HomeMy WebLinkAbout1710 YADA PL; PLAN 2; FPR2018-0159; Permit11:24:41T, UZZ11:34 Fk
1(7city of
Carlsbad
I I
Print Date: 10/24/2022 Permit No: FPR2018-0159
Job Address: 1710 YADA P1, CARLSBAD, CA Status: Closed - Finaléd
Permit Type: FIRE-Construction Residential Work Class: Single Family Fire Sprinkl
Parcel #: Track #: Applied: 09/27/2018
Valuation: $0.00 Lot #: Issued: 12/10/2018
Occupancy Group: Project #: Finaled Close Out: 11/21/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix
Plan Check #:
Project Title:
Description: PLAN 2 - YADA FARM LOT 8 - 13D NEW SPRINKLER SYSTEM
FPContractor:
NP MECHANICAL INC
P0 BOX 309
CORONA, CA 92878-0309
(951) 667-4220
FEE AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) $125.00
FIRE NFPA 13D Single Family System (Plan Review) $246.00
Total Fees: $371.00 Total Payments To Date: $371.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
-
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : 12 PACIFIC
Building : PLAN 2
Location : CALC AREA 1
System
Contract
Data File : PLAN2 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
S
Y
S
T
E
M
D
E
S
I
G
N
NP Mechanical Page 1
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - CALC AREA 1
Building - PLAN 2 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Number of Sprinklers Flowing: ( )l (X)2 ( )4
)Other
)Specific Ruling Made by Date
Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
Additional Flow Added - Gpm Make RELIABLE Model RFC49
Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
Note: Temperature Rating 165
Calculation Gpm Required 28.045 Psi Required 28.248 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - 8 Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
City Water Supply: Demand:
Cl -Static Pressure : 67.5 Dl - Elevation : 15.592
C2 - Residual Pressure: 38.7 D2 - System Flow :28.045
C2 - Residual Flow : 3050 D2 - System Pressure : 62.189
Hose ( Demand) : 5
D3 - System Demand : 33.045
Safety Margin : 5.304
150
140
130
P 120
R0
E 100
s 90
s 80
u 70 --
R 60
D3 ___ ____ ______ ________ _________ E 50
--ci-___
30
.
40
20
10
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 1/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N* CPVC9OEllHarvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplinglee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *• The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Rea.
Hi 10.0 4.9 7.04 na 13.0
H2 10.0 4.9 9.43 na 15.04
H3 10.0 11.48 na
Dl 11.0 7.36 na
1 11.0 9.52 na
D2 11.0 9.49 na
D3 11.0 11.05 na
2 11.0 11.05 na
3 11.0 12.6 na
4 11.0 14.21 na
5 11.0 15.22 na
6 11.0 15.46 na
7 11.0 12.24 na
8 11.0 10.77 na
TR 11.0 17.01 na
GA 5.0 20.5 na
BR 2.0 28.25 na
EL -3.0 30.76 na
X -3.0 36.07 na 5.0
Ml -3.0 37.3 na
M2 -3.0 41.55 na
CM -3.0. 52.22 na
100 -3.0 52.22 na
101 -3.0 52.23 na
SRC -26.0 62.19 na
0.05 256 7.039
0.05 256 7.0
The maximum velocity is 13.63 and it occurs in the pipe between nodes M2 and CM
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point at Pf/Ft Eqv. Ln. Total Pf Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
Dl 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 15.04 0.874 0 3.0 1.000 9.427 K Factor = 4.90
to 150.0 0.0 3.000 -0.433
D2 15.04 0.1238 0.0 4.000 0.495 Vel = 8.04
0.0
15.04 9.489 K Factor = 4.88
H3 0.0 0.874 N 7.0 1.000 11.483
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 11.050 K Factor =0
Dl 13.00 0.874 N 7.0 11.917 7.361
to 150.0 R 1.0 11.000 0.0
1 13.0 0.0944 0 3.0 22.917 2.164 Vel = 6.95
1 -19.60 0.874 R 1.0 0.333 9.525
to 150.0 0.0 1.000 0.0
D2 -6.6 -0.0270 0.0 1.333 -0.036 Vel = 3.53
02 15.04 0.874 2R 2.0 31.750 9.489
to 150.0 0 3.0 5.000 0.0
2 8.44 0.0425 0.0 36.750 1.561 Vel = 4.51
0.0
8.44 11.050 K Factor = 2.54
D3 0.0 0.874 R 1.0 7.000 11.050
to 150.0 0.0 1.000 0.0
2 0.0 0.0 0.0 8.000 0.0 Vel = 0
2 8.44 0.874 4R 4.0 29.500 11.050
to 150.0 0 3.0 7.000 0.0
3 8.44 0.0425 0.0 36.500 1.550 Vel = 4.51
3 0.0 0.874 3R 3.0 32.000 12.600
to 150.0 0 3.0 6.000 0.0
4 8.44 0.0425 0.0 38.000 1.614 VeI= 4.51
4 0.0 0.874 2R 2.0 14.750 14.214
to 150.0 N 7.0 9.000 0.0
5 8.44 0.0425 0.0 23.750 1.009 Vel = 4.51
5 0.0 1.101 0 5.0 12.417 15.223
to 150.0 0.0 5.000 0.0
6 8.44 0.0138 0.0 17.417 0.240 Vel = 2.84
6 -28.04 1.101 3R 3.0 39.167 15.463
to 150.0 N 7.0 10.000 0.0
7 -19.6 -0.0656 0.0 49.167 -3.224 Vel = 6.60
7 0.0 1.101 3R 3.0 12.417 12.239
to 150.0 N 7.0 10.000 0.0
8 -19.6 -0.0655 0.0 22.417 -1.469 Vel = 6.60
8 0.0 0.874 R 1.0 5.167 10.770
to 150.0 0.0 1.000 0.0
1 -19.6 -0.2019 0.0 6.167 -1.245 Vel = 10.48
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fihal Calculations - Hazen-Williams
/ NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-19.60 9.525 K Factor = -6.35
6 28.04 1.101 N 7.0 5.167 15.463
to 150.0 0.0 7.000 0.0
TR 28.04 0.1271 0.0 12.167 1.547 VeI= 9.45
0.0
28.04 17.010 K Factor = 6.80
TR 28.04 1.101 R 1.0 6.000 17.010
to 150.0 0.0 1.000 2.599
GA 28.04 0.1271 0.0 7.000 0.890 Vel = 9.45
GA 0.0 1.101 Fsp 0.0 3.000 20.499
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 28.04 0.1272 0 5.0 27.126 3.450 Vel = 9.45
BR 0.0 1.245 0.0 5.000 28.248
to 150.0 0.0 0.0 2.166
EL 28.04 0.0698 0.0 5.000 0.349 Vel = 7.39
EL 0.0 1.245 0.0 76.000 30.763
to 150.0 0.0 0.0 0.0
X 28.04 0.0699 0.0 76.000 5.312 Vel = 7.39
X 5.00 1.025 Ball 3.037 2.000 36.075 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 33.04 0.2439 0.0 5.038 1.229 VeI= 12.85
Ml 0.0 1.025 0.0 1.000 37.304
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 33.04 0.2440 0.0 1.000 0.244 Vel = 12.85
M2 0.0 0.995 T 5.841 32.000 41.548
to 150.0 0.0 5.841 0.0
CM 33.04 0.2820 0.0 37.841 10.673 Vel = 13.63
CM 0.0 7.98 T 52.855 275.000 52.221
to 150.0 0.0 52.855 0.0
100 33.04 0.0 0.0 327.855 0.004 Vel = 0.21
100 0.0 9.79 T 67.474 240.000 52.225
to 150.0 0.0 67.474 0.0
101 33.04 0.0 0.0 307.474 0.001 Vel = 0.14
101 0.0 6.16 E 22.818 10.000 52.226
to 150.0 0.0 22.818 9.961
SRC 33.04 0.0001 0.0 32.818 0.002 Vel = 0.36
0.0
33.04 62.189 K Factor = 4.19
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name 12 PACIFIC
Building : PLAN 2
Location CALC AREA 2
System
Contract
Data File : PLAN2 CA2 20X20.WXF
II
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
S
Y
S
T
E
M
D
E
S
I
G
N
NP Mechanical Page 1
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - CALC AREA 2
Building - PLAN 2 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Number of Sprinklers Flowing: (X)l ( )2 ( )4
)Other
)Specific Ruling Made by Date
Listed Flow at Start Point - 20 Gpm System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( ) Dry
MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge ( ) PreAction
Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
Additional Flow Added - Gpm Make RELIABLE Model RFC49
Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
Note: Temperature Rating 165
Calculation Gpm Required 20.024 Psi Required 34.497 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test:
A Date of Test -
T Time of Test -
E Static (Psi) - 75
R Residual (Psi) - 43
Flow (Gpm) - 3050
S Elevation -
P Location:
P
L Source of Information:
Y
Pump Data: Tank or Reservoir:
Rated Cap. Cap.
@ Psi Elev.
Elev.
Other Well
Proof Flow Gpm
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
City Water Supply: Demand:
Cl - Static Pressure : 67.5 Dl - Elevation : 15.592
C2 - Residual Pressure: 38.7 D2 - System Flow : 20.024
C2 - Residual Flow : 3050 D2 - System Pressure : 60.925
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 6.571
150
140
130
p120
R°
E10°
90
80
U 70
R 60 - -
_____ _______ _________ __________
E 50D2
____________ C2
30
20
10D1
-77,
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name 1/2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100
E NFPA 13 90 Standard Elbow
Fsp Flow Switch Potter VSR
N * CPVC 90Ell Harvel-Spears
0 * CPVC Tee - Branch
R * CPVC Coupling Tee - Run
S NFPA 13 Swing Check
T NFPA 13 90 Flow thru Tee
2.25 2 2.5 2.25 10
1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fitting generates a Fixed Loss Based on Flow
7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
PFessure / Flow Summary - STANDARD
-, NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Rea.
