Pacific Ridge Gymnasium Review Comments. Page 2
Review Comments
Pacific Ridge Gymnasium, 6269 El Fuerte Street, Carlsbad, CA
I. Our only comment is that the underground entrance to the building may not be in conformance
with the Carlsbad policy regarding entrance to the building above grade. The underground
installation is done by others, and was not a part of this review. This can be field verified to
conform, and may result in revisions being required. No resubmittal should be required.
-- Carlsbad Municipal Water District
Potab!e Water Discharge LE C Ü PY Event Report
Date:
Location: V
Reason for Discharge Event: L ftw flof\J
Type of Event: Initial
Dewatering Water Mains IA- Estimated Discharge Flow:
Note: Includes flow testing and flushing
Dewatering Reservoirs Start Time 2
Unscheduled Water Discharge )A- End Time
Pre-Dechlorination Residual: O. 1
Clear flow path of debris, surface
contaminants and/or hazardous Post-Dechlorination Residual: 0. I
materials. Do not remove native (less than 0.1 mg/L)
vegetation. _____
pH within limits of 6.0 and 9.0
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
of discharge water.
Upon completion of dewatering, ensure
that the flow path is free of all
temporary erosion prevention materials.
Upon completion completion of dewatering, ensure
that any sediment or silted areas are
cleared.
Water Sampling Performed by:
Comments:
Submitted by: Reviewd by:
(Name & Date) me & Date)
Flow Test Record
Test Hydrant
Location 2.Qf'i. L_ /
Hydrant ID No. Size Main
Static...............
Residual..........
Pressure Drop.. 4-. (PDI 1).....K factor for PDI 1 Z.\
Flow Hydrant(s)
Hydrant 1 location 42i
Hydrant 2 location
Hydrant 3 location
Hydrant I Pitot\A. PSI GPM: 144,g Size of Orifice__________
Hydrant 2 Pitot PSI GPM: Size of Orifice___________
Hydrant 3 Pitot PSI GPM: Size of Orifice.__________
Total:
Calculated test and flow data - p x PD2 k =Q2
PDI*k
Static: .................... I'm
Desired Residual.......20
Pressure Drop (PD 2) K factor PD 2:\2. 0'2-
- 144c.7 x \2 .02_- divided b 1Z. k equals 2$? GPM at 20 psi residual
Q PD2k PD1k Q2
Comments:
Test conducted for:
Conducted by:L'C- fljZ. fl2CT t1OI /
fr,
Date: 44-1 Time:__________
Flow Test Record Formulas
GPM-Flow
2V" 4"
PSI GPM PSI GPM PSI GPM PSI GPM 1 170 16 670 1 430 16 1720 2 240 17 690 2 610 17 1770
3 290 18 710 3 740 18 1820
4 340 19 730 4 860 19 1870
5 380 20 750 5 960 20 1920
6 410 22 790 6 1050 22 2020
7 440 24 820 7 1140 24 2110
8 480 26 860 8 1220 26 2190
9 500 28 890 9 1290 28 2280
10 530 30 920 10 1360 30 2330
11 560 33 950 11 1430 32 2430
12 580 34 980 12 1490 34 2510
13 610 36 1010 13 1550 36 2580
14 630 38 1040 14 1610 38 2650
15 650 40 1060 15 1660 40 2720
K Factor Formula
PD K PD K PD K PD K PD K
1= 1.0 21= 5.18 41= 7.43 61= 9.21 81= 10.73
2= 1.45 22= 5.31 42= 7.53 62= 9.29 82= 10.80
3= 1.81 23= 5.44 43= 7.62 63= 9.37 83= 10.87
4= 2.11 24= 5.56 44= 7.72 64= 9.45 84= 10.94
5= 2.39 25= 5.69 . 45= 7.81 65= 9.53 85= 11.01
6= 2.63 26= 5.81 46= 7.91 66= 9.61 86= 11.08
7= 2.86 27= 5.93 47= 8.00 67= 9.69 87= 11.15
8= 3.07 28= 6.05 48= 8.09 68= 9.76 88= 11.22
9= 3.28 29= 6.16 49= 8.18 69= 9.84 89= 11.29
10= 3.47 30= 6.28 50= 8.27 70= 9.92 90= 11.36
11= 3.65 31= 6.39 51= 8.36 71= 9.99 91= 11.43
12= 3.83 32= 6.50 52= 8.44 72= 10.07 92= 11.49
13= 4.00 33= 6.61 53= 8.53 73= 10.14 93= 11.56
14= 4.16 34= 6.71 54= 8.64 74= 10.22 94= 11.63
15= 4.32 35= 6.82 55= 8.71 75= 10.29 95 11.69
16= 4.48 36= 6.93 56= 8.79 76 10.37 96= 11.76
17= 4.72 37= 7.03 57= 8.88 77= 10.44 97= 11.83
18= 4.76 38= 7.13 58= 8.96 78= 10.51 ,98= 11.89
19= 4.90 39= 7.23 59= 9.04 79= 10.59 99= 11.96
20= 5.04 40= 7.33 60= 9.12 . 80= 10.66' 100= 12.02
*PD = Pressure drop K = K factor
Mea of Spiin1c1e Operation 1950 SQ FT System Type
Density .10 Z Wet LI Dry LI] Deluge LI Pre-Action
Area Per Sprinkler. 20x20 MAX Sprinkler or Nozzle
Hose Allowance GPM: Inside 0 Make TYCO Model EC-1 1
Hose Allowance GPM: Outside 100 Size %" K-Factor: 11.2
Rack Sprinkler Allowance Temperature Rating 200
a.,
.2
CALCULATION SUMMARY
A
EPIC FIRE PROTECTION, INC.
