HomeMy WebLinkAbout5808 VAN ALLEN WAY; ; AS140273; PermitCity ot Carlsbad
Sprinkler Permit
Permit No: AS140273
5808 VAN ALLEN
Job Address:
WY
Permit Type: SPRINK
Parcel No: 2121205600
Lot #: 0
Status: ISSUED
Applied 10/23/2014
Approved: 11/4/2014
Reference No.: Issued: 11/4/2014
PC #: Inspector:
Project Title: JOSE TACOS INSTALL NEW RECESSED STANDARD SPRAY
PENDENT FROM EXISTING 1" OUTLET AT LOCATION ON
PLANS,
Applicant:
TOTAL FIRE PROTECTION, INC
STE. 244
1611-A S. MELROSE DR.
VISTA, CA
760-525-4329
Owner:
BERDAN HOLDINGS L L C
C/O BLT ENTERPRISES
501 SPECTRUM CIR
OXNARD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
280 0 280 0
1 40
MATERIAL DATA SUBMITTAL
Jose Tacos
5808 Van Allen Way, Suite 112
Carlsbad, CA 92008
r'S
Des
Pipe Allied Dyna-Thread Pipe
Fittings Tyco Ductile Iron Fittings
Mechanical Tee Tyco Fig 40-5 Strap Tee
Sprinkler Tyco TY-FRB Recessed Sprinkler
Hanger Afcon Fig. 300 Ring Hanger
Hanger Afcon Fig 655 All Thread Rod
Attachment Sammy Wood Vertical Mount
AS 140273
Total Fire Protection, Inc.
1611 A S. Melrose Dr. *244
Vista, CA 92081
(760)525-4329 fax (877) 724-4329
C16-955387
tfpjohnc@gmail.com
Page *
1-2
3-10
11-12
13-19
20
21
22
(S
S Full Line Sch-40 Replacement
Dyna-Thread' offers the life expectancy of Sch40 with superior hydraulics and greater value.
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
S
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is fully listed and
approved by UL, IJLC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
~D ei
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR=1.00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Super 40/Dyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA-13. All sizes of Super 40fDyna-
Thread are rated at 300 psi working
pressure. Super 40/Dyna-Thread is UL
and ULC Listed for wet, dry deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
f!Speci fications
NPS Nominal I.D. Wt. WI. (1120 Filled) Pc WtlUft (21') Wtititt (24') Wt/Lift (25')
In; mm In; mm Lbs/Fl; Kg/rn Lbs/F!; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.080 1.330 1.75 70 1955 2234 2327
25 27.4 2.0 2.60 70 887 1013 105
1Y4 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1'/? 1.639 2.290 3.22 44 2115 2418 2511
40 41.6 3.4 4.79 44 959 1097 114
2.104 3.050 4.57 30 1921 2196 2287
50 53.4 4.5 6.80 30 871 996 103
tqco/F/ow Control (') cIIje3 16100 S. Lathrop• Harvey, IL 60426
11350 Norcom Rd. • Philadelphia, PA 19154
TUBE & CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009
Customer Service: 1 (800) 882-5543
Fax 708-339-1806
S3-3
Submittal Data Sheet Dyna Threade
Full Line Sch-40 Replacement
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with
quality and superior hydraulic advantages.
Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6% larger than
Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe, down sizing often occurs. Dyna-Thread is fully listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna-Thread and Sch-40
are equal based on the calculated wall thicknesses per UL. The consistent quality of
steel used to make Dyna-Thread facilitates smooth threading and lower maintenance
costs. The exterior of Dyna-Thread is protected by a clean, durable mill coating for
extended shelf life and easy paint application. With its increased strength and lighter
weight, Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications.
Corrosion Resistance Ratio (CRR) is a UL (Underwriters Laboratory) term for the
estimated life expectancy of a pipe joint. This is based on the calculated wall thickness
at the base of the first exposed thread, assumed to be the weakest point of the pipe
length. Dyna-Thread and Sch-40 have the same calculated wall thicknesses at this
point and are both assigned the same CRR of 1.00.
Comparison to L.W.T. Pipe More wall thickness at the thread (CRR=l .00) gives
Dyna-Thread better life expectancy than lightwall threadable pipe joints. Unlike
lightwall threadable pipe Dyna-Thread has no thread gauge warning. Dyna-Thread is
approved for standard hanger spacing (15 ft. O.C.), can be used as earthquake sway
bracing, and is safe to use as drops. Dyna-Thread is safer to weld on than many zinc-
coated lightwall threadable pipe products. Dyna-Thread is more widely accepted than
lightwall threadable where Sch40 is specified.
Stamp Here
Specifications & Approvals Super 40/
Dyna-Thread pipe is manufactured to
meet: ASTM A 135, Grade A and is in
compliance with NFPA-13. All sizes of
Super 40/Dyna-Thread are rated at 300
psi working pressure. Super 40/ Dyna-
Thread is UL and ULC Listed for wet,
dry and pre-action sprinkler systems and
FM Approved for use in wet systems.
Super 40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all roll-
grooved, and plain-end fittings. (See
listing information).
The internal surface of all black Fire
Sprinkler pipe up to 4.5000" in diameter
shall be coated with Allied Tube &
Conduit Antibacterial Formula "ABF".
