Loading...
HomeMy WebLinkAbout4625 RED BLUFF PL; ; FA130037; PermitCity of Carlsbad Fire Alarm Permit Permit No: FA1 30037 Job Address: 4625 RED BLUFF PL Permit Type: FALARM Parcel No: 1683100600 Lot #: 0 Reference No.: Status: APPROVED Applied 6/4/2013 Approved: 6/12/2013 Issued: 6/12/2013 PC #: Inspector: Project Title: THE GODDARD SCHOOL INSTALL NEW ADDRESSABLE FIRE ALARM SYSTEM. LOCATE ALL COMPONENTS AS SHOWN ON FLOOR PLANS. MONITOR THE SPRINKLER VALVE TAMPER SWITCHES AND H20 FLOW SWITCHES SHOWN ON PLANS. Applicant: Owner: JJJ ENTERPRISES OHIMAN SANJEEV&SHALOO 533 S VINEWOOD ST 7040 AVENIDA ENCINAS #104-52 ESCONDIDO CA CARLSBAD CA 760-747-3050 Fees ($) Add'I Fees ($) Total ($) Balance ($) 286 0 286 0 The Goddard School Alarms Review Comments. Page 2 Review Comments The Goddard School Alarms, 4625 Red Bluff Place, Carlsbad, CA 1. There were minor errors in the voltage drop calculations: IC2, there was no information in the catalog data sheets for a weatherproof horn/strobe rated at 1 80cd. The value of 168 mA was used in the calculations. The demand maybe higher, and this can be verified during testing. IC3, the current demand shown for the STC15cd was 168 mA, while the actual is 61 mA. The calculation is worst case and no change is required. 2. IC3 is mislabeled in the riser diagram, this has been redlined, and no revision is required. We strongly recommend the following operational tests be performed once the system installation has been completed. A "power off' test, where the normal power supply is shut off, and the system is left to function on battery power alone for a period of 24 hours, at which time the system should still be functioning and operational. At the end of the end of the above test, prior to the primary power being restored, the system should be placed in an "alarm" condition for a period of not less than five minutes, during which time all notification appliances, including the off-station notification, are to function as designed. Once the two prior tests have been completed, the current level in the batteries should be checked, the primary power restored, and at the end of 48 hours the current level checked again to verify that the charging function of the panel is both operational, and able to recharge the batteries within the time period specified by NFPA-72. Once the test in item "c" has been completed, one of the leads to the battery should be disconnected, to determine that the system will provide notification of an "off-normal" power condition to the monitoring company. ,il\L- -.. \" J - p1 v' MPiISEs FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS The Goddard School 4625 Red Bluff Place Carlsbad, CA 92010 FIRE ALARM SYSTEM MATERIAL DATA SHEETS These plaits hac e been reviewed for anparccit cot iipliatice with the ciii clii applicable codes and standards tic circe III the urisdtciion. Tue owner or contractor ttta [11111/c tins eview cit support of ui application 101 a building erotic itch tile exptes. uridersiaccdicig liii this cci ccii in co is av relies Cs the owner cii ccititrtcctccr cit titeit pcotcssicinal cngtiteer or atcittieci icr sole respicttschtict\ for lull coitipltuttce with said codes and stattdards. including Ille bttilditcg code or icr an\ rcspicttsibtltv for uleiictenccee rricrs. icttttsstolts or cteicliizectce ill these plaits is tether or not toted in 011s review. l)ute. 3/1//3 Revtewer:,/ 13 RECOMMENI) APPROVAL Eg Ri-C(tNlN1ENl) Al'PR(\'Ai.. AS NOTl-l) The Goddard School 4625 Red Bluff Place Carlsbad, CA 92010 FIRE ALARM SYSTEM BILL OF MATERIALS NOTIFIER FIREWARDEN-100-2 ADDRESSABLE FIRE ALARM CONTROL PANEL CSFM# 7165-0028:0235 NOTIFIER N-ANN-80 REMOTE FIRE ALRM ANNUNCIATOR CSFM# 7120-0028:0240 NOTIFIER NP-100 ADDRESSABLE SMOKE DETECTOR CSFM# 7272-0028:0231 NOTIFIER NOT-BG-12LX MANUAL PULL STATION CSFM# 7150-0028:0199 NOTIFIER N-100P ADDRESSABLE MINI MODULE CSFM# 7300-0028:0230 WHEELOCK EXCEDER ST/C - CEILING MOUNTED STROBES CSFM# 7125-0785:0168 WHEELOCK EXCEDER HS/C - CEILING AND WALL MOUNTED HORN /STROBES CSFM# 7125-0785:0168 WHEELOCK ASWP-2475W - WALL MOUNTED WEATHERPROOF HORN/STROBE CSFM# 7125-0785:0131 DN-60602:A1 FireWarden-1 00-2(E) Rev 3 Intelligent Addressable FACP NOTIFIER Sy •S - - The Notifier FireWarden-100-2 Rev 3 (NFW2-100) with Version 5.0 firmware is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact intelligent addressable control panel has an extensive list of powerful features. The SLC (Signaling Line Circuit) of the FireWarden-100-2 Rev 3 operates using a Rapid Group Polling communication protocol technology that polls multiple devices simultaneously for a quicker device response time.This patented technology allows a fully-loaded panel with up to 198 devices to report an incident and activate the notification circuits in under 10 seconds. With this improved polling, devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. The 's quick-remove chassis protects the electronics during con- struction. The backbox can be installed allowing field wiring to be pulled. When construction is completed, the electronics can be quickly installed with just two bolts. New features for Rev 3 with Version 5.0 firmware include removable terminal blocks, improved transient protection, addi- tional secondary ANN-BUS, and increased power for the reset- table and remote sync outputs. Available accessories include ANN-BUS devices as well as ACS LED, graphic and LCD annunciators, and reverse polarity/city box transmitter. The integral DACT transmits system status (alarms, superviso- ries, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote and local pro- gramming of the control panel using the PS-Tools Upload/Down- load utility. In addition, the control panel may be programmed or interrogated off-site via the public switched telephone network. Any personal computer with Windows® XP or greater, a com- patible modem, and PS-Tools—the Upload/Download software kit—may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. The panel can also be programmed through the FACPs keypad or via a standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board. This permits easy typing of address labels and other programming information. Version 5.0 firmware supports the following: Primary and Sec- ondary ANN-bus devices, NP-Al 00, USB port, NAC circuit diag- nostics, a new report has been added to the walk-test that lists untested devices, new device types added: audio telephone type code for NFV-25/50ZST, Photo Supervisory and auto-reset- table Drill (non-latching). The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two dedicated business tele- phone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. NOTE: Unless otherwise specified, the term "Fire Warden-100-2" is used in this document to refer to both the Fire Warden- 100-2 and the Fire Warden-100-2E FACP5 (Fire Alarm Control Panels). Like- wise, "NFW2-100" refers to NFW2-100E as well. Features Listed to UL standard 864, 9th edition. On-board DACT. Remote site or local JSB port upload/download, using PS- Tools. Four (4) Style Y (Class B) NAC circuits, which can be con- verted to four (4) Style Z (Class A) circuits with optional ZNAC-92 converter module. (Up to 6.0 amps total NAC power wien using optional XRM-24B.) Selectatle strcbe synchronization for System Sensor, Whee- lock, and Gentex devices. Remote Acknowledge, Silence, Reset and Drill via address- able monitor modules or FCU-80, N-ANN-80 or Legacy ACS Annunciators. ANN-BUS for connection to following optional modules (cannot be used if ACS. annunciators are used): - N-ANN-80(-W) Remote LCD Annunciator - N-ANN-UO LED Driver - N-ANN-S/PG Printer Modle - N-At4N-RLY Relay Module - N-ANN-LED Annunciator Module - N-ANN-RLED Annunciator Module alarms only - ROME Relay Option Module Enclosure ACS & Terminal-mode Annunciators: - ACS Annunciators: Up to :32 Legacy CM Series annuncia- tors (ACM-16AT or ACM-32 series). Cannot be used if ANN-BUS devices are used. - Terminal-mode Annjnciators: Up to 32 Legacy FDU-80 annuncators. EIA-232 printer/PC imerface (variable baud rate) on main cir- cuit board, for use witna optional UL-listed printer PRN-6. Integra 80-character LCD display with backlighting. Real-time clock/calendar with automatic daylight savings control. Detecto senstivity test capability (NFPA 72 compliant). DN-60602:A1 • 12/07/2010—Page 1 of 6 History file with 1,000-event capacity. Maintenance alert warns when smoke detector dust accumu- lation is excessive. Automatic device type-code verification. One person audible or silent walk test with walk-test log and printout. Point trouble identification. Waterflow (nonsilenceable) selection per monitor point. System alarm verification selection per detector point. PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant). NOTE: Only detectors may participate in PAS. SLC LOOP: SLC can be configured for NFPA Style 4, 6, or 7 operation. SLC supports up to 198 addressable devices per loop (99 detectors and 99 monitor, control, or relay modules). SLC loop maximum length 10,000 ft. (3,000 m.). See installation manual for wire tables. NOTIFICATION APPLIANCE CIRCUITS (NACS): Four onboard NACs with additional NAC capability using out- put control modules (NC-100). The four Class B NACs can be converted to four Class A NACs with optional ZNAC-92 converter module. Silence Inhibit and Auto Silence timer options. Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability. Selectable strobe synchronization per NAC. 2.5 amps maximum per each NAC circuit. NOTE: Maximum 24VDC system power output is shared among all NAC circuits and 24VDC special-application auxiliary power outputs. Total available output is 3.0 amps. Using the optional XRM-24B transformer increases 24VDC output to 6.0 amps. PROGRAMMING AND SOFTWARE: Autoprogram (learn mode) reduces installation time. Custom English labels (per point) may be manually entered or selected from an internal library file. Three Form-C relay outputs (two programmable). 99 software zones. Continuous fire protection during online programming at the front panel. Program Check automatically catches common errors not linked to any zone or input point. OFFLINE PROGRAMMING: Create the entire program in your office using a Windows®-based software package (NFW2-100 requires PS-Tools Programming software, avail- able on www.magni-fire.com). Upload/download system pro- gramming locally to the NFW2-100 Rev 3 in less than one minute. USB upload/download programming with standard Male-A to Male-B cable. User Interface LED INDICATORS AC Power (green) Fire Alarm (red) Supervisory (yellow) Alarm Silenced (yellow) System Trouble (yellow) Maintenance/P resign al (yellow) Disabled (yellow) Battery Fault (yellow) Ground Fault (yellow) KEYPAD CONTROLS Acknowledge/Step Alarm Silence Drill System Reset (lamp test) 16-key alpha-numeric pad (similar to telephone keypad) 4 cursor keys Enter Product Line Information NFW2-100: FireWarden-100-2 Rev 3 198-point addressable Fire Alarm Control Panel, one SLC loop. Includes 80-character LCD display, single printed circuit board mounted on chassis, and cabinet. 120 VAC operation. NFW2-1 OUR: Same as NFW2-100, except in a red backbox. NFW2-1 ODE: Same as NFW2-100, except with 240 VAC opera- tion. 4XTM Reverse Polarity Transmitter Module: Provides super- vised output for local energy municipal box transmitter, alarm, and trouble. ZNAC-92: Optional converter module which converts four (4) Style V (Class B) NAC circuits to four (4) Style Z (Class A) cir- cuits. PS Tools: Programming software for Windows®-based PC computer (cable not included), available on www.firelite.com. 1313-969213: Optional dress panel for FireWarden-100-2 Rev 3. TR-CE-B: Optional trim Ring for semi-flush mounting. BB-26: Battery backbox, holds up to two 26 AH batteries and CHG-75. NFS-LBB: Battery box, houses two 55 AH batteries. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. CHG-120: Remote battery charging system for lead-acid batter- ies with a rating of 55 to 120 AH. Requires additional NFS-LBB for mounting. NOTE: CHG-120 or CHG-75 required for batteries larger than 1BAH. BAT Series: Batteries, see data sheet DN-6933. XRM-24B(E): Optional transformer. Increases system power output to 6.0 amps. Use XRM-24BE with FireWarden-100-2E Rev 3. PRT/PK-CABLE: Cable printer/personal computer interface cable; required for printer or for local upload/download program- ming and updating panel firmware. PRN-6: UL listed compatible event printer. Uses tractor-fed paper. IPDACT-2/2UD, IPDACT Internet Monitoring Module: Mounts in bottom of enclosure with optional mounting kit (PN IPBRKT). Connects to primary and secondary DACT telephone output ports for internet communications over customer provided ether- net internet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static I P. (See data sheet DN-60408 for more information.) IPBRKT: Mounting kit for IPDACT-2/2UD in common enclosure. IPSPLT: V-adaptor option allows connection of both panel dialer outputs to one IPDACT-2/2UD cable input. COMPATIBLE ANNUNCIATORS N-ANN.80(-W): LCD Annunciator is a remote LCD annunciator that mimics the information displayed on the FACP LCD display. Recommended wire type is un-shielded. (Basic model is black; order -W version for white; see DN-7114.) Page 2 of 6— DN-60602:A1 • 12/07/2010 N-ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. Ships with red or black enclosure (see DN-60242). N-ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DN-60242). N-ANN-RLY: Relay Module, which can be mounted inside the cabinet, provides 10 programmable Form-C relays. (See ON- 7107.) ROME-B: Relay Option Module Enclosure (order ROME-13 for black or ROME for red). Provides one N-ANN-RLY Relay Mod- ule already installed. The ROME Series provides mounting space for one additional Relay Module or one addressable Multi- module. (See Installation Sheet PN 53530.) N-ANN-S/PG: Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. (See DN-7103.) N-ANN-I/O: LED Driver Module provides connections to a user supplied graphic annunciator. (See DN-7105.) ACM-8R: Relay module provides 8 Form-C 5.0 amp relays. ACM Annunciator Series: LED-type fire annunciators capable of providing up to 99 software zones of annunciation. Available in increments of 16 or 32 points to meet a variety of applications. LDM Graphic Series: Lamp Driver Module series for use with custom graphic annunciators. FDU-80 (Liquid Crystal Display) point annunciator: 80-char- acter, backlit LCD-type fire annunciators capable of displaying English-language text. NOTE: For more information on Compatible Annunciators for use with the Fire Warden-100-2 Rev 3, see the following data sheets (document numbers) ACM-SR (DN-3558), ACS/ACM Series (DN- 0524), LDM Series (DN-0551), FDU-80 (DN-6820). COMPATIBLE ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. NI-100: Addressable low-profile ionization smoke detector. NP-100: Addressable low-profile photoelectric smoke detector. NP-lOOT: Addressable low-profile photoelectric smoke detector with thermal sensor. NP-100R: Addressable remote test capable detector for use with DNR(W) duct smoke detector housings. NH-100: Fast-response, low-profile heat detector. NH-100R: Fast-response, low-profile heat detector with rate-of- rise option. NH-100H: Fixed high-temperature detector that activates at 190F/88C. NP-A100: Addressable low-profile multi-sensor detector. DNR: Innovair Flex low-flow non-relay duct-detector housing. Order NP-100R separately. DNRW: Innovair Flex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight. (Order NP-100R separately.) NMM-100: Addressable Monitor Module for one zone of nor- mally-open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B (Class B) or Style D (Class A) IDC. NDM-100: Dual Monitor Module. Same as NMM-100 except it provides two Style B (Class B) only lDCs. NMM-100P: Miniature version of NMM-100. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. NZM-100: Similar to NMM-100, but may monitor up to 20 con- ventional two-wire detectors. Requires resettable 24 VDC power. Consult factory for compatible smoke detectors. NC-100: Addressable Control Module for one Style Y/Z (Class B/A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance Circuit option requires external 24 VDC to power noti- fication appliances. NC-100R: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMBSOO. NOT-BG12LX: Addressable manual pull station with interface module mounted inside. N100-ISO: Fault Isolator Module. This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 oper- ation). SMB500: Used to mount all modules except the NMM-100P. NMM-100-10: Ten-input monitor module. Mount one or two modules in a BB-XP cabinet (optional). Mount up to six modules on a CHS-6 chassis in a 1313-25. NZM-100-6: Six-zone interface module for compatible conven- tional two-wire detectors. Mount one or two modules in a BB-XP cabinet (optional). Mount up to six modules on a CHS-6 chassis in a 1313-25. NOTE: For more information on Compatible Addressable Devices for use with the Fire Warden-100-2 Rev 3, see the following data sheets (document numbers): N100-ISO (DN-6994), NP-100 series (DN-6995), NI-100 (DN-6996), NH-100 series (DN-6997), ND-100 series (DN-7006), NP-A100 (DN-6998), NMM-IOOINMM-100P/ NDM-100/NZM-100 (DN-6999), NC-100/NC-I0OR (DN-7000), NOT-BGI2LX (DN-7001), NMM-100-10 (DN-6990), and NZM- 100-6 (DN-60150). Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Wire size should be no smaller than 18 AWG (0.78 mm2) and no larger than 12 AWG (3.1 mm2). The wire size depends on the length of the SLC circuit. Refer to the panel manual for wiring details. DN-60602:A1 • 12/07/2010 - Page 3 of 6 EIA-232 INTERFACE (PIM-24) built into the motherboard FireWarden-100-2 Rev 3 Fire Alarm Control/ Communicator ANN-BUS or ANN-BUS DEVICES EIA-485 N-ANN-80, N-ANN-LED, in ACS mode N-ANN-S/PG, N-ANN-I/O (two wires) 4........ NOTE: System can use either ANN-BUS devices OR ACS-mode annunciators. They cannot be used simultaneously. —* L u-1U SMOKE DETECTORS NP-100, NP-100T, NI-100, NP-A100 —+ L HEAT DETECTORS NH-100, NH-100R, NH-100H N] DUCT DETECTORS ND-1100, ND-100R, DNR —+:, MONITOR/CONTROL NMM-100, NZM-100, NDM-100, N100-ISO, NC-100, NC-100R 0 — 11111 I'll' ADDR ABLE MULTI-MODULE NZM-100-6, NMM-100-10 Optional REVERSE POLARITY/ CITY BOX OUTPUT (4XTM) 8 FORM-C, 5-AMP RELAYS (optional, order ACM-BR) NACs (Notification Appliance Circuits) BELLS, SIGNALS, STROBES EIA-485 INTERFACE (four wires) NOTE: System can use either the printer OR the FDU-80. They cannot be used simultaneously. 24 VDC MINI-MONITOR NMM-1 OOP 0 CD CD CD FDU-80 Up to 6,000 ft. (1825.8 m) between each FDU-80 in the EIA-485 loop, and between each FDU-80 and the FACP. PULL STATION NOT-BG12LX Page 4 of 6— DN-60602:A1 • 12/07/2010 SYSTEM SPECIFICATIONS System Capacity Intelligent Signalling Line Circuits.........................................1 Addressable device capacity ............................................198 Programmable software zones ...........................................99 ACS Annunciators ..............................................................32 ANN-bus devices................................................................16 Electrical Specifications AC Power: FireWarden-100-2 Rev 3: 120 VAC, 60 Hz, 3.0 amps. FireWarden-100-2 Rev 3(E): 240 VAC, 50 Hz, 1.5 amps. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Battery charger capacity: 7 AH - 18 AH batteries. Up to two 18 Ah batteries can be housed in the FACP cabinet. Larger batter- ies require an external battery charger such as the CHG-75 or CHG-120, and a separate battery cabinet such as the BB-26 or NFS-LBB. Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Each terminal block provides connections for two Style V (Class B) for a total of four Style V (Class B) or with an optional ZNAC-92 module converts to four Style Z (Class A) NACs. Maximum signaling current per circuit: 2.5 amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL listed) for Style V (Class B) NAC. Refer to panel documenta- tion and Notifier Device Compatibility Document for listed com- patible devices. Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). Form-C relays. Special Application Non-resettable Power (24 VDC Nomi- nal): Jumper selectable (JP4) for conversion to resettable power output. Up to 1.0 amp total DC current available from each out- put. Power-limited. Special Application Resettable Power (24 VDC nominal): Jumper selectable (JP6) for conversion to non-resettable power. Up to 1.0 amp total DC current available. Refer to the Notifier Device Compatibility Document for listed compatible devices. Remote Sync Output: Remote power supply synchronization output. Nominal special application power: 24 VDC. Maximum current: 300 mA. End-of-Line Resistor: 4.7K ohm. Output linked to NAC 1 control. Supervised and power-limited. Telephone Interface: Unless used with Teldat VISORALARM, requires dedicated business telephone number with a minimum of 5 volts DC (off-hook voltage). Obtain dedicated phone line directly from your local phone company. Do not use shared phone lines or PBX (digital) type phone line extensions. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.12' (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.20 (13.34 cm.) deep. Trim Ring (TA-CE- B): 22.00 (55.88 cm.) high x 19.65 (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00' (50.80 cm.) high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 - 49°C/32 - 120°F and at a relative humidity 93% ± 2% RH (non- condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic compo- nents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 - 27°C/60 - 80°F. NFPA Standards The FireWarden-100-2 Rev 3 complies with the following NFPA 72 Fire Alarm Systems requirements: - LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). - AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTM). - REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTM is required.) - PROPRIETARY (Automatic, Manual, Waterflow and Sprin- kler Supervisory). - CENTRAL STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory). - OT, PSDN (Other Technologies, Packet-switched Data Net- work) Agency Listings and Approvals The listings and approvals below apply to the basic FireWarden- 100-2 Rev 3 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S635 FM approved CSFM: 7165-0028:0235 MEA: 120-06-E, Volume 2 For ULC-listed version, see DN-60600. NOTIFIER® is a registered trademark of Honeywell International Inc. Wheelock® is a registered trademark of and ExcederTM is a trademark of Cooper Notification. 