HomeMy WebLinkAbout3683 VALLEY ST; ; FPR2017-0253; PermitPERE"iflET REPORT CC City of
Carlsbad
I L1HiiU
-
-1
Print Date: 10/05/2022 Permit No: FPR2017-0253
Job Address: 3683 VALLEY ST, CARLSBAD, CA 92008-2640 Status: Closed - Finaled
Permit Type: FIRE-Construction Residential Work Class: Single Family Fire Sprinkl
Parcel #: Track #: Applied: 06/21/2017
Valuation: $0.00 Lot #: Issued: 07/06/2017
Occupancy Group: Project #: Finaled Close Out: 04/15/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Stowe, Daniel
Plan Check #:
Project Title:
Description: MAZOR RESIDENCE - SFD SPRINKLER NFPA 13D
CoApplicant:
SERGIO ARREOLA
6893 BROWNING RD
HIGHLAND, CA 92346-5012
(909) 674-7151
FEE AMOUNT
FIRE NFPA 13D Single Family System (Insp/Bldg) $121.00
FIRE NFPA 13D Single Family System (Plan Review) $239.00
FIRE Reinspection (per inspection) $187.00
Total Fees: $547.00 Total Payments To Date: $547.00 Balance Due: $000
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Signature
RECEIVED FPR20I 7-0253
JUN 212017
CARLSBAD FIRE PERI 3683 Valley ST
FIRE DEPARTMENT J 1635 Farada
Phone: 760-61
ww
Project Information
Project Name fl, 2. i R f-6 J &6Z.
Project Add res
Scope of Work
Associated Building Permit # (if applicable)
0 Fire Sprinkler System: Number of risers --L Number of heads _____
0 Fire Alarm 0 Underground: Number of hydrants_________
0 Sprinkler Monitoring 0 Other:
New system 0 Tenant Improvement
Contractor Information
Company Name
Address L6 193 City i4'iL)o.irl State CA Zip
Applicant Name
Phon('O) h ' /5/ Email rrep). ê~& 'r
Contractor License Number and Type C /4 /O22 2AJ Exp. Date _____
City Business License Number
- - --*----.--- ---.---.-- ---.----- - --
- -
-
- - - - - - - - - - - -
-
',GM 2)&W tUfl bLcAWC!
J - --
r J ( ! )i1'!. ' - - -
:••!_ ''I --
9jcq --
-
-
i-Loiq 4fl.J
bP:
- :tiqA VAG CLjpsq CV S003
-
No. 107
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4666
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 3683 Valley Street CITY: Carlsbad
PHONE: (714) 855-6021 (Custom Fire Sprinklers) FAX NUMBER:
Largest Building (ft.2): Sprinkled? Construction Type:________________
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): Magnolia Ave at Valley St
Flow Test Results
Static pressure: 65 PSI Hydrant Number (if applicable): H60807
Elevation of test: 178 Feet Date/Time of Test':
Pitot Tube Reading: PSI Corresponding Flow: GPM
Total Flow: 4.350 GPM Residual Pressure 24 PSI
t peak demand . this water system is capable of providing a fire flow discharge of 4,350 gpm at the maximum velocity
f 10 fps. At 20 psi, the velocity in this area would exceed the maximum 10 fps and is not recommended per criteria.
tTest to be performed as close as possible to the time the most conservative flows and pressures are expected.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here:
I have witnessed and/or reviewed this water flow information and by personal knowledge and/or on-site
observation certify that the above information is correct.
Name: Jennifer R.Mael.P.E. Eng. Lic. No. (if applicable): C69606
Signature:______________________________________
iv
Title/Org: PLo_Ct Manager Date: 06/16/2017
:
ii OAECU'.3
Cflt - cf'.
ou
MnCF VTI.HEif- JAVA ThT'.VJ
FIN 5 rIT-1 U-1 !lj (ir1j .(fl
T p.- I. /c.i• J i:''T
- -- :..?
Z11 ( T? .41 .11,LVI MUMUND PITAIJ itL)OJ Vi C iqMOD i 3T :
- - - - -- - /
y_t,
-- 'i J ji.qin .-r9.