Hi 10.0 22.78 na
H2 10.0 22.68 na
H3 10.0 4.9 16.7 na 20.02 0.05 400 16.7
Dl 11.0 22.34 na
11.0 22.34 na
D2 11.0 22.25 na
D3 11.0 17.95 na
2 11.0 19.63 na
3 11.0 21.32 na
4 11.0 23.08 na
5 11.0 24.18 na
6 11.0 24.44 na
7 11.0 23.3 na
8 11.0 22.78 na
TR 11.0 25.27 na
GA 5.0 28.35 na
BR 2.0 34.5 na
EL -3.0 36.85 na
X -3.0 39.7 na 5.0
Ml -3.0 40.43 na
M2 -3.0 44.58 na
CM -3.0 50.96 na
100 -3.0 50.96 na
101 -3.0 50.96 na
SRC -26.0 60.93 na
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5 A
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 22.776
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 22.343 K Factor = 0
H2 0.0 0.874 0 3.0 1.000 22.681
to 150.0 0.0 3.000 -0.433
D2 0.0 0.0 0.0 4.000 0.0 Vel = 0
0.0
0.0 22.248 K Factor = 0
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel = 10.71
0.0
20.02 17.946 K Factor = 4.73
Di 0.0 0.874 N 7.0 11.917 22.343
to 150.0 R 1.0 11.000 0.0
1 0.0 0.0 0 3.0 22.917 0.0 Vel = 0
1 -11.17 0.874 R 1.0 0.333 22.343
to 150.0 0.0 1.000 0.0
D2 -11.17 -0.0713 0.0 1.333 -0.095 Vel = 5.97
D2 0.0 0.874 2R 2.0 31.750 22.248
to 150.0 0 3.0 5.000 0.0
2 -11.17 -0.0713 0.0 36.750 -2.622 Vel = 5.97
0.0
-11.17 19.626 K Factor= -2.52
D3 20.02 0.874 R 1.0 7.000 17.946
to 150.0 0.0 1.000 0.0
2 20.02 0.2100 0.0 8.000 1.680 Vel= 10.71
2 -11.17 0.874 4R 4.0 29.500 19.626
to 150.0 0 3.0 7.000 0.0
3 8.85 0.0464 0.0 36.500 1.692 Vel = 4.73
3 0.0 0.874 3R 3.0 32.000 21.318
to 150.0 0 3.0 6.000 0.0
4 8.85 0.0463 0.0 38.000 1.761 Vel = 4.73
4 0.0 0.874 211 2.0 14.750 23.079
to 150.0 N 7.0 9.000 0.0
5 8.85 0.0464 0.0 23.750 1.101 Vel= 4.73
5 0.0 1.101 0 5.0 12.417 24.180
to 150.0 0.0 5.000 0.0
6 8.85 0.0150 0.0 17.417 0.262 Vel = 2.98
6 -20.02 1.101 311 3.0 39.167 24.442
to 150.0 N 7.0 10.000 0.0
7 -11.17 -0.0232 0.0 49.167 -1.139 VeI= 3.76
7 0.0 1.101 3R 3.0 12.417 23.303
to 150.0 N 7.0 10.000 0.0
8 -11.17 -0.0232 0.0 22.417 -0.520 Vel= 3.76
8 0.0 0.874 R 1.0 5.167 22.783
to 150.0 0.0 1.000 0.0
1 -11.17 -0.0713 0.0 6.167 -0.440 Vel= 5.97
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-11.17 22.343 K Factor = -2.36
6 20.02 1.101 N 7.0 5.167 24.442
to 150.0 0.0 7.000 0.0
TR 20.02 0.0682 0.0 12.167 0.830 Vel = 6.75
0.0
20.02 25.272 K Factor = 3.98
TR 20.02 1.101 R 1.0 6.000 25.272
to 150.0 0.0 1.000 2.599
GA 20.02 0.0681 0.0 7.000 0.477 Vel = 6.75
GA 0.0 1.101 Fsp 0.0 3.000 28.348
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 20.02 0.0682 0 5.0 27.126 1.850 Vel = 6.75
BR 0.0 1.245 0.0 5.000 34.497
to 150.0 0.0 0.0 2.166
EL 20.02 0.0374 0.0 5.000 0.187 Vel = 5.28
EL 0.0 1.245 0.0 76.000 36.850
to 150.0 0.0 0.0 0.0
X 20.02 0.0375 0.0 76.000 2.848 Vel = 5.28
X 5.00 1.025 Ball 3.037 2.000 39.698 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 25.02 0.1459 0.0 5.038 0.735 Vel = 9.73
Ml 0.0 1.025 0.0 1.000 40.433
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 25.02 0.1460 0.0 1.000 0.146 Vel = 9.73
M2 0.0 0.995 1 5.841 32.000 44.579
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 37.841 6.381 Vel = 10.32
CM 0.0 7.98 T 52.855 275.000 50.960
to 150.0 0.0 52.855 0.0
100 25.02 0.0 0.0 327.855 0.002 Vel = 0.16
100 0.0 9.79 T 67.474 240.000 50.962
to 150.0 0.0 67.474 0.0
101 25.02 0.0 0.0 307.474 0.001 Vel = 0.11
101 0.0 6.16 E 22.818 10.000 50.963
to 150.0 0.0 22.818 9.961
SRC 25.02 0.0 0.0 32.818 0.001 Vel = 0.27
0.0
25.02 60.925 K Factor = 3.21
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : 12 PACIFIC
Building : PLAN 2
Location : ALT. CALC AREA 1
System
Contract
Data File : ALT. PLAN2 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
F
NP Mechanical Page
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - ALT. CALC AREA 1
Building - PLAN 2 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4
S )Other
T )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 28.051 Psi Required 21.210 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - 8 Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
City Water Supply: Demand: Cl - Static Iressure : 67.5 Dl - Elevation : 15.592
C2 - Residual Pressure: 38.7 D2 - System Flow : 28.051
C2 - Residual Flow : 3050 D2 - System Pressure : 62.908
Hose ( Demand) : 5
D3 - System Demand : 33.051
Safety Margin : 4.586
150
140
130
p120
R°
E100
S90
s 80
u 70 :j
R 60
D3
E50
40
30 -
20
10
- ....,.I.I.I.I.I ... .. ... .. I....
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N "1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
F NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 0* CPVCTee - Brarich 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R* CPVCCouplinglee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 139O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
PFessure I Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Rea.
