HomeMy WebLinkAbout4625 RED BLUFF PL; ; FPC2017-0012; PermitF 11ISJI Fi *I] F4I
Cr'cityof
Cdflsbad
IAUG EftIIUu
Print Date: 09/27/2022 Permit No: FPC2017-0012
Job Address: 4625 RED BLUFF PL, CARLSBAD, CA 92010-4671 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: Track #: Applied: 01/09/2017
Valuation: $0.00 Lot #: Issued: 01/24/2017
Occupancy Group: Project #: Finaled Close Out: 04/20/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check 4*: INSPECTOR: Wong, Cindy
Plan Check U:
Project Title:
Description: GODDARD SCHOOL -ALARM TI
FPContractor:
THE STEINHILBER CORPORATION
533 S VINEWOOD ST
ESCONDIDO, CA 92029-1924
(760) 747-3050
FEE AMOUNT
FIRE TI Fire Alarm System $601.00
Total Fees: $601.00 Total Payments To Date: $601.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Nfirml EHcmpapmoEs
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
THE GODDARD SCHOOL
TENANT IMPROVEMENT
4625 RED BLUFF PLACE
CARLSBAD, CA 92010
FIRE ALARM SYSTEM
MPTERiALDATASHEETS-j
The Goddard School
Tenant Improvement
4625 Red Bluff Place
Carlsbad, CA 92010
FIRE ALARM SYSTEM BILL OF MATERIALS
WHEELOCK EXCEDER HSC/STC - CEILING MOUNTED HORN/STROBES & STROBE
CSFM# 7125-0785:0168
COOPER Notification
1- Save up to 480/6 in current draw*
- Up to 9 models now in 1 appliance
- Save up to 14% cost of lnstallatlon**
Sleek Modern Aesthetics
Finger Slide Switches
Voltage Test Points
Multiple Voltages
3 Audible Settings
90, 95, 99 dB
8 Candela Settings
%fl wail - 15/1575/30/75/95/110/135/185 ceiling - 15/30/60/75/95/115/150/177
I
Universal Mounting Base
Ceiling and wall
Mounts to 5 Backbox Types
EZZCE~D_I Strobe, Horn Strobe, and Horn
Notification Appliances
Description:
The Wheelock® ExcederrM Series of notification appliances feature
a sleek modern design that will please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelock® ExcederlM Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® ExcederTM Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre-wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
complete with a Contact Cover for protection against dirt, dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
Environmentally Friendly
Low Current Draw
Compatibility and Requirements
Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol
Compatible with UL "Regulated Voltage using filtered VOC or unfiltered VRMS input voltage
Strobes produce 1 flash per second over the Regulated Voltagerarige
Compared to competitive models Patented
Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol At All warnings are printed In bold capital letters!
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWWCOOPERNOT1FICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION ANDIOR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their 'Regulated Voltage Range.
All candela ratings represent minimum effective strobe Intensity based on UL Standard 1971.
Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32F to 120'F (0C to 49'C) and
maximum humidity of 93% (± 2%) UL 464 (85% UL 1971).
Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Low ACurrent 1111 PA' 1Fewer Power Supplies
Strobe Ratings per UL Standard 1971
UL Max Current*
24 VDC /24FWR 12 VDC
Model Regulated Voltage
Range VDC 15/75 30 60 75, 95 110 115 135 150 177 185 15 15/75
ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140
STC 80330 r 0.085 0.103 0.163 -0.1 82
-
0.205 0.253 -0.110
-
Horn Strobe Ratings per UL 1971 & Anechoic at 24VDC
UL Max Current* at =dBA
l RegulatedVoltage 15 15/75 30 60 95 110 115 135 150 177 VDC 185Range
-Mode
24VDC
M0.125
8.0-33.0 0.082 0.095 0.102 0. 0.176 0.197 0.242 0.282
80330 0082 -77 0102 0141 6 0197 0242 0282 N••E Max Current* at Anechoic 95 dBA
24VDC 12VDC
Model Regulated 15 15/75 130 60 95 110 115 135 150 177 185 15 15/75 Rang
HS 80330 0.073 0.083 0.087 0.139 0.163 0186 0230 0.272 0.122 0.153
HSC 80330 0.073 V?l87J 01 0139 163 0.186 0.230 0.272 0.122 EMax Current* at Anechoic 90 dBA
24VDC 12VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 - 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120
Horn Ratings per UL Anechoic -
Model Regulated Voltage
Range VDC 99 dB 95 dB 90 dB
HN 16-33.0 0.064 0.044 0.022
HNC 16-33.0 0.084 0.044 0.022
RN 8.0-17.5 0.047 0.026 0.07
]0.0117 HNC 8.0-17.5 0.047 0.026
* UL max current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
Specification & Ordering Information
Sync WI
Strobe DSM or Mounting Model Candela Wheelock Power 12/24VDC* Options
Supplies
HSR 15/1575/30/75/95/110/135/185 X X LIMB**
HSW 15/1575/30/75/95111011351185 X X UMB**
HSRC 15130/60/75/95/115/1501177 X
X
X
X
UMB**
UMB** HSWC 15/30/60175/95/11511501177
STR 15/1575/30175/95/1101135/185 X X UMB**
STW 15/1575130/75/951110/135/185 X X UMB**
STRC 15/30/60/75/95/115/150/177 X X UMB**
ST\NC 15/30/60/75/95/115/150/177 X X
X
UMB**
UMB** HNR X
HNW X
X
X 17 UMB**
UMB** HNRC X
HNWC X X UMB**
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions.
Architects and Engineers Specifications
The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on-axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24"
H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock® Power Supplies
or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with Wheelock® synchronization protocol.
Wall Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Member
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
Wheelock* tMEDCJ SAFEPATH WAV Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION MIMI OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 25-07851 Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper Wheelock lnc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Exceder Series: Model trobe
ffodelo-IS
rn strobe and HN horn. Model ST is a synchronous
and non-synchronous scrcse light. a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). AdditionaIlygac'nay be
added for ceiling models and/or a -NR may be added for non-resettable mods'Ft'non
-NR models and optional 'S for silver fascia may be added*. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING: Electrical: 12 VDC/24VDC/FWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee's
Installation Instructions Manual for details.
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing Expires June 30, 2017
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division