02010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I so 000i This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. ffTTqr?b We cannot cover all specific applications or anticipate all requirements. tCINtINC I MMUFACTUMNG All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 6 of 6- DN-60602:A1 • 12/07/2010 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-0028:0235 Page 1 of I CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com DESIGN: Models Fire Warden 100 and *Fire Warden 100-2 addressable control units. Local, auxiliary, remote station, central station and proprietary (protected premise). This panel also can be used with NFV-25/50ZST (Fire Voice-251-50ZST) Zoned System Voice with Telephone for Emergency Voice evacuation Applications. Refer to listee's data sheet for detailed product description, operational considerations and required/optional accessories. When required, accessories shall be CSFM listed. RATING: 120 VAC, 60 Hz, 2.06 A Primary, 24 VDC Secondary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as an addressable fire alarm control panel for use with separately listed compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual for details. This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. This control unit meets the requirements of UL Standard 864, 9th Edition. NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. XLF: 7165-0075:0208 *Rev. 08-17-09 fm TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division dn-71 14:c • A1-65 N-ANN-80 NOTU Fl ER® 80-Character LCD Serial Annunciator by Honeywell General The N-ANN-SO annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi- tions. The N-ANN-80 and the FACP communicate over a two- wire serial interface employing the ANN-BUS communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. N-ANN-80 is black; for white order N-ANN-80-W. The N-ANN-80 displays English-language text of system point information including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes con- trol switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.) Up to eight N-ANN-805 may be connected to the ANN-BUS of each FACP. Minimal programming is required, which saves time during system commissioning. The N-ANN-80 is compatible with NOTIFIER FACPs with an ANN-BUS, such as the NFW-50. Features Listed to UL Standard 864, 9th Edition. Backlit 80-character LCD display (20 characters x 4 lines). Mimics all display information from the host panel. Control switches for System Acknowledge, Signal Silence, Drill, and Reset. Control switches can be independently enabled or disabled at the FACP. Keyswitch enables/disables control switches and mechani- cally locks annunciator enclosure Keyswitch can be enabled or disabled at the FACP. Enclosure supervised for tamper. System status LEDs for AC Power, Alarm, Trouble, Supervi- sory, and Alarm Silence. Local sounder can be enabled or disabled at the FACP. N-ANN-80 connects to the ANN-BUS terminal on the FACP and requires minimal panel programming. Displays device type identifiers, individual point alarm, trou- ble, supervisory, zone, and custom alpha labels. Time-and date display field. Surface mount directly to wall or to single, double, or 4" square electrical box. Semi-flush mount to single, double, or 4" square electrical box. Use ANN-SB80KlT for angled view mounting. Can be remotely located up to 6,000 feet (1,800 m) from the panel. Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs. May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC). Up to eight N-ANN-805 can be connected on the ANN-BUS. Controls and Indicators AC Power Alarm Trouble Supervisory Alarm Silenced Specifications Operating voltage range: 18 VDC to 28 VDC. Current consumption © 24 VDC nominal (filtered and non- resettable): 40 mA maximum. Ambient temperature: 32°F to 120°F (0°C to 49°C). Relative humidity: 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). 5.375" (13.65 cm.) high x 6.875" (17.46 cm.) wide x 1.375" (3.49 cm.) deep. For use indoors in a dry location. All connections are power-limited and supervised. Agency Listings and Approvals The listings and approvals below apply to the N-ANN-80. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S635 FM approved CSFM: 7120-0028:240 MEA: 442-06-E Vol. 2 The ANN-BUS POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY The ANN-BUS can be powered by an auxiliary power supply when the maximum number of ANN-BUS devices exceeds the ANN-BUS power requirements. See the FACP manual for more information. dn-71 14:c • 5/22/09 - Page 1 of 2 ANN-BUS DEVICE ADDRESSING Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the FACP. A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. See the FACP manual for more information. WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT The N-ANN-80 connects to the FACP ANN-BUS communica- tions circuit. To determine the type of wire and the maximum wir- ing distance that can be used with FACP ANN-BUS accessory modules, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. NOTE: For total worst case current draw on a single ANN-BUS refer to appropriate FACP manual. After calculating the total worst case current draw, the following table specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is lim- ited by resistance, but for heavier wire gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*) Maxi- mum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. See table below. WIRE REQUIREMENTS: POWER CIRCUIT 14 to 18 AWG (0.75 -2.08 mm2) wire for 24 VDC power cir- cuit is acceptable. All connections are power-limited and supervised. A maximum of eight N-ANN-80 modules may be connected to this circuit. Communication Pair Wiring Distance: FACP to Last ANN-BUS Module Total Worst Case 22 Gauge Current Draw (amps) 18 Gauge 16 Gauge 14 Gauge 0.100 1,852 ft. 4,688 ft. 6,000 ft. *6,000 ft. 0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft. 0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft. 0.400 463 ft. 1,172ft. 1,866 ft. 2,953 ft. 0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft. 0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft. 0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft. 0.800 231 ft. 586 ft. 933 ft. 1,476 ft. 0.900 206 ft. 521 ft. 829 ft. 1,312 ft. 1.000 (max.) 185 ft. 469 ft. 746 ft. 1,181 ft. WIRING CONFIGURATION The following figure illustrates the wiring between the FACP and ANN-BUS devices. ANN-BUS and power wiring are supervised W21 __ and power-limited. TBI ORDERING OPTIONS: N-ANN-80: Black 80 character LCD Annunciator. N-ANN-80-W: White, 80 character LCD Annunciator. ANN-SB80KIT-B: Black surface mount backbox with angled wedge. ANN-SB80KIT-W: White surface mount backbox with angled wedge. FACP Wiring to ANN-BUS Device ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Iso 9001 K31=1=1 ENSINEEMNS III MRNDM11JHINt QUALITY SYSTEMS Page 2 of 2— dn-71 14:c • 5/22/09 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203)484-7161, FAX: (203) 484-7118. www.notifier.com Made in the U.S. A. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7120-0028:0240 Page 1 of 1 CATEGORY: 7120--ANNUNCIATORS LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com DESIGN: Model N-ANN-80 remote fire annunciator. Unit is a 80-character, supervised backlit LCD fire annunciator. Communication between the control panel and the annunciator is accomplished over a two-wire serial interface employing the ANN-BUS protocol. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product number, electrical rating and UL label. APPROVAL: Listed as an annunciator for use separately listed compatible fire alarm control units. Refer to manufacturer's installation manual for details. XLF: 7120-0075:0211 10-03-06 jw TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division NP-100(A), NP-I OOT(A), dn-6995:b.A1-320 NP-I OOR(A) NOTI Fl ER® Addressable Photoelectric Detectors (0 for the FireWarden Series by Honeywell General The NP-100 and NP-100T addressable, low-profile plug-in photoelectric detectors use a state-of-the-art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with NOTIFIER's FireWar- den Series (FireWarden-100-2 and FireWarden-50) Address- able Fire Alarm Control Panels (FACP5). The NP-100T adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annun- ciator capability is available as an optional accessory (P/N RA100Z(A)). The NP-i OOR is a remote test capable detector for use with DNR(W) duct smoke detector housings. Features SLC loop: Two-wire loop connection. Unit uses base for wiring. Addressing: Addressable by device. Direct Decade entry of address: 01 - 99 with FireWarden- 100-2, and 01 —50 with FireWarden-50. Architecture: Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires. Sleek, low-profile design. Integral communications and built-in type identification. Built-in tamper-resistant feature. Removable cover and insect-resistant screen for simple field cleaning. Operation: Withstands air velocities up to 4,000 feet-per-minute (20 m/ sec.) without triggering a false alarm. Factory preset at 1.5% nominal sensitivity for panel alarm threshold level. Visible LED 'blinks" when the unit is addressed (communi- cating with the fire panel) and latches on in alarm. Mechanicals: Sealed against back pressure. Direct surface mounting or electrical box mounting. Mounts to: single-gang box, 3.5° (8.89 cm) or 4.0" (10.16 cm) octagonal box, or 4.0° (10.16 cm) square electrical box (using a plaster ring - included). Other system features: Fully coated circuit boards and superior RF/transient pro- tection. 94-VO plastic flammability rating. Low standby current. Options: Remote LED output connection (P/N RA100Z). NP-1 00 with B7IOLP base NP-lOOT with 671 OLP base Applications Use photoelectric detectors in life-safety applications to pro- vide a broad range of fire-sensing capability, especially where smoldering fires are anticipated. Ionization detectors are often better than photoelectric detectors at sensing fast, flaming fires. Construction These detectors are constructed of off-white LEXAN®. NP-100(T) plug-in, low-profile smoke detectors are designed to commercial standards and offer an attractive appearance. Installation NP-100(T) plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base on box which is at least 1.5 inches (3.81 cm) deep. Suitable boxes include: 4.0° (10.16 cm) square box with plaster ring. 4.0° (10.16 cm) octagonal box. 3.5° (8.89 cm) octagonal box. Single-gang box. NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 (Class B) wiring. NP-100R mounts in a DNR(W) duct detector housing. dn-6995:b • 3/12/10 - Page 1 of 2 Operation Each NP-100/T/R uses one of 99 possible addresses on the FireWarden-100-2 and one of 50 possible addresses on the FireWarden-50 Signaling Line Circuit (SLC). It responds to regular polls from the system and reports its type and status. The NP-100fTIR addressable photoelectric sensors unique unipolar chamber responds quickly and uniformly to a broad range of smoke conditions and can withstand wind gusts up to 4,000 feet-per-minute (20 rn/sec.) without sending an alarm level signal. Because of its unipolar chamber, the NP-100/T/R is approximately two times more responsive than most photo- electric sensors. This makes it a more stable detector. Detector Sensitivity Test Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/connected to a FireWarden-100-2 or FireWar- den-50 addressable fire alarm control panel. The results of the sensitivity test can be printed off the FireWarden-100-2 or Fire- Warden-50 for record keeping. Specification Voltage range: 15 -32 VDC (peak). Standby current: 300 pA @ 24 VDC. LED current: 6.5 mA © 24 VDC (latched "ON"). Air velocity: 4,000 ft/mm. (20 rn/sec.) maximum. Diameter: 6.1° (115.5 cm) installed in B71OLP base. Height: 2.1° (5.33 cm) installed in B71OLP base. Weight: 3.6 oz. (102 g). Operating temperature range: for NP-100: 0°C to 49°C (32°F to 120°F); for NP-100T. 0°C to 38°C (32°F to 100°F). NP-IOOR: installed in a DNR(W) -20°C to 70°C (-4°F to 1580F). Temperature: 0°C - 49°C (32°F - 120°F). Relative humidity: 10% - 93%, non-condensing. Listings Listings and approvals below apply to the NP-100 and NP- 100T detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL Listed, file S1115. CSFM approved: file 7272-0028:231. MEA approved: file 243-02-E Vol. 2. Maryland State Fire Marshal: permit 2173. FM approved. Product Line Information NP-100: Adressable photoelectric detector; B71OLP base included. NP-i OOA: Sames as NP-100 with ULC Listing (B710LPA base included). NP-lOOT: Same as NP-100 but with thermal element; B71OLP base included. NP-100TA: Same as NP-100T with ULC Listing (B710LPAbase included). NP-100R: Remote test capable addressable photoelectric detector for use with a DNR(W) duct detector housing. B71OLP: Plug-in detector base. Dimensions: 6.1' (15.5 cm). Mounting: 4.0° (10.16 cm) square box with or without plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm) octagonal box, or single-gang box. All mounting boxes have a minimum depth of 1.5" (3.81 cm). B224RB: Plug-in System Sensor relay detector base. Diame- ter: 6.2° (15.75 cm). Mounting: 4.0° (10.16 cm) square box with or without plaster ring, 4.0" (10.16 cm) octagonal box, or 3.5" (8.89 cm) octagonal box. All mounting boxes have a mini- mum depth of 1.5° (3.81 cm). B224B1: Plug-in System Sensor isolator detector base. Maxi- mum 25 devices between isolator bases (see DN-6994). Diameter: 6.2° (15.75 cm). Mounting: 4.0° (10.16 cm) square box with or without plaster ring, 4.0" (10.16 cm) octagonal box, or 3.5° (8.89 cm) octagonal box. All mounting boxes have a minimum depth of 1.5" (3.81 cm). B200SR: Sounder base capable of producing temporal-3 or steady sound output. ACCESSORIES: RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501 and B71OLP bases only. SMK400E: Surface mounting kit provides for entry of surface wiring conduit. For use with B501 base only. RMK400: Recessed mounting kit. For use with B501 base only. M02-04-00:Test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applications. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections. T55-127-010:Detector removal tool without pole. BCK-200B: Black detector covers, box of 10. WCK-200B: White detector covers, box of 10. NOTIFIER® is a registered trademark of Honeywell International Inc. Bayblend® is a registered trademark of Bayer Corporation. ©2008 by Honeywell International Inc. All rights reserved, unauthorized use of this document is strictly prohibited. Iso 9001 :b dl U .1 INGINIOUNI S MANSFACIURINC QUALITY SYSTEMS Page 2 of 2- dn-6995:b • 3/12/10 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION ... OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM . LISTING SERVICE LISTING No. 7272-0028:0231 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyevhoneywell.com DESIGN: Models NP-100, NP100R* and NP-100T photoelectric type smoke detectors. Model NP-100T has a 135°F supplement integral heat sensor which only assists in a fire situation. The purpose of this thermal circuitry is to increase the sensitivity of the detector. This thermal circuitry is NOT approved for use as a heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 24VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm control units and bases. All models are suitable for open areas and inside duct installations with air velocities between 0 - 4000 FPM. *Models NP-100 and NP-100R are also approved for installations inside Notifier duct detector housing ND-200 (OSFM Listing No. 3242-0028:236) and System Sensor duct detector housing DNRW (OSFM Listing No. 3242-1653:210). Refer tolistee's Installation Instruction Manual for details. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires, which smolder for hours before bursting into flames. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. XLF: 7272-0075:0194 *Rev. 01-27-10 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division DN-7001:D • Al -380 V4~NCOT I F I ER ell dreafe 911157 General NOT-BGI 2LX Addressable Manual Pull Station The Notifier NOT-BG12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for FireWarden series intelligent control panels, and the NSP-25 panel. Because the NOT-BG12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features Maintenance personnel can open station for inspection and address setting without causing an alarm condition. Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. Handle latches in down position and the word "ACTIVATED" appears to clearly indicate the station has been operated. Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. Smooth dual-action design. Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. Highly visible. Attractive shape and textured finish. Key reset. Includes Braille text on station handle. Optional trim ring (BG12TR). Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications Shipping Weight: 9.6 oz. (272.15 g) Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. Maximum SLC standby current: 375 pA. Maximum SLC alarm current: 5 mA. Temperature Range: 32°F to 120°F (0°C to 49°C) Relative Humidity: 10% to 93% (noncondensing) For use indoors in a dry location Installation The NOT-BG12LX will mount semi-flush into a single-gang, double-gang, or standard 4° (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O sur- face backbox. If the NOT-BG12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The NOT-BGI2LX Addressable Manual Pull Station The BG12TR is usually needed for semi-flush mounting with 4° (10.16 cm)or double-gang boxas (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down!activated position. Once latched, the word "ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull tie door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 - 99 on NFW2-100/NFW2-100C, 1 —50 for N FW-50/N FW- 50C). Architectural/Engineering Specifications Manual Fire Alarm Stations si-all be non-coded, with a key- operated reset lock in order t1at they may be tested, and so designed tha after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall a:omatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructicns provided on the cover. The word FIRE shall appear on the front of the staticns in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting or matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or 4"(10.16 cm) square electrical box, and shall be installed DN-7001:1) • 4/13/2012 - Page 1 012 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information NOT-BG1 2LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17021: Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL/ULC Listed: S692 (listed for Canadian and non-Cana- dian applications). MEA: 67-02-E Vol. IV. CSFM: 7150-0028:0199. FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER® is registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I so 000i This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. BYRIIEMINC & MANUFACTUMNS All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203)484-7118. www.notifier.com Page 2 of 2— DN-7001 :D • 4/13/2012 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-0028:0199 Page 1 of 1 CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyev@honeywell.com DESIGN: Models NBG-12, NBG-125, NBG-12LR, NBG-12LRA, NBG-12LAO, NBG-12LAOB, NBG-12-LO, NBG-12L0B, NBG-12W, NBG-I2LW, NBG-12NC, NBG-12WP, NBG-I2LWP, NBG-12L, NBG-12LX, NBG-12LA, NBG-I2PS, NBG-12LSP, NBG-12LPS, NBG-12LPSP, NBG-12SP, NOT-BG12LX, NBG-12LXSP, NBG12LXBL* and NBG12LXP* fire alarm pull boxes. All units except Model NBG-12S are dual action pull stations. Models NBG-12LR and NBG-12LRA are intended for agent releasing device. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Models NBG-12WP, NBG-12LW, NBG-12W, NBG-12LWP, NBG-12LAO, NBG-12L0, NBG-12LAOB and NBG-12LOB are intended for outdoor use when installed with Models WBB, SB-I/O, or WP-10 back box. Refer to listee's Installation Instruction Manual for details. *These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and California amendments which the controls and operating mechanisms required to be operable at no more than 51b5. force with one hand and shall not require tight grasping, pinching, or twisting of the wrist. *Rev. 04-08-10 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division Monitor Modules DN-6999:C NMM-1 00(A), NMM-1 OOP(A), NOTIFIER N7M.lflfl1A1 nn,I NflM.lflfllftl ;.i;;;;i;; ie;i;;• Panels by Honeywell F - General Four different monitor modules are available for Notifier's Fire- Warden Series intelligent control panels for a variety of appli- cations. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (NZM-1 00(A)). NMM-100(A) is a standard-sized module (typically mounts to a 4° [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. NMM-100P(A) is a miniature monitor module a mere 1.3' (3.302 cm) H x 2.75° (6.985 cm) W x 0.5° (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the NMM-100P(A) to be mounted in a single-gang box behind the device it monitors. NZM-100(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. NDM-100(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (lDCs) at two separate, consecutive addresses in intelligent, two-wire systems. NMM-100(A) Monitor Module Built-in type identification automatically identifies this device as a monitor module to the control panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFl) immunity. SEMS screws with clamping plates for ease of wiring. Direct Decade entry of address: 01 - 99 on FireWarden- 100-2, 01 —50 on Fire Warden-50. LED flashes during normal operation and latches on steady to indicate alarm. The NMM-100(A) Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro- vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. NMM-100(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterfiow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. NMM-100(A) (Type II) NMM-100(A) OPERATION Each NMM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). NMM-100(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 350 pA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 40 ohms. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5° (11.43 cm) high x 4° (10.16 cm) wide x 1.25' (3.175 cm) deep. Mounts to a 4° (10.16 cm) square x 2.125° (5.398 cm) deep box. DN-6999:C • 10/06/2010 - Page 1 of 4 NMM.IOOP(A) Mini Monitor Module Built-in type identification automatically identifies this device as a monitor module to the panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. Tinned, stripped leads for ease of wiring. Direct Decade entry of address: 01 - 99 on FireWarden- 100-2, 01 —50 on FireWarden-50. 1415 0 1 _ ADDRESS I 0 1 U6 LOOP 9 7 8 76 10 TENS ONES II Iii- H I o!I liw Ol L) -ill h • -I lI-i w ca 110 • L 1I I The NMM-100P(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The NMM-100P(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- ing device circuit for normally-open-contact fire alarm and security devices. NMM-1 OOP(A) NMM-100P(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterfiow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the cir- cuit. NMM-100P(A) OPERATION Each NMM-100P(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). NMM-100P(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 pA, 1 communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 40 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 400 pA. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 491C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75 (6.985 cm) wide x 0.65 (1.651 cm) deep. Wire length: 6 (15.24 cm) minimum. NZM.1 00(A) Interface Module Supports compatible two-wire smoke detectors. Supervises IDC wiring and connection of external power source. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct Decade entry of address:, 01 - 99 on FireWarden- 100-2, 01 —50 on FireWarden-50. LED flashes during normal operation. LED latches steady to indicate alarm on command from control panel. The NZM-100(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (nor- mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni- tored must be UL compatible with the module. NZM-100(A) APPLICATIONS Use the NZM-100(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. NZM-100(A) OPERATION Each NZM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). NZM-100(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 ohms. Average operating current: 300 pA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4 (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4 (10.16 cm) square x 2.125 (5.398 cm) deep box. Page 2 of 4— DN-6999:C • 10/06/2010 NDM.100(A) Dual Monitor Module The NDM-100(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two- wire initiating device circuits (lDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel- controlled LED. NOTE: The NOM- 100(A) provides two Style B (Class B) IDC cir- cuits ONLY Style 0 (Class A) IDC circuits are NOT supported in any application. NDM-100(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 pA (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 pA EOL resistance: 47K ohms. Maximum SLC Wiring resistance: 40 Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5' (11.43 cm) high x 4° (10.16 cm) wide x 2.125" (5.398 cm) deep. NDM-100(A) AUTOMATIC ADDRESSING The NDM-100(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the NDM-100(A) is set to address "26", then it will automati- cally assign itself to addresses "26" and "27". NOTE: "Ones" addresses on the NDM-100(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: Avoid duplicating addresses on the system. Installation NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regu- lations. These modules are intended for power-limited wiring only. The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordi- nances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S635 ULC: S635 FM Approved CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM- 100); 7300-0028:0237 (NDM-100) MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); 227-03-E Vol. 3 (NDM-100) Product Line Information NOTE: "A" suffix indicates ULC-listed model. NMM-100(A): Monitor module. NMM-100P(A): Monitor module, miniature. NZM-100(A): Monitor module, two-wire detectors. NDM-100(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 52304. DN-6999:C • 10/06/2010 - Page 3 of 4 Notifier® and FireWarden® are registered trademarks and FireWatch is a trademark of Honeywell International Inc. @2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I S0 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. MCIRMING I MANUFACTUMNS All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203)484-7118. www.notifier.com Page 4 of 4— DN-6999:C • 10/06/2010 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0028:0230 Page 1 of 1 CATEGORY: 7300-- FIRE ALARM CONTROL UNITACCESSORIES/MISC. DEVICES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309 Email: vladimir.kireyevhoneywell.com DESIGN: Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-IOOR and NC-100 control modules; and *NzM.1006 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 15-32 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7300-0075:0185 08-23-11 rev. mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division Save up to 48% in current draw* - Up to 9 models now in I appliance - Save up to 14% cost of installation** up Sleek Modern Aesthetics Finger Slide Switches CA IF mw Voltage Test Points Multiple Voltages 3 Audible Settings 90, 95, 99 dB (j 8 Candela Settings Wall - 15/1575/30/75/95/110/135/185 Ceiling - 15/30/60/75/95/115/150/177 I Universal Mounting Base " Ceiling and Wall Mounts to 5 Backbox Types Q1 Environmentally Friendly Low Current Draw COOPER Notification EJOCEO~D_ ~ Finally, Design and Safety Meet... LL Ceiling EJ Description: The Wheelock ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. The Wheelock® ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM Series of wall and ceiling notification appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts. The Contact Cover also acts as a shunting device to allow pie-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed. The UMB allows for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra secure installation, while the ceiling models provide a captivated screw to prevent the screw from falling during installation. [cc-0im—patibilrity and Requirements - Synchronize using the Wheelock® Sync Modules or panels with built-in Wheelock® Patented Sync Protocol I - Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage - Strobes produce 1 flash per second over the "Regulated Voltage" range * Compared to competitive models *** Patented ** Compared to previous models NOTE: All CAUTIONS and WARNINGS are identified by the symboIà All warnings are printed in bold capital letters. A! WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range". All candela ratings represent minimum effective strobe intensity based on lJL Standard 1971. 'Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32"F to 120"F (O"C to 49"C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971). Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only). Low ACurrent Draw = Fewer.A'L] III !J .] I [* Strobe Ratings per UL Standard 1971 UL Max 24 VDC /24FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.2051 0.253 0.110 0.140 SIC 8.0-33.0 10.061 i 0.08510.103_0.135 0.163 0.182 0.205 0.253 10.1101 Horn Strobe Ratings per UL 1971 & UL 464 at 24 VDC • - - • • • -77- 24 VDC 12 VDC 77----- 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HSRegulated .-. 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 •• .•• i===• •• _• 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 10.073 0.087 0.128 0.139 0.163 1, 0.186 0.230 0.272 0.122 •• •••UL Max Current*' dBA•• •• 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 1 .226 0.2267- 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 - 0.1841 0.226 0.267 0.120 Horn Ratings per UL 464 - - Model Regulated Voltage Range VDC 99 dB 95 dB 90 dB HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 FIN 8.0-17.5 10.047 0.026 0.017 HNC 8.0-17.5 10.047 0.026 0.017 * UL max current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). For strobes the 1 UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. 1=Specification & Ordering Information I Strobe Sync W/ SM, Mounting Model DSM orCandela 12/24VDC* Options PS-6 & PS-8 HSR 15/1575/30/75/95/110/135/185 X X UMB** HSW 15/1575/30/75/95/110/135/185 X X UMB HSRC 15/30/60/75/95/115/150/177 X X UMB** HSWC 15/30/60175195/1151150/177 X X al UMB Strobes STR 15/1575/30/75/95/110/135/185 X X UMB** STW 15/1575/30/75/95/110/135/185 X X UMB** STRC 15/30/60/75/95/115/150/177 X X UMB** STWC 15/30/60/75/95/115/150/177 X X UMB** X UMB** :1.111 HNR X HNW X X UMB HNRC • X X UMB HNWC X X UMB** *12 VDC models feature 15 & 15/75 settings **UMB = Universal Mounting Base NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. Notification Architects and Engineers Specifications The notification appliances shall be Wheelock® ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W 2.19" D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock®'s SM, DSM Sync Modules, Wheelock® Power Supplies or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock® synchronization protocol. Wall Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM Ceiling Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder - Spec Sheet 10/10 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION WA dmakh OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-0785:0168 Page 1 of 1 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243 Contact: Tom Conover (941) 487-2336 Email: thomas.conover@cooperindustries.com DESIGN: Exceder Series: Models ST strobe, HS horn strobe and HN horn. Model ST is a synchronous and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an audible signal appliance. All units followed by R (red) or W (white). Additionally, a 'C' may be added for ceiling models and/or a -NR' may be added for non-resettable models. For non -NR models and optional 'S for silver fascia may be added*. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Electrical: 12 VDC/24VDC/FWR Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185 Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177 INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. All models are for indoor use and for wall mount only or ceiling mount only* MARKING: Listee's name, model number, electrical/candela rating, and UL label. APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when used with separately listed electrically compatible fire alarm control units. Refer to listee's Installation Instructions Manual for details. *Rev. 9-24-09 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct " operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWI1T, Deputy State Fire Marshal Fire Engineering Division COOPER Notification Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Strobes, RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories El Description: Designed for life safety, performance and reliability, Cooper All models may be synchronized using the Wheelock SM, DSM Wheelock's cost effective weatherpoof notification appliances Sync Modules, Wheelock Power Supplies or other manufacturers include: panels incorporating the Wheelock Patented Sync Protocol. The Weatherproof Appliances Series horn output of horn strobes can be independently controlled on 2-wire circuits using the Wheelock patented sync protocol. MTWP Strobes RSSWP horn strobe models are 4-wire appliances; the strobes can be Horn Strobes ASWP synchronized while the audible can be connected to a coded fire Horns AH-24WP, AH12WP alarm system or can be set to produce any of eight selectable Multitone Horn Strobes MTWP tones. Multitone Horns MT Speaker Strobes ET70WP Speakers ET-1010 Features: All strobe models are UL dual listed - meeting both UL1638 and UL1971 requirements. As dual listed appliances, these weatherproof strobes, horn strobes and speaker strobes are listed for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. With an extended temperature range of —31°F to 150°F (-40°C to 66°C), Wheelock weatherproof appliances meet or exceed UL outdoor test requirements for rain, humidity and corrosion resistance while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 strobe spacing tables (up to 185 candela for wall mounting and 177 candela for ceiling mounting). To enable weatherproof mounting, Cooper-Wheelock provides the industry's widest choice of mounting options for surface or unique semi-flush installation. Models are available for surface mounting to Wheelock weatherproof backboxes on walls or ceilings. The optional WP-KIT allows the weatherproof backboxes (lOB, WPBB or WPSBB) to be mounted to a recessed electrical box for concealed conduit installation. For semi-flush installation, the WPA° and WFPA* kits allow a customer to mount the weatherproof appliances to a recessed electrical box without the need for an external weatherproof backbox. See the Backboxes, Plates and Gaskets Table on page three of this document for a summarization of these mounting options and the required accessories. Approvals include: UL Standards 1971, 1638, 464 and 1480 California State Fire Marshal (CSFM) and New York City (MEA), Factory Mutual (FM) and Chicago (BFP). See agency approvals by model number on page two of this document Compliance with the following requirements: NFPA, UFC, ANSI 117. 