Hi 10.0 4.9 7.04 na 13.0
H2 10.0 4.9 9.43 na 15.05
H3 10.0 11.8 na
Di 11.0 7.36 na
11.0 9.52 na
D2 11.0 9.5 na
D3 11.0 11.37 na
2 11.0 11.37 na
3 11.0 13.22 na
4 11.0 15.16 na
5 11.0 16.16 na
6 11.0 14.99 na
7 11.0 12.02 na
8 11.0 10.67 na
TRA 11.0 17.72 na
GA 5.0 21.21 na
BR 2.0 28.96 na
EL -3.0 31.48 na
X -3.0 36.79 na 5.0
Ml -3.0 38.02 na
M2 -3.0 42.26 na
CM -3.0 52.94 na
100 -3.0 52.94 na
101 -3.0 52.94 na
SRC -26.0 62.91 na
0.05 256 7.039
0.05 256 7.0
The maximum velocity is 13.64 and it occurs in the pipe between nodes M2 and CM
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 'C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
Dl 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 15.05 0.874 0 3.0 1.000 9.435 K Factor = 4.90
to 150.0 0.0 3.000 -0.433
D2 15.05 0.1238 0.0 4.000 0.495 Vel = 8.05
0.0
15.05 9.497 K Factor = 4.88
H3 0.0 0.874 N 7.0 1.000 11.800
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 11.367 K Factor =0
Dl 13.00 0.874 N 7.0 11.917 7.361
to 150.0 R 1.0 11.000 0.0
1 13.0 0.0944 0 3.0 22.917 2.164 Vel = 6.95
1 -18.74 0.874 R 1.0 0.333 9.525
to 150.0 0.0 1.000 0.0
D2 -5.74 -0.0210 0.0 1.333 -0.028 Vel= 3.07
D2 15.05 0.874 2R 2.0 31.750 9.497
to 150.0 0 3.0 5.000 0.0
2 9.31 0.0509 0.0 36.750 1.870 Vel = 4.98
0.0
9.31 11.367 K Factor = 2.76
D3 0.0 0.874 R 1.0 7.000 11.367
to 150.0 0.0 1.000 0.0
2 0.0 0.0 0.0 8.000 0.0 Vel = 0
2 9.31 0.874 4R 4.0 29.500 11.367
to 150.0 0 3.0 7.000 0.0
3 9.31 0.0509 0.0 36.500 1.857 Vel = 4.98
3 0.0 0.874 3R 3.0 32.000 13.224
to 150.0 0 3.0 6.000 0.0
4 9.31 0.0509 0.0 38.000 1.933 Vel= 4.98
4 0.0 0.874 2R 2.0 14.750 15.157
to 150.0 0 3.0 5.000 0.0
5 9.31 0.0509 0.0 19.750 1.005 Vel = 4.98
5 -28.05 1.101 N 7.0 12.417 16.162
to 150.0 0.0 7.000 0.0
6 -18.74 -0.0604 0.0 19.417 -1.172 Vel= 6.32
6 0.0 1.101 3R 3.0 39.167 14.990
to 150.0 N 7.0 10.000 0.0
7 -18.74 -0.0603 0.0 49.167 -2.967 Vel = 6.32
7 0.0 1.101 3R 3.0 12.417 12.023
to 150.0 N 7.0 10.000 0.0
8 -18.74 -0.0604 0.0 22.417 -1.353 Vel = 6.32
8 0.0 0.874 R 1.0 5.167 10.670
to 150.0 0.0 1.000 0.0
1 -18.74 -0.1857 0.0 6.167 -1.145 Vel= 10.02
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-18.74 9.525 K Factor = -6.07
5 28.05 1.101 N 7.0 5.250 16.162
to 150.0 0.0 7.000 0.0
TRA 28.05 0.1273 0.0 12.250 1.559 Vel = 9.45
0.0
28.05 17.721 K Factor = 6.66
TRA 28.05 1.101 R 1.0 6.000 17.721
to 150.0 0.0 1.000 2.599
GA 28.05 0.1271 0.0 7.000 0.890 Vel = 9.45
GA 0.0 1.101 Fsp 0.0 3.000 21.210
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 28.05 0.1272 0 5.0 27.126 3.451 Vel = 9.45
BR 0.0 1.245 0.0 5.000 28.960
to 150.0 0.0 0.0 2.166
EL 28.05 0.0698 0.0 5.000 0.349 Vel = 7.39
EL 0.0 1.245 0.0 76.000 31.475
to 150.0 0.0 0.0 0.0
X 28.05 0.0699 0.0 76.000 5.314 Vel = 7.39
X 5.00 1.025 Ball 3.037 2.000 36.789 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 33.05 0.2441 0.0 5.038 1.230 Vel = 12.85
Ml 0.0 1.025 0.0 1.000 38.019
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 33.05 0.2450 0.0 1.000 0.245 Vel = 12.85
M2 0.0 0.995 T 5.841 32.000 42.264
to 150.0 0.0 5.841 0.0
CM 33.05 0.2821 0.0 37.841 10.676 Vel = 13.64
CM 0.0 7.98 T 52.855 275.000 52.940
to 150.0 0.0 52.855 0.0
100 33.05 0.0 0.0 327.855 0.004 Vel = 0.21
100 0.0 9.79 1 67.474 240.000 52.944
to 150.0 0.0 67.474 0.0
101 33.05 0.0 0.0 307.474 0.001 Vel = 0.14
101 0.0 6.16 E 22.818 10.000 52.945
to 150.0 0.0 22.818 9.961
SRC 33.05 0.0001 0.0 32.818 0.002 Vel = 0.36
0.0
33.05 62.908 KFactor= 4.17
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
KAIIU
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : 12 PACIFIC
Building : PLAN 2
Location : ALT. CALC AREA 2
System
Contract
Data File : ALT. PLAN2 CA2 20X20.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page 1 64
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - ALT. CALC AREA 2
Building - PLAN 2 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: (X)l ( )2 ( )4
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 20 Gpm System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 20.024 Psi Required 34.524 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - 8 Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
----------------
City Water Supply: Demand:
Cl -Static Pressure : 67.5 Dl - Elevation : 15.592
C2 - Residual Pressure: 38.7 D2 - System Flow : 20.024
C2 - Residual Flow : 3050 D2 - System Pressure : 60.952
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 6.544
150
140
130
p120
R0
E100
s 9°
s 80
-
R6°
E 50D3
C2 40
u70--ci-____
30
20
P1
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N"1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC 100 2.25 2 2.5 2.25 10
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPV0 Coupling Tee -Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 139O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 -
P'ressure I Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Rea.
Hi 10.0 22.55 na
H2 10.0 22.47 na
H3 10.0 4.9 16.7 na 20.02 0.05 400 16.7
Dl 11.0 22.12 na
1 11.0 22.12 na
D2 11.0 22.03 na
D3 11.0 17.95 na
2 11.0 19.63 na
3 11.0 21.5 na
4 11.0 23.45 na
5 11.0 24.46 na
6 11.0 24.05 na
7 11.0 23.0 na
8 11.0 22.53 na
TRA 11.0 25.3 na
GA 5.0 28.37 na
BR 2.0 34.52 na
EL -3.0 36.88 na
X -3.0 39.72 na 5.0
Ml -3.0 40.46 na
M2 -3.0 44.61 na
CM -3.0 50.99 na
100 -3.0 50.99 na
101 -3.0 50.99 na
SRC -26.0 60.95 na
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 22.555
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 22.122 K Factor =0
H2 0.0 0.874 0 3.0 1.000 22.468
to 150.0 0.0 3.000 -0.433
D2 0.0 -0.0002 0.0 4.000 -0.001 Vel = 0
0.0
0.0 22.034 K Factor = 0
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel= 10.71
0.0
20.02 17.946 K Factor = 4.73
Di 0.0 0.874 N 7.0 11.917 22.122
to 150.0 R 1.0 11.000 0.0
1 0.0 0.0 0 3.0 22.917 0.0 Vel = 0
1 -10.67 0.874 R 1.0 0.333 22.122
to 150.0 0.0 1.000 0.0
D2 -10.67 -0.0660 0.0 1.333 -0.088 Vel = 5.71
D2 0.0 0.874 2R 2.0 31.750 22.034
to 150.0 0 3.0 5.000 0.0
2 -10.67 -0.0655 0.0 36.750 -2.408 Vel = 5.71
0.0
-10.67 19.626 K Factor = -2.41
D3 20.02 0.874 R 1.0 7.000 17.946
to 150.0 0.0 1.000 0.0
2 20.02 0.2100 0.0 8.000 1.680 Vel= 10.71
2 -10.67 0.874 4R 4.0 29.500 19.626
to 150.0 0 3.0 7.000 0.0
3 9.35 0.0513 0.0 36.500 1.873 Vel = 5.00
3 0.0 0.874 3R 3.0 32.000 21.499
to 150.0 0 3.0 6.000 0.0
4 9.35 0.0513 0.0 38.000 1.951 VeI= 5.00
4 0.0 0.874 2R 2.0 14.750 23.450
to 150.0 0 3.0 5.000 0.0
5 9.35 0.0513 0.0 19.750 1.013 Vel= 5.00
5 -20.02 1.101 N 7.0 12.417 24.463
to 150.0 0.0 7.000 0.0
6 -10.67 -0.0213 0.0 19.417 -0.413 Vel = 3.60
6 0.0 1.101 3R 3.0 39.167 24.050
to 150.0 N 7.0 10.000 0.0
7 -10.67 -0.0213 0.0 49.167 -1.047 Vel = 3.60
7 0.0 1.101 3R 3.0 12.417 23.003
to 150.0 N 7.0 10.000 0.0
8 -10.67 -0.0213 0.0 22.417 -0.477 Vel = 3.60
8 0.0 0.874 R 1.0 5.167 22.526
to 150.0 0.0 1.000 0.0
1 -10.67 -0.0655 0.0 6.167 -0.404 Vel = 5.71
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-10.67 22.122 K Factor = -2.27
5 20.02 1.101 N 7.0 5.250 24.463
to 150.0 0.0 7.000 0.0
TRA 20.02 0.0682 0.0 12.250 0.836 Vel = 6.75
0.0
20.02 25.299 K Factor = 3.98
TRA 20.02 1.101 R 1.0 6.000 25.299
to 150.0 0.0 1.000 2.599
GA 20.02 0.0681 0.0 7.000 0.477 Vel = 6.75
GA 0.0 1.101 Fsp 0.0 3.000 28.375
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 20.02 0.0682 0 5.0 27.126 1.850 Vel = 6.75
BR 0.0 1.245 0.0 5.000 34.524
to 150.0 0.0 0.0 2.166
EL 20.02 0.0374 0.0 5.000 0.187 Vel = 5.28
EL 0.0 1.245 0.0 76.000 36.877
to 150.0 0.0 0.0 0.0
X 20.02 0.0375 0.0 76.000 2.848 Vel = 5.28
X 5.00 1.025 Ball 3.037 2.000 39.725 Oa = 5
to 150.0 0.0 3.038 0.0
Ml 25.02 0.1459 0.0 5.038 0.735 Vel = 9.73
Ml 0.0 1.025 0.0 1.000 40.460
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 25.02 0.1460 0.0 1.000 0.146 VeI= 9.73
M2 0.0 0.995 T 5.841 32.000 44.606
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 37.841 6.381 Vel = 10.32
CM 0.0 7.98 T 52.855 275.000 50.987
to 150.0 0.0 52.855 0.0
100 25.02 0.0 0.0 327.855 0.002 Vel = 0.16
100 0.0 9.79 T 67.474 240.000 50.989
to 150.0 0.0 67.474 0.0
101 25.02 0.0 0.0 307.474 0.001 Vel = 0.11
101 0.0 6.16 E 22.818 10.000 50.990
to 150.0 0.0 22.818 9.961
SRC 25.02 0.0 0.0 32.818 0.001 Vel = 0.27
0.0
25.02 60.952 K Factor = 3.20
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Bulletin 006 Rev. I
Alllllllllllll Model RFC30 (SIN RA0611)
® Model RFC43 (SIN RA0612) Rell"111 C Model RFC49 (SIN RA061 6)
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
Very low water flow requirements.
