Loading...
HomeMy WebLinkAbout6515 AMBROSIA LN; ; AS130006; Permit (2)9/27/22,11:35 AM AS 130006 Permit Data City of Carlsbad Sprinkler Permit Job Address: 6515 AMBROSIA LN Permit Type: SPRINK Parcel No: 2158410700 Lot #: 0 Reference No.: PC #: Permit No: AS130006 Status: APPROVED Applied 1/11/2013 Approved: 7/16/2013 Issued: 7/16/2013 Inspector: Project Title: DAYBREAK COMMUNITY CHURCH NEW CONSTRUCTION Applicant: EPIC FIRE PROTECTION, INC. 765 TURTLE POINT WY SAN MARCOS, CA 760-310-6122 Owner: DAYBREAK COMMUNITY CHURCH OF COASTAL NORTH COUNT 6515 AMBROSIA LN CARLSBAD CA P Fees ($) TI Fees RP[Total ($)I Balance ($) 132 0 132 0 about:blank 1/1 Daybreak Community Church, Phase III Review Comments. Page 2 Review Comments Daybreak Community Church, Phase III, 6515 Ambrosia Lane, Carlsbad, California In the event that the t-bar ceilings are not rigidly braced per ASME E580, the sprinklers to be installed in the suspended panels will require either a 2" clearance around the penetration through the panel, or the use of a flexible drop fitting, per ASCE7-05, section 13.5.6.2.2(e), which is attached. However, gypsum board ceilings are assumed to be rigidly braced. All the above conditions can be field verified. There was no detail for the longitudinal braces to be provided. However, the method attachment for the lateral is sufficient to carry the load for the longitudinal. As long as the same hardware and fasteners are installed there is no need for resubmittal. Field verify that flexible couplings are provided at the top and bottom of the 2Y2" rise up to the second floor. As the new addition can be isolated from the existing portion of the system, only the new portion should be subjected to hydrostatic testing to 200 psi, per NFPA-13, section 24.2.1.5. The existing system should not be subjected to pressures in excess of system working pressure, per section 24.2.1.6. Advisory -if possible, the system should be provided with a pressure relief valve, set to 175 psi, per the requirements of section 7.1.2. If the existing system was installed in accordance with an edition of NFPA-13 prior to the 2010, this is not mandated however it is a prudent addition to the system. for size eel, ctile ility l t e or In the event that the t-bar ceilings are not rigidly braced per ASME E5.80, the sprinklers to be in fl imately equal. installed in the suspended panels will require either a 2" clearance around the penetration through the panel, or the use of a flexible drop fitting, per ASC[7-05. section 13.5.6.2.2(e), which is attached. However, gypsum board ceilings are assumed to be rigidly braced. All the above conditions can be field verified. erts, 41 be values of R1, and a1, taken 'm 3.5-1 applied at the center of mass of the panel. \ e. Where anchorage is achieved ug flat straps embed e concrete or masonry, such straps sh be attached to or ho around reinforcing steel or otherwise rminated so as to effec- tively transfer forces to the reinforcin teel or to assure that pullout of anchorage is not the initial fai e mechanism. 