NPS Nominal I.D. M. WI. (H20 Filled) Pcs/ WI/lift(211) Wi/tIlt (241) Wi/tIlt (25'
In; mm In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105i
11R 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1h/2 1.639 2.290 3.22 44 2115 2418 2511
40 41.6 3.4 4.79 44 959 1097 114
2 2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
American Tube and Pipe was acquired by Allied Tube and Conduit on February I,
1997. The engineered lightwall and standard wall family of products although they
have different names are the same in all respects with regard to strength, weight,
bundle count, listings and approvals. For example,
Dyna-Flow and Super Flo are the same product as
(U@L are Dyna Thread and Super 40. XL is manufactured
with Exterior galvanized coating. BLT is Listed Approved Listed manufactured with Black lacquer coating.
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments:
S3-4
tqC0 Fire & Building
liProducts
Technical Services: Tel: (800) 381-9312/ Fax: (800)791-5500
0
[I
Pipe Fittings
NPT Threaded,
Ductile Iron
General
Description
The Tyco5 Series 800 Threaded Pipe
Fittings and California Tees & Elbows
are manufactured from ductile iron.
They are stronger and more corrosion
resistant than cast iron fittings. The
additional strength is provided by the
ductile properties and by adding mag-
nesium while the iron is being poured
into the final cast shape. Although
lighter than standard cast iron, the fit-
tings have an added advantage of be-
ing less susceptible to cracking due to
their added strength.
The Series 800, California, and Figure
719 Threaded Pipe Fittings are a re-
designation for the Central Series 800,
California, and Figure 719 Threaded
Pipe Fittings.
WARNINGS
The Threaded Pipe Fittings described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals:
UL Listed and FM Approved
Maximum Working Pressure:
Series 800 and California Fittings:
250 psi (17,2 bar)
Figure 719 Plug:
250 psi (17,2 bar)
Page 1 of 10
Material:
Series 800 and California Fittings: Ductile Iron
Figure 719 Plug:
Cast Iron
Pipe Thread:
NPT per ANSI B1.20.1
Installation
Apply Teflont tape or high quality pipe
joint compound on male pipe threads
and tighten two to three turns beyond
hand tight.
NOTE
Installers who have not used ductile
iron threaded fittings should be in-
structed that the fittings are stron-
ger than the pipe and overtightening
the fitting can create leaks and cause
damage to pipe threads. In general,
there is about one-half turn difference
between cast iron and ductile iron fit-
tings. Apply Teflon tape or high qual-
ity pipe joint compound on the male
pipe threads and tighten two to three
turns beyond hand tight. If an auto-
matic make-on machine is being used,
please exercise caution in setting the
machine to the proper parameters pri-
or to tightening fittings onto the male
pipe threads.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty Is given for products or components
manufactured by companies not af-filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
JANUARY, 2008
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made In lieu
of any and all other warranties, ex-
cress or implied, including warranties
of merchantability and fitness for a
carticular curoose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
quantity, figure number, wall thickness,
and size.
tregistered trademark of E. I. du Pont de () Nemours and Company or Its affiliates.
TFPI7IO
Page 2otlO TFPI7I0
FIGURE 811 FIGURE 813
900 ELBOW 450 ELBOW
Figure 811
B Approx. A B
Inches Weight Part Inches Inches
(mm)
Lbs. Number (mm) (mm)
(kg)
0.56 0.24 86206 0.88 0.38
(14,2) (0,11) (22,4) (9,7)
0.75 0.40 86205 00 0.44
(19,0) (0,18) (25,4) (11,2)
0.81 0.64 86200 1.13 0.81
(20,6) (0,29) (28,7) (20,6)
1.06 0.95 86201 1.31 0.63
(26,9) (0,43) (33,3) (16,0)
1.19 1.24 86202 1.44 0.69
(30,2) (0,56) (36,6) (17,5)
1.50 1.74 86203 1.68 0.94
(38,1) (0,79) (42,7) (23,9)
1.56 3.28 86204 1.94 1.00
(39,6) (1,49) (49,3) (25,4)
TABLE I
NOMINAL DIMENSIONS FIGURES 811 & 813
Nominal Pipe Figure 813 Size
ANSI A Approx.