:&fl 1T v c13
I
— —-Div
" fi 4 J-i
i
H .. JflCmi,•rnr ljr. :O t . r/rri 1.
r : br 6 r.ji r v,cat, "rc.-' .-,r'I '
.' .\L:Lj -
'.
__
-- 1
£ -
Fr - -. -
-i 1
1'.
1
L - -
-
rr
0
i
13
MAZURE NEW RESIDENCE Drawing Date: 6-20-17 6/17/17 11:16
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: MAZURE NEW RESIDENCE
Location: 3683 VALLEY STREET,
CARLSBAD, CA 92006
Drawing Date: 6-20-17
Contractor: CUSTOM FIRE SPRINKLERS
6983 BROWNING ROAD
HIGHLAND, CA 92346
Designer: PAXTON
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-B
Reviewing Authorities:CARLSBAD FIRE DEPT
SYSTEM DESIGN
Remote Area Number: 1
Telephone:909-674-7151
Occupancy: R-3
Code:NFPA 13D Hazard: LIGHT System Type:WET
Area of Sprinkler Oper. NFPA 13D I Sprinkler or Nozzle
Density (gpm/sq ft) RES I Make: VIKING
Area per Sprinkler 256.0 sq ftl Model: VK494
Hose Allowance Inside 0 gpm K-Factor: 4.90
Hose Allowance Outside 100 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 31.6 psi Required: 46.5 @ City Supply
WATER SUPPLY
Water Flow Test I Pump Data I
Date of Test 6-16-17 Rated Capacity 0 gpm I
Static Pressure 65.0 psi Rated Pressure 0.0 psi
Residual Pres 24.0 psi I Elevation 0
At a Flow of 4350 gpm I Make:
Elevation 0" I Model: I
Location: MAGNOLIA AVE & VALLEY ST
Source of Information: CITY OF CARLSBAD
SYSTEM VOLUME 19 Gallons
Notes:
FPR20I 7-0253
3683 Valley ST
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:16
HYDRAULIC CALCULATION DETAILS
HYDRAULIC
QTY DESCRIPTION LENGTH C ID
Hydr Ref TR Required at Hyd Area 1
1 1" Grvd Check Valve 0' 0 1.049
1 F' Thrd Ball Valve Central F19 0' 0 1.049
1 Pipe F' PVx15 BiazeMa Plastic 10' 150 1.101
Elevation Change 12'0"
Fixed Flow Domestic Allowance
Hydr Ref BR Required at Base of Riser
4 1-1/4" CPVC 90 Eli CPVC 24' 120 1.380
1 Pipe 1-1/4" PVx15 BiazeMa Plastic 50' 150 1.394
1 1" Thrd Other Valve Tyco Water Me CHART LOSS
1 Pipe 1" Kxl0 Copper 15' 150 0.995
Hydr Ref SR Required at City Supply
Water Source 65.0 psi static, 24.0 psi residual @ 4350 gpm
SAFETY PRESSURE
FLOW LOSS
gpm psi TOTALS
27 26.6 psi
27 0.0
27 0.0
27 1.1
5.2
5 gpm
32 32.9 psi
32 3.1
32 2.5
32 4.1
32 3.9
32 46.5 psi
32 gpm 65.0 psi
18.5 psi
Available Pressure of 65.0 psi Exceeds Required Pressure of 46.5 psi
This is a safety margin of 18.5 psi or 28 % of Supply
Maximum Water Velocity is 9.0 fps
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:16
Page 3
--------------------------------------------------------------------------------
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram. - K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pa = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)"1.85 / ID"4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:16
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI")) (PSI) (GPM) (GPM) (GPM/SQ.FT)
1 20.50 7.4
is 20.00 4.90 7.0 13.0 13.0 0.05
2 20.50 8.1
2S 20.00 4.90 7.7 13.6 13.0 0.05
11 20.50 8.4
12 20.50 8.4
13 20.50 16.8
A3 10.50 24.7
TR 10.50 26.6
Max velocity of 9.04 occurs in the pipe from TR TO A3
Nodes with "S" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "S" is on the branch.