765 TURTLE POINT WAY
SAN MARCOS, CA 92069
(760) 310-6122 FAX (760) 798-0556
ASuot&1-
Hydraulic Design information Sheet
Name: PACIFIC RIDGE GYMNASIUM - GYM AREA Date: 6-27-11
Location: 6269 EL FUERTE, CARLSBAD
Building: NEW System No.
Contractor: EPIC FIRE PROTECTION, INC. Contract No.
Calculated By: RAE Drawing No.
Construction: [] Combustible Non-Combustible Ceiling Height
SYSTEM DESIGN
NFPA 13: M Light Hazard Ordinary Hazard Group I 2Li3
[Ii] NFPA 231 -LI NFPA 231C: Figure: Curve:
[] Other (Specify)
ESpecific Ruling Made By
1 OF 1
2 OF 2
25' Ft.
Extra Hazard
Date
GPM Required 283.02 PSI Required 72.07 At Base of Riser
"C" Factor Used: Overhead 120 Underground 150
WATER SUPPLY
Water Flow Test Pump Data Tank or Reservoir
Date & Time 4-4-11 Rated Capacity Capacity
Static PSI 128 At PSI Elevation
Residual PSI 124 Elevation
GPM Flowing 1440 Well
Elevation 0 Proof Flow GPM
Location SITE
Source of Information FLOW TEST BY EPIC FIRE AND CARLSBAD WATER DEPT.
COMMODITY STOKAUE
Commodity GYM Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
Rack
LI Single Row LI Conventional Pallet
LI Double Row LI Slave Pallet
Li Multiple Row Li Open
Flue Spacing In Inches
Longitudinal Transverse -
Horizontal Barriers Provided
LI Automatic Storage LI Encapsulated
LI Solid Shelving LI Non-Encapsulated
Clearance From Top of Storage to Ceiling
Ft. In.
2
2
2:
2:
2
2
1
1
1
1
1
1
1:
I
1
I
PACIFIC RIDGE GYMNASIUM - GYM .10/1950 Sigma Dynamics Corporation
7700 Supply I Demand Graph
40
30 - Margin
Pressure 33.93 PSI
Flow 4477.04 GPM - ____ _____ _____ _____ ______ ______ _______ _______ _J
10
DO
90
80
70
60
50
40
30
20
10
00
90
80 Hi
70
60
50 -1
An .,
30
2 D
10
0
N185
200 400 600 800 1000 1200 1400 1600 1800 20
Water. Flow (GPM)
System Demand..
Sprinkler Demand 80.78 PSI @ 283.02 GPM
Additional Flows 100.00 GPM
Hose at Source 0.00 GPM
Total Demand 80.95 PSI @ 383.02 GPM
Water Supply..
Static 115.20 PSI
Residual 111.60 PSI @ 1440.00 GPM
Elevation 0.00 PSI
00
SUBMITTAL SERIAL NO:2932HY7
PACIFIC RIDGE GYMNASIUM - GYM .10/1950
FLOW TEST RESULTS
Water Supply
STATIC 115.20 PSI
RESIDUAL 111.60 PSI @ 1440.00 GPM
CITY PRESSURE AVAILABLE AT 383.0 GPM
06-30-2011 PAGE 1
114.89 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FI,OW FLOW K-FACTOR PRESSURE
100 40.62 33.00 11.20 13.15
101 40.53 33.00 11.20 13.10
102 34.79 33.00 11.20 9.65
103 34.71 33.00 11.20 9.61
104 33.07 33.00 11.20 8.72
105 33.00 33.00 11.20 8.68
106 66.31 33.00 11.20 35.05
TOTAL WATER REQUIRED FOR SYSTEM 283.02 GPM
OUTFLOWS AT 1 100.00 GPM
TOTAL WATER REQUIREMENT 383.02 GPM
PRESSURE REQUIRED AT 0 80.95 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 10 TO 15 18.78 FPS
SUBMITTAL SERIAL NO :293 2HY7
PACIFIC RIDGE GYMNASIUM - GYM .10/1950
Location Flow Pipe Fittings
in Size
From To GPM IN Devices
103 105 1.536 L
Q 33.00 F=0 F
EN T
101 103DQ 34.71 1.536 L
Q 67.71 F=0 F
EN T
16 101DQ 40.53 1.536 L
Q 108.24 F=E F
EN T
11 16 1.536 L
Q 108.24 F=T F
NR T
14 106 - 1.536 L
Q 66.31 F=E F
EN T
9 14 1.536 L
Q €6.31 F=T F
NR T
102
------------------
104 1.536 L
Q 33.07 F=0 F
EN T
100 1021JQ 34.79 1.536 L
Q 67.86 F=0 F
EN T
15 100DQ 40.62 1.536 L
Q 108.47 F=E F
BN T
10 15 1.536 L
Q 108.47 F=T F
NR T
10
------------------
11 3.314 L
Q 108.24 F=0 F
FM T
06-30-2011 PAGE 2
Equiv Friction Pressure
Length Loss Summary
Ft PSI/Ft PSI
18.00 C120 PT 8.68 (105)
0.00 PE 0.00
18.00 0.0513 PF 0.92
18.00 C=120 PT 9.60 (103)
0.00 PE 0.00
18.00 0.1939 PF 3.49
58.00 C=120 PT 13.09 (101)
3.60 PE 0.00
61.60 0.4619 PF 28.45