13.5.4 Glass. Glass in glazed curtain walls an torefronts shall be designed and installed in accordance with Sec n 13.5.9. 13.5.5 Out-of-Plane Bending. Transverse or out-o lane bend- ing or deformation of a component or system that is objected to forces as determined in Section 13.5.2 shall not ex ed the deflection capability of the component or system. 13.5.6 Suspended Ceilings. 13.5.6.1 Seismic Forces. The weight of the ceiling, W1,, shall' include the ceiling grid and panels; light fixtures if attached fto clipped to, or laterally supported by the ceiling grid; and other components that are laterally supported by the ceiling. W,, shall be taken as not less than 4 psf (19 N/rn2). The seismic force, F, shall be transmitted through the ceiling attachments to the building structural elements or the ceiling- structure boundary. 13.5.6.2 Industry Standard Construction. Unless designed in accordance with Section 13.5.6.3, suspended ceilings shall be designed and constructed in accordance with this section. 13.5.6.2.1 Seismic Design Category C. Suspended ceilings in structures assigned to Seismic Design Category C shall be designed and installed in accordance with ASTM C635, ASTM C636, and the CISCA for Seismic Zones 0-2, except that seismic forces shall be determined in accordance with Sections 13.3.1 and 13.5.6.1. pended ceilings in Seismic Design Categories D, E, and F shall be designed and installed in accordance with ASTM C635, ASTM C636, and the CISCA for Seismic Zones 3-4 as modified by the following: A heavy duty T-bar grid system shall be used. The width of the perimeter supporting closure angle shall be not less than 2,0 in. (50 mm). In each orthogonal horizontal direction, one end of the ceiling grid shall be attached to the closure angle. The other end in each horizontal direction shall have a 0.75 in. (19 mm) clearance from the wall and shall rest upon and be free to slide on a closure angle. For ceiling areas exceeding 1,000 ft2 (92.9 m2), horizontal re- straint of the ceiling to the structural system shall be provided. Minimum Design Loads for Buildings and Other Structures EXCEPTION: Rigid braces are permitted to be used instead of di- agonal splay wires. Braces and attachments to the structural system above shall be adequate to limit relative lateral deflections at point of attachment of ceiling grid to less than 0.25 in. (6 mm) for the loads prescribed in Section 13.3.1. For ceiling areas exceeding 2,500 ft2 (232 m2), a seismic sepa- rationjoint or full height partition that breaks the ceiling up into areas not exceeding 2,500 ft2 shall be provided unless struc- tural analyses are performed of the ceiling bracing system for the prescribed seismic forces that demonstrate ceiling system penetrations and closure angles provide sufficient clearance to accommodate the anticipated lateral