Inches Inches Weight Part
DN (mm)
Lbs. Number,
(kg)
1/2 1.13 0.22 86780 0N15 (28,7) (0,09)
3/4 1.31 0.33 86781 DN20 (33,3) (0,15)
1 1.50 0.48 86280 0N25 (38,1) (0,21)
1-1/4 1.75 0.73 86281 DN32 (44,5) (0,33)
1-1/2 1.94 0.93 86282 DN40 (49,3) (0,42)
2 2.25 1.55 86283 DN50 (57,1) (0,70)
2-1/2 2.69 2.70 86782 DN65 (68,3) (1,22)
TFPI7IO Page 3 of 10
FIGURE 812
90 REDUCING ELBOW
Nominal Pipe Figure 812 Size
ANSI A B C D Approx. Weight Part Inches Inches Inches Inches Inches Lbs. DN (mm) (mm) (mm) (mm) Number
(kg)
314x1/2 1.19 1.19 0.63 0.63 0.33 86342 DN20 x 15 (30,2) (30,2) (16,0) (16,0) (0,15)
1 x1/2 1.25 1.38 0.56 0.81 0.44 86210 0N25 x 15 (31,8) (35,1) (14,2) (20,6) (020)
1 x3/4 1.38 1.44 0.69 0.88 0.53 86211 DN25 x 20 (35.1) (36,6) (17,5) (22,4) (0,24)
1-1/4x1/2 1.31 1.50 0.63 0.94 0.64 86212 0N32 x 15 (33,3) (38,1) (16,0) (23,9) (0,29)
1-1/4 x 3/4 1.44 1.63 0.75 1.06 0.75
DN32 x 20 (36,6) (41,4) (19,0) (26,9) (0,34) 86213
1-1/4x1 1.56 1.68 0.88 1.00 0.77 86214 DN32 x 25 (39,6) (42,7) (22,4 (25,4) (0,35)
1-1/2x3/4 1.50 1.75 0.75 1.19 0.95 86221 DN40x20 (38,1) (44,4) (19,0) (30,2) (0,43)
1-1/2 x 1.63 1.81 0.88 1.13 0.99 86215 DN40 x 25 (41,4) (46,0) (22,4) (28,7) (0,45)
1-1/2x1-1/4 1.81 1.88 1.13 1.19 1.14 86216 DN40 x 32 (46,0) (47,8) (28,7) (30,2) (0,52)
2x3/4 1.63 1.94 0.88 1.38 1.39 86217 DN50x20 (41,4) (49,3) (22,4) (35,1) (0,63)
2x1 1.75 2.06 2.00 1.31 1.58 86218 DN50x25 (44,4) (52,3) (50,8) (33,3) (0,72)
2 x 1-1/2 2.00 2.19 1.25 1.44 1.67 86220 DN50x40 (50,8) (55,6) (31,8) (36,6) (0,76)
2-1/2x2 2.38 2.63 1.25 1.88 3.01 86262 DN65 x 50 (60,5) (66,8) (31,8) (47,8) (1,36)
TABLE 2
NOMINAL DIMENSIONS FIGURE 812
11
TFPI7I0 Page 5of 10
Nominal Pipe
Size
ANSI Inches
DN
112
DN15
3/4
DN20
1
0N25
1-1/4
0N32
1-1/2
DN40
2
DN50
2-1/2
DN65
_ Wil
FIGURE 814 FIGURE 818
IRON TEE STRAIGHT COUPLING
Figure 814 Figure 818
A B Approx. A B Approx.
Inches Inches Weight Part Inches Inches Weight Part
(mm) (mm)
Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg)
1.13 0.56 0.33 86340 1.38 0.31 0.18 72779 (28,7) (14,2) (0,15) (35,1) (7,9) (0,08)
1.31 0.75 0.50 86341 1.63 0.56 0.26 72778 (33,3) (19,0) (0,23) (41,4) (14,0) (0,11)
1.50 0.81 0.85 86230 1.75 0.38 0.44 72755 (38,1) (20,6) (0,38) (44,4) (9,7) (0,20)
1.75 1.06 1.30 86231 2.00 0.56 0.54 72754 (44,4) (26,9) (0,59) (50,8) (14,0) (0,24)
1.94 1.19 1.63 86232 2.19 0.75 0.71 72753 (49,3) (30,2) (0,74) (55,6) (19,0) (0,32)
2.25 1.50 2.63 86233 2.63 1.13 1.15 72752 (57,1) (38,1) (1,19) (66,8) (28,7) (0,52)
2.69 1.56 4.55 86234 3.00 0.75 2.29 72756 (68,3) (39,6) (2,06) (76,2) (19,0) (1,04)
TABLE 4
NOMINAL DIMENSIONS FIGURES 814 & 818
TFPI7I0 Page 6of 10
Page 7 of 10 TFPI7IO
FIGURE 815
REDUCING TEE
Nominal Pipe Size Figure 815
A B C 0 E F Approx.