6.00 C=120 PT 41.54 ( 16)
8.90 PE 2.60
14.90 0.4619 PF 6.88
PT 51.02 ( 11)
58.00 C=120 PT 35.05 (106)
3.60 PE 0.00
61.60 0.1866 PF 11.49
6.00 C=120 PT 46.54 ( 14)
8.90 PE 2.60
14.90 0.1866 PF 2.78
PT 51.92 ( 9)
18.00 C=120 PT 8.72 (104)
0.00 PE 0.00
18.00 0.0515 PF 0.93
18.00 C=120 PT 9.65 (102)
0.00 PE 0.00
18.00 0.1947 PF 3.50
58.00 C=120 PT 13.15 (100)
3.60 PE 0.00
61.60 0.4637 PF 28.56
6.00 C=120 PT 41.71 ( 15)
8.90 PE 2.60
14.90 0.4637 PF 6.91
PT 51.22 ( 10)
17.67 Cr120 PT 51.03 ( 11)
0.00 PE 0.00
17.67 0.0109 PF 0.19
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 3
PACIFIC ,RIDGE GYMNASIUM - GYM .10/1950
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
9 10DQ 108.47 3.314 L 17.67 C=120 PT 51.22 ( 10)
Q 216.71 F=0 F 0.00 PE 0.00
FM T 17.67 0.0394 PF 0.70
3 9DQ 66.31 3.314 L 135.50 C=120 PT 51.92 ( 9)
Q 283.02 F=E F 7.30 PE 0.00
FM T 142.80 0.0646 PF 9.22
2 3 3.314 L 21.00 C=120 PT 61.14 ( 3)
Q 2,83.02 F=E F 7.30 PE 9.10
FR T 28.30 0.0646 PF 1.83
1 2 5.914 L 25.00 C=150 PT 72.07 ( 2)
Q 283.02 F=T,3E/DDC F 110.93 PE 0.00
UN T 135.93 0.0025 PF 0.34
6" AMES C500 RPDA 8.11
0 1DQ 100.00 7.758 L 290.00 C=150 PT 80.53 ( 1)
Q 383.02 F=T,GV F 58.94 PE 0.00
UN T 348.94 0.0012 PF 0.42
PT 80.95 ( 0)
-;
EPIC FIRE PROTECTION, INC. As U 765 TURTLE POINT WAY
SAN MARCOS, CA 92069
(760) 310-6122 FAX (760) 798-0556
Hydraulic Design information Sheet
Name: PACIFIC RIDGE GYMNASIUM - 1ST FLOOR Date: 6-27-11
Location: 6269 EL FUERTE, CARLSBAD
Building: NEW System No. 1 OF 1
Contractor: EPIC FIRE PROTECTION, INC. Contract No.
Calculated By. RAE Drawing No. 1 OF 2
Construction: LI Combustible Non-Combustible Ceiling Height 9' Ft.
NFPA 13:
LI NFPA 231
[I Other (Specify)
LI Specific Ruling
SYSTEM DESIGN
Light Hazard Ordinary Hazard Group
-[I NFPA 231C: Figure:
Made By
1 [1] 2 Li 3 Li Extra Hazard
Curve:
Date
Area of Sprinldei Operation
Density
Area Per Sprinider
Hose Allowance GPM: Inside
Hose Allowance GPM: Outside
Rack Surinkler Allowance
1500 SQ FT System Type
.1.0 E Wet LI Dry LI Deluge LI Pre-Action
20x20 MAX Sprinkler or Nozzle
0 Make TYCO Model EC-8
100 Size %" K-Factor: 8.0
Temperature Rating 135
CALCULATION SUMMARY
GPM Required 411.99 PSI Required 93.98 At Base of Riser
"C" Factor Used: Overhead 120 Underground 150
WATFP SITPPT,Y
Water Flow Test Pump Data Tank or Reservoir
Date & Time 4-4-11 Rated Capacity Capacity
Static PSI 128 At PSI Elevation
Residual PSI 124 Elevation
GPM Flowing 1440 Well
Elevation 0 Proof Flow GPM
Location SITE
Source of Information FLOW TEST BY EPIC FIRE AND CARLSBAD WATER DEPT.
COMMODITY S1OEAUL
Commodity OFFICE/GYM AREAS Class Location -
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
Rack
LI Single Row LI Conventional Pallet
LI Double Row LI Slave Pallet
Lit Multiple Row Lit Open
Flue Spacing In Inches
Longitudinal __
Transverse
-
Horizontal Barriers Provided
LI Automatic Storage LI Encapsulated
LI Solid Shelving LI Non-Encapsulated
Clearance From Top of Storage to Ceiling
Ft. In.
250
240 240
230
220
210
200
190
180
170
C/)
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
IC
C
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500 Sigma Dynamics Corporation
7700 Supply / Demand Graph
- Margin
Pressure 11.64 PSI
J Flow 2268.55 GPM
os
______________
W1.85
'200 400 600 800 1000 1200 1400 1600 1800 20 00
Water Flow (GPM)
System Demand..
Sprinkler Demand 102.79 PSI @ 411.99 GPM
Additional Flows 100.00 GPM
Hose at Source 0.00 GPM
Total Demand 103.02 PSI @ 511.99 GPM
Water Supply..