displacement. Each area shall be provided with closure angles in accordance with item 2 and horizontal restraints or bracing in accordance with item 3. Except where rigid braces are used to limit lateral deflec- tiçrns, sprinkler heads and other penetrations shall have a 2 in. (50 mm) oversize ring, sleeve, or adapter through the ceiling tile to allow for free movement of at least 1 in. (25 mm) in all horizontal directions. Alternatively, a swing joint that can accommodate I in. (25 mm) of ceiling movement in all hori- zontal directions is permitted to be provided at the top of the sos-inkier head extension. in ceiling plan elevation shall be provided with posi- live bracing. Cable trays and electrical conduits shall be supported indepen- dently of the ceiling. Suspended ceilings shall be subject to the special inspection requirements of Section 11 A. 1.3.9 of this standard. 135.6.3 Integral Coustruclion. As an alternate to providing large clearances around sprinkler system penetrations through ceiling systems, the sprinkler system and ceiling grid are per- mitted to be designed and tied together as an integral unit. Such a design shall consider the mass and flexibility of all elements involved, including the ceiling system, sprinkler system, light fixtures, and mechanical (HVAC) appurtenances. Such design shall be performed by a registere d design professional. 13.5.7 Access Floors. 13.5.7.1 General. The weight of the access floor, Wi.,, shall in- clude the weight of the floor system, 100 percent of the weight of all equipment fastened to the floor, and 25 percent of the weight of all equipment supported by, but not fastened to the floor. The seismic force, F1,, shall be transmitted from the top surface of the access floor to the supporting structure. Overturning effects of equipment fastened to the access floor panels also shall be considered. The ability of "slip on" heads for pedestals shall be evaluated for suitability to transfer overturning effects of equipment. Where checking individual pedestals for overturning effects, the maximum concurrent axial load shall not exceed the portion of W. assigned to the pedestal under consideration. 13.5.7.2 Special Access Floors. Access floors shall be consid- ered to be "special access floors" if they are designed to comply with the following considerations: 1. Connections transmitting seismic loads consist of me- chanical fasteners, anchors satisfying the requirements of Appendix D of ACI 318, welding, or bearing. Design load capacities comply with recognized design codes and/or certified test results. 147 Flow Test Record Test-Hydrant . . . . ... Location Hydrant .TI) No. S.ize:Main . Static:...............92. Residual............ .Q Pressure. Drop. 2. (Pifi 1)...... K factor fOr PDI 1 I. 4S Flow Hydrant(s) Hydrant I location S9 Hyiraht 2 locatiOn______________________________________________________ Hydrant 3 location______________________________________________________ Hydrant 1 Pitot —7o PSI GPM Size of Orifice__________ Hydrant .2 Pitoj PSI GPM. Size of Orifice__________ Hydrant 3 Pitot PSI GPM: Size of Orifice__________ T1. (Q3) Calculated test and flow data - 0 x PD2 k _Q2 PDI*k Static................ .............92. Desired Residual. .. .... ....20 Pressure Drop.(PD 2).. .. ................Kfactor PD 2:_)O x '1 divided by \ 4 ' equals 197 GPM at 20 psi residual 11 I.D.2.k PD 1k Q2 Comments: . . . . Test conducted for: el EPIC FIRE PROTECTION, INC. 765 TURTLE POINT WAY SAN MARCOS, CA 92069 (760) 310-6122 FAX (760) 798-0556 Hydraulic Design Information Sheet Name: DAYBREAK COMMUNITY CHURCH PHASE ifi Date: 12-12-12 Location: 6515 AMBROSIA LANE CARLSBAD Building: NEW J, FIRST FLOOR! System No. 1 OF 1 Contractor: EPIC FIRE Contract No. Calculated By: RAB Drawing No. 1 OF 1 Construction: 0 Combustible El Non-Combustible Ceiling Height W Ft. NFPA 13: El NFPA 231 El Other (Specify) []Specific Ruling SYS!tM UtSIUN Light Hazard Ordinary Hazard Group [1 NFPA 231C: Figure: Made By 1 II 2 II 3 U Extra hazard Curve: Date Area of Sprinkler Operation 1500 System Te Density .10 0 Wet El Dry El Deluge El Pre-Action Area Per Sprinkler 225 SQ FT MAX Sprinkler or Nozzle Hose Allowance GPM: Inside 0 Make GLOBE Model GL5615 Hose Allowance GPM: Outside 100 Size 'A" K-Factor: 5.6 Rack Sprinkler Allowance NA Temperature Rating 155 CALCULATION SUMMARY GPM Required 319.33 PSI Required 67.50 At Base of Riser "C" Factor Used: Overhead 120 Underground 150 WATER SUPPLY Water Flow Test Pump Data Tank or Reservoir Date & Time 8-20-12 Rated Capacity Capacity Static PSI 92 At PSI Elevation Residual PSI 90 Elevation GPM Flowing 1405 Well Elevation 0 Proof Flow GPM Location SITE Source of Information EPIC FIRE AND CARLSBAD MWD COMMODITY STORAGE Commodity OFFICE/CLASSROOM Class Location Storage Height Area Aisle Width Storage Method: Solid Piled % Palletized % Rack Rack El Single Row El Conventional Pallet El Double Row fl Slave Pallet U Multiple Row U Open Flue Spacing In Inches Longitudinal Transverse - Horizontal Barriers Provided El Automatic Storage El Encapsulated El Solid Shelving El Non-Encapsulated Clearance From Top of Storage to Ceiling Ft. In. Thesc plans liasc heii wvivel or inparLnt eoiitpliance wit lithe current appl iah!e Li ds aisi standards in folce ii lie urisdtetiini_ The 'u lie, orcontractor may utilize In suppnit of' an applicaitiii I*or a hitildine periltit ri]ill he L \picss tittdcisiajidtii that dij, reran II' uI cii he owner mtoti'iiicttt or their tIi)lcsIi'Iiil cIttiiicr or aicliiiecl kit sok respotisihilits lot tall ettitiphutice with said codes and staitdartls. including lie hoilding code or ldr any tespoitsihilty Cor deheicitce s. errors. otittasitilts or iceltancc ill these Plans wltctltcr 01 llol tiolci ill this review. )utc tivto ki ten Cr: Rl-(Ohl dEN ) \i 1I<I ' \t S NO1El) DAYBREAK CHURCH PHASE III 1ST FLOOR .10/1500 Sigma Dynamics Corporation 7700 Supply