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:16
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 1 TO TR (PRIMARY PATH)
12.96 0.874 1E 0.50 7.0 7.0 K = 4.90
15 C=150 5.60 -0.2 0.0
12.96 0.094 6.10 0.6 7.0 Vel = 7.00
0.874 iT
--------------------------------------------------------------------------------
2.74 7.4 7.4 EqK = 4.78
1 C=150 8.40 0.0 0.0
12.96 0.094 11.14 1.0 7.4 Vel = 7.00
1.01 0.874 2E
--------------------------------------------------------------------------------
41.86 8.4 8.4
12 C=150 3T 36.41 0.0 0.0 See PATH 3
13.97 0.108 78.27 8.4 8.4 Vel = 7.54
12.59 1.101 1E
--------------------------------------------------------------------------------
16.87 16.8 16.8
13 C=150 iT 13.39 4.3 0.0 See PATH 2
26.56 0.115 30.26 3.5 16.8 Vel = 9.04
1.101 1E
--------------------------------------------------------------------------------
12.82 24.7 24.7
A3 C=150 3.83 0.0 0.0
26.56 0.115 -------------------------------------------------------------------------------- 16.65 1.9 24.7 Vel = 9.04
TR 26.56 26.6 K = 5.15
PATH 2 FROM HYDRAULIC REFERENCE 2 TO 13
13.60 0.874 1E 0.50 7.7 7.7 K = 4.90
2S C=150 5.60 -0.2 0.0
13.60 0.103 6.10 0.6 7.7 Vel = 7.34
0.874
--------------------------------------------------------------------------------
2.74 8.1 8.1 EqK = 4.77
2 C=150 0.00 0.0 0.0
13.60 0.103 2.74 0.3 8.1 Vel = 7.34
-1.01 0.874 1E
--------------------------------------------------------------------------------
64.25 8.4 8.4
11 C=150 3T 30.81 0.0 0.0 See PATH 3
12.59 0.089 -------------------------------------------------------------------------------- 95.06 8.5 8.4 Vel = 6.80
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:16
Tyco Fire Products Page 6
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
13 12.59 16.8 K = 3.07
PATH 3 FROM HYDRAULIC REFERENCE 11 TO 12
1.01 0.874 iT
--------------------------------------------------------------------------------
9.69 8.4 8.4
11 C=150 8.40 0.0 0.0 See PATH 2
1.01 0.001
--------------------------------------------------------------------------------
18.09 0.0 8.4 Vel = 0.54
12 1.01 8.4 K = 0.35
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW .(GPM) PRESSURE (PSI)
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:17
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: MAZURE NEW RESIDENCE
Location: 3683 VALLEY STREET,
CARLSBAD, CA 92006
Drawing Date: 6-20-17 Remote Area Number: 2
Contractor: CUSTOM FIRE SPRINKLERS Telephone:909-674-7151
6983 BROWNING ROAD
HIGHLAND, CA 92346
Designer: PAXTON
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-B Occupancy:R-3
Reviewing Authorities:CARLSBAD FIRE DEPT
SYSTEM DESIGN
Code:NFPA 13D Hazard:LIGHT System Type:WET
Area of Sprinkler Oper. NFPA 13D I Sprinkler or Nozzle
Density (gpm/sq ft) RES I Make: VIKING
Area per Sprinkler 256.0 sq ftl Model: VK494
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 100 gpm Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 31.4 psi Required: 53.4 @ City Supply
WATER SUPPLY
Water Flow Test Pump Data
Date of Test 6-16-17 I Rated Capacity 0 gpm I
Static Pressure 65.0 psi I Rated Pressure 0.0 psi I
Residual Pres 24.0 psi I Elevation 0 I
At a Flow of 4350 gpm I Make: I
Elevation 0" Model:
Location: MAGNOLIA AVE & VALLEY ST
Source of Information: CITY OF CARLSBAD