1, OSHA Part 29, 1910.165, ADA Weatherproof with extended temperature range of —40°F to 150°F (-40°C to 66C)* Dual Listed strobe models (UL 1638 and UL 1971) Industry's highest strobe candela options Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol Models with field selectable tone, dBA and candela settings Wall or ceiling mounting options Surface of semi-flush mounting IN/OUT wiring termination accepting two #12-18 AWG wires at each terminal *The series RSSWP, ASWP, MTWP and ET70WP have UL approval down to -40F. TheAH-24WP, MT-12/24 and the ET-1010 have been ULC tested and approved to -40F, but not submitted to UL. The AH-12WP has UL/ULC approval to -31F. © META APPROVED * Patent Pending E5946 151-92-E 7125-0785.131 (ASWP) S5391 7125-0785:146 (ET70WP) S2652 7125-0785:156 (MTWP) 7300-0785:154 (RSSWP) NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at I flash per second minimum over their UL Listed Regulated Voltage Range. All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table. Wall Mount Ceiling Mount Wall or Ceiling Mount RSSWP MTWP L RSSWP MTWP MT AH ASWP ET70WP ASWP ET10WP ET-1010 Strobe Order Code Strobe Order Code RSSWP-2475W-FR Red 9013 RSSWP-2475C-FR Red 4338 Audible Order Code RSSWP-2475W-FW White 3034 RSSWP-2475C-FW White 4446 AH-24WP-R Red 7416 RSSWP-24MCWH-FR Red 5161 RSSWP-24MCCH-FR Red 5167 AH-12WP-R Red 7415 RSSWP-24MCWH-FW White 5165 RSSWP-24MCCH-FWWhite 5187 Audible Strobe Audible Strobe ASWP-2475W-FR Red 9012 ASWP-2475C-FR Red 4251 ASWP-24MCWH-FR Red 5137 ASWP-2475C-FW White 4502 ASWP-24MCWI-I-FW White 5140 ASWP-24MCCH-FR Red 5149 ASWP-24MCCH-FW White 5157 Multi-tone Strobe MTWP-2475W-FR Red 8420 Multi-tone Strobe MTWP-2475W-FW White 3112 MTWP-2475C-FR Red 4457 MTWP-24MCWI-I-FR Red 5132 MTWP-2475C-FW White 4478 MTWP-24MCWH-FW White 5134 MTWP-24MCCH-FR Red 5102 MTWP-24MCCH-FW White 5122 Speaker Strobe ET70WP-2475W-FR Red 9077 Speaker Strobe ET70WP-2475W-FW White 3179 ET70WP-2475C-FR Red 4452 ET70WP-24185W-FR Red 4885 ET70WP-2475C-FW White 4454 ET70WP-24185W-FW White 4891 ET70WP-24177C-FR Red 4845 ET70WP-24135W-FR Red 4872 ET70WP-24177C-FW White 4859 ET70WP-24135W-FW White 4875 ET70WP-24115C-FR Red 4550 ET70WP-24115C-FW White 4732 Candela Ratings Series UL 1971 UL 1638 @ 77°F UL 163 8 @ -40°F RSS, ET70WP and MTWP UL Max Current (Strobe Only) ASWP High Med Low 2475 30°° 180 115 0.138 0.168 0.155 0.150 135 135 56 0.300 0.355 0.340 0.335 MC WI-I 185 185 77 0.420 0.480 0.465 0.460 115 115 47 0.300 0.355 0.340 0.335 MCCH 177 177 73 0.420 0.480 1 0.465 0.460 24185 185 185 77 0.420 **Wall mount rating only 24177 177 177 73 0.420 UL Max. Current (Audible) MTWP/MT 24 VDC MT 12 VDC IBA HI STD HI STD Horn 0.108 0.044 0.177 0.034 Bell 0.053 0.024 0.095 0.020 March Time 0.104 0.038 0.142 0.034 Code 3 Horn 0.091 0.035 0.142 0.034 Code 3 Tone 0.075 0.035 0.105 0.021 Slow Whoop 0.098 0.037 0.142 0.035 Siren 0.104 1 0.036 10.152 0.030 Hi/Lo 1 0.057 1 0.025 10.1141 0.026 Horn MT-12/24-R Red 5023 Speaker ET-1010-R Red 3135 ET-1010-W White 3137 UL Max. Current AH 24 VDC 12 VDC High (99) dBA 0.080 0.192 Med (95) dBA 0.043 0.108 Low (90) dBA 0.021 0.058 UL Reverberant dBA@ 10 Feet VVatts 1/8 1/4 1/2 1 2 4 8 lET-101a 77 80 83 86 187 192 94 ET70WP 78 81 84 87 90 93 95 Model Number Agency Approvals Strobe UL MEA CSFM FM BFP RSSWP-2475 X X X X RSSWP-24MCWH X * X * * RSSWP-24MCCH X * X ° * Audible Strobe ASWP-2475 X X X X X ASWP-MCWI-I X * X * ASWP-MCCH X ° X * * Muititone Strobe MTWP-2475 X X X X MTWP-MCWH X * X * * MTWP-MCCH X * X * Horns/Audibles AH-24WP X X X - X AH-12WP X X X - X MT-12/24 X X X X X Speaker Strobe ET70WP-2475 X X X ° * ET70WP-185 X * X * * ET70WP-177 X * X * ET70WP-115 X * X * ET70WP-135 X * X ° * *pending Mounting Accessories WFP WFPA lOB WPSBB WPBB WBB Gasket Kit WP-KIT Flush Plates WFPA-R WFPA-W WFP-R WFP-W Backboxes IOB-R IOB-W WPSBB-R WPSBB-W WPBB-R WPBB-W WBB-R WBB-W Order Code 4486 Red 4698 White 4701 Red 4696 White 4697 Red 5046 White 5047 Red 9751 White 3033 Red 9014 White 4692 Red 2959 White 2960 Mounting Options: Backboxes, Plates, Gasket Kits Surface Mount Flush Mount Exposed Conduit Concealed Conduit RSSWP Strobes WPSBB WPSBB + WP-KIT WFP ET70WP Speaker Strobes lOB lOB + WP-KIT WFP ASWP Horn Strobes WPBB WPBB + WP-KIT WFPA AHWP Horns WBB - WFP ET-1010 Speakers WBB - WFP MTWP Multitone Horn Strobes lOB lOB + WP-KIT WFP Multitone Horn lOB lOB + WP-KIT WFP Wiring Diagrams SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED. UVILJ TO NEXTLI ECEDINGO +L] I REDO APPLIANCE I PLIANCED -D g V —DOR EOLREIBLACKO FACPU 0 4_ r_~_ STROEEO AUDIBLEO SERIES RSSWP, ASWP, AHWP, MTWP AND MT-12/24 APPLIANCES FROND +Li TO NEXTU PRECEDINGU APPLIANCE ORG 95T~ _[APPLIANCED OR EOLRD FACPL SERIES MTWP APPLIANCES SYNCHRONIZED STROBE OPERATION WITH CODED FACP MTWRO Moduleo NAC 910 -0 Oro 0 PowerD Lr FACPD NRC I Note: Strobe circuit requires constant voltage. SERIES RSSWP/ASWP APPLIANCES SYNCHRONIZED WI DSM MODULE SINGLE CLASS "A" NAC CIRCUIT D S MEl ST RO B ED +00 NACO SYNCO CIRCUITD OUTO I 0 OUT 10 I -0:+ IN 10 RSS 0-- I 0 N3 1 11 FAC PLO D 0 11 JDIBLE MINUS 20 ii + IN 20 RSS STROBED NACO 0+ OUT 20 CJRCUITD RETURNU Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Notification Cooper Notification is Wheelock* (MEDCJ SAFEPATH WAV ARCHITECTS AND ENGINEERS SPECIFICATIONS General Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using Wheelock mounting accessories. Weatherproof Strobes Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77°F shall be available. The strobes shall operate over an extended temperature range of —40°F to 150°F (-40°C to 66°C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. The horns shall have at least 3 sound level settings. Horn/Strobe combinations shall be able to be synchronized on a single NAC. Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. The audibles shall be able to be coded when operated on a separate NAC. Weatherproof Speakers and Speaker/Strobes Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480. All speakers shall provide field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET-1010. They shall be listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series ET70WP. They shall be available for surface or semi-flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA. Synchronization Modules When synchronization of strobes or temporal code-3 audibles is required, the appliances shall be compatible with the Wheelock Series SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes and audibles shall not drift out of synchronization at any time during operation. Series ASWP audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required. The strobes on Series MT multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC. Weatherproof Mounting Accessories Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings. Surface mounted appliances shall mount to Wheelock lOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit. For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock's WP-KIT to provide a weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance. AEPA4 WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9004 WP 11/09 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL _____ FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 1 ( LISTING No. 7125-0785:0131 Page 1 of 2 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243 Contact: Tom Conover (941) 487-2336 Email: thomas.conover@cooperindustries.com DESIGN: Models AS-1215,-2415,-1230,-2430,-121575,-241575,-2475 and -24110 audible/strobes for the hearing impaired followed by any three alpha/numeric characters indicating lens orientation, lettering and color. Models AS-1 215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W audible/strobes for the hearing impaired followed by any three alpha/numeric characters indicating lens orientation, lettering and color. These units with suffix -Ware for wall mount only. *Models AS-1 21575W and AS-241575W lens color may be white, red, blue, green, or amber. Models AS-2415C, -2430C, -2475C and -24100C audible/strobes for the hearing impaired followed by two alpha/numeric characters indicating lens lettering, orientation and color. These units are intended for ceiling mount only. Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or numeric character indicating product color. Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric character indicating lettering and product color. *Lens color may be white, red, blue, green, or amber. Models ASWP-2475W and *ASWP2475C audible/strobe with integral private mode fire/emergency visual signaling for non-hearing impaired applications. Lens color may be white, red, blue, green, and amber. Both models are suitable for outdoor use when mounted on the Model WPBB back box. Models AS-24MCWH, AS-24MCCH, *AS\/%JJ24MCWH and *ASWP24MCCH audible/strobes for the hearing impaired followed by two alpha/numeric characters indicating lens lettering and product color. Units with suffix CH are for ceiling mount only. Units with suffix WH are for wall mount only. *Lens color may be white, red, blue, green, or amber. Refer to the listee's data sheet for detailed product description and operational considerations. *Rev. 10-01-07 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division Listing No. 7125-0785:0131 Page 2 of 2 RATING: Electrical: 8-17.5/16-33 VDCNFWR Flash Rate: 60 flashes/minute Candela: 15:l5cd, 1575:15/75cd,30:30cd,75:75cd,95:95cd, 100: 100cd, 110: ll0cd MCW: Selectable 15cd, 30cd, 75cd, 110cd MCC: Selectable 15cd, 30cd,75cd,95cd MCWH: Selectable 135cd,185cd (65cd, 90cd at -40 C) MCCH: Selectable 115cd,177cd (50cd, 75cd at -40 C) INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W, ASWP-24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models ASWP-2475C, ASWP-24MCCH, AS-24MCCH, AND AS-24MCC are for ceiling mount only. Models with suffix -w or WH are for wall mount only. Models with suffix -C or -CH are for ceiling mount only. MARKING: Listee's name, model number, electrical/candela rating, and UL label. APPROVAL: Listed as audible and audible/visual signaling devices suitable for the hearing impaired when used in conjunction with separately listed electrically compatible fire alarm control units. For indoor use only except Models AH-12WP, AH-24WP, *ASwI2475w ASWP-2475C, ASWP-24MCWH, and ASWP-24MCCH audible appliances are suitable for indoor/outdoor. For synchronization, Models AS Series must be used with Model SM-12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 sync control module (CSFM Listing No. 7300-0785:132). Refer to listee's Installation Instruction Manual for details. These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. NOTE: Models AH-12, AH-24, -12WP and -24WP audible devices are not suitable for the hearing impaired applications. *Rev. 10-01-07 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2012 Listing Expires June 30, 2013 Authorized By: JASON DEWITT, Deputy State Fire Marshal Fire Engineering Division qll~`A3 M"a __!nA fA1oc3- F FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. PROPERTY INFORMATION Name of property: GODDARD SCHOOL Address: 4625 RED BLUFF PLACE, CARLSBAD, CA 92010 Description of property: PRESCHOOL Occupancy type: B, E Name of property representative: Address: Phone: Fax: E-mail: Authority having jurisdiction over this property: CARLSBAD F.D. Phone: Fax: E-mail: INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION Installation contractor for this equipment: JJJ ENTERPRISES Address: 533 S. VINEWOOD, ESCONDIDO, CA 92029 License or certification number: 582169 Phone: 760-747-3050 Fax: 760-747-7561 E-mail: INFO@JJJENT.COM Service organization for this equipment: Address: License or certification number: Phone: Fax: E-mail: A contract for test and inspection in accordance with NFPA standards is in effect as of: Contracted testing company: Address: Phone: Fax: E-mail: Contract expires: Contract number: Frequency of routine inspections: DESCRIPTION OF SYSTEM OR SERVICE Fire alarm system (nonvoice) F1 Fire alarm with in-building fire emergency voice alarm communication system (EVACS) Mass notification system (MNS) Combination system, with the following components: E] Fire alarm 0 EVACS 0 MNS 0 Two-way, in-building, emergency communication system Other (specify): NFPA 72, Fig. 10.18,2.1.1 (p. 1 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 3. DESCRIPTION OF SYSTEM OR SERVICE (continued) NFPA 72 edition: 2010 Additional description of system(s): 3.1 Control Unit Manufacturer: NOTIFIER Model number: NFW2 100 3.2 Mass Notification System Z This system does not incorporate an MNS 3.2.1 System Type: El In-building MNS—combination In-building MNS—stand-alone 0 Wide-area MNS 0 Distributed recipient MNS Other (specify): 3.2.2 System Features: Combination fire alarm/MNS 0 MNS autonomous control unit 0 Wide-area MNS to regional national alerting interface Local operating