I Demand Graph 25 - - - - 15 ao Margin Pressure 9.53 PSI Flow 3073.37 GPM _____ ______ ______ ______ _______ - J - - ____ ____ _____ D5 DO - - - - - - - - Do- - -: - - - 75 - 70 -- -- 60 50 45 40 35 0 -- 30 25 20cDY 10 5 n - - - - ____ 1.85 200 400 bOO bOO 1000 1ZUU System Demand.. Sprinkler Demand 73.08 PSI @ 319.33 GPM Additional Flows .0.00 GPM Hose at Source 100.00 GPM Total Demand 73.08 PSI @ 419.33 GPM I I I I I I iquu iouu I OUU Water Flow (GPM) Water Supply.. Static 82.80 PSI Residual 81.00 PSI @ 1405.00 GPM Elevation 0.00 PSI 2000 SUBMITTAL SERIAL NO:2932HY7 DAYBREAK CHURCH PHASE III 1ST FLOOR .10/1500 PLOW TEST RESULTS Water Supply STATIC 82.80 PSI RESIDUAL 81.00 PSI @ 1405.00 GPM CITY PRESSURE AVAILABLE AT 419.3 GPM SUMMARY OF SPRINKLER OUTFLOWS ACTUAL MINIMUM SPR FLOW FLOW K-FACTOR PRESSURE 12 23.26 22.50 5.60 17.25 13 23.15 22.50 5.60 17.09 14 23.12 22.50 5.60 17.04 15 22.64 22.50 5.60 16.35 16 22.53 22.50 5.60 16.19 17 22.50 22.50 5.60 16.14 18 23.92 22.50 5.60 18.25 (17 23.46 22.50 5.60 17.55 23.44 22.50 5.60 17.52 21 23.09 22.50 5.60 17.00 22 22.98 22.50 5.60 16.84 23 22.95 22.50 5.60 16.80 24 42.30 40.00 11.20 14.26 12-12-2012 PAGE 1 82.61 PSI TOTAL WATER REQUIRED FOR SYSTEM OUTSIDE HOSE STREAMS AT 0 TOTAL WATER REQUIREMENT PRESSURE REQUIRED AT 0 MAXIMUM PRESSURE UNBALANCE IN LOOPS MAXIMUM VELOCITY FROM 5 TO 7 319.33 GPM 100.00 GPM 419.33 GPM 73.08 PSI 0.00 PSI 26.88 FPS StJBV1ITTAL SERIAL NO:2932HY7 12-12-2012 PAGE 2 DAYREAK CHURCH PHASE III 1ST FLOOR .10/1500 Location Flow Pipe Fittings Equiv Friction Pressure in Size & Length Loss Summary Srorn To GPM IN Devices Ft PSI/Ft PSI 16 17 2.203 L 10.00 C120 PT 16.14 ( 17) Q 22.50 F=0 F 0.00 PE 0.00 EN T 10.00 0.0044 PF 0.04 15 16DQ 22.53 2.203 L 10.00 C=120 PT 16.18 ( 16) Q 45.03 F0 F 0.00 PE 0.00 BN T 10.00 0.0157 PF 0.16 11 15DQ 22.64 2.203 L 17.50 C=120 PT 16.34 ( 15) Q 67.67 F=T/E F 16.40 PE 0.00 EN T 33.90 0.0335 PF 1.14 PT 17.48 ( 11) 10 24 1.080 L 3.00 C=120 PT 14.26 ( 24) Q 42.3.0 F=T,E F 8.10 PE -0.43 AO T 11.10 0.4514 PF 5.03. ------------------ PT, 18.84 ( 10) 22 23 2.203 L 10.00 C=120 PT 16.80 ( 23) Q 22.95 F=0 F 0.00 PE 0.00 EN T 10.00 0.0045 PF 0.04 21 22DQ 22.98 2.203 L 10.00 C120 PT 16.84 ( 22) Q 45.93 F=0 F 0.00 PE 0.00 BN T 10.00 0.0163 PF 0.16 19 21DQ 23.09 2.203 L 4.00 C=120 PT 17.00 C 21) Q 69.02 F=T F 11.60 PE 0.00 EN T 15.60 0.0347 PF .0.54 PT 17.54 ( 19) 19 ------------------ 20 2.203 L 6.50 C=120 PT 17.52 C 20) Q 23.44 F=0 F 0.00 PE 0.00 BN T 6.50 0.0047 PF 0.03 iS 19DQ 92.48 2.203 L 3.00 C=120 PT 17.55 ( .19) Q 115.92 F=E F 4.80 PE 0.00 BN T 7.80 0.0905 PF 0.71 8 18DQ 23.92 2.203 L 42.00 C=120 PT 18.26 C 18) Q 139.84 F=T F 11.60 PE 0.00 EN T 53.60 0.1281 PF 6.87 PT 25.13 ( 8) 13 ------------------ 14 2.203 L 10.00 C=120 PT 17.04 ( 14) Q 23.12 . F=0 F 0.00 PE 0.00 EN T 10.00 0.0046 PF 0.05 SUBMITTAL SERIAL NO:2932HY7 12-12-2012 PAGE 3 DAYBREAK CHURCH PHASE III 1ST FLOOR .10/1500 / Location Flow Pipe Fittings Equiv