Cover plate attachment (Plain or Perforated)
with ½" (13mm) Total adjustment.
Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½" (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
Plain Cover Plate
Perforated Cover Plate
and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D.
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Reliable Automatic Sprinkler Co, Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal-
lations, use a 165°F (74°C) fusible solder link in a tun-
ing fork style sprinkler frame with a drop-down deflector.
This assembly is recessed into the ceiling and concealed
by a flat cover plate. The cover plate is attached to the
skirt, using 135°F (57°C) ordinary temperature classifica-
tion solder. When the ceiling temperature rises, the solder
holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
inside to ceiling temperature. The subsequent operation
of the solder link opens the waterway and causes the de-
flector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler de-
flector. Any adjustment of thread engagement between
the cover plate and cup will assure that the drop-down
deflector is properly located below the ceiling. The resi-
dential distribution pattern contains a finer droplet size
than a standard sprinkler, and the pattern produces sig-
nificantly higher wall wetting.
After a 2 /8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexago-
nal body of-the sprinkler frame. The Wrench must bottom
out against the cup in order to ensure proper, safe instal-
lation. The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COV-
ERS.
Note: A leak tight 1/2" NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2" (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option,
the cover assembly is pushed onto the cup and final ad-
justment is made by turning the cover clockwise until the
skirt flange makes full contact with the ceiling. Cover re-
moval requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the
sprinkler, the plenum space may have neutral or neg-
ative pressurization but must not be positively pres-
surized. Inspect all sprinklers after installation to en-
sure that the gap between the cover plate and ceiling
and the 4 slots in the cup are all open and free from
any air flow impediment.
r
Model Thread Nominal Sprinkler CCP Assembly Max.
Ambient K Max.
(SIN) Size Orifice Temp Rating Temp. Rating
______ Temp. Factor Pressure
Inch (mm) Inch (mm) psi (bar) °F °C °F °C °F
RFC 30
(RAO611) 1/2" (15) 21/64(82) 165 74 135 57 100 38 3.0(43.2) 175 (12)
RFC 43
(RA0612) 1/2 (15) 3h(10) 165 74 135 57 100 38 4.3(62) 175 (12)
RFC49
(RA0616) 1/2" (15) 7/l6 (11) 165 74 135 57 100 38 4.9 (70.6) 175 (12)
Note: 1 bar= 100 Kpa
RFC 30
Ordinary Temp. Rating Max. Coverage Max. Spacing (165°F174°C) Top of Deflector Installation Minimum
area
FtxFt(mxm) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Pressure
GPM (L/min) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0 (0,62) Smooth Ceilings ½ to 1(13 to 25.4)
Beamed ceilings per NFPA 13D, 13R or Concealed 8(2,4)
14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11.0(0,76) 13 installed in beams ½ to 1(13 to 25.4)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
RFC43
Ordinary Temp. Rating Max. Coverage Max. Spacing (165°F/74°C) Top of Deflector Installation Minimum
area
Ft x Ft (m x m) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Pressure
GPM (1/mm) PSI (bar)
12x 12(3,6x3,6) 12(3,6) 12(4,5) 7.8 (0,54)
Smooth Ceilings ½ to 1(13 to 25.4)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63)
16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2,4)
18 x 18 (5,5 x 5,5) 18(5,5) 18(68) 17.5(1,21)
20x20(6,1 x6,1) 20(6,1) 21(79) 23.8(1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49
Max. Coverage Max. Spacing
Ordinary Temp. Rating
(165' 4-C) Top of Deflector Installation Minimum
area Ft (m) to Ceiling Type Spacing Flow Pressure Ft x Ft (m x m) GPM (Llmin) PSI (bar) Inch (mm) Ft (m)
12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0 (0,48)
Smooth Ceilings 1/2 to 1(13 to 25.4)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0 (0,48)
16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 7.0(0,48) Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 17 (64,3) 12.0(0,83)
20 x 20 (6,1 x 6, 1) 20(6,1) 20(75,73) 16.7 (1,14)
For Ceiling types refer to NFPA 13, 13R or 130
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remo''e any sprinkler cover plate as-
sembly which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½" NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler K-
factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6)
having a 5/", 3/s" and 7A6" orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (57°C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½" cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty - specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA061 1
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
3.
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On Feature
Cover Plate Finishes0
Standard Finishes
Chrome
White Paint
Special Application
Finishes (2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(I) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
x 1/.2 REDUCING
TEE OR ELBOW
In---- ---4W— t-----juI
- I 2 [66.55mm]
[58.42mm] D14
_____________________
HOLE IN CEILING
CUP —k
I I I I I 2 [50.8mm] MAX.
__________ FACE OF F1T17NG [12.70mm] MAX. 70 FACE OF CEiLING 1" COVER AW DIMENSIONUSThENT
1/2
1
1 (25.4mm] MAX.
70 CEiLING
CEILING
Al [4.96mm]
DROPPED DEFLECTOR
FIAT COVER PLATE_1 Jj [84.2 1mm] ASSEMBLY
COVER PLATE: 1/2" [12.7mm] ADJUSTMENT
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
Recycled
NW Paper Rell (800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
-
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 11/14 P/N 9999970261
Bulletin 135 Rev.G
®R ReHabk Model Fl
Residential Sprinklers for
Design Density of .05 gpmlft
1
Model Fl Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm/ft2
Types:
F1 Res 30Pendent
Fl Res 30 Recessed Pendent/F2
Fl Res 30 Recessed Pendent/FP
Fl Res 49 Pendent
Fl Res 49 Recessed Pendent/F1
Fl Res 49 Recessed Pendent/FP
Fl Res 58 Pendent
Fl Res 58 Recessed Pendent/F1
Fl Res 58 Recessed Pendent/FP
Fl Res 76 Pendent
Fl Res 76 Recessed Pendent/Fl
Fl Res 76 Recessed Pendent/FP
Fl Res 30 COP Pendent
Fl Res 49 COP Pendent
Fl Res 58 COP Pendent
Fl Res 76 COP Pendent
F1 Res 44HSW
Fl Res 44 Recessed HSW/F2
Fl Res 58 HSW
Fl Res 58 HSW Recessed HSW/F2
Fl Res 44SWC
Fl Res 40 HSW
Fl Res 40 Recessed HSW/F2
Listings & Approvals
Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
NYC MEA 258-93-F
Slope Ceiling Approvals: Refer to Bulletin 035
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model Fl Res 49 & 58 Pendent Sprinklers
Product Description
Model Fi Res Pendent sprinklers (Figs. 1, 2,3, &4)are
El Res 30,49,58&76 Fl Res 30,49,58 & 76
Recessed Pendent I Fl Recessed Pendent/ EP
El Res 3O,49,58&76 Fl Res 44&58
CCP Pendent Recessed HSW/F2
Fl Res 44 SWC Fl Res 40 Recessed
HSW/E2
The low flow El Res sprinklers are specially
engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest
residential market standards (UL 1626 Standard). Upon
fire conditions, rising heat causes a sprinkler's
heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly
distributing the discharged water to control a fire.
Technical Data:
Thermal Sensor: Nominal 3mm glass-bulb
Sprinkler Frame: Brass Casting
Sprinklers' Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: ½" NPT (R1/2)
K-Factor: 3.0 (Actual) - El Res 30 Pendent Sprinkler
4.9 (Actual) - El Res 49 Pendent Sprinkler
5.8 (Actual) - Fl Res 58 Pendent & HSW Sprinkler
7.6 (Actual) - El Res 76 Pendent Sprinkler
4.4 (Actual) - El Res 44 HSW Sprinkler
4.0 (Actual) - El Res 40 HSW Sprinkler
Density: Minimum 0.05 gpm/ft2
response sprinmerscombining wcuIIrl1UUfttL)lII1y, Application high sensitivity glass-bulb and low profile decorative
design. The El Res Horizontal Sidewall sprinklers (Figs. Model El Res Sprinklers are used for Residential Eire
5,6 & 7) are equally attractive when above ceiling piping Protection according to UL 1626 Standard*. Be sure
cannot be used. that orifice size, temperature rating, deflector style and
The 3mm glass-bulb pendent sprinklers permit the sprinkler type are in accordance with the latest
efficient use of residential water supplies for sprinkler published standards of The National Fire Protection
coverage in residential fire protection design. Association or the approving authority having
jurisdiction.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
l3FGO3
Installation
Models El Res sprinklers are to be installed as
shown. Model El, F2 and FP Escutcheons, illustrated
herewith, are the only recessed escutcheons to be used
with Model El Res sprinklers. Use of any other
recessed escutcheon will void all approvals and
warranties. Eor installing Model El Res Pendent
sprinklers use only the Model D sprinkler Wrench; for
installing Models El Res Recessed Pendent, COP &
Model Fl Res 30, 49, 58 & 76 Pendent
SWC sprinklers use only the Model GER2 sprinkler
wrench; for installing Model El Res Recessed HSW
sprinklers use only the Model GER2 Sprinkler Wrench.
Use of wrenches other than those specified may
damage these sprinklers. Install El Res 44 and 40 HSW
with a ceiling to deflector distance of 4"- 12". Flow arrow
on deflector must point away from near wall and "Top"
marking must face ceiling.
Model Fl Res 30 Recessed
Pendent/172
Model Fl Res 49, 58 & 76
Recessed Pendent / Fl
V
Fl escutcheon, 3/4" (19) adjustment
2 /4 HOLE D4.