ANSI Inches Inches Inches Inches Inches Inches Inches Weight Part
DN Lbs. Number (mm) (mm) (mm) (mm) (mm) (mm) (kg)
1-1/2x1-1/4x1/2 1.44 1.31 1.69 0.69 0.63 1.13 1.03
DN40 x 32 x 15 (366) (33,3) (42,9) (17,5) (16,0) (28,7) (0,47) 86257 1
1-112x1-1/4x3/4 1.50 1.44 1.75 0.75 0.75 1.19 1.10
DN40x32x20 (38,1) (36,6) (44,5) (19,0) (19,0) (30,1) (0,50)
86258
1-112x1-114x1 1.63 1.56 1.81 0.88 0.88 1.13 1.31
DN40 x 32 x 25 (41.4) (39,7) (460 (22,4) (22,4) (28,7) (0.59) 86259
1-1/2x1-1/4x2 2.19 2.13 2.00 1.44 1.44 1.25 1.94 86260 DN40x32x50 (55,6) (54,1) (50,8) (36.6) (36,6) (57,1) (0,88)
1-112x1-1/2x1/2 1.44 1.44 1.69 0.69 0.69 1.13 1.14 86261 DN40 x 40 x 15 (36.6) (36,6) (42,9) (17.5) (17,5) (28,7) (0,52)
1-112x1-112x314 1.50 1.50 1.75 0.75 0.75 1.19 1.23 86262 DN40x40x20 (38,1) (38,1) (44,4) (19,0) (19,0) (30,1) (0,56)
1-1/2x1-1/2x1 1.63 1.63 1.81 0.88 0.88 1.13 1.38
0N40 x 40 x 25 (41,2) (41,2) (46,0) (22,4) (22,4) (28,7) (0,62)
86263
1-1/2x1-1/2x1-1/4 1.81 1.81 1.88 1.06 1.06 1.19 1.50
DN40 x 40 x 32 (46,0) (46,0) (47,6) (27,0) (27,0) (30,1) (0,68) 86264
1-112x1-1/2x2 2.19 2.19 2.00 1.44 1.44 1.25 2.00
DN40x40x50 (55,5) (55,5) (50,8) (36,6) (36,6) (31,7) (0.91)
88265
2x1 x2 2.25 2.00 2.25 1.50 1.31 1.50 2.18
DN50x25x50 (57,2) (50,8) (57,2) (38.1) (33,3) (38,1) (0.99) 86266
2 x 1-1/4 x 2 2.25 2.13 2.25 1.50 1.44 1.50 2.31
DN50 x 32 x 50 (57,2) (54,1) (57,2) (38,1) (36,6) (38,1) (1,05)
86267
2x1-1/2x112 1.50 1.44 1.88 0.75 0.69 1.31 1.50 86268 DN50x40x15 (38,1) (36.6) 1 (47,8) (19,0) (17,5) (33,3) (0,68)
2x1-1/2x3/4 1.63 1.50 1.94 0.88 0.75 1.38 1.61
DN50x40x20 (41,4) (38,1) (49,3) (22.4) (19.0) (35,0) (0,73)
86269
2x1-1/2x1 1.75 1.63 2.00 1.00 0.88 1.31 1.65 86270 DN50 x 40 x 25 (44,5) (41,4) (50,8) (25,4) (22,4) (33,3) (0,75)
2x1-112x1-112 2.06 1.94 2.19 1.31 1.19 1.44 2.03
DN50 x 40 x 40 (52,4) (49,2) (55,5) (33,3) (30,2) (36,6) (0 86272,92)
2x1-1/2x2 2.25 2.19 2.50 1.50 1.44 1.50 2.37
DN50x40x50 (57,1) (55,5) (63,5) (38,1) (36,6) (38,1) (1,07)
86273
2x2x1/2 1.50 1.50 1.88 0,75 0.75 1.31 1.50
DN50x50x15 (38,1) (38,1) (47,8) (19,0) (19,0) (33,3) (0,68)
86222
2x2x3/4 1.63 1.63 1.94 0.88 0.88 1.38 1.67 86223 DN50x50x20 (41,4) (41,4) (49,3) (22,4) (22,4) (35,0) (0,76)
2x2x1 1.75 1.75 2.00 1.00 1.00 1.31 1.91
DN50 x 50 x 25 (44,5) (44,5) (50,8) (25,4) (25,4) (33,3)
86224
2x2x1-114 1.88 1.88 2.13 1.13 1.13 1.44 2.05
DN50 x 50 x 32 (47.8) (47,8) (54,1) (28,7) (28,7) (36.6) (0,93) 86225
2x2x1-1/2 2.00 2.00 2.19 1.25 1.25 1.50 2.11 86226 DN50x50x40 (50,8) (50,8) (55,6) (31,8) (31,8) (38,1) (0,96)
2x2x2-1/2 2.63 2.63 2.38 1.75 1.88 1.44 3.67
DN50 x 50 x 65 (68,8) (66.8) (60,5) (44,5) (47.8) (36,6) (1.66)
86227
2-112x2x3/4 1.75 1.63 2.31 0.63 0.88 1.75 2.22
DN65 x 50 x 20 (44,5) (41,4) (58,7) 1 (15,9) (22.4) 1 (44,5) (1.01)
86274
TABLE 5(2 0F2)
NOMINAL DIMENSIONS FIGURE 815
0
Page 8 of 10 TFPI7IO
iiniii
e, fl hlll
FIGURE 820 FIGURE 830 FIGURE 719
CAP BRASS SEAT UNION PLUG
Nominal Pipe
Size Figure 820 Figure 830 Figure 719
ANSI A Approx. A B Approx. A Approx.