console (LOC) 0 Direct recipient MNS (DRMNS) 0 Wide-area MNS to DRMNS interface Wide-area MNS to high-power speaker array (HPSA) interface 0 In-building MNS to wide-area MNS interface El Other (specify): 3.3 System Documentation An owner's manual, a copy of the manufacturer's instructions, a written sequence of operation, and a copy of the numbered record drawings are stored on site. Location: FACP - 3.4 System Software This system does not have alterable site-specific software. Operating system (executive) software revision level: Site-specific software revision date: Revision completed by: O A copy of the site-specific software is stored on site. Location: 3.5 Off-Premises Signal Transmission 0 This system does not have off-premises transmission. Name of organization receiving alarm signals with phone numbers: Alarm: JJJENTERPRISES Phone: Supervisory: SAME Phone: Trouble: SAME Phone: Entity to which alarms are retransmitted: Phone: Method of retransmission: If Chapter 26, specify the means of transmission from the protected premises to the supervising station: If Chapter 27, specify the type of auxiliary alarm system: 0 Local energy 0 Shunt Z Wired 0 Wireless NFPA 72, Fig. 10.18.2.1.1 (p.20112) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 4. CIRCUITS AND PATHWAYS 4.1 Signaling Line Pathways 4.1.1 Pathways Class Designations and Survivability Pathways class: B Survivability level: 1 Quantity: (See NFPA 72, Sections 12.3 and 12.4) 4.1.2 Pathways Utilizing Two or More Media Quantity: Description: 4.1.3 Device Power Pathways No separate power pathways from the signaling line pathway Power pathways are separate but of the same pathway classification as the signaling line pathway El Power pathways are separate and different classification from the signaling line pathway 4.1.4 Isolation Modules Quantity: 4.2 Alarm Initiating Device Pathways 4.2.1 Pathways Class Designations and Survivability Pathways class: Survivability level: Quantity: (See NFPA 72, Sections 12.3 and 12.4) 4.2.2 Pathways Utilizing Two or More Media Quantity: Description: 4.2.3 Device Power Pathways 0 No separate power pathways from the initiating device pathway El Power pathways are separate but of the same pathway classification as the initiating device pathway Power pathways are separate and different classification from the initiating device pathway 4.3 Non-Voice Audible System Pathways 4.3.1 Pathways Class Designations and Survivability Pathways class: B Survivability level: 1 Quantity: 3 (See NFPA 72, Sections 12.3 and 12.4) 4.3.2 Pathways Utilizing Two or More Media Quantity: Description: 4.3.3 Appliance Power Pathways 0 No separate power pathways from the notification appliance pathway C] Power pathways are separate but of the same pathway classification as the notification appliance pathway El Power pathways are separate and different classification from the notification appliance pathway NFPA 72, Hg. 10.18.2,1.1 (p.3 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. S. ALARM INITIATING DEVICES 5.1 Manual Initiating Devices 5.1.1 Manual Fire Alarm Boxes Type and number of devices: Addressable: Other (specify): 5.1.2 Other Alarm Boxes Description: Type and number of devices: Addressable: Other (specify): 5.2 Automatic Initiating Devices 0 This system does not have manual fire alarm boxes. 1 Conventional: Coded: Transmitter: ED This system does not have other alarm boxes. Conventional: Coded: Transmitter: 5.2.1 Smoke Detectors 0 This system does not have smoke detectors. Type and number of devices: Addressable: 2 Conventional: Other (specify): Type of coverage: 0 Complete area 0 Partial area 0 Nonrequired partial area Other (specify): Type of smoke detector sensing technology: 0 Ionization 0 Photoelectric 0 Multicriteria 0 Aspirating 0 Beam Other (specify): 5.2.2 Duct Smoke Detectors This system does not have alarm-causing duct smoke detectors. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: Type of smoke detector sensing technology: 0 Ionization Z Photoelectric 0 Aspirating 0 Beam 5.2.3 Radiant Energy (Flame) Detectors Z This system does not have radiant energy detectors. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: 5.2.4 Gas Detectors Z This system does not have gas detectors. Type of detector(s): Number of devices: Addressable: Conventional: Type of coverage: 5.2.5 Heat Detectors This system does not have heat detectors. Type and number of devices: Addressable: Conventional: Type of coverage: 0 Complete area 0 Partial area 0 Nonrequired partial area 0 Linear 0 Spot Type of heat detector sensing technology: 0 Fixed temperature 0 Rate-of-rise 0 Rate compensated NFPA 72, Fig. 10,1821.1 (p.4 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. ALARM INITIATING DEVICES (continued) 5.2.6 Addressable Monitoring Modules 0 This system does not have monitoring modules. Number of devices: 2 5.2.7 Waterflow Alarm Devices 0 This system does not have waterfiow alarm devices. Type and number of devices: Addressable: 1 Conventional: Coded: Transmitter: 5.2.8 Alarm Verification Z This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds 5.2.9 Presignal This system does not incorporate pre-signal. Number of devices subject to presignal: Describe presignal functions: 5.2.10 Positive Alarm Sequence (PAS) This system does not incorporate PAS. Describe PAS: 5.2.11 Other Initiating Devices Z This system does not have other initiating devices. Describe: SUPERVISORY SIGNAL-INITIATING DEVICES 6.1 Sprinkler System Supervisory Devices 0 This system does not have sprinkler supervisory devices. Type and number of devices: Addressable: 1 Conventional: Coded: Transmitter: Other (specify): 6.2 Fire Pump Description and Supervisory Devices This system does not have a fire pump. Type fire pump: 0 Electric pump 0 Engine Type and number of devices: Addressable: Conventional: Coded: Transmitter: -. Other (specify): 6.2.1 Fire Pump Functions Supervised E] Power 0 Running 0 Phase reversal 0 Selector switch not in auto 0 Engine or control panel trouble 0 Low fuel Other (specify): 6.3 Duct Smoke Detectors (DSDs) 0 This system does not have DSDs causing supervisory signals. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: Type of smoke detector sensing technology: 0 Ionization 0 Photoelectric 0 Aspirating 0 Beam 6.4 Other Supervisory Devices 0 This system does not have other supervisory devices. Describe: NEPA 72, Fig. 10.18.2.1.1 (p.5 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 7. MONITORED SYSTEMS 7.1 Engine-Driven Generator Z This system does not have a generator. 7.1.1 Generator Functions Supervised Engine or control panel trouble 0 Generator running 0 Selector switch not in auto 0 Low fuel Other (specify): 7.2 Special Hazard Suppression Systems Z This system does not monitor special hazard systems. Description of special hazard system(s): 7.3 Other Monitoring Systems This system does not monitor other systems. Description of special hazard system(s): ANNUNCIATORS 0 This system does not have annunciators. 8.1 Location and Description of Annunciators Location 1: Location 2: Location 3: ALARM NOTIFICATION APPLIANCES 9.1 In-Building Fire Emergency Voice Alarm Communication System This system does not have an EVACS. Number of single voice alarm channels: Number of multiple voice alarm channels: Number of speakers: Number of speaker circuits: Location of amplification and sound-processing equipment: Location of paging microphone stations: Location 1: Location 2: Location 3: 9.2 Nonvoice Notification Appliances 0 This system does not have nonvoice notification appliances. Horns: 16 With visible: 16 Bells: With visible: Chimes: With visible: Visible only: 12 Other (describe): 9.3 Notification Appliance Power Extender Panels 0 This system does not have power extender panels. Quantity: Locations: NFPA 72, Fig. 10182.1.1 (p6of12) Copyright © 2009 National Fire Protection Association. This form maybe copied for individual use other than for resale. It may not be copied for commercial sale or distribution. MASS NOTIFICATION CONTROLS, APPLIANCES, AND CIRCUITS Z This system does not have an MNS 10.1 MNS Local Operating Consoles Location I: Location 2: Location 3: 10.2 High-Power Speaker Arrays Number of HPSA speaker initiation zones: Location 1: Location 2: Location 3: 10.3 Mass Notification Devices Combination fire alarm/MNS visible appliances: MNS-only visible appliances: Textual signs: Other (describe): Supervision class: 10.3.1 Special Hazard Notification El This system does not have special suppression predischarge notification. o MNS systems DO NOT override notification appliances required to provide special suppression predischarge notification. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS 11.1 Telephone System Z This system does not have a two-way telephone system. Number of telephone jacks installed: Number of warden stations installed: Number of telephone handsets stored on site: Type of telephone system installed: 0 Electrically powered 0 Sound powered 11.2 Two-Way Radio Communications Enhancement System 0 This system does not have a two-way radio communications enhancement system. Percentage of area covered by two-way radio service: Critical areas: % General building areas: % Amplification component locations: Inbound signal strength: dBm Outbound signal strength: dBm Donor antenna isolation is: dB above the signal booster gain Radio frequencies covered: Radio system monitor panel location: NFF'A 72, Fig. 10,18.21,1 (p. 7 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued) 11.3 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems E] This system does not have an area of refuge (area of rescue assistance) emergency communications system. Number of stations: Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: 11.4 Elevator Emergency Communications Systems E] This system does not have an elevator emergency communications system. Number of elevators with stations: Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: 11.5 Other Two-Way Communication Systems Describe: CONTROL FUNCTIONS This system activates the following control fuctions: Hold-open door releasing devices 0 Smoke management 0 HVAC shutdown 0 F/S dampers Door unlocking 0 Elevator recall 0 Fuel source shutdown 0 Extinguishing agent release O Elevator shunt trip 0 Mass notification system override of fire alarm notification appliances Other (specify): 12.1 Addressable Control Modules 0 This system does not have control modules. Number of devices: Other (specify): 13. SYSTEM POWER 13.1 Control Unit 13.1.1 Primary Power Input voltage of control panel: 120VAC Control panel amps: 3 Overcurrent protection: Type: INTERNAL FUSE Amps: Location (of primary supply panel board): MAIN ELECTRIC ROOM Disconnecting means location: BREAKER 13.1.2 Engine-Driven Generator Z This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: A/EPA 72, Fig. 1018.2.1.1 (p. 8 of 12) Copyright © 2009 National Fire Protection Association. This form maybe copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 13. SYSTEM POWER (continued) 13.1.3 Uninterruptible Power System Z This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): 13.1.4 Batteries Location: FACP Type: AGM Nominal voltage: 12 Amp/hour rating: 12 Calculated capacity of batteries to drive the system: In standby mode (hours): 24 In alarm mode (minutes): 5 Batteries are marked with date of manufacture 0 Battery calculations are attached 13.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System Z This system does not have an EVACS or MNS system. 