I I5/I6 D. f49..2m,,J
,• t I • REXCER
AM COLLAR WX I71T A405T SMWNKW
nnwc TO
ADJUSMENr
112-1
,....
__
I
__ 7J5F2 227/i2 _________ (72.2
Fig. 1 Fig. 2
Escutcheon*. Fl or F2. Data:
Adjustment "A" Face of fitting to
Type Inch (mm) Inch (mm) ceiling
Inch (mm)
Fl 3/4(19.0) Min.= 3/4' (19.1)
Max.=1X" (38.1) X6 - 15/6 (4.724.0)
F2 % (12.7) Min.= 15/" (23.8)
Max.=1,4" (38.1) 3/ - 16 (4.7- 17.4)
* Note: Escutcheons Fl or F2 may be used with
Model Fl Res 49, 58 & 76 Recessed Pendent
2.
Technical Data: Fl Res 30 Pendent and Recessed Pendent
Nominal Sprinkler Max. Max. Actual Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating Temp Factor Inch I °c OF I °C (mm) (bar) (mm)
"NPT 2y"(82) 15
°F
5
175
68
79 175 (12) 100 38 3.0 2.25(57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler Flow Pressure Sprinkler
Spacing
ft (m) gpm (Lpm) psi (bar) Identification
Number (SIN) I
12 x 12 (3.6x3.6) 8(30.3) 7.0 (0.48) R3511 14 x 14 (4.3x4.3) 10(37.8) 11(0.76)
Technical Data: Fl Res 49 Pendent and Recessed Pendent
Nominal Sprinkler Max Max. Actual Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating psi Temp. Factor Inch
°F °c OF °c (mm) (bar) (mm)
Y2"NPT 6(h1) 155
175
68
79 175(12) 1001
150166
38 4.9 2.25(57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler
Spacing
ft_(m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13(49) 7.0 (0.48)
R3516
16.7(l.14)
14 x 14 (4.3x4.3) 13(49) 7.0(0.48)
16 x 16 (4.9x4.9) 13(49) 7.0 (0.48)
18 x 18 (5.5x5.5) 17(64.3) 12.0(0.83)
20 x 20 (6. 1 x6. 1) 20 (75.7)
*Deflector - to - ceiling
Maximum 4" (100mm) to 8" (203mm)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)
R3516
20.2(1.4)
14 x 14 (4.3x4.3) 16 (60.5) 10.6(0.73)
16 x 16 (4.9x4.9) 17(64.3) 12.0(0.83)
18 x 18 (5.5x5.5) 19(72) 15.0(1.0)
20 x 20 (6.1x6.1) 22(83.2)
*Note: The Fl Res 49 pendent and recessed pendent
residential sprinklers can be installed per NEPA 13 in
beamed ceilings meeting the following criteria:
Maximum beam depth = 7" (178mm)
Beam spacing ator greaterthan 7.5 ft. (2.3m) on center.
Technical Data: Fl Res 58 Pendent and Recessed Pendent
Nominal Sprinkler Max. Max. Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating psi Temp. Factor Inch
°F oc °F I 00 (mm) (bar) (mm)
½" NPT
(R1/2) y (13) 155
1751
68
79 175(12) 100
1501
38
66
5.8 2.25 (57)
Max. Sprinkler Flow Pressure Ceiling -to- Sprinkler
Spacing m (L gpm psi (bar) Deflector Identification
ft (m) Inch (mm) Number (SIN)
12 x 12 (3.6x3.6) 16 (61) 7.6(0.53)
1-4
(25-100)
14.4(1.0)
R3513
14 x 14 (4.3x4.3) 16 (61) 7.6(0.53)
16x 16(4.9x4.9) 16(61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19(72) 10.8 (0.75)
20 x 20 (6.1x6.1) 22(83.3)
3.
Technical Data: Fl Res 76 Pendent and Recessed Pendent
Nominal Sprinkler MwL Max. I Sprinkler
Thread Orifice TempL Pmssue Antient K Length Size Inch no psi Teni Factor hch
°F °c OF oc (mm) (bar) (mm)
3/4"NPT
(R3/4) %' (13.5)
155
1751
68
79 175(12) 100
150
38
66 7.6 2.25 (57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Ptessur
psi (bar)
Sprinkler
Identification
Number (SIN)
12x 12(3.6x3.6) 21 7.6 (0.53)
R7618
9.2(0.63)
14x 14(4.3x4.3) 21 7.6 (0.53)
16 x 16 (4.9x4.9) 21 7.6(0.53)
18 x 18 (5.5x5.5) 21 7.6 (0.53)
20 x 20 (6. 1 x6. 1) 23
Model Fl Res 30, 49, 58 & 76 • Model Fl Res 30, 49, 58 & 76
Recessed Pendent / FP
I-P push-on/thread-off
escutcheon
- 2 5/8' [66.7mm] 0/A.
2 5/76" 0/A. HOLE IN CEILING
[58. 7mm]
CUP
lx 1/2 REDUCER
CUP
CEILING
MAX. FACEOF FITTING j TO FACE OF CEILING F---' DIMENSION
COVER ADJUSTMENT / HEIGHT
3 5/16" 0/A.
1J5FC04D I [84.1mm]
'Fl RES 30, 49. 58 & 76 CCP PEND.
Fig. 3
NOTE: The El Res 76 will use a 1 x 3/4"reducer,
2 5/8' DA [6& 7--j HOLE IN CEILING
2 5/76 W. (587nnJ Cup
lXI/2W
CEILING
I 7/2 (38,7 )MAX F'ACE OF FIllING FO FACE OFCVLWG
- -- - 73K. /2
FP AIIjusruEwr 'A'
Fig. 4
ri
CCP ODtions Data:
Cover Adjustment CCP Height
Inch (mm) Inch (mm)
%(12.7) /i'6(24)
/6(7.9) 3A(19)
FP Data "A":
FP Position Inch (mm)
M. Recessed X6 (11)
Mm. Recessed 15/ (24)
Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent I FP
Nominal Sprinkler CCP
Asmi-bly Max. Max Spriinkler
Thread Orifice Temp. pressureSize Temp, M11 K Length
Inch Rallig Fç Temp. Factor Inch
( (mm) ) °F °C °F I I
Y2" NFl 2y"(82) 155168 135 I 57 175(12) 1 1001 38 3.0 2.25
(R1/2)
Max. Sprinkler Flow Pressure Sprinkler
Spacing gpm (Lpm) psi (bar) Identification
ft (m) Number (SIN)
12x 12,6x3.6) 80.3) 7.0 (0.48) R3511 13.4_(0.92) 14 x_14_(4.3x4.3) 11(41.6)
Technical Data: Fl Res 49 CCP Pendent and Recessed Pendent / FP
ccp Nominal Sprinkler Max Spñlder
Thread Orifice Temp Assem*Mwc Ambient K Length
Size Inch Rating Temp. Ptessue
Rating psi 'a Temp. Factor Inch
(nni) (mm) °F_I_00 °F_I
TO3
½ 2.25 I I
NFl X6 (11) 155168 1351 57 175(12) 4.9
(R½) I I
Spacing
Max. Sprinkler Flow Pressure Sprinkler
ft (m) gpm (Lpm) psi (bar) Number (SIN)
Identification
12 x 12 (3.6x3.6) 13(49) 7.0(0.48)
14 x14(4.3x4.3) 13(49) 7.0(0.48)
16x16(4.9x4,9) 14(53) 8.2(0.56) R3516
18 x_18_(5.5x5.5) 18(68.1) 13.5(0.93)
____
20 x 20(6.1x6.1) 20(75.7) 16.7(1.14) -
- suitable for installation in ceilings which have
positive pressure in the space above.
Technical Data: Fl Res 58 CCP Pendent and Recessed Pendent/FP
cc
Thread Orifice Ten!1 Pressure Antftt TempL
Max Max Spñlder Nominal Sprinkler Assen1 K Length
size Inch Ratlig
___Flating psi Temp. Factor Inch
1/2"NPT /"(13) 15568 13557 175 (12) 10038 8 2.25(57)
(mm) °F I°C °F _0 (bar) °FI_°c (nITI)
Spacing
Max. Sprinkler flow Pressure Sprinkler
ft (m) gpm (Lpm) psi (bar) Number (SIN)--
Identification
x12(3.6x3.6) 16_(61) 7.6(0.53) 12
14 x14_(4.3x4.3) 16(61) 7.6(0.53)
16 x16(4.9x4.9) 16(61) 7.6(0.53) R3513
18x18(5.5x5.5) 19(72) 10,8(0.75)
20x20(6.1x6.1) 22(83.3) 14.4(1.0)
Technical Data: Fl Res 76 CCP Pendent and Recessed Pendent/FP
Nominal Sprinkler CCP Max Max
Thread Orifice Temp,Assm" Pressure Ambient K Spulder
Length Size Inch Rathg Rai___ psi Temp Factor Inch (rmn)
(R3/4) (13.5) 1751_79 150 66
3/4"NPT l" 15568 135 _57 175(12) 10038 76 2.25(57)
(mm) °F _°C °F_°c (bar) °F _0c
ft (m)
Max. Sprinkler Flow Pressure Sprinkler
Spacing gpm (Lpm) psi (bar) Number (SIN)
Identification
12_x_12_(3.6x3.6) 21 7.6(0.53)
14 x_14_(4.3x4.3) 21 7.6(0.53)
16 x_16_(4.9x4.9) 21 7.6(0.53) R7618
18 x 18 (5.5x5.5) 22 8.4_(0.58)
20x20(6.1x6.1) 25 10.8(0.74)
Note: Sprinklers shown in Hg. 3 and Fig. 4 are not
5.
