HomeMy WebLinkAbout2855 GAZELLE CT; ; AS150023; Permit12/29/2020 AS1 50023 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS150023
Job Address: 2855 GAZELLE CT Status: ISSUED
Permit Type: SPRINK Applied 2/9/2015
Parcel No: 2091201800 Approved: 2/18/2015
Lot #: 0
Reference No.: Issued: 2/18/2015
PC #: Inspector:
Project Title: ISIS PHARACEUTICAL INC NEW TI OF 2,700 SF PER NFPA 13, 2013
EDITION. NEW SPRINKLERS ADDED TO NEW T-BAR CEILING. -
EXISTING UPRIGHTS REMOVED AND RELOCATED TO NEW
PENDANTS. -NON-COMBUSTIBLE CONTRUCTION -MAX
DEFLECTOR DISTANCE 12: BELOW CEILING -ORDINARY HAZARD
-MAX 130 SF -HANG ALL ARMOVER 2-0" OR LONGER OR 12" OR
GREATER IF IOOPSI OR GREATER -PROVIDE UPWARD
RESTRAINT
Applicant:
TITAN FIRE PROTECTION
2880 SCOTT ST
VISTA, CA 92081
760-295-3436
Owner:
CARLSBAD OAKS NORTH PARTNERS L P
P 0 BOX 80036
SAN DIEGO CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
210 0 210 0
1/1
I
ISIS PHARMACEUTICAL, INC.
JOB NO. 15-106
Equipment Submittal
NFPA 13 WET FIRE SPRINKLER SYSTEM
Provide Stamps For Approval In Space Below
APQJ9ED AS SUBMITTED
t FIRE DEPARTMENT
AS1 50023
2880 SCOTT STREET VISTA CA 92081 P:760.295.3436 F:760.295.3437
SECTION DESCRIPTION PAGE
PRODUCTS
1. SPRINKLER HEADS
A. V1CTAULIC V3802 1/2 155 K=5.62
2. PIPING, FITTINGS & COUPLINGS
ALLIED SCHEDULE 10140 STEEL PIPE
BULL MOOSE SCHEDULE 10/40 STEEL PIPE
C.SMITH-COOPER CAST IRON THREADED FITTINGS
3. PIPE HANGERS & SUPPORTS
ALL THREAD ROD-TOLCO #103
ROD COUPLING- TOLCO #70
ADJUSTABLE BAND HANGER - TOLCO#200
HILTI KB-TZ3
*MATERIALS MAY BE SUBSTITUTED WITH LISTED EQUAL DUE TO PRODUCT AVAILABILITY