Friction Pressure in Size & Length Loss Summary From To GPM IN Devices Ft PSI/Ft PSI 12 13DQ 23.15 2.203 L 10.00 C=120 PT 17.09 ( 13) Q 46.26 F=0 F 0.00 PE 0.00 BN T 10.00 0.0166 PF 0.17 11 12DQ 23.26 2.203 L 6.50 C=120 PT 17.26 C 12) Q 69.52 F=0 F 0.00 PE 0.00 BN T 6.50 0.0352 PF 0.23 10 11DQ 67.67 2.203 L 11.00 C=120 PT 17.49 C 11) Q 137.19 F=0 F 0.00 1PE 0.00 BN T 11.00 0.1237 PF 1.36 7 10DQ 42.30 2.203 L 30.00 C=120 PT 18.85 ( 10) Q 179.49 F=T F 11.60 PE 0.00 BN T 41.60 0.2033 PF 8.46 PT 27.31 ( 7 8 -- 2.203 L 17.00 C=120 PT 25.12 C Q 139.84 F=0 F 0.00 PE 0.00 FM T 17.00 0.1281 PF 2.18 5 7DQ 179.49 2.203 L 26.00 C=120 PT 27.30 C 7) Q 319.33 F=T/E F 16.40 PE 0.00 FM T 42.40 0.5902 PF .25.02 4 5 2.703 L 18.00 C=120 PT 52.32 C 5) Q 319.33 F=E F 6.60 PE 0.00 FM T 24.60 0.2180 PF 5.36 3 4 2.703 L 12.00 C=120 PT 57.68 C 4) Q 319.33 F=2E F 13.20 PE 4.3.3 FR T 25.20 0.2180 PF 5.49 2 3 6.340 L 5.00 C=140 PT 67.50 C 3) Q 319.33 F=E F 23.11 PE 0.00 UN T 28.11 0.0026 PF 0.07 1 2 5.914 L 110.00 C=150 PT 67.57 ( 2) Q 319.33 F=T,EE F 57.00 PE 0.00 UN T 167.00 0.0032 PF 0.53 0 1 5.914 L 90.00 C=150 PT 68.10 C 1) Q 319.33 F=T,DCA/E,EE F 78.57 PE 0.00 UN T 168.57 0.0032 PF 0.54 6" FEECO 876V DOUBLE DETECTOR CHECK 4.43 PT 73.07 ( 0) EPIC FIRE PROTECTION, INC. 765 TURTLE POINT WAY SAN MARCOS, CA 92069 (760) 310-6122 FAX (760) 798-0556 Hydraulic Design Information Sheet t. Name: DA Location: 65 Building: -NJ Contractor: Calculated By: Construction: Date: 12-12-12 r—'SECOND FLOOR System No. 1 OF 1 IC FIRE Contract No. RAB . Drawing No. I OF I Combustible. U Non-Combustible Ceiling Height 10 Ft. NFPA 3: N Light Hazard Hazard Group Li i: Li 2 LI 3 Li Extra Hazard L NFPA 231. [1] NFPA 23 IC: Figure: Curve: U] Other (Specify) [II Specific Ruling Made By Date Area of Sprinkler Operation 1170 Swtem Type Density .10 M Wet U] Dry U] Deluge El Pre-Action Area Per Sprinkler 225 SQ FT MAX . Sprinkler or Nozzle Hose Allowance GPM.: Inside 0 Make GLOBE Model GL5615 Hose Allowance GPM: Outside 100 Size ½" K-Factor: 5.6 Rack Sotinkler Allowance NA. .. Temperature Rating 1.55 PM Required . .. .PS1.Required oZ. At Base of Riser "C" Factor Used Overhead 120 Underground 150 WATPP SuPPLY Water Flow Test Pump Data Tank or Reservoir Date & Time 8-20-12 Rated Capacity Capacity Static PSI 92 At PSI Elevation Residual PSI 90 Elevation GPM Flowing 1405 . . Well Elevation 0 Proof Flow GPM Location SITE Source of Information EPIC FIRE AND CARLSBAD MWD Commodity OFFICE/CLASSROOM Storage Height Storage Method: Solid Piled L UW11V1JL.'1 I I Z I Class Area % Palletized Location - Aisle Width %.Rack Rack El Single Row U] Conventional Pallet U] 4 utornatic Storage [I] Encapsulated U] Double Row U] Slave Pallet LII Solid Shelving U] Non-Encapsulated U Multiple Row Li Open Flue Spacing In Inches Clearance From Top of Storage to Ceiling Longitudinal Transverse Ft. Horizontal Barriers Provided hi. Tsr plaits have been reviewed for !par fit cpaiive Willi the