Escutcheon. F2. Data:
Type Adjustment Face of Fitting I
to wall I Inch (mm) Inch (mm) I
F2 X(13)
Model Fl Res 44 & 58 HSW • Model Fl Res 44 & 58
Recessed HSW/F2
F2 escutcheon, " (13mm
adjustment
Technical Data: Fl Res 44 HSW & HSW/F2
Nominal Spiilder Max. Max. Spriiicier
ilvead Orifice Ti Resa,e Ambient K Lngfli
Size Inch Fiig psi Tenp.Pactor Inch
°F °c iOC (mm) (bar) (mm)
1/2"NPT Y8"(10) 155 68 175 (12) 100
150
38
66 4.4 2.45 (62)
Ma.Sptinlder
Spacing
ft (m)
Ceiling
Deflector
Inch (mm)
Sprinkler Temp.
Rating
OF (°C)
Flow
gpm
(Lpm)
E_75
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101152)
12(45.4)
14
155 (68) 175 (79)
R3531
x 14 (4.3x4.3) 155(68) 175(79) 14(53.0) 0.2(0.71)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 16(60.6) 13.3 (0.92)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 18(68.1) 16.8(l.16)
18 x 18 (5.5x5.5) 155 (68) 175(79) 19(72.0) 18.7(l.29)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23(87.1) 27.4(1.89)
12 x 12 (3.6x3.6)
6 -12
(152-305)
155 (68) 175 (79) 14(53.0) 10.2 (0.71)
27.4(1.89)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 16(60.6) 13.3 (0.92)
16 x 16(4.9x4.9) 155 (68) 175(79) 17(64.4) 15.0 (1.04)
16 x 18(4.9x5.5) 155 (68) 175 (79) 20 (75.7) 20.7(l.43)
16 x 20(4.9x6.1) 155 (68) 175 (79) 23(87.1)
91
Escutcheon, F2, Data:
Type
Adjustment I Face of Fitting I
I to wall Inch (mm) Inch (mm) I
F2 Y2 (13) 1(47174)
Technical Data: Fl Res 58 HSW & HSW/F2
Nominal Spñikler Max. Max. Spni'ier
Thad Orifice Teni pressure Ambient K Length
Size Inch Riig psi Teni Faor Inch
°F ° °t °c (mm) (bar) (mm)
1/2"NPT
(R 112)
)/2" (13) 155 1751 68
79 175(12) 100
150
38
I 66
5.8 2.45 (62)
Ma. Sprinkler
Spacing
ft (m)
Ceiling --
Deflector
Sprinkler Temp.
Rating
°F (°C)
Inch (mm)
Flow
gpm
(Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155 (68) 175 (79) 16(60.6) 7.6(0.53)
R3533
14 x 14 (4.3x4.3) 155 (68) 175 (79) 18(68.2) 9.7 (0.67)
16x 16(4.9x4.9) 155(68) 175(79) 21(79.5) 13.2 (0.91)
16 x 18(4.9x5.5) 155 (68) 1 175 (79) 25(94.7) 18.6(l.28)
16 x 20 (4.9x6. 1) 155 (68L 175(79) 29(109.8) 25(1.73)
12 x 12 (3.6x3.6)
6-12
(152-305)
155(68) 175 (79) 22(83.3) 14.4(1.0)
28.6 (1.97)
14 x 14 (4.3x4.3)— 155(68) 175(79) 22(83.3) 14.4(1.0)
16x 16(4.9x4.9) 155(68) 175(79) 26(98.4) 20.1 (1.39)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 31(117.4)
7.
Model Fl Res 44 SWC
7I)
I 7/4 [3I.75mm] Maximum
Face Of Fitting
To Woll Oi,,,ension
7X I/2 Reducer -7
4 to 12'
(IOI.6O,nn To
304.80mrnJ
PUSH ON COVER. THEN TURN TO AOJUST UNtIL
now AGAINST WALL.
Recom,nendedWall Hole 25116-
TURN COLLAR UNTIL
SPRINKLER 1 21152- WRENCH
_::1 SJ5FVO7
Adjustment
Fl RES 44 SWC
Fig. 5
Technical Data: Fl Res 44 SWC
Nominal
Orifice
Sp.ilder
Temp. Ten COTeni
Rati-Ig
rnax. Max.
An1Teni K
Sprinkler
Length Size Inch Rating psi Fcr hch
CF CC CF I °c OF
___________ (mm) (bar) CC (mm)
1/2"NPT
(R½)
/(1O) 155 68 135 57 175(12) 100 38 4.4 2.45(62)
Ma.Spnnkler
Spacing
ft (m)
Ceiling
Deflector
Inch (mm)
Flow
gpm
(Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
13(49.2) 8.7 (0.60)
R3531
20.7(1.43)
14 x 14 (4.3x4.3) 14(53.0) 10.2(0.71)
16 x 16 (4.9x4.9) 17(64.3) 15.0(1.1)
16x 18(4.9x5.5) 19(71.8) 18.7(l.13)
16 x 20 (4.9x6.1) 23(87.1) 27.4(1.89)
12 x 12 (3.6x3.6)
6-12
(152-305)
________
14(52.9) 10.2(0.71)
14 x 14 (4.3x4.3) 15 (56.7) 11.7 (0.81)
16x16(4.9x4.9) 18(68.1) 16.8(1.16)
16 x 18 (4.9x5.5) 20(75.6)
EI
Escutcheon. F2. Data:
Type Adjustment Face of Fitting
to wall Inch (mm) Inch (mm)
F2 X(13) y 1y(47174)I
FA • Model Fl Res 40 Recessed
Model Fl Res 40 HSW HSW/F2
F2 escutcheon, /2" (13mm)
adjustment
135FC05
Fig. 6
FACE OF FIT7ING TO
WALL DIMENSION - 7 7/4 MIN.
-2 7/4 HOLE ON.
[57.2,,,m] CEILING TO
DEFLECTOR
7/2REOUCER DIMENSION
1 15116- DL4 1
2 27 /32 OL&
TURN COLLAR UN7IL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
- 7/2 [73c,] 135FG06-C ADJUSTMENT
Fl RES 58. 44 & 40 HSW/F2
Fig. 7
Technical Data: Fl Res 40 HSW & HSW/F2
Nominal Sprilder Max Sp.iiider
Thread Orifice Temp. Ambient K Length
Stze Inch Fklu p Ten Factor hch
c I cc °F cc (mm) (bar) (mm)
1/2"NPT y"(10) 155
175
68
79 175(12) 100
150
38 I 66
4.0 2.45(62)
Max. Sprinkler Ceiling -to- Sprinkler Temp. ROW Pressure Sprinkler
Spacing Deflector Rating gpm psi (bar) Identification
ft (m) Inch (mm) °F (°C) (Lpm) Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155(68) 175 (79) 13 (49.0) 10.6(0.73)
R3538
14 x 14(4.3x4.3) 155 (68) 175 (79) 16(60.5)
16 x 16 (4.9x4.9) 155(68) _______ 17(64.3) 18.1 (1.24)
16x 16(4.9x4.9) 175(79) 18(68.1) 20,2(1.39)
16 x 18(4.9x5.5) 155 (68) 175 (79) 20(75.7) 25.0 (1.72)
18 x 18 (5.5x5.5) 155(68) 175 (79) 22 (83.3) 30.2(2.08)
25.0(1.72)
16 x 20 (4.9x6. 1) 155(68) 175(79) 23(87.0) 33.1 (2.28)
12 x 12 (3.6x3.6)
6-12
(152-305)
155 (68) 175 (79) 13(49.0) 10.6(0.73)
14x 14(4.3x4.3) 155(68) 175(79) 17(64.3) 18.1 (1.24)
16x 16(4.9x4.9) 155(68) 175(79) 20(75.7)
Finishes(l)
Standard Finishes
Sprinkler Fl, F2, FP Cover Plates Escutcheons
Bronze Brass White Painted
Chrome Plated Bright Chrome Plated Chrome
White Polyester White Painted
Coated
Special Application Finishes
Sprinkler Fl, F2,
Escutcheons
Cover Plates
Bright Brass Bright Brass Bright Brass
Black Plated Black Plated Black Plated
Black Paint Black Paint Black Paint
Off White Off White Off White
Satin Chrome Satin Chrome Satin Chrome
(1> Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will
void all approvals and warranties.
Maintenance
Model El Res 30, 49, Fl Res 58, Fl Res 76, Fl Res 44
and Fl Res 40 Sprinklers should be inspected quarterly,
and the sprinkler system maintained in accordance with
NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with
soap and water, Ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers ,should remain in the original cartons
and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper
operation or non-operation.
Model Fl Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12] to
[8/12], the sprinklers shall be listed for such use.
Deflector-to-ceiling distance listing shall be 1" to 8"
maximum. Sprinkler frame and deflector shall be of bronze
frame construction having a ½" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 3.0, 4.9 and 5.8.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be Reliable Model El Res 30, 49 & 58, SIN
R3511, R3516&R3513 (Bulletin 135).
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
Model Fl Res 49 & 58 Recessed PendentlFl,
Model Fl Res 30,49 & 58 Recessed Pendent/F2,
Model Fl Res 30,49 & 58 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/e over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
deflector shall be of bronze frame construction having a ½"
NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb containing
no plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (7911C)]. Sprinklers shall have a nominal
K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish- specify].