13.2.1 Primary Power Input voltage of EVACS or MNS panel: EVACS or MI'JS panel amps: Overcurrent protection: Type: Amps: Location (of primary supply panel board): Disconnecting means location: 13.2.2 Engine-Driven Generator This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: 13.2.3 Uninterruptible Power System This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): 13.2.4 Batteries Location: Type: Nominal voltage: Amp/hour rating: Calculated capacity of batteries to drive the system: In standby mode (hours): In alarm mode (minutes): 0 Batteries are marked with date of manufacture 0 Battery calculations are attached NFPA 72, Fig. 10.182.1.1 (p.9 of 12) Copyright © 2009 National Fire Protection Association, This form maybe copied for individual use other than for resale. It may not be copied for commercial sale or distribution, SYSTEM POWER (continued) 13.3 Notification Appliance Power Extender Panels Z This system does not have power extender panels. 13.3.1 Primary Power Input voltage of power extender panel(s): Power extender panel amps: Overcurrent protection: Type: - Amps: Location (of primary supply panel board): Disconnecting means location: 13.3.2 Engine-Driven Generator Z This system does not have a generator. Location of generator: Location of fuel storage: Type of fuel: 13.3.3 Uninterruptible Power System Z This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): 13.3.4 Batteries Location: Type: Nominal voltage: Amp/hour rating: 7 Calculated capacity of batteries to drive the system: In standby mode (hours): - In alarm mode (minutes): Batteries are marked with date of manufacture 0 Battery calculations are attached RECORD OF SYSTEM INSTALLATION Fill out after all installation is complete and wiring has been checked for opens, shorts, ground faults, and improper branching, but before conducting operational acceptance tests. This is a: Z New system 0 Modification to an existing system Permit number: The system has been installed in accordance with the following requirements: (Note any or all that apply.) 0 NFPA 72, Edition: 2010 0 NFPA 70, National Electrical Code, Article 760, Edition: 2008 Manufacturer's published instructions Other (specify): System deviations from referenced NFPA standards: Signed: Printed name: JIM MCKINLEY Date: 9/12/13 Organization: JJJ Enterprises Title: PROJECT MGR Phone: 760-747-3050 NFPA 72, Fig. 1018.21.1 (p. 10 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 15. RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST 0 New system All operational features and functions of this system were tested by, or in the presence of the signer shown below, on the date shown below, and were found to be operating properly in accordance with the requirements for the following: Modifications to an existing system All newly modified operational features andfunctions of the system were tested by, or in the presence of the signer shown below, on the date shown below, and were found to be operating properly in accordance with the requirements of the following: 0 NFPA 72, Edition: 2010 0 NFPA 70, National Electrical Code, Article 760, Edition: 2008 0 Manufacturer's published instructions Other (specify): Individual device testing documentation [Inspection and Testing Form (Figure 14.6.2.4) is attached] Signed: Printed name: JIM MCKINLEY Date: Organization: JJJ Enterprises Title: PROJECT MGR Phone 16. CERTIFICATIONS AND APPROVALS 9/12/13 760-747-3050 16.1 System Installation Contractor: This system, as specified herein, has been installed and tested according to all NFPA standards cited herein. Signed: Printed name: JIM MCKINLEY Date: 9/12/13 Organization: JJJ Enterprises Title: PROJECT MGR Phone: 760-747-3050 16.2 System Service Contractor: The undersigned has a service contract for this system in effect as of the date shown below. Signed: Printed name: JIM MCKINLEY Date: 9/12/13 Organization: JJJ Enterprises Title: PROJECT MGR Phone: 760-747-3050 16.3 Supervising Station: This system, as specified herein, will be monitored according to all NFPA standards cited herein. Signed: Printed name: Date: Organization: Title: Phone: NFPA 72, Fig. 10.18.21i (p. 11 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale, It may not be copied for commercial sale or distribution. 16. CERTIFICATIONS AND APPROVALS (continued) 16.4 Property or Owner Representative: I accept this system as having been installed and tested to its specifications and all NFPA standards cited herein. Signed: Printed name: Date: Organization: Title: . Phone: 16.5 Authority Having Jurisdiction: I have witnessed a satisfactory acceptance test of this system and find it to be installed and operating properly in accordance with its approved plans and specifications, with its approved sequence of operations, and with all NFPA standards cited herein. Signed: - - Printed name: gt,lZ( L1 Date: I'I. '/. Organization: Title: J JQT/ Phone: 71e42' t669 NFPA 72, Fig. 10.182.1.1 (p.12 of 12) Copynght © 2009 National Fire Protection Association. This form maybe copied for individual use other than for resale. It may not be copied for commercial sale or distribution. All Act for 26201018 Goddard school.txt 09/12/13 All Activity Report 3 3 3 ENTERPRISES THE GODDARD SCHOOL P.O. BOX 463021 4625 RED BLUFF PLACE ESCONDIDO, CA 92046 ** FIRE SYS ** Page: 1 CARLSBAD, CA 92010 USA THE GODDARD SCHOOL 4625 RED BLUFF PLACE ** FIRE SYS ** CARLSBAD , CA 92010 USA Date Time Signal Account: 26201018 Dealer: 2620 From: 09/12/13 To: 09/12/13 Information Account: 26201018 09/12/13 THU 09/12/13 THU 08:35:00 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 08:35:03 SIGNAL RECEIVED: (R200 ) R200 162 00 RESTORE FIRE SUPERVISORY(RST) AREA 00 08:41:03 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 08:41:08 SIGNAL RECEIVED: (E602 ) E602 0 00 TIMER TEST AREA 00 08:46:04 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 Page 1 U All Act for 26201018 Goddard school.txt 08:46:05 SIGNAL RECEIVED: (E602 ) E602 0 00 TIMER TEST AREA 00 09:07:00 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:07:04 SIGNAL RECEIVED: (E111 ) Elli 2 00 FIRE-SMOKE DETECTOR ZONE 2 AREA 00 CASE NUMBER: 6991807 09:07:09 ALARM GIVEN TO OPR 09:07:10 CALLED CA CARLSBAD DIALED (858) 756-1126 CONTACTED GAVE BADGE NUMBER - LEAH AUTHORITIES CALLED AUTH INFO-FD 09:08:51 ADDED MESSAGES ADVISED TESTING AND WILL NOT RESPOND REFUSED THE CASE # 09:08:51 CALLED SCOTT DIALED (858) 449-7681 ANSWERING MACHINE-LEFT MESSAGE 09:10:18 ADDED MESSAGES NO RESPONSIBLES AVAILABLE 09:10:19 ALARM RESOLUTION NO FURTHER ACTION/COMPLETED 09:10:21 PRINTED ALARM TICKET 09:10:33 SIGNAL RECEIVED: (CALLS) CALLS 09/12/13 A 1 1 A C t i V i t y R e p o r t PAGE: 2 Date Time Signal Information Account: 26201018 09/12/13 THU SIM ID NUMBER 089014104255290611466 Page 2 All Act for 26201018 Goddard School .txt 09:10:36 SIGNAL RECEIVED: (Rill ) R111 2 00 RESTORE SMOKE AREA 00 09:10:39 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:10:41 SIGNAL RECEIVED: (E111 ) Elli 1 00 FIRE-SMOKE DETECTOR ZONE 1 AREA 00 CASE NUMBER: 7101810 > MULTIPLES/DUPLICATES RCVD 4/1 09:10:45 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:10:48 SIGNAL RECEIVED: (Rill ) R111 1 00 RESTORE SMOKE AREA 00 09:10:51 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:10:54 SIGNAL RECEIVED: (E200 ) E200 162 00 FIRE SUPERVISORY AREA 00 OS&Y TAMPER SWITCHES > THIS ALARM WAS HANDLED AS A MULTIPLE/DUPLICATE 09:10:59 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:10:59 ALARM GIVEN TO OPR 09:11:00 SIGNAL RECEIVED: (R200 ) R200 162 00 RESTORE FIRE SUPERVISORY(RST) AREA 00 09:11:04 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:07 SIGNAL RECEIVED: (E200 ) E200 162 00 FIRE SUPERVISORY AREA 00 OS&Y TAMPER SWITCHES > THIS ALARM WAS HANDLED AS A MULTIPLE/DUPLICATE 09:11:11 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:11 CALLED CA CARLSBAD DIALED (858) 756-1126 CONTACTED GAVE BADGE NUMBER - LIA Page 3 All Act for 26201018 Goddard school.txt AUTHORITIES CALLED AUTH INFO-FD 09:11:13 SIGNAL RECEIVED: (E351 ) E351 1 00 PRIMARY PHONE LINE FAILURE AREA 00 > THIS ALARM WAS HANDLED AS A MULTIPLE/DUPLICATE 09:11:17 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:18 SIGNAL RECEIVED: (R200 ) R200 162 00 RESTORE FIRE SUPERVISORY(RST) AREA 00 09:11:24 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:26 SIGNAL RECEIVED: (E311 ) E311 0 00 BATTERY MISSING AREA 00 > THIS ALARM WAS HANDLED AS A MULTIPLE/DUPLICATE 09:11:30 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:31 SIGNAL RECEIVED: (E352 ) E352 2 00 Ii 09/12/13 All Activity Report PAGE: 3 Date Time Signal Information Account: 26201018 09/12/13 THU SECONDARY PHONE LINE FAILURE AREA 00 > THIS ALARM WAS HANDLED AS A MULTIPLE/DUPLICATE 09:11:36 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:39 SIGNAL RECEIVED: (R311 ) R311 0 00 RESTORE BATTERY MISSING AREA 00 09:11:43 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 Page 4 All Act for 26201018 Goddard School .txt 09:11:45 SIGNAL RECEIVED: (R351 ) R351 1 00 PRIMARY PHONE LINE RESTORE AREA 00 09:11:48 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:11:51 SIGNAL RECEIVED: (R352 ) R352 2 00 SECONDARY PHONE LINE RESTORE AREA 00 09:12:28 ADDED MESSAGES FIRE DEPARTMENT NOTIFIED LIA ADVISED THEY ARE STILL TESTING AT PREM 09:12:30 CALLED SCOTT DIALED (858) 449-7681 SPOKE WITH SCOTT CONTACTED 09:12:33 ADDED MESSAGES BELATED ENTRY REVIEW HISTORY/NOTES PER INSTRUCTIONS:SIGNAL CALL LIST 09:13:33 ADDED MESSAGES ON HOLD 09:13:36 ADDED MESSAGES ADVISED SCOTT OF SIGNALS AND FD DISPATCH AND FD ADVISING OF THEM STILL TESTING 09:14:07 ALARM RESOLUTION NO FURTHER ACTION/COMPLETED 09:14:07 PRINTED ALARM TICKET 09:14:25 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:14:27 SIGNAL RECEIVED: (EllO ) E110 160 00 COMMERCIAL FIRE ALARM COMMERCIAL FIRE AREA 00 PULL CASE NUMBER: 7181814 PULL STATION-LOBBY (FIRE) 09:14:34 ALARM GIVEN TO OPR Page 5 All Act for 26201018 Goddard School .txt 09:14:35 CALLED CA CARLSBAD DIALED (858) 756-1126 CONTACTED GAVE BADGE NUMBER - LEAH AUTHORITIES CALLED AUTH INFO-FD 09:15:21 ADDED MESSAGES FIRE DEPARTMENT NOTIFIED TESTING 09:15:29 ALARM RESOLUTION NO FURTHER ACTION/COMPLETED El 09/12/13 All Activity Report PAGE: 4 Date Time Signal Information Account: 26201018 09/12/13 THU 09:15:29 PRINTED ALARM TICKET 09:18:00 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:18:02 SIGNAL RECEIVED: (Rib ) RhO 160 00 RESTORE FIRE ALARM AREA 00 PULL STATION-LOBBY (FIR PULL STATION-LOBBY (FIRE) 09:20:40 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:20:43 SIGNAL RECEIVED: (E110 ) E110 161 00 COMMERCIAL FIRE ALARM COMMERCIAL FIRE AREA 00 WATE CASE NUMBER: 7421820 WATERFLOW-RISER ROOM (FIRE) 09:21:18 ALARM GIVEN TO OPR 09:21:19 CALLED CA CARLSBAD DIALED (858) 756-1126. CONTACTED Page 6 All Act for 26201018 Goddard School.txt GAVE BADGE NUMBER - LEAH AUTHORITIES CALLED AUTH INFO-FD 09:21:33 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:21:34 SIGNAL RECEIVED: (RhO ) RhO 161 00 RESTORE FIRE ALARM AREA 00 WATERFLOW-RISER ROOM (F WATERFLOW-RISER ROOM (FIRE) 09:22:12 ADDED MESSAGES TESTING 09:22:14 ALARM RESOLUTION NO FURTHER ACTION/COMPLETED 09:22:14 PRINTED ALARM TICKET 09:22:33 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:22:36 SIGNAL RECEIVED: (E110 ) E110 161 00 COMMERCIAL FIRE ALARM COMMERCIAL FIRE AREA 00 WATE CASE NUMBER:7591822 WATERFLOW-RISER ROOM (FIRE) 09:22:57 SIGNAL RECEIVED: (CALLS) CALLS SIM ID NUMBER 089014104255290611466 09:22:59 SIGNAL RECEIVED: (Rib ) RhO 161 00 RESTORE FIRE ALARM AREA 00 WATERFLOW-RISER ROOM (F WATERFLOW-RISER ROOM (FIRE) 09:25:06 ALARM GIVEN TO OPR 09:25:18 CALLED CA CARLSBAD DIALED (858) 756-1126 CONTACTED GAVE BADGE NUMBER - BRITTANY AUTHORITIES CALLED AUTH INFO-FD 09:26:27 ADDED MESSAGES FIRE DEPARTMENT NOTIFIED Page 7 All Act for 26201018 Goddard School.txt BRITANY ADVISED THEY ARE STILL TESTING 09:26:29 CALLED SCOTT DIALED (858) 449-7681 ANSWERING MACHINE-LEFT MESSAGE Ii 09/12/13 A 1 1 A c t I V I t y R e p o r t PAGE: 5 Date Time Signal Information Account: 26201018 09/12/13 THU 09:27:59 ALARM RESOLUTION NO FURTHER ACTION/COMPLETED 09:27:59 PRINTED ALARM TICKET Page 8