current applicable codes and standaidc in lowe in the jtjrisdiction. The owner or contractor niav nil lire Jils revicts iii support of all application or a huilding ret lit 55 itli the espress unilerstaiidin hai this Fe' test no stay riieves the owiier or cilliractor or iheir i okssioita ci;Ciiiecr or tucliittct Im sole resl,iiiislhiits or full compliance wilt said codes and standard, including the building cock or for any respotisihilmy for lelicielietes. errors. oniissii'ns or iielisence in these plaits ss hodi cr or not noted ill ([its review. Reviewer: Rh(i)NIMENI) A'Pfl.)VM, I D RiC( iMishNt) Al'h'ROVAI.. AN '.01 F) CL 0.1708-2013 PAGE 1 SUBMITTAL SERIAL NO:2932HY7 DAYBREAK CHURCH PHASE III 2ND FLOOR .10/1170 FLOW TEST RESULTS Water Supply STATIC 82.80 p5:1 RESIDUAL 81-00 :PSI @ 1405.00 GPM CITY PRESSURE AVAILABLE AT 417.0 GPM 8.2.61 PSI SUMMARY OF SPRINKLER OUTFLOWS ACTUAL MINIMUM SPR FLOW FLOW K-FACTOR PRESSURE 50 23.51 14.83 - 5.6.0 17.63 51 22.85 14.83 5.60 16.65 52 25.03 14.83 5.6.0 19.97 .53 25.02 14.83 5.60 19.97 .54 20.06 14.83 5.60 12.83 57 24.88 14.83 5.60 19.74 58 18.69 14.83 560 11.14 59 24.55 14.83 5.60 19.22 60 17.91 14.83 5.60 10.23 61 15.97 14 83 5 60 8.13 62 15.62 14.83 5.60 7.78 64 16 .62 .1.4 -83 5.1 60 8 .81 65 .16.26 .14.83 .5.60 8.43 67 14.8.3 14.83 5.6.0 7.01 68 1544 14.83 5.60 7.60 69 19.78 . 1.4,83 5.6.0 12.48 TOTAL WATER REQUIRED FOR SYSTEM 317.03. GPM OUTSIDE HOSE STREAMS AT 0 100,. 00 GPM TOTAL WATER REQUIREMENT 417.013 GPM PRESSUR E REQUIRED AT 0 75.79 PSI MAXIMUM PRESSURE UNBALANCE IN LOOPS 000 PSI MAXIMUM VELOCITY FROM 31 TO 41 18.99 FPS SUBMITTAL SERIAL NO:2932HY7 01-08-2013 PAGE 2 DAYBREAK CHURCH PHASE III 2ND FLOOR .10/1170 Location Flow Pipe Fittings Equiv Friction Pressure in Size Length Loss Summary From To GPM IN Devices Ft PSI/Ft PSI 63 67 1.080 L 6.50 C=120 PT 7.01 ( 67) Q 14.83 F=2E F 4.60 PR 0.00 EN T 11.10 0.0649 PF 0.72 62 63 1.536 L 4.00 C=120 PT 7.73 ( 63) Q 14.83 F=0 F 0.00 PE 0.00 EN T 4.00 0.0117 PF 0.05 61 6:2DQ 15.62 1.536 L 8.00 C=120 PT 7.78 ( 62) Q 30.45 F=0 F 0.00 PE 0.00 BN T 8.00 0.0442 PF 0.35 60 61DQ 15.97 1.536 L .10.00 C=120 PT 8.13 ( 61) Q 46.42 F=2E F 7.20 PE 0.43 EN T 17.2.0 0.0965 PF 1.66 54 60DQ 17.91 1.536 L 10.00 C=120 PT 10.22 .,( 60) Q 64.33 F=2E F 7.20 PE -0.43 EN T 17.20 0.1764 PF 3.03 40 54DQ 20.06 1.536 L 8.50 C=120 PT 12.82 ( 54) Q 84.39 F=T F 8.90 PE 0.00 EN T 17.40 0.291.4 PF 5.07 PT 17.89 ( 40) 55 69 .1.53.6 L 6.00 .C120 PT 12.48 ( 69) .Q 19.78 F=T,E F 12.50 PE 0.00 EN T 18.50 .0.0199 PF 0.37 PT .128.5 ( 55) 66 ------------------ 68 1.080 L 6.50 C=120 PT 7.60 ( 6) Q 15.44 F=2E F 4.60 PR 0.00 BN T 11.10 0.0700 PF 0.78 65 .66 1.536 L. 4,00 C=120 PT 8.38 ( 66) Q 15.44 F=0 F 0.00 PE 0.00 EN T 4.00. 0.0126 PF 0.0:5 64 65DQ 16.26 1.536 L 8.00. C120 PT 8.43 ( 65) Q 31.70 F=0 F 0.00 PR 0.00 EN T 8.00 0.0476 PF 0.3.8 58 64DQ 16.62 1.536 L 8.00 C=12.0 PT 8.81 ( 64) Q 48.32 F=4E F 14,40 PE 0.00 BN T 22.40 0.1039 PF 2.33 55 5.8DQ: 18.69 1.5.36 L .9.00 C=120 PT 11.14 (. 