HomeMy WebLinkAbout2020 CASSIA RD; ; AS070250; Permit11/3/2020 AS070250 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 2020 CASSIA RD
Permit Type: SPRINK
Parcel No: 2150210200
Lot #: 0
Reference No.:
Permit No: AS070250
Status: ISSUED
Applied 10/12/2007
Approved: 10/17/2007
Issued: 10/17/2007
PC #: Inspector:
Project Title: CASSIA MEDICAL OFFICE BLDG TI FIRE SPRINKLER PLAN CHECK
& INSPECTION
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
FRANZ FAMILY REVOCABLE TRUST 06-26-
96
P0 BOX 2711
RANCHO SANTA FE CA
L Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
4C tauuic®®
AUTOMATIC SPRINKQ
FIRE PROTECTION PRO cTs4O.1O
V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
<
designed to produce a
hemispherical spray pat-
tern for standard commer-
cial applications. They are
V2708 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo-
() ()
J responsive,
rates state-of-the-art, heat
frangible glass
See Victaulic bulb design (standard or
publication 10,51 for details. quick response) for prompt,
V2708 ...._ precise operation.
Pendent
V2703 -
V2704
Upright
The die cast frame is more
streamlined and attractive
than traditional sand cast
frames. It is cast with a
hex-shaped wrench boss to
allow easy tightening from
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to 3/4" (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
attire reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
TECHNICAL SPECIFICATIONS
Models: V2703, V2704. V2707
V2708
Style: Pendent. Uptight or
Recessed Pendent
Nominal Orifice Size:
½' (13 mm)
K-Factor: 5.6 Imp. (8.1 S.1.^)
Nominal Thread Size:
1/2' NPI' (IS tutu)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (3450 kPa)
Mm. Operating Pressure:
7 psi (48 kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector:
Bronze per UNS 022000
Pendent Deflector:
Bronze per UNS C51000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
U Standard: 5,0 mm
U Quick Response: 3.0 mm
Load Screw: Bronze per UNS
065100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Tellorl* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS 530200
ACCESSORIES
Installation Wrench:
U Open End: V27
U Recessed: V38, V38-3
U Socket: V27
Finishes:
U Plain brass
U Chrome plated
U White painted*v
U Custom painted
U Lead"
155, 200, 286SR Only:
U Wax**
U Wax overlead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE. Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mea-
sured in Bar, multiply S.!. units by
10.0.
Teflon is a registered trademark of
Dupont co.
UL Listed for corrosion resistance in
till configurations.
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-vlc (1-800-742-5842) Phone: 905-884-7444 Phone: 32-9-381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fan: 905-884-9774 Fan: 32-9-380-4438 Fax: 610-559-3608 Fax: 65.6235-0535
e-mail:pitkvit@victaalic.com e-mail: vitcanada@victnulic.com e-mail: viteuro@lsittaulit.be e-mail: vical@victaulic.com e-mail: vicap@victaulic.com
2544 Rev.O 8/03 5 Registered Trademark of Victaulic øCopynght 2003 Victaulic Printed in U.S.A.
I _j
APPROVALS!LISTINGS
Nominal Approved Temperature Ratings *F/°C
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.I. Response Type UL FM ULC NYC1MEAt CSFM §
1h 5.6 135-360 135-360 135-360 135-360 135-360
V2703 13 8,1 Standard Upright 57-182 57-182 57-182 57-182 57-182
½ 5.6 135-360 135-360 135-360 135-360 135-360
V2707 13 8,1 Standard Pendent 57-182 57- 182 57-182 57- 182 57-182
½ 5.6 Recessed Pendent 135-360 135-200 135-360 135-360 135-360
V2707 13 8,1 Std t Up to V4' Adjustment 57-182 57-93 57-182 57-182 57-182
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2704 13 8,1 Quick upright 57-141 57-141 57-141 57-141 57-141
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2708 13 8,1 Quick Pendent 57-141 57-141 57-141 57-141 57-141
1h 5.6 RecessedPendent 135-200 135-200 135-200 135-200 135-200
V2708 13 8,1 Quick Up toW Adjustment 57-93 57-93 57-93 57-93 57-93
½ 5.6 Recessed Pendent T135-200 135-200 135-200 135-200
V2708 13 8.1 Quick Up to 3/4- Aciustmerit No 57-93 1 57-93
I Listings ann approval as oi printing. IAAll are approveo open, except lUl ames uesiyreixeu iiv
" For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
MBA #62-99-B. § CSFM #7690-0531:112
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) up to those shown
in adjacent table,
Temperature - 'F/'C
Sprinkler Victaulic Nominal Maximum Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary - C 155 100
68 38 Red
Intermediate E 175 150
79 65 Yellow
Intermediate F 200 150
93 65 Green
High 286
141
225 -
107 Blue
Extra High f K 360
182
300
149 Purple
- M Open : No Bulb
1 btanclarcl response only.
All are approved open, except for areas designated "No".
- 150165 ifwax coated.
ORDERING INFORMATION
Please specify the following
when ordering: 'U Sprinkler Model Number U K-Factor U Sprinkler Finish
U Style U Thread Size U Escutcheon Finish
U Temperature Rating U Quantity U Wrench Model Number
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
- Always wear safety glasses and foot protection,
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031, 610.559-3300.
40.10 -2
DIMENSIONS
2%"
(60 mm) 1%" I (41mm)
(25mm)
Standard Pendent - V2707, V2708
(60
Standard Upright - V2703, V2704
2'W'(60
mm)
Max. Hole
mm)
Min. Hole
"A." (17 mm) (14mm) $ a,
Typical Ceiling Tile
T —oll
Finished Surface (30 mm)
(43 mm)
________________
L
MAXIMUM RECESS
_ 211A"
(75 sirs)
MAXIMUM EXTENSION
½' Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
2W'(60 sirs)
Max. Hole
2" (51 mm)
Mm. Hole
(24 mm) Typical Ceiling Tile
111Ao' Finished Surface
(24 mm)
(43 mm)
MAXIMUM RECESS
24o"
(75 mm)
MAXIMUM EXTENSION
W Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
I _j
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V2707,V27O8Pendent.
V2707, V2708 Recessed Pendent
V2703, V2704 Upright
40.10 -3
--
- -
m
- - -
• -------- -
m
-
• --_s N
m \. N
_-__
•
m
-
-
10'
3,0 m
8
2,4
6
1,8
4
1,2
2
0,6
0
7 psi
48 kPa
15 psi
103 kPa
30 psi -------
207 kPa
DISTRIBUTION PATTERNS
MODELS V2107, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' 3,0 m
8'
2,4 m
6'
1,8m
4,
1,2 rn
2'
0,6 m
0
7 psi
48 kPa
15 psi
103 kPa
30 psi -------
207 kPa
2' 4' 6' 8' 10' 12' 14'
0,6m 1,2w I,8m 2,4m 3,0m 3,7m 43m
MODELS V2103, V2104
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
2' 4' 6' 8' 10' 12 14 16'
0,6m 1,2m 1,8m 2,4m 3,0m 3,7m 4,3m 4,9m
NOTES:
Data shown is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories. Iloor-wetting. and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropr ate NFPA National Fire Code and the authority having jurisdiction forspeciftc information regarding obstructions. spacing limitations and area of
coverage requirements. Failure to follow these guldelities could adversely affect the performance of he sprinkler and will void all List togs. Approvals and War-
rant es.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic company. Al products to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.10 -4