Inches Inches Weight Part Inches Inches Weight Part Inches Weight Part
ON (mm)
Lbs. Number (mm) (mm) Lbs. Number (mm) Lbs. Number
(kg) (kg) (kg)
1/2 0.88 0.15 72776 1.88 0.81 0.47 86207 0.94 0.10 86292 DN15 (22,4) (0,06) (47,8) (20,6) (0121) (23,9) (0,04)
3/4 1.00 0.22 72777 2.00 0.94 0.66 86275 1.13 0.18 86293 DN20 (25,4) (0,10) (5018) (23,9) (0,30) (28.7) (0,08)
1 1.18 033 72824 2.19 0.81 1.08 86276 1.25 0.28 86294 0N25 (30,0) (0,15) (55,6) (20,6) (0,49) (31,7) (0,13)
1-1/4 1.31 0.54 72756 2.50 1.06 1.54 86277 1.38 0.50 86295 0N32 (33,3) (0,24) (63,5) (26,9) (0,70) (35,1) (0,23)
1-1/2 1.38 0.68 72822 2.63 1.19 2.03 86278 1.44 0.70 86296 DN40 (35,1) (0,31) (66.8) (30,2) (0,92) (36,6) (0,32)
2 1.50 0.96 72823 3.13 1.63 3.15 86279 1.50 0.90 86297 DN50 (38,1) (0143) (7915) (41,4) (1,43) (38,1) (0,41)
2-1/2 1.75 1.80
72825 - - - - - - - DN65 (44,5) (0,82) I
TABLE 6
NOMINAL DIMENSIONS FIGURES 820,830 & 719
TFPI7I0 Page 9of 10
EA __ to Eh U
FIGURE 825 FIGURE 827 FIGURE 816
EXTENSION PIECE HEX BUSHING REDUCING COUPLING
TABLE 7
NOMINAL DIMENSIONS FIGURE 825, 827 & 816
Nominal Pipe Figure 825 Figure 827 Figure 816
Size Extension Piece Hex Bushing Reducing Coupling
A Approx. A Approx. A B Approx.
ANSI Inches Inches Weight Part Inches Weight Part Inches Inches Weight Part
ON
(mm)
Lbs. Number (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg) (kg)
1/2x1/2 1.50 0.20 72751 - - - - - - - DN15 x 15 (38,1) (0,09)
1/2x112 2.00 0.27 72980 - - - - - - - DN15 x 15 (50.8) (0,12)
3/4 x 3/4 1.50 0.22 72981 - - - - - - - DN20 x 20 (38,1) (0,10)
3/4 x 3/4 2.00 0.31 73982 - - - - - - - DM20 x 20 (50,8) (0,14)
3/4 x 1/2
- - - - - -
1.75 0.69 0.38 86772 DN20 x 15 (43,2) (17,5) (0,17)
1 x 1/2
- -
1.06 0.22 72726 1.69 0.50 0.38 86228 DN25 x 15 (26,9) (0,10) (42,9) (12,7) (0,17)
1 x3/4
- - -
1.06 0.18 72762 1.75 0.50 0.53 86229 DN25 x 20 (26,9) (0,08) (43,2) (12,7) (0,24)
1-114x1
- - -
1.19 0.31 72763 - - - - DN32x25 (30,2) (0,14)
1-1/2x1
- - -
1.25 0.53 72757 - - - - DN40 x 25 (31,7) (0,24)
1-112x1-114
- - -
1.25 0.35 72764 - - - - DN40x32 (31,7) (0,10)
2x1
- -
1.38 0.75 72759 - - - - DM50 x 25 (35,1) (0,34)
2 x 1-1/4
- - -
1.38 0.69 72761 - - - - DN50x32 (35,1) (0.31)
2 x 1-1/2
- - -
1.38 0.62
T
______
72775 - - - - DN50x40 (35,1) (0,28)
0
tqCo /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 40-5
Strap
General
Description
, - 1•-.
/ •1
VdS
(.üi) See Fire Protection
Submittal Sheet for FM Pressure Rating and
Listing/Approval Information
The Figure 40-5 Strap is an economical alternative
to welded pipe outlets on steel pipe.
The Figure 40-5 Strap may be used with full
lengths of pipe and eliminates threading and
welding, decreasing waste and installation time.
The 40-5 Strap may be used in wet, dry pipe and
deluge systems.
WARNING
The Figure 40-5 Strap described herein must be
installed and maintained in compliance with this
document, as wellas with theapp/icablestandards
of the National Fire Protection Association, in
addition to the standards of any otherauthorities
ha ving jurisdiction. Failure to do so mayimpair
the performance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or
sprinkler manufacturershouldbe contacted with
any questions.
Technical
Data
Figure: 40-5
Outlet: Threaded
Approvals: UL, FM, LJLC, and VdS;
See Fire Protection Submittal Sheet for exact
Listing /Approval information.
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Clear rust inhibitive coating
Zinc electroplated conforming to
ASTM B-633, Type Ill Service 2 (optional)
U-Bolt: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Nuts: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Gasket: (specify when ordering)
Grade "E" EPDM green color code.
(See Data Sheet TFP1895 for aid in selecting
proper gasket)
Ordering
Procedure
When placing an order, indicate the full product
name. Please specifythe quantity, figure number,
type of gasket, Grade 'E" EPDM, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughoutthe U.S., Canada, and internationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicable standards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractor or product manufacturer
should be contacted relative to any questions.
Any impairment must be Immediately corrected.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by
a qualified Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid for and property installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment byTyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated by ownership withTyco Fire Products orfor
products and components which have been subject
to misuse, improperinstallation, corrosion, orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
and/or the standards ofanyotherAuthorities Having
Jurisdiction. Materials found by Tyco Fire Products
to be defective shall be either repaired or replaced, at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumeforit, any other obligation inconnectionwith
the sale of products or parts of products. Tyco Fire
Products shall notberesponsibleforsprinklersystem
design errorsor inaccurate orincompleteinformation
supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENTIALDAMAGES, INCLUDING BUTNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHEThERTYCOFIREPRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
I
(B
Page 1 of 2 September 2004 TFPI72O
Pipe Nominal Dimensions Hole Net
Size Size Wt. A C D
Run x Inches InchB es Inches Inches Inches Lbs.