SYSTEM VOLUME 19 Gallons
Notes:
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:17
HYDRAULIC CALCULATION DETAILS
HYDRAULIC
QTY DESCRIPTION LENGTH C ID
Hydr Ref TR Required at Hyd Area 2
1 1" Grvd Check Valve 0' 0 1.049
1 1" Thrd Ball Valve Central F19 0' 0 1.049
1 Pipe 1" PVx15 BlazeMa Plastic 10' 150 1.101
Elevation Change 12'0"
Fixed Flow Domestic Allowance
Hydr Ref BR Required at Base of Riser
4 1-1/4" CPVC 90 Ell CPVC 24' 120 1.380
1 Pipe 1-1/4" PVx15 BlazeMa Plastic 50' 150 1.394
1 1" Thrd Other Valve Tyco Water Me CHART LOSS
1 Pipe 1" Kx10 Copper 15' 150 0.995
Hydr Ref SR Required at City Supply
Water Source 65.0 psi static, 24.0 psi residual 8 4350 gpm
SAFETY PRESSURE
FLOW LOSS
gpm psi TOTALS
26 33.6 psi
26 0.0
26 0.0
26 1.1
5.2
5 gpm
31 39.9 psi
31 3.1
31 2.5
31 4.1
31 3.9
31 53.4 psi
31 gpm 65.0 psi
11.6 psi
Available Pressure of 65.0 psi Exceeds Required Pressure of 53.4 psi
This is a safety margin of 11.6 psi or 18 % of Supply
Maximum Water Velocity is 14.3 fps
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:17
Page 3 --------------------------------------------------------------------------------
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
- K FACTOR Flow factor for open head or path where Flow (gpm) = K x
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)"1.85 / ID4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
lu
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:17
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI)) (PSI) (GPM) (GPM) (GPM/SQ.FT)
3 13.00 7.4
3S 12.50 4.90 7.0 13.0 13.0 0.05
4 13.00 8.2
4S 12.50 4.90 7.6 13.5 13.0 0.05
11 20.50 27.3
12 20.50 27.3
13 20.50 27.3
Al 13.00 16.6
A2 13.00 26.5
A3 10.50 31.7
TR 10.50 33.6
Max velocity of 14.28 occurs in the pipe from Al TO 4
Nodes with "5" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "5" is on the branch.
4
MAZURE NEW RESIDENCE Drawing Date:6-20-17 6/17/17 11:17
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 3 TO TR (PRIMARY PATH)
12.96 0.874 1E 0.50 7.0 7.0 K = 4.90
3S C=150 5.60 -0.2 0.0
12.96 0.094 6.10 0.6 7.0 ye! = 7.00
0.874
--------------------------------------------------------------------------------
9.50 7.4 7.4 EqK = 4.78
3 C=150 0.00 0.0 0.0
12.96 0.094 9.50 0.9 7.4 ye! = 7.00
13.48 0.874 1E
--------------------------------------------------------------------------------
18.32 8.2 8.2 EqK = 4.69
4 C=150 5.60 0.0 0.0
26.44 0.351 23.93 8.4 8.2 Vel = 14.28
0.874
--------------------------------------------------------------------------------
28.00 16.6 16.6
Al C=150 0.00 0.0 0.0
26.44 0.351 28.00 9.8 16.6 Vel = 14.28
1.101 3E
--------------------------------------------------------------------------------
24.52 26.5 26.5
A2 C=150 11.48 1.1 0.0
26.44 0.114 35.99 4.1 26.5 ye! = 9.00
1.101 1S
--------------------------------------------------------------------------------
12.82 31.7 31.7
A3 C=150 3.83 0.0 0.0
26.44 0.114
--------------------------------------------------------------------------------
16.65 1.9 31.7 ye! = 9.00
TR 26.44 33.6 K = 4.56
13.48 0.874 1T 0.50 7.6 7.6 K = 4.90
4S C=150 8.40 -0.2 0.0
13.48 0.101 -------------------------------------------------------------------------------- 8.90 0.9 7.6 ye! = 7.28
4 13.48 8.2 K = 4.69
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)