regulated actuators are used, the following
lank and cartridge combinations apply for each regulated actuator:
Regulated Actuator Regulated Actuator
Tank(s) Cartridge
(1) 1.5 Gallon LT-20-R or 101-10
(1) 3.0 Gallon LT-30-R or 101-20
(1) 1.5 Gallon and LT-A-101-30 or 10130**
3.0 Gallon
3.0 Gallon LT-A-101-30 or 101 30**
For exceptions to maximum flow numbers, son Distribution Piping Requirements for 1,5 gal-
lon and 30 gallon systems in this Section.
The 101-30 cartridge Pert No. 15851, can not be used when (2) two 3.0 gallon tanks are man-
ilolded together,(
For higher total flow numbers (23 to 110), multiple cartridges and
regulated actuators are required as shown in the System Selection
Guide in Section IX - Appendix.
ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS
This section contains the guidelines for installing the actuation and
expellant gas lines between the regulated release mechanism reg-
ulator, each regulated actuator regulator, and each agent tank.
These limitations should be considered when selecting the com-
ponent mounting locations.
Actuation Gas Line - 6 to 8* Tanks Maximum
8 Tank maximum reflects the utilization of 3 tank regulated actuators.
Use only 1/4 in. Schedule 40 black iron, hot-dipped galva-
nized, chrome-plated, or stainless steel pipe and fittings.
The actuation gas line piping is installed from the regulated
release mechanism to each regulated actuator connected
within the system. The total length of the actuation gas line
from the regulated release assembly to the regulated actuator
assembly(ies) must not exceed 20 ft. (6 ci) when using an
LT-20-R (Part No. 7032), an LT-30-R nitrogen cartridge (Part
No. 5373), or a 101 -10 (Part No. 15850) or a 101 -20 (Part No.
17492) carbon dioxide cartridge. See Figure 73.
REGULATED ACTUATOR ASSEMBLY
EXPELLANT GAS LINES
NOT INCLUDED IN ACTUATION
GAS LINE LENGTH TOTALS
REGULATED
ACTUATOR
ACTUATION GAS LINE WITH AN LT-20-R,
LT-30-R, 101-10 OR 101-20 CARTRIDGE ~
REGULATED
MAXIMUM LENGTH OF 20 FT. (
MAXIMUM NO. OF FITTINGS
ACTUATOR
ASSEMBLY
ANSULAUTOMAN"
ASSEMBLY
REGULATED RELEASE
FIGURE 73
000775
NOZZLE PLACEMENT REQUIREMENTS (Continued)
2-Flow Griddle Protection (Continued)
Option 2 - Nozzle Perimeter Located
High Proximity Application: 30 in. to 50 in. (76 cm to 127 cm)
above the cooking surface.
This high proximity application uses the 260 nozzle, Part No.
419341.
The nozzle tip is stamped with 260 indicating this is a two-flow '
nozzle and must be counted as two flow numbers.
One 260 nozzle will protect a maximum cooking area of 1440 sq.
in. (9290 sq. cm) with a maximum dimension of 48 in. (122 cm).
When using this nozzle for griddle protection, the nozzle must be
positioned along the cooking surface perimeter to 2 in.
(5.1 cm) inside perimeter, and aimed at the center of the cooking
'surface. See Figure 52 and 53.
NOZZLE LOCATION I 0-2 IN. (0.-Scm) )ifl
INSIDE PERIMETER 50 IN.
- OF COOKING SURFACE (127 cm) I I ' MAXIMUM I HEIGHT
OF 260
NOZZLE TIP
I / I 301N.(76
(cm) I
I MINIMUM I
EDGE HEIGHT
/ OF 260 I
COOKING I NOZZLE TIP I
SURFACE I
000243
FIGURE 52
000243
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-21
7-1-98 REV. 2
- COOKING AREA
I MIDPOINT OF
COOKING SURFACE ( -
COOKING
AREA
I AIM POINT
II
260 NOZZLE LOCATED ALONG COOKING SURFACE EDGE
ANY SIDE OF GRIDDLE SURFACE
WITHIN 0-2 IN. (0-sCM) OF
COOKING SURFACE EDGE.
NOZZLE MUST BE AIMED AT MID-
POINT OF COOKING SURFACE.
FIGURE 53 000241
:ING
FIGURE 45
SECTION-IT - SYSTEM DESIGN
'IL JLX. 3470 ULCCEx747 Page 4-16
-1-98 REV. 4
INOZZLE PLACEMENT REQUIREMENTS (Continued)
Flange Protection 2-Flow Nozzle
ugh Proximity Application (2-Flow Nozzle): 40 in. to 50 in.
(102 cm to 127 cm) above the cooking surface.
1. he high proximity application uses the 245 nozzle, Part No.
H19340.
±he nozzle tip is stamped with 245 indicating this is a two-flow 245 NOZZLE TIP
tzzle and must be counted as two flow numbers. LOCATION CENTER 0
e 245 nozzle will protect a maximum cooking area of 672 sq in
COOKING SURFACE OR
4335 sq. cm) with a maximum longest dimension of 28 in. (71 11 IN. (29 cm)
MAXIMUM FROM
4m). CENTERLINE OF NOL
'I TO CENTER OF ANY
When using this nozzle for range protection, the nozzle must BURNER
4 die pointed vertically down and positioned as shown in Figures
245 NOZZLE TIP LOCATION if and 45.
CENTERLINE OF COOKING SURFACE
-7 I
245 NOZZLE TIP t 50 IN. LOCATION CENTER 0
t
(127 cm) COOKING SURFACE
MAXIMUM OR
HEIGHT 11 3/8 IN. (29 cm) OF 245 MAXIMUM FROM NOE CENTERLINE OF NOZ
I
TIP TO CENTER OF ANY i BURNER 40 IN. I
(102 CM) I
MINIMUM I
HEIGHT I
0F245 I
NOZZLE I
ITip
000236
!0000 1
FIGURE 44
NOTICE
Four burners shown in Figure 45. For single or
double burners, locate nozzle at center of cook-
ing surface or 11 3/8 in. (29 cm) maximum from
nozzle centerline to center of any burner.
ING