Branch mm mm mm mm mm Kg.
11!4" X 1/2° 2.00 1.50 3.50 1.20 1/io 0.84
50.8 38.1 88.9 30.5 30.2 0.4
11/40 x 3/40 2.00 1.50 3.50 1.20 1/16 0.88
50.8 38.1 88.9 30.5 30.2 0.4
1'/4°X ill 2.31 1.68 3.50 1.20 13'16 1.13
58.7 42.7 88.9 30.5 30.2 0.5
11/20 X 1/2 2.12 1.62 3.50 1.32 1/16 0.84
53.8 41.1 88.9 33.5 30.2 0.4
1'/2" X3/4 2.12 1.62 3.50 1.32 1/,& 0.88
53.8 41.1 88.9 33.5 30.2 0.4
11/2 i 2.43 1.80 3.50 1.32 1/16 1.13
61.7 45.7 88.9 33.5 30.2 0.5
2 x 1/2 2.36 1.86 3.74 1.55 1/16 0.88
59.9 47.2 95.0 39.4 30.2 0.4
2" x 3/0 2.36 1.86 3.74 1.55 13/16 0.95
59.9 47.2 95.0 39.4 30.2 0.4
2" x 1" 2.67 2.04 3.74 1.55 1/16 1.16
67.8 51.8 95.0 39.4 30.2 0.5
21/2 X /2" 2.61 2.11 4.25 1.80 1/16 0.90
66.3 53.6 1 108.0 45.7 30.2 0.4
21/20 X314° 2.61 2.11 4.25 1.80 13'16 0.99
66.3 53.6 108.0 45.7 30.2 0.4
21/2" x 1' 2.92 2.29 4.25 1.80 1/16 1.21
74.2 58.2 108.0 45.7 30.2 0.5
Item Description
1 Housing
2 Gasket
3 Flanged Nut
4 U-Bolt
Fitting
Size
Equivalent Length
(1 inch pipe)
11/4°X 1 8
1'/2"X 1 6
2"x 1" 6
21/2"X 1" 4
The friction loss for these outlets is specified in
equivalent length of 1 inch Schedule 40 (C=120) pipe.
Page 2 of 2 TFP1 720
Figure 40-5 Strap
The 1 inch outlets can be used with a nipple leading Note: Outlet threads conforming to ISO 7-1 are available, contact
directly to a sprinkler. These fittings should be used Tyco Fire Products.
for hydraulically calculated systems only.
(:12)
General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure IS that pressure ratings and performance data is not exceeded. Always read and understand the installation 9001
instructions (11-1-1 000). Never remove any piping component or correct or modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified to be compatible
for the specific application. . Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
tqCJ3 Fire & Building
IlProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB 28, 4.2, 5.6, and &O K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
AUGUST, 2007
] =OIL
i1
~4_ J
Model/Sprinkler
Identification
Numbers
TY1I3I - Upright 2.81K, 1/2"NPT
TY1231 - Pendent 2.81K, 1/2"NPT
1Y2131 - Upright 4.21K, 1/2"NPT
1Y2231 - Pendent 4.2K. 1/2"NPT
1Y3131 - Upright 5.61K, 1/2"NPT
1Y3231 - Pendent 5.61K, II2NPT
TY4131 - Upright 8.01K, 3/4"NPT
1Y4231 - Pendent 8.01K, 314"NPT
TY4831- Upright 8.0K, 112"NPT
TY4931- Pendent 8,0K, 1/2"NPT
(B TFPI7I
TFPI7I
ESCUTCHEON 7/161(11,1 mm)
PLATE SEATING ,, NOMINAL
SURFACE 1/2
NPT MAKE-IN
-r-
2-3/16" \
(55,6 mm)
1-1/2"
(38,11 mm)
SSP DEFLECTOR *
Page 3 of 10
STYLE 100r20
RECESSED SSU*
ESCUTCHEON DEFLECTOR
6
7/16"
(1111,11 mm) I
_____ NOMINAL 1
MAKE-IN 2-316"
WRENCH ______ __ (55,6 mm)
'. FLATS
1/2" NPT t 2-7/8" (73,0 mm) DIA
PENDENT I RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6 - Deflector 2 - Button Assembly 5 - Compression
Screw
* Temperature rating is indicated on deflector or adjacent
orifice seat on frame.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3 131) AND PENDENT (TV3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 0r40
PLATE SEATING NOMINAL RECESSED
SURFACE MAKE-IN ESCUTCHEON SSU*
6*:
2-5/16"
NPT DEFLECTOR
T_ —
(1 mm) H 1/2"
(58,7 mm) OMINAL Il II 4
MAKE-IN
1-9/16" I 2-1/4"
WRENC (57,2 mm) V (39,7 mm)
-
2-7/8" (73 m) DIA. -__J 3/4" NPT
FL
SSP DEFLECTOR*
PENDENT REC D PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
0
Page 4of1O TFPI7I
7/16 (11,1 mm)
NOMINAL SStJ 1/2' MAKE-IN DEFLECTOR NPT
2-1/4' f 2-3/16"
(57,2 mm) I -.. I
/
FFLATS
(55,6
1-9/16 ' ________ WRENCH I (39,7 mm)
EFLECTOR CROSS
PE NT UPRIGHT SECTION
- Frame 3 - Sealing 4 ulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
Button - Assembly 5 Compression orifice seat on frame. Screw
FIGURE 5
UICK RESPONSE SERIES B UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi112 (40,3 LPM/bar1/2)
K = 4.2 GPM/psi112 (60,5 LPM/barll2)
K = 5.6 GPM/psil/2 (80,6 LPM/bar1121
K = 8.0 GPM/psil/2 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel wiTeflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED i WHITE
1POLYESTER
LEAD
COATED
-
5.6
1/2"
PENDENT
(TY3231)
and
135°F/57C Orange
1,2,3,4,5,6,7 1,2,3,5
I155°F168°C Red I