Static 115.20 PSI
Residual 111.60 PSI @ 1440.00 GPM
Elevation 0.00 PSI
SUBMITTAL SERIAL NO:232H?7
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500
FLOW TEST RESULTS
Water Supply
STATIC 115.20 PSI
RESIDUAL 111.60 PSI @ 1440.00 GPM
CITY PRESSURE AVAILABLE AT 512.0 GPM
06-30-2011 PAGE 1
114.67 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL
FLOW
- r - -
39.33
36.32
37 .92
35.66
38,59
.11
35.38
33.00
23.81
33.12
31.19
32.57
MINIMUM
FLOW
33.00
33.00
33.00
33.00
33.00
33.00
33.00
33.00
14 .83
33 .00
26.00
22.00
8.00
8.00
8.00
8.00
8.00
8 .00
8 .00
8.00
5.60
8.00
8 .00
8.00
24 .17
20.62
22.47
19.86
23.27
19.26
19.55
17 .02
18.08
17 .14
15.20
16.58
S PR
150
151
152
153
154
155
156
157
158
159
160
161
K- FACTOR PRESSURE
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 1
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
411.99 GPM
100.00 GPM
511.99 GPM
103.02 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 54 TO 85 18.87 FPS
LUI1PIII1LC
LL
tic
c m
ti
ut011 Ic I"
Iml,Thc'" MI. ,t%U %C\SW tY JIil I
p le,I\\
it at.
1t\' \' 11.I i
1 tILU II C
V. id 1id
11,c iite e.pl 11ihd iii
di
111iiill 11,1 c Ill
I IIO 1' Cd II I) I V IC iV.
NF'fl) AP'R )\A
0 R
) ND AvI AS
SUBMITTAL SERIAL NO :2932HY7 06-30-2011 PAGE 2
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
87 157 1.080 L 3.75 C=120 PT 17.02 (157)
Q 33.00 F=T,E F 8.10 PE -0.65
AO T 11.85 0.2852 PF 3.38
PT 19.75 ( 87)
91 161 1.080 L 3.75 C=120 PT 16.58 (161)
Q 32.57 F=2E F 4.60 PE -0.65
AO T 8.35 0.2784 PF 2.32
90 91 2.203 L 5.50 C=120 PT 18.25 ( 91)
Q 32.57 F=0 F 0.00 PE 0.00
BN T 5.50 0.0086 PF 0.05
PT 18.30 ( 90)
90
------------------
160 1.080 L 6.50 C=120 PT 15.20 (160)
Q 31.19 F=T,E F 8.10 PE -0.65
AO T 14.60 0.2569 PF 3.75
89 90DQ 32.57 2.203 L 9.50 C=120 PT 18.30 ( 90)
Q £3.76 F=0 F 0.00 PE 0.00
BN T 9.50 0.0300 PF 0.28
PT 18.58 ( 89)
89
------------------
159 1.080 L 1.50 C=120 PT 17.14 (159)
Q 33.12 F=T F 5.80 PE -0.65
AO T 7.30 0.2871 PF 2.10
88 89DQ 63.76 2.203 L 16.00 C=120 PT 18.59 C 89)
Q 96.88 F=0 F 0.00 PE 0.00
BN T 16.00 0.0650 PF 1.04
PT 19.63 ( 88)
88
------------------
158 1.080 L 6.00 C=120 PT 18.08 (158)
Q 23.81 F=T,E F 8.10 PE -0.65
AO T 14.10 0.1559 PF 2.20
87 88DQ 96.88 2.203 L 1.25 C=120 PT 19.63 ( 88)
Q 120.69 F=0 F 0.00 PE 0.00
BN T 1.25 0.0976 PF 0.12
86 87DQ 33.00 2.203 L 10.00 C=120 PT 19.75 ( 87)
Q 153.69 F=0 F 0.00 PE 0.00
EN T 10.00 0.1526 PF 1.53
PT 21.28 ( 86)
86
------------------
156 1.080 L 1.50 C=120 PT 19.55 (156)
Q 35.38 F=T F 5.80 PE -0.65
AO T 7.30 0.3243 PF 2.37
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 3
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
85 86DQ 153.69 2.203 L 9.00 C=120 PT 21.27 ( 86)
Q 129.06 F=0 F 0.00 PE 0.00
EN T 9.00 0.2238 PF 2.01
PT 23.28 ( 85)
85 155 1.080 L 6.50 C=120 PT 19.26 (155)
Q 35.11 F=T,E F 8.10 PE -0.65
AO T 14.60 0.3199 PF 4.67
54 85DQ 189.06 2.203 L 19.50 C=120 PT 23.28 ( 85)
Q 224.18 F=T F 11.60 PE 0.00
BN T 31.10 0.3067 PF 9.54
PT 32.82 ( 54)
84
------------------
154 1.080 L 1.50 C=120 PT 23.27 (154)
Q 38.59 F=E F 2.30 PE -0.65
AO T 3.80 0.3810 PF 1.45
83 84 2.203 L 9.75 C=120 PT 24.07 ( 84)
Q 38.59 F=0 F 0.00 PE 0.00
BN T 9.75 0.0118 PF 0.12
PT 24.19 ( 83)
83
------------------
153 1.080 L 7.00 C=120 PT 19.86 (153)
Q 35.66 F=T;E F 8.10 PE -0.65
AO T 15.10 0.3291 PF 4.97
82 83DQ 38.59 2.203 L 8.25 C=120 PT 24.18 ( 83)
Q 74.25 F=0 F 0.00 PE 0.00
EN T 8.25 0.0397 PF 0.33
PT 24.51 ( 82)
82
------------------
152 1.080 L 1.50 C=120 PT 22.47 (152)
Q 37.92 F=T F 5.80 PE -0.65