Recessed escutcheon assembly shall be a steel, two-piece
escutcheon [with ½" adjustment (Model F2)] [with 3/4"
adjustment (Model El)] [of push-on and thread off design
with ½" adjustment (Model FP)]. Standard finish shall be
[brass] [bright chrome] [white painted]. Residential
recessed pendent sprinklers shall be Reliable [Model Fl
Res 3.0, 49 & 58 Recessed Pendent/Fi] [Model El Res 30,
49 & 58 Recessed Pendent/F2] [Model El Res 30, 49 & 58
Recessed Pendent/EP] SIN R3511, R3516 & R3513
(Bulletin 135).
00
Model Fl Res 30,49 & 58 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12]
to [8/12], the sprinklers shall be listed for such use.
Sprinkler frame and deflector shall be of bronze frame
construction having a ½" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville
spring washer with top-loaded extruded or cold head
cup with 3 m glass bulb containing no plastic parts, and
having a temperature rating of 1550F (680C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange. Method of attaching the cover plate
to the sprinkler cup shall be a push-on and thread-off
design allowing a ½" cover plate adjustment. Cover
plate temperature rating shall be 135°F (570C). A plastic
protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before
the cover plate is installed. Standard cover plate finish:
[White] [Custom Color- specify]. ]. Concealed pendent
sprinklers shall be Reliable Model Fl Res 30, 49 & 58
CCP, SIN R3511, R3516 & R3513 (Bulletin 135).
Model Fl RES 40 and Fl Res 44 Horizontal Sidewall
Residential Sprinkler Specifications
Model Fl Res 40 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Where horizontal sidewall
residential sprinklers are installed under sloped ceilings
having a pitch from [4/12] to [8/12], the sprinklers shall be
listed for such use. Sprinkler frame and deflector shall be
of bronze frame construction having a ½" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (790C)]. Sprinklers shall have a nominal K-factor of
4.0 (57.1). Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40, SIN R3538 (Bulletin 135).
Model Fl Res 40 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 40 horizontal
sidewall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½" adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish- specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40/F2, SIN R3538 (Bulletin 135).
Model Fl Res 44 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the
applicable installation standard. Where horizontal
sidewall residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Sprinkler frame
and deflector shall be of bronze frame construction
having a ½" NPT thread. Water seal assembly shall
consist of a Teflon-coated Belleville spring washer with
top-loaded extruded or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a
temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 4.4 (62.8).
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 44, SIN R3531 (Bulletin 135).
Model Fl Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 44 horizontal
sidewall sprinkler with the following modifications:
Replace "horizontal sidewall sprinkler" with 'recessed
horizontal sprinkler." Add: Recessed escutcheon
assembly shall beasteel, two-piece escutcheon with 1/2"
adjustment (Model F2). Standard finish shall be
[brass][bright chrome] [white painted] [Special finish-
specify]. Residential recessed horizontal sidewall
sprinklers shall be Reliable Model Fl Res 44/F2, SIN
R3531 (Bulletin 135).
Model Fl Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall be
of bronze frame construction having a 3/4" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with machined or cold head cup
with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155°F (680C)] [175°F
(790C)]. Sprinklers shall have a nominal K-factor of 7.6.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish— specify]. Residential pendent
sprinklers shall be Reliable Model Fl Res 76, SIN R7618
(Bulletin 135).
Model Fl Res 76 Recessed PendentlFl,
Model Fl Res 76 Recessed PendentIF2,
Model Fl Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineerd to provide a
minimum design density of 0.05 gpm/ft over the listed
coverage area. Listed flows as specified by the
manufacturer's technical data sheets are to be used.
Residential sprinklers shall be installed in conformance
with the manufacturer's installation guidelines and the
applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a
3/4" NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with machined or
cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (791C)]. Sprinklers shall have a nominal
K-factor of 7.6. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish—
specify]. Recessed escutcheon assembly shall be a
steel, two-piece escutcheon [with ½" adjustment (Model
F2)] [with 3/4" adjustment (Model Fl)] [of push-on and
thread off design with ½" adjustment (Model FP)].
Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall
be Reliable [Model Fl Res 76 Recessed Pendent/Fl]
[Model Fl Res 76 Recessed Pendent/F2] [Model Fl Res
76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model Fl Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprinklers
shall be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Sprinkler frame and deflector shall be of bronze
frame construction having a 3/4" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with machined or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a temperature
rating of 155°F (680C). Cover plate assembly shall consist
of a brass cover plate and copper alloy retainer flange.
Method of attaching the cover plate to the sprinkler cup
shall be a push-on and thread-off design allowing a ½"
cover plate adjustment. Cover plate temperature rating
shall be 135°F (570C). A plastic protective cap shall be
provided and factory installed inside the sprinkler cup to
protect the sprinkler from damage, which could occur
during construction before the cover plate is installed.
Standard cover plate finish: [White] [Custom Color—
specify]. ]. Concealed pendent sprinklers shall be Reliable
Model Fl Res 76 CCP, SIN R7618 (Bulletin 135).
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
I- • (800) 431-1588 Sales Offices Recycled
I (800) 848-6051 Sales Fax \/ Paper
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
w.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 06/08 P/N 9999970235
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
510
CPVC - STEEL - COPPER
HANGER
SIZE - 3/4" thru 3" pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Hanger in listed mounting positions - Top, Bottom or Side.
Also, provides stability on vertical piping.
INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers
instructions on top, bottom or side of building element. Space by pipe type.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC pipe - #905 screw - no pre-drill.
3/4" - 3" Copper pipe - #905 screw - no pre-drill.
3/4" - 3" Steel pipe - 1/4"x 11/2" lag screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON#905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
*CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shalt NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
Side View - For
Drawings Below
Hanger - Wood Stud Hanger - Metal Stud
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
SIDE MOUNT
CPVC - COPPER
HANGER
SIZE - 3/4" thru 2" pipe.
MATERIAL -. Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
®an 203 - EX 4231, EX 2551
FUNCTION - Hanger on CPVC and Copper pipe.
INSTALLATION - Per NFPA 13,13R, 13D and CPVC
manufacturers instructions on top or bottom of beam.
Space by pipe type
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwitl NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
513
CPVC - STEEL - COPPER
HANGER
SIZE - 3/4" thru 2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Tab up = Hanger.
INSTALLATION - Per NFPA 13,13R and 13D on
side or top of beam. Space by pipe type.
SPECIAL NOTE When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
FEATURES
* Offset edge eliminates abrasion.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
P 5 ~4 -0 nizo I
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
#905 #906
3.00
OFFSET CPVC HANGER
SIZE - 3/4" thru 3"pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized..
LISTING/APPROVAL -
203 - EX 4231, EX 2551
PATENT - No. 6,648,278.
FUNCTION - 314"-2" Hanger/restrainer for horizontal CPVC, Copper or Steel pipe.
Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and
bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Size 2 %" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions.
i.e. vertical surface and both top and bottom of horizontal surface.
Size 3" Hanger for horizontal CPVC pipe in two mounting positions, side and bottom.
i.e. vertical surface and bottom of horizontal surface.
Stabilizes vertical piping by providing horizontal restraint.
INSTALLATION - Per NFPA 13,13R and 13D.
Space by pipe type. Install on wood, concrete or steel - See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed
When #905 threads are exposed in wood, install #906 backing nut. 3/4
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre-drill.
3/4" - 2" Copper pipe - #905 screw- no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
Thru 5/8" gypsum board - 1/4" x 2" lag screw.
STEEL - mm. 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fastener = 5(wt)+2501bs.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* 3/4" and 1" pipe size made with common center-line.
* Patented design for superior strength.
* Offset edge eliminates abrasion.
* AFCON#905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold separately.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the followingwarranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
6/08
Pipe
Manufactured for Viking SupplyNet by Viking Plastics, LLC (Huntsville, Alabama USA.)
egg!!g - 1
Size •Part
3/4"
Number y
34PIPE 240 ft
1PIPE 150 ft
1-1/4" 114P1PE 105 ft
1-1/2" 112P1PE 75 ft
2PIPE 60 ft
2-1/2" 212PlPE 30 ft
3PIPE 15 It
BlazeMaster® CPVC fittings are manufactured/supplied for Viking SupplyNet by NIBCO, Inc.
Standard Fittings
Size
3/4"
t Number
V5011-007
Box Qty.
250
1" V5011-010 100
1-1/4" V5011-012 25
1-1/2" V5011-015 25
-The I Part Number I Box Qty.
Tee (continued)
V5011-020 2
2-1/2" V5011-025 1
V5011-030 1
Tee
Reducing Tee
C:j
Size
3/4"x3/4'xl"
Part NumberBox
V5011 R-102
Qty.
10
1"x3/4"x3/4" V5011 R-125 100
1"x3/4"xl" V5011 R-126 10
1"xl"x3/4" V5011 R-131 100
1-1/4"xl"0/4" V5011 R-157 5
1-1/4"xl"x1" V5011 R-158 25
1-114"xl"x1-114" V5011 R-159 5
1-1/4"xl-1/4"x3/4" V5011R-167 25
1-1/4"x1-1/4"xl" V5011 R-168 25
1-1/4"x1-114"xl-1/2" V501 R-169 5
1-1/2"xl-1/4"x3/4" V5011 R-201 5
1-112"x1-1/4"xl" V5011 R-202 5
1-1/2"xl-1/2"x3/4" V5011 R-.210 25
1-1/2"xl-112"xl" V5011 R-211 25
Size I Part Number Box Qty.