175°F/79°C Yellow
UPRIGHT
'3131) 200°F193°C Green
286°F/141°C Blue
NPT 135°F/57°C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)*
Figure 10
1155°F/68°C Red I
175F/79°C Yellow
200F/93C Green
135°F/57°C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(TY3231)**
Figure 11
155FI68°C Red
175°F/79°C Yellow
200°F/93°C Green
-
8.0
3/4,,
PENDENT
(TY4231)
and
UPRIGHT
(1Y4131)
1350F/57eC Orange
1,2, 3,4,5, 6,7
1, 2, 5
155°F/68C Red
175°F/79°C Yellow
200°F/93°C Green
286F/141C Blue
NPT 135F/57C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)*
Figure 12
155F/68C Orange
175eF/79.0 Red
200°F193°C Yellow
135FI57C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(TY4231)
Figure 13
155F/68°C Red
175°17/791C Yellow
20DF/93°C Green
-
8.0
1/2'
NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135°F/57C Orange
1,2,4,5,6
1, 2,5
155°F/68C Red
175°F/79C Yellow
200F/93C Green
286F/141C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use In Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-4284444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/20 NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4H NPT) 1/2 Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order). . N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5,6 AND &O K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED
I
POLYESTER
I
COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2° RECESSED PENDENT NPT (TY323)
PENDENT (1Y4231)
and
4.2 UPRIGHT (TY4 131) 175 PSI (12,1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 OR I UPRIGHT (1Y3131)
1/2" 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 115 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT (1Y4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F/57°C to 3/32
inch (2,4 mm) for the 2860F/141C
temperature ratings.
A leak tight 112 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.Ibs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
TFPI7I
2-7/8" DIA.
5/8±1/4" (73,0 mm) I 3/4" (19,1 mm
(15,9±6,4 mm) 2-1/4" DIA 1/4'(6,4
FACE OF (5712 mm) MO TING
SPRINKLER PLATE
FITTING
I 1/8"
fly
u MOUNTING
SURFACE _____
SERIES 1-1/4" (31,8 mm) I CLOSURE TY-FRB 3/4" (19.1 mm)
FIGURE 10
RIES TY-FRB RECESSED PENDENT
WIT TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
5/8±1/4" (73,0 mm) - 3/4"(19.1 mm)
(15,9±6,4 mm) 2-114" DIA. 1/4" (6,4 m
(57,2 mm) FACE OF MOU ING
SPRINKLER TE
FITTING
I (3.2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/18" (33,3 mm)
TY-FRB 13/16"(20,6 mm)
FIGURE 12
S IES TY-FRB RECESSED PENDENT
WIT 0-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
- 2-7/8" DIA.
(73,0 mm) 1/2±1/8" 1/r2"(12,7 m
(12,7*3,2 mm) 2-1/4" DIA. 1/4" (6,4 m)
FACE OF (57,2 mm) MO TING
SPRINKLER PLATE
FITTING
/ 1/8"
I - (3.2 mm)
\
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4'(31,8 mm)
TYFRB 1- (25,4 mm)
FIGURE 11
RIES TY-FRB RECESSED PENDENT
WI TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA.
(73.0 mm) 1/2"(12, mm)
(12,7±3.2 mm) 2.1/4' DIA. -.__.
1/4" (6,4
(57,2 mm)
FACE OF MO TING
SPRINKLER LATE
FITTING
I - (3.2 mm)
_ -i
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TYFR8 1-1/16"(27.0 mm)
FIGURE 13
RIES TY-FRB RECESSED PENDENT
WIT TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A' USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4' NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
ft
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes. 0
Page 10 of 10 TFPI7I
P/N 57-XXX-X-XXX
L
I MODEL/SIN
330 2.BK UPRIGHT (1/2"NPT) TYII31
331 2.81< PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2°NPT) TY2131
341 4.21< PENDENT (1/2"NPT) TY2231
5.61< UPRIGHT (1/2'NPT) TY3131 E71 5.61K PENDENT (1/2"NPT) TY3231
390 8.01< UPRIGHT (3/4NPT) TY4131
391 8.0K PENDENT (314"NPT) TY4231
360 8.0K UPRIGHT (112"NPT) TY4831
361 8.01< PENDENT (1/2"NPT) TY4931*
I I L 135
SPRINKLER
155
175
200
286
RATING
1 NATURAL BRASS 155F/68°C
4 WHITE POLYESTER 175°F/79°C
3 WHITE (RAL9O1O)* 200°F/93C
9 CHROME PLATED 286F/141C
7 I LEAD COATED
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TV-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
IMPERIAL MAX REC.