AO T 7.30 0.3688 PF 2.69
81 82DQ 74.25 2.203 L 7.00 C=120 PT 24.51 ( 82)
Q 112.17 F=0 F 0.00 PE 0.00
BN T 7.00 0.0852 PF 0.60
PT 25.11 ( 81)
81
------------------
151 1.080 L 7.00 C=120 PT 20.62 (151)
Q 36.32 F=T,E F 8.10 PE -0.65
AO T 15.10 0.3406 PF 5.14
80 81DQ 112.17 2.203 L 9.00 C=120 PT 25.11 ( 81)
Q 148.49 F=0 F 0.00 PE 0.00
EN T 9.00 0.1432 PF 1.29
PT 26.40 ( 80)
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 4
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
80 150
------------------
1.080 L 1.50 C=120 PT 24.17 (150)
39.33 F=T F 5.80 PE -0.65
AO T 7.30 0.3945 PF 2.88
53 80DQ 148.49 2.203 L 26.00 C=120 PT 26.40 ( 80)
Q 187.82 F=T F 11.60 PE 0.00
BN T 37.60 0.2211 PF 8.31
52 53 2.703 L 0.50 C=120 PT 34.71 ( 53)
Q 187.82 F=0 F 0.00 PE 0.00
FM T 0.50 0.0817 PF 0.04
51 52DQ 224.18 3.314 L 50.75 C=120 PT 34.75 ( 52)
Q 411.99 F=T,E F 26.20 PE 0.00
FM T 76.95 0.1294 PF 9.96
50 51 3.314 L 7.50 C=120 PT 44.71 ( 51)
Q 411.99 F=T,E F 26.20 PE 0.00
FM T 33.70 0.1294 PF 4.36
49 50 3.314 L 22.00 C=120 PT 49.07 ( 50)
Q 411.99 F=T,E F 26.20 PE -5.20
FM T 48.20 0.1294 PF 6.24
12 49 3.314 L 33.00 C=120 PT 50.11 ( 49)
Q 411.99 F=2E F 14.60 PE -1.42
FM T 47.60 0.1294 PF 6.16
11 12 3.314 L 11.00 C=120 PT 54.85 ( 12)
Q 411.99 F=2E F 14.60 PE 0.00
FM T 25.60 0.1294 PF 3.31
10 11 3.314 L 17.67 C=120 PT 58.16 ( 11)
Q 411.99 F=0 F 0.00 PE 0.00
FM T 17.67 0.1294 PF 2.29
9 10 3.314 L 17.67 C=120 PT 60.45 ( 10)
Q 411.99 F=0 F 0.00 PE 0.00
FM T 17.67 0.1294 PF 2.29
3 9 3.314 L 135.50 C=120 PT 62.74 ( 9)
Q 411.99 F=E F 7.30 PE 0.00
FM T 142.80 0.1294 PF 18.48
2 3 3.314 L 21.00 C=120 PT 81.22 ( 3)
Q 411.99 F=E F 7.30 PE 9.10
FR T 28.30 0.1294 PF 3.66
SUBMITTAL SERIAL NO :2932HY7 06-30-2011 PAGE 5
PACIFIC RIDGE GYMNASIUM 1ST FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
1 2 5.914 L 25.00 C=150 PT 93.98 ( 2)
Q 411.99 F=T,3E/DDC F 110.93 PE 0.00
UN T 135.93 0.0051 PF 0.69
6" AMES C500 RPDA 7.63
0 1DQ 100.00 7.758 L 290.00 C=150 PT 102.29 ( 1)
Q 511.99 F=T,GV F 58.94 PE 0.00
UN T 348.94 0.0020 PF 0.70
PT 95.37 ( 0)
------------------
52 54 2.703 L 17.00 C=120 PT 32.82 ( 54)
Q 224.18 F=0 F 0.00 PE 0.00
FM T 17.00 0.1133 PF 1.93
PT 34.75 ( 52)
EPIC FIRE PROTECTION, INC.
765 TURTLE PONT WAY
SAN MARCOS, CA 92069
(760)310-6 122 FAX (760) 798-0556
Hydraulic Design information Sheet
Asucs4
Name: PACIFIC RIDGE GYMNASIUM - 2ND FLOOR Date: 6-27-11
Location: 6269 EL FUIERTE, CARLSBAD
Building: NEW System No. 1 OF 1
Contractor: EPIC FIRE PROTECTION, INC. Contract No.
Calculated By. RAE Drawing No. 2 OF 2
Construction: LI Combustible Non-Combustible Ceiling Height 9' Ft.
SYSTEM DESIGN
NFPAI3: Light Hazard Ordinary Hazard Group 1 LI 2 [] 3 LI Extra Hazard
[II NFPA 231 III] NFPA23IC: Figure: Curve:
LI Other (Specify)
LI Specific Ruling Made By Date
Area of Spin1der Operation 1500 SQ FT System Type
Density .10 Z Wet LI Dry LI Deluge LI Pre-Action
Area Per Sprinkler 20x20 MAX Sprinkler or Nozzle
Hose Allowance GPM: Inside 0 Make TYCO Model EC-8
Hose Allowance GPM: Outside 100 Size %" K-Factor: 8.0
Rack Sprinkler Allowance Temperature Rating 135
CALCULATION SUMMARY
GPM Required 367.70 PSI Required 98.75 At Base of Riser
"C" Factor Used: Overhead 120 Underground 150
WATER SUPPLY
IL
Water Flow Test Pump Data Tank or Reservoir
Date & Time 4-4-11 Rated Capacity Capacity
Static PSI 128 At PSI Elevation
Residual PSI 124 Elevation
GPM Flowing 1440 Well
Elevation 0 Proof Flow GPM
Location SITE
Source of Information FLOW TEST BY EPIC FIRE AND CARLSBAD WATER DEPT.