Reducing Tees (continued)
1-112"xl-1/2"xl-1/4" V5011 R-212 5
1-1/2"xl-1/2"x2" V5011 R-213 5
2"x2"x3/4" V5011 R-248 2
2"x2"xl" V5011 R-249 10
2"x2"xl-1/4" V5011 R-250 2
2"x2"x1-1/2" V5011R-251 2
2-1/2"x2-1/2"x l" V5011 R-289 1
2-1/2"x2-1/2"xl-1/4" V5011 R-290 1
2-1/2"x2-1/2"xl-112" V5011 R-291 1
2-1/2"x2-1/2"x2" V5011 R-292 1
3"x3"xl-1/2" V5011 R-337 1
3"x3"x2" V5011 R-338 1
3"x3"x2-1/2" V5011 R-339 1
www.vikinggroupirtc.com Refer to manufacturer's DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions.
Size I Part Number I Box I!11'j
450 Elbow (continued)
V5006-020 2
2-1/2" V5006-025
V5006-030 1
450 Elbow
Standard Fittings continued from Page 1
900 Elbow Size
3/4"
Part Number
V5007-007
Box Qty.
250
V5007-010 100
1-1/4" V5007-012 25
1-1/2" V5007-015 25
V5007-020 j 10
Size I Part Number I Box Qty.
900 Elbow (continued)
2-1/2" V5007-025 1
V5007-030
1" x 3/4" V5007R-131 100
Cross 14'
3/4"
iNumber
V5035-007
Box Qty.
10
1" V5035-010 100
1-1/4" V5035-012 5
1-1/2" V5035-015 6
2" V5035-020 4
Size I Part Number I Box Qty.
Cross (continued)
2-1/2" V5035-025 4
3" V5035-030 1
1 "xl "x3/4"x3/4" V5035R-131 10
Coupling
0,
Size
3/4"
Part Number
V5001-007
Box Qty.
250
1" V5001-010 100
1-1/4" V5001-012 25
1-1/2" V5001-015 25
Size I Part Number I Box Qty.
Coupling (continued)
2' V5001-020 10
2-1/2" V5001-025 1
3" V5001-030
Reducing Coupling Size
1" x3/4'
Part Number
V5001 R-131
Box Qty.
10
1-1/4" x 1" V5001 R-168 5
1-1/2' x 3/4" V5001 R-210 5
1-1/2" x 1' V5001 R-211 5
Size I •irt Number Box Qty.
Reducing Coupling (continued)
1-1/2"x 1-1/4" V5001 R-212 5
2" x 1" V5001 R-249 2
2' x 1-1/2' V5001 R-251 2
Bushing
Ci
Size
1"x314'
Part Number
V5018-131
Box 11
100
1-1/4" x 3/4" V5018-167 25
1-1/4" x 1' V5018-168 25
1-1/2" x 3/4" V5018-210 5
1-1/2" x 1" V5018-211 25
1-1/2" x 1-1/4' V5018-212 25
2" x 3/4" V5018-248 2
2" x 1" V5018-249 2
Size Part Number Box Qty.
Bushing (continued)
2" x 1-1/4" V5018-250 2
x 1-1/2' V5018-251 2
2-1/2" x 1-1/4" V5018-290 1
2-1/2" x 1-1/2" V5018-291 1
2-1/2" x 2" V5018-292 1
3" x 2" V5018-338
x 2-1/2" V5018-339 1
Cap Size
3/4"
Part Number
V5017-007
Box Qty
250
1" V5017-010 100
1-1/4" V5017-012 5
1-1/2" V5017-015 5
Size I Part Number —1 Box Qty.
Cap (continued)
V5017-020 2
2-1/2" V5017-025
V5017-030 1
www.vikinggroupinc.com
Sprinkler Head Adapters
BRASTIC° Sprinkler -- •PailiF Number IBox !11'j
Head Adapter
II
3/4" x 1/2" V5003SBT-101 100
1" x 1/2" V5003SBT-130 50
Brass starter thread molded into plastic, virtually eliminating cross-threading.
Female Sprinkler Head Size Part Number Box Qty.
Adapter with Metal
Thread Insert 3/4" X 1/2" V50035B1101 100
CA
1" x 1/2" V5003SB1-130 50
1" x 3/4" V50035B1-131 10
Spigot Female Sprinkler Size Part NumberBox Qty
Head Adapter with Metal
Thread Insert 3/4" X 1/2" V500325B1-101 100
1" x 1/2" V50032S81-130 50
(j, I I
Sprinkler Head 90 with
Metal Thread Insert
QO
'IrA-
3/4" x 1/2"
Part Number
V50073SB1-101
Box Qty.
100
1" x 1/2" V500735B1-130 50
1" x 3/4" V500735B1-131 10
1-1/4" x 1/2" V500735B1-166 5
Sprinkler Head Tee with
Metal Thread Insert
lc~ij
'IrA'
lxi "xl"
Part Number
V50125B1-010
Box Qty.
50
3/4"0/4"xl/2" V50125B1-101 10
1"xl"xl/2" V50125B1-130 50
1-1/4"xl-1/4"xl/2" V50125B1-166 5
1-112"xi-1/2"xl/2" V5012SBI-209 5
2"x2"xl/2" V5012SBI-247 2
'IrA' Part Number I Box QtY.
Sprinkler Head Tee w/Metal Thread Inserts (continued)
1"x314"x112" V5012R5B1-124 10
1-1/4"xl"x112" V5012RSB1-156 5
1-1/2"xl-114"xl/2" V5012R5B1-199 5
2"xl-1/2"x112" V5012RSB1-237 2
1 x1/2 x1 V5014R5B1-122" 10
*Socket x FIPT x Socket
Sprinkler Head Back to ,,., Part Number Box I.'1I'1 Back Cross with Metal
Thread Insert 1x1"xl/2"x1/2" 1-1/8" V50353SBlS-130 1
-
lxl"xl/2"xl/2" 1-15/16" V50353SBlL-130 1
Back to Back Tee with Size Part Number Box Qty
Metal Threads Insert 112"xl/2"xl" 1-1/8" V5011335B1S-075 48
61 1 1/2"xl/2"xl" 1-15/16" V501133SB1L-075 48
Size •iTTiT I Box Ii11
Test Plug
1/2" V450-005 50
U
www.vikinggroupinc.com
Transition Fittings
Female Adapter with Size 1!?1I Box Qty. '' Part Box fIQty.
Metal Thread Insert 3/4" VS003BI-007 10 Female Adapter w/Metal Thread Inserts (continued)
1" V5003Bl-010 50 1-1/2" V5003B1-015 I c1iIIII? 1-1/4" V5003B1-012 5 2" V5003131-020 2
Spigot Female Adapter Size ITTT1 Box Qty. ii
with Metal Thread Insert 3/4W V50032B1-007 10
V50032B1-010 10
Male Adapter with Size Part Number Box Qty. - ir Part Number Box Qty.
Metal Thread Insert 3/4" V5004B1-007 10 Male Adapter w/Metal Thread Inserts (continued)
V5004Bl-010 10 1-1/2" V5004B1-015 F
1-1/4" V5004Bl-012 5 2" V5004B020 2
Grooved Coupling Size itii Box Qty. - 1 ipx I Part Number Box Qty.
Adapter 1-1/4" V5001 G-012 30 Grooved Coupling Adapter (continued)
1-1/2" V5001 G-015 25 2-1/2" V5001G-025 10
V5001 G-020 15 V5001 G-030 8
Standard Union
O(D
Size
3/4"
Part Number
V5033E-007
Box wj
1
1" V5033E-010 1
1-1/4" V5033E-012
1-1/2" V5033E-015 1
- ipx I Part Number I Box Qty.
Standard Union (continued)
V5033E-020 1
2-1/2" V5033E-025 1
V5033E-030 1
Accessories
Solvent Cement Size Part Number Box Qty Size Part Number J Box Qty
Quart V5097Q 12
Pint V5097P 12
Dauber Size Part Number Box Qty
Small V5093-S 100
Large V5093-L 100 77 Size Part Number Box Qty
Refer to manufacturer's DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions,
c®us <~> @ APPROVED www.vikinggroupinc.com
September 2010
No. 162
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: 12 Pacifi SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 1835 Buena Vista Way CITY: Carlsbad
PHONE: (951) 667-4220 x348 FAX NUMBER:
Largest Building (ft.2): 3 Sprinkled? YES Construction Type: new
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): Loker Ave E east of El Fuerte Street
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 75 PSI Hydrant Number (if applicable):new
Elevation of test: 157 Feet Main Size: 10 INCH
Pressure Zone: 330 Feet Date/Time of Test:
Pitot Tube Reading: PSI Corresponding Flow: GPM
Total Flow: 3.050 GPM Residual Pressure 43 PSI
At peak demand , this water system is capable of providing a fire flow discharge at 20 psi of 4,585 gpm. However, this
flow exceeds the District's maximum pipeline velocity of 10 fps. The maximum fire flow that meets both the velocity
and pressure criteria is 3,050 gpm. There was no specific request for fire flow from the Client or Fire Department.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
Name: JenniferR.Mael.P.E. Eng. Lic. No. (if applicable): C69606
Signature:________________________________
Title/Orgf1ect_Manager Date: 08/17/2018
I11. N
Project Site
Fire Flow Test
A \ \\ \\ \
Location (new hydrant)
Op
NK
#162 1835 Buena Vista Way - Fire Flow Analysis