LOAD LBS.
METRIC
PIPE ROD PIPE ROD
112 3/8 400 10
314 3/8 400 20 10
400 25 10
11/4 3/8 400 32 10
11/2 3/8 400 40 10
2 3/8 400 50 10
21/2 318 600 65 10
3 318 600 80 10
31/2 3/8 600 10
1000 122_ ...10.
5 1250 125 12
6 112 1 1250 1 150 12
8 1250 1 200 1 12
* Order Part #300m
Note: 1/2 Ring Hanger not <FM> approved
F~
300
RING HANGER
zS A)US I thru 4 Inch pipe 1/2 and 3/4 Inch pipe
5 thru 8 Inch pipe
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mil. Galvanized to G-90 specification.
FINISH - Mil. Galvanized and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL - Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H- 171 (Type 10),
Manufacturers Standardization Society ANSIIMSS-SP-58 (Type 10); install
in accordance with ANSI/MSS- SP-69.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - For fire sprinkler and general piping purposes.
Swivel nut permits hanger adjustment after installation.
FEATURES -
1 thru4 inch:
* Offset edge for EASY pipe insertion.
1 thru 8 inch:
* Full length knurl on swivel nut for better grip.
UNIQUE FEATURES
1 thru 3 inch:
* UL listed to accept AFCON#3 10 Surge Restrainer. * Swivel nut
Retained in ring to keep the assembly intact prior to installation.
Removed easily if needed.
* UL listed for use on CPVC pipe.
ORDERING - Part # and pipe size.
Index
JAcn
655
ALL THREADED ROD CUT TO LENGTH
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
650°F 750°F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
NOTE; maximum Temperature: 750°F
SIZE - 3/8 thru 7/8 inch rod in 1 inch
increments.
MATERIAL - Carbon Steel.
FINISH - Plain, Electro-Galvanized and
Stainless Steel.
ORDERING - Part #, rod diameter, rod
length and finish.
2/00 C,
SIS] 1iTi 1&V1W1 Mount)
Use #14 Nut Driver (Item #100)
Item # Model Shk Lgth Shk Dia Box Qty i
1
g0 Case Qty
GST.750
(per
20 3/4 1/4 100 4.75 1000
21 GST 100 1 1/4 100 5.00 1000
22 GST 200 2 1/4 100 6.50 1000
23 GST 300 3 1/4 100 7.50 1000
24 GST 600 6 1 1/4 50 9.00 500
WOOD - Sammys
3
I
#14
(Item #100-black)
Sammys 114". 318" rod
Not less than
2" nominal width
(1112")
U .0 mE
mE
U S
0
WOOD - 3/:" Rodr&ni IliTliTi
Use #14 Nut Driver (Item #100)
Approvals Item # Model Shk Lgth Shk Dia FMTest
Loa lb.
ULTest
Load lb. UIJFMActual Pipe Size
Pullout Box Qty
10 CST.75 3/4 1/4 564#-6Ply 100
NFPA 11 GST 10 1 1/4 2104- 7/16 OSB 100 670# - 3/4" Ply
IUI..fMFPA 12 GST 20 2 1/4 9404 8504 3/4-2 1/2 1760# - Fir 100
UL4'4FPA * 27 GST 25-380 21/2 3/8 15004 4 21134 - Fir 50
UL4M('JFPA 13 GST30 3 1/4 14754 1500# 3/4-4 20604 - Fir 100
NFPA 403 GST40 4 1/4 2180#-Fir 50
NFPA 14 GST60 6 1/4 22304-Fir 50
#I4SW
(Item #101-red)
Sidewinders &
Sammys 1/2" rod
I•I•]
Use #14SW Nut Driver (Item #101)
Item# Model Shk Lgth Shk Dia Actual Pullout Box Qty Weight
(per 100) Case ~Y
8 CST2 2 1/4 17604- Fir 50 7.00 500
* 06 GST2.5-380 21/2 3/8 21134- Fir 50 10.00 500
15 GST3 3 1/4 22754- Fir 1 50 1 10.50 500
16 JGST4 4 1/4 2180#-Fir 50 10.60 500
17 JGST6 6 1 1/4 2230#-Fir 1 50 1 10.95 500
O Double Sheetrock Ceiling
Wood Flooring
Tr TJI Joist/ Truss
Consult truss manufacturer for
recommended installation point.
q Wood Joist *pre dr illing may be required
for items #27 and #06.
- Tools available on page 9.
Minimum 2" imbedment into base For vertical use. material for NFPA 13 compliance Install in center
of lowerface.
lb 22
Page 4 Nose: Screws must be installed with appropriate nut driver to comply with warranty