COMMODITY STORAGE
Commodity OFFICE/GYM AREAS Class Location -
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
Rack
LI Single Row LI Conventional Pallet
LI Double Row LI Slave Pallet
L! Multiple Row EL Open
Flue Spacing In Inches
Longitudinal Transverse -
Horizontal Barriers Provided
LI Automatic Storage LI Encapsulated
LI Solid Shelving LI Non-Encapsulated
Clearance From Top of Storage to Ceiling
Ft. In.
PACIFIC RIDGE GYMNASIUM 2ND FLOOR .10/1500
Slgma Dynamics Corporation
7700 Supply / Demand Graph
Margin
Pressure 7.07 PSI
Flow 167S.97 GPM
-
V1 I I
_____ _____ ______ ______ _______ _______ N1
200 400 600 800 1000 1200 1400 1600 1800 2000
Water Flow (GPM)
System Demand.. Water Supply..
Sprinkler Demand 107.46 PSI @ 367.70 GPM Static 115.20 PSI
Additional Flows 100.00 GPM Residual 111.60 PSI @ 1440.00 GPM
Hose at Source 0.00 GPM Elevation 0.00 PSI
Total Demand 107.68 PSI @ 467.70 GPM
250
240
230
220
21t
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
SUBMITTAL SERIAL NO:2932HY7
PACIFIC RIDGE GYMNASIUM 2ND FLOOR .10/1500
FLOW TEST RESULTS
Water Supply
STATIC 115.20 PSI
RESIDUAL 111.60 PSI @ 1440.00 GPM
CITY PRESSURE AVAILABLE AT 467.7 GPM
06-30-2011 PAGE 1
114.75 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE
210 46.72 40.00 8.00 34.11
211 33.36 14.83 5.60 35.49
212 45.30 40.00 8.00 32.07
213 41.91 40.00 8.00 27.45
214 41.40 40.00 8.00 26.78
215 40.00 40.00 8.00 25.00
216 43.39 40.00 8.00 29.42
217 43.36 40.00 8.00 29.37
218 32.25 19.60 5.60 33.17
TOTAL WATER REQUIRED FOR SYSTEM 367.70 GPM
OUTFLOWS AT 1 100.00 GPM
TOTAL WATER REQUIREMENT 467.70 GPM
PRESSURE REQUIRED AT 0 107.68 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 22 TO 33 21.35 FPS
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 2
PACIFIC RIDGE GYMNASIUM 2ND FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
35 215 1.080 L 1.75 C=120 PT 25.00 (215)
Q 40.00 F=0 F 0.00 PE -0.76
AO T 1.75 0.4071 PF 0.71
34 35 1.536 L 16.00 C=120 PT 2495 ( 35)
Q 40.00 F=T V 8.90 PE 0.00
BN T 24.90 0.0732 PF 1.82
PT 26.77 ( 34)
38 218 1.080 L 1.75 Cr120 PT 33.17 (218)
Q 32.25 F=0 F 0.00 PE -0.76
AO T 1.75 0.2733 PF 0.48
37 38 1.536 L 16.00 C=120 PT 32.89 ( 38)
Q 32.25 F=0 F 0.00 PE 0.00
BN T 16.00 0.0492 PF 0.79
PT 33.68 ( 37)
36 216
------------------
1.080 L 1.75 C=120 PT 29.42 (216)
Q 43.39 F=0 F 0.00 PE -0.76
AO T 1.75 0.4732 PF 0.83
23 36 1.080 L 13.25 C=120 PT 29.49 ( 36)
Q 43.39 F=T,E F 8.10 PE 0.00
AO T 21.35 0.4732 PF 10.10
PT 39.59 ( 23)
34 214
------------------
1.080 L 1.75 C=120 PT 26.78 (214)
Q 41.40 F=0 F 0.00 PE -0.76
AO T 1.75 0.4338 PF 0.76
33 34DQ 40.00 1.536 L 12.50 C=120 PT 26.78 ( 34)
Q 81.40 F=T F 8.90 PE 0.00
BN T 21.40 0.2726 PF 5.83
PT 32.61 ( 33)
202 213
------------------
1.080 L 1.75 C=12.0 PT 27.45 (213)
Q 41.91 F=0 F 0.00 PE -0.76
AO T 1.75 0.4438 PF 0.78
33 202 1.080 L 3.50 C=120 PT 27.47 (202)
Q 41.91 F=T,E F 8.10 PE 0.00
AO T 11.60 0.4438 PF 5.15
22 33DQ 81.40 1.536 L 3.50 C=120 PT 32.62 ( 33)
Q 123.31 F=T F 8.90 PE 0.00
BN T 12.40 0.5878 PF 7.29
PT 39.91 ( 22)
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 3
PACIFIC RIDGE GYMNASIUM 2ND FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
32
------------------
212 1.080 L 1.75 C=120 PT 32.07 (212)
Q 45.30 F=0 F 0.00 PE -0.76
AO T 1.75 0.5125 PF 0.90
21 32 1.080 L 11.00 C=120 PT 32.21 ( 32)
Q 45.30 F=T F 5.80 PE 0.00
AO T 16.80 0.5125 PF 8.61
PT 40.82 ( 21)
201
------------------
211 1.080 L 1.75 C=120 PT 35.49 (211)
Q 33.36 F=0 F 0.00 PE -0.76
AO T 1.75 0.2910 PF 0.51
31 201 1.080 L 3.75 C=120 PT 35.24 (201)
Q 33.36 F=T,E F 8.10 PE 0.00
AO T 11.85 0.2910 PF 3.45
30 31 1.536 L 10.50 C=120 PT 38.69 ( 31)
Q 33.36 F=0 F 0.00 PE 0.00
BN T 10.50 0.0524 PF 0.55
PT 39.24 ( 30)
200
------------------
210 1.080 L 1.75 C=120 PT 34.11 (210)
Q 46.72 F=0 F 0.00 PE -0.76