58) Q 67.01 F=0 F 0.00 PE 0.00 EM T 9.00 0.1902 PF 1.71 SUBMITTAL SERIAL NO: 2932HY7 0108-2013 PAGE 3 DAYBREAK CHURCH PHASE III 2ND FLOOR .10/1170 Location Flow Pipe Fittings .Equiv Friction Pressure in Size & Length Loss Summary From To GPM IN Devices Ft PSI/Ft PSI 41 55DQ 1978 1.536 L 4.50 C120 PT 12.85 ( 55) Q 86.80 F=T F 8.90 PE 0.00 BN T 13.40 0.3070 PF 4.11 PT 16.96 ( 41) 56 59 1.536 L. 11.00 C=120 PT 19.22 ( 59) Q 2.4.55 F=2E F 7.20 PE 0.00 BN T 18.20 0.0297 PF 0.54 42 56 1.536 L 3.50 C=120 PT 19.76 ( 56) Q 2.4.55 F=T,2E F 16.10 PE 0:00 EN T 19.60 0.0297 PF 0.58 PT .20.. 34 ( 42) 43 57 ------------- 1.536 L 8.50 C=120 PT 19.74 ( 57) Q 24.88 .P=T F 8.90 PE 0.00 BN T 17.40 0.0304 PF 0.53 PT 20.27 ( 43) 43 ------------------ 53 1.536 L 1,00 C=120 PT 19.97 ( 53) Q 25.02 F=T F 8.90 PE 0.00 EN T 9.90 0.0308 PP 0.30 33 43DQ .2.4.88 1.536 L 1.00 C=120 PT 20.27 ( 43) Q 49.91 F=T F 8.90 PE 0.43 NR T 9.90 0.1103 PP 1.09 PT 21.79 ( 33) 42 ------------------ 52 1.536 L. 3.00 C=120 PT 19.97 ( 52) Q 25.03 F=T F 8.90 PE 0.00 BN T 11.90 0.0308 .PF 0.37 3.2 42DQ .24.55 1.536 L 1..00 C=120 PT 20.34 ( 42) Q 4-9.58 F=T F 8.90 PE 0 43 MR T 9.9.0 0.1089 PF 1.08 PT 21.85 C 32) 41 ------------------ 51 1.536 L 3.00 C=120 PT 16.65 ( 51) Q 22.85 F=T F 8.90 PE 0.00 EN T 11.90 0.0260 PF 0.31 .31 41DQ 86.80 1.5.36 L 1.00 C120 PT 16.96 ( 41) Q 109.65 F=T F 8.9.0 PE 0.43 NR T 9.90 0.4731 PP 4.68 PT 22.07 ( 31) 40 ------------------ 50 1.536 L 1.00 C=120 PT 17.63 ( 50) Q 23.51 F=T F 8.90 PE 0.00 EN T .9.90 0.0274 PF 0.27 SUBMITTAL SERIAL NO.: 2932HY1 01-08-2013 PAGE 4 DAYBREAK CHURCH PHASE III 2ND FLOOR .. 10/1170 Location Flow Pipe Fittings Eguiv Friction Pressure in Size & Length.. Loss Summary From To GPM IN Devices Ft PSI/Ft PSI 30 40DQ 84.39 1.536 L 1.00 C=120 PT 17.90 ( 40) Q 107.90 F=T F 8.90 FE 0.43 NR T 9.90 0.4592 PF 4.55 PT 2.2.88 ( 32 ------------------ 33 2.703 L .8.00 C=120 PT 21.80 ( 33) Q 49.9.1 F=0 F 0.00 FE 0.00 FM T 8.00 0.0070 PF 0.06 .31 32DQ. 49.58 2.703 L 9.00 C=1.20 PT 21.86 ( Q 99.48 F=0 F 0.00 FE 0.00 FM .9.00 0.0252 PP .0.2.3 30 31DQ 10.9.65 2.703. L 8.00 C=120 PT 22.09 ( Q 209.13 F=0 F 0.00 PE 0.00 FM T 8.00 0.0996 .PF 0.80 6 30DQ .107.90 2.703 L 71.00 C=120 PT 22.89 ( 30) Q 317.03 F=2E F 13.20 PE 0.00 FM r 84.20 0.2151 PF 18.11 5 6. 2...7Q3 L 14.00 C=120 PT 4..00 ( 6) Q .317.03 .F=T,2E F 29.90 PE 4.77 FM T 43.90 0.2151 PF 9.44 4 5 2.703 L 18.00 C=120 PT 55.21 ( 5) Q 317.03 F=E F 6.60 PE 0.00 FM T 24.60 0.2.151 PF 5.29 3. 4 2.703 L. 12.00 C120 PT 6.0.50 ( 4.) Q 317,03 . F=2E F 13.20 PE. 433 FR T 25 .20 0 .2151 PP :5 .42 2 3 6.340 L 5.00 Cr140 PT 70.25 .( 3) Q 317.03 F=E F 23.11 PE 0.00 UN T 2.8.11 0.0025 PF 0.07 1 2 5.914 L 110.00 C=150 PT 70.32 .( 2) Q 317.03 F=T,EE F 57.00 PE .0.00 UN T 167.00 0.0031 PF 0.52 0 1 5.914 L 90.00 C150 PT 70.84 ( 1) Q 317.03 FT,DCA/E,EE F 7:8.57 PR .0.00 UN T 168.57 0.0031 pp. 0.52 6" FEBCO 876V DOUBLE DETECTOR CHECK 4.43 PT 75.78 ( 0)