AO T 1.75 0.5427 PF 0.95
30 200 1.080 L 1.00 C=120 PT 34.30 (200)
Q 46.72 F=T,E F 8.10 PE 0.00
AO T 9.10 0.5427 PF 4.94
20 30DQ 33.36 1.536 L 3.50 C=120 PT 39.24 ( 30)
Q 80.09 F=T F 8.90 PE 0.00
BN T 12.40 0.2646 PF 3.28
PT 42.52 ( 20)
37
------------------
217 1.080 L 1.00 C=120 PT 29.37 (217)
Q 43.36 F=T,E F 8.10 PE 0.00
AO T 9.10 0.4725 PF 4.30
23 37DQ 32.25 1.536 L 16.00 C=120 PT 33.67 ( 37)
Q 75.61 F=T F 8.90 PE 0.00
BN T 24.90 0.2378 PF 5.92
22 23DQ 43.39 2.703 L 8.75 C=120 PT 39.59 ( 23)
Q 119.00 F=0 F 0.00 PE 0.00
FM T 8.75 0.0351 PF 0.31
SUBMITTAL SERIAL NO:2932HY7 06-30-2011 PAGE 4
PACIFIC RIDGE GYMNASIUM 2ND FLOOR .10/1500
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
21 22DQ 123.31 2.703 L 7.00 C=120 PT 39.90 ( 22)
Q 242.31 F=0 F 0.00 PE 0.00
FM T 7.00 0.1308 PF 0.92
20 21DQ 45.30 2.703 L 9.50 C=120 PT 40.82 ( 21)
Q 287.61 F=0 F 0.00 PE 0.00
FM T 9.50 0.1796 PF 1.71
13 20DQ 80.09 2.703 L 63.50 C=120 PT 42.53 ( 20)
Q 367.70 F=0 F 0.00 PE 0.00
FM T 63.50 0.2830 PF 17.97
49 13 3.314 L 20.00 C=120 PT 60.50 ( 13)
Q 367.70 F=0 F 0.00 PE -0.86
FM T 20.00 0.1049 PF 2.10
12 49 3.314 L 33.00 C=120 PT 61.74 ( 49)
Q 367.70 F=2E F 14.60 PE -1.42
FM T 47.60 0.1049 PF 4.99
11 12 3.314 L 11.00 C=120 PT 65.31 ( 12)
Q 367.70 F=2E F 14.60 PE 0.00
FM T 25.60 0.1049 PF 2.69
10 11 3.314 L 17.67 C=120 PT 68.00 C 11)
Q 367.70 F=0 F 0.00 PE 0.00
FM T 17.67 0.1049 PF 1.85
9 10 3.314 L 17.67 C=120 PT 69.85 ( 10)
Q 367.70 F=0 F 0.00 PE 0.00
FM T 17.67 0.1049 PF 1.85
3 9 3.314 L 135.50 C=120 PT 71.70 C 9)
Q 367.70 F=E F 7.30 PE 0.00
FM T 142.80 0.1049 PF 14.98
2 3 3.314 L 21.00 C=120 PT 86.68 ( 3)
Q 367.70 F=E F 7.30 PE 9.10
FR T 28.30 0.1049 PF 2.97
1 2 5.914 L 25.00 C=150 PT 98.75 C 2)
Q 3-67.70 F=T,3E/DDC F 110.93 PE 0.00
UN T 135.93 0.0041 PF 0.56
6" AMES C500 RPDA 7.77
0 1DQ 100.00 7.758 L 290.00 C=150 PT 107.09 C 1)
Q 467.70 F=T,GV F 58.94 PE 0.00
UN T 348.94 0.0017 PF 0.59
PT 107.68 ( 0)
,LfPh? 74*5L- CHoOl!YL(
- -• -
Gregory Ryan LoZ#7
From: Epic Fire Protection, Inc. <epicfire@coxnet>
Sent: Tuesday, January 03, 2012 9:39 AM
To: Gregory Ryan
Subject: Fw: hangers
Attachments: HANGER.pdf
Greg,
Here is the email I sent to Dominic. See you tomorrow.
Adam
From: Epic Fire Protection, Inc.
Sent: Thursday, December 22, 20119:03 AM
To: dominic.fieri@carlsbadca.gov
Subject: hangers
Dominic,
Here is a sketch of the hanger detail at Pac Ridge Gym that we talked about yesterday. There really is no way
to install a secondary hanger or splay wire due to the other z-purlins being over 5' away so we ran the lines
tight to the I-beams and stiff-rodded the all thread. This installation does not allow the line to move either up
or down or side to side since the line is tight to the I-beam. Please discuss it with Greg in your Tuesday
meeting as we talked about and let us know if this installation is acceptable to Carlsbad. We also added the
secondary hangers at all the office areas as we discussed.
Adam Boisvert
Epic Fire Protection, Inc.
765 Turtle Point Way
San Marcos, CA 92069
760-310-6122 Fax 760-798-0556
epicfire@cox.net
1
FftcL_jJ
;fl
LI!IE Tk*tT T
r
LJfI
T
1
04/25/2012 10:16 FAX 17607980556 EPIC FIRE PROTECTION INC 002/004
Contractor's Material and Test Certificate for Abovegro3lng
PROCEDURE .
Upon compM'
All deface aba
1 of work, Inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative.
be corrected and eyétem left In service before contractors personnel finally leave thO job.
A certificate eli
contractor. It Ii
H be filled out and signed by both representatives. Copies shall be prepared for approving authôrltIee owners, and
understood the owner's representative's signature In no way prejudices any claim against Contractor for faulty material, poor
worlunanshlp, i r failure to comply with approving authority's requirements or local ordinances.
Property nam, .0 12
— ° 4.
Property addra s LC)
Accepted by approving authorities $) iPtT~. 0
Address.
Plans .
•
.
Installation conforms to accepted plane .
0 0 fJ Yes D No
EquIpment used Is approved .
0 . Yes No
•. . Ifflo, explain deviations .. :. . . . 0 .•
Has person In charge of fire equipment been instructed as . Yes E] No
to location of control valves and care and maintenance . ... .
ofthlsnewequlprnenl? .
•0
If no,
InstructIons
.
0
Have copies of the following been left on the premises? LJ Yes D No
System components instructIons .' Yes LJ No
Care and maintenance. Instructions ,. . . YeS 0 0 No
NFPA25 . . . Yes . [J No
Location of:Supplies
0
0 buildingssystem
•
Spniniders
-
Make
•
Model
Year of
manufacture
. Orifice
size QuantIty •.
Temperature
rating
0
4.. 3
_____________
Pipe and - Type of pipe
Stings Type of linings t"to
0 0 •.• •, . . 0 Medmum time 0 operate
Alarm 0 Alarm device •.•
0 0 throughtost connection __0
VaW or ______________ -Make Model Mlnutós. Seconds
Indicator
.••• • :. Dry
0 40.0,
Make Model Serial no.Make Model no
-
,0 . 00 0 .•
.•
..••
-
•
Dry *0
test . roung
... _
Time
through test
oUon1 --_w_ater
0
Air
ressure
.
It
a
nt
ir pressure __
'Time water
reached
__ _____
. Alarm
operated
property
__
Minutes Seconds
.
psi psi Minutes Seconds YO No No
0
____. ,.
• With
222
pe
04/25/2012 10:17 FAX 17607980556 EPIC FIRE PROTECTION INC 003/004
'Z " Operation 1J Electric Hydraulics
PJpiogsupervised 0 ye. 0 NO Detecting mdlaeupeMsed 0 No
Does valve porate from the manual trip, remote, or both Yes No
Deluge and
valves
Make Model
Does each ckult to
supelyfelo alarm?
Does each drcutt operate
valve releaso?
Ma,dmum time to
operate release
J
No Yee—, NO Minutes Seconds
Pressure
Location
an r
akeand
modal
Setting Static pressure Rd" pcauro
(fiowIn.
Pow rate
0 lnlet(pel) Oullet(psl) Ir11óteI) Outlet(psl) (gprn)
Test
Hydflc Hydroetatictestsehaflbomadeatnotleaathan200pei(la6bar)tor2hoursor5opsl(a4bw)
above static pressure In excess of 150 pel (10.2 bar) for 2)'cws. Dltferpnflal drypipe Valve dappers shall be left
Opefl duringihe tost to prevent damage All aboveground piping leakage shall be stopped
description Pnuc Establish 40 psi (27 bar) air pressure and measure drop, which shall not exceed 1½ pal (0.1 bar)
In 24betir Test pressure tanks at normal Vater lovol and air pressure and measure air pressure drop, which shall
notexceodl½pel(O,1 bar) In24hours
Ati piping hydràetatiàallyteted at2OC?psl(_ forhorn
Drypiping pneumatIcally tested [J Yes No WA
Eqpment operates PrOPertY Yes 0 No
if no, atate.reaecn -.
Do you certify as the apdnkle( cOntractor that additives and corrosive Chemicals, aodkim silicate or derivatives
of sodium silicate, brine, or other corrosive chemicals were not used for testing systems or stopping leaks?
Yes No ,..• . ......
0
S
Teats
Drain.
test Isupplytestconnectlon
Reading of gauge located near water
11(. bat) jconnectlonopenwide
Reakival pressure with valve inteet 6 pel(_ bar)
Underground maIns and load In connectIoie to system risers flushed before connection made
to Sprinkler piping
Vortflød by Copy of the U Form No.855. I) Yes •0 No Other. . Explain
flUshed by Installer of underground . . . . . .
sprinkler piping . ..
Yes
• No . .
.
.
If POwderdlfVefl fastenem are used fri concrete, has 0 Yes 0 No If no, explain
representative sample testing be satisfactorily
Blank testing
gaskets
Number used
. .. . .
Number removed
Walding piping Yes 0 No
Ifyas...
Do you ertIf -as the .apn)dor contractor that weklIngprc9edures.00mply .• ... Yes 0 No
wIth the requIrements of at leastAWS B2 1?
'Welding Do you certify that the weldlngwas performed .by.weidsrsquallfled In . .. •. Yes 0 No Do
with the requirements of at ISast AWS B2M
Doyoucerllfy.thatth Id ardedon with documented . . . yQ 0 No
quality conttol procedure to ensure that all discs are .1 that openings
In piping are atnooth, that slag andothar welding residue ate removed, and that
the internal diameters of pIping are not penetrated?
Cutouts
(discs)
Do you certify that you havo a control feature to ensure that . . Yes [J No
-all cut U. (discs) are retrieved? . 0
0
- 0•• 0 0 0 0 .
04/25/2012 10:17 FAX 17607980556 EPIC FIRE PROTECTION INC 004/004
Hydraulic Nameplate piv1ded if no, explain
data
fl5lfleplStO [Yes : No
Date left In service with all control valves open 4 T%5p. (2..
Remerm
Name of aFdfllder ContrUor
iEP&- lFi me ?t. (- C
Tesbwith.isdby
Signatum For piperty owner (signed) Title Date
spdnldor- .0on"r (6icae bgfn