HomeMy WebLinkAbout2077 LAS PALMAS DR; ; CBC2020-0188; PermitBuilding Permit Finaled
{city of
Carlsbad
Commercial Permit
Print Date : 05/02/2024
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
2077 LAS PALMAS DR, CARLSBAD, CA 92011-1519
BLDG-Commercial Work Class:
2130611800 Track#:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
P/M/E
Permit No:
Status:
CBC2020-0188
Closed -Finaled
Applied: 05/30/2020
Issued : 06/20/2020
Finaled Close Out: 05/02/2024
Final Inspection: 10/06/2021
INSPECTOR: Kersch, Tim
Alvarado, Tony
Description: UPGRADE 600A 3 HANDLE SWITCHGEAR TO 1200A 6 HANDLE SWITCHGEAR (E-REVIEW)
Applicant:
ROPER ELECTRIC INC
MATTHEW ROPER
1116 SUNVIEW PL
OCEANSIDE, CA 92057-1958
(760) 681-7108
FEE
MANUAL BLDG PLAN CHECK FEE
Property Owner:
GREENE AND STREUER FAMILY
890 DEL MAR DOWNS RD
SOLANA BEACH, CA 92075
PLUMBING, ELECTRICAL, AND MECHANICAL PERMIT
Total Fees : $343.75 Total Payments To Date: $343.75
Contractor:
ROPER ELECTRIC INC
1116 SUNVIEW PL
OCEANSIDE, CA 92057-1958
(760) 681-7108
Balance Due:
AMOUNT
$168.75
$175.00
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
{ City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check CBR2020-0188
Est. Value
PC Deposit ---------
5/30/20 Date ---------
Job Address 2077 Las Palmas Drive, Carlsbad, CA 92011 Suite: ____ APN: __________ _
CT/Project#: __________________ Lot#: ___ _
Fire Sprinklers: 0 YES Q NO Air Conditioning: Q YES O NO Electrical Panel Upgrade: 0 YES O NO
BRIEF DESCRIPTION OF WORK: Upgrade 600A 3 Handle Switchgear to 1200A 6 Handle Switchgear
0 Addition/New: _____ Living SF, ___ Deck SF, ___ Patio SF, ___ Garage SF
Is this to create an Accessory Dwelling Unit? 0 Y O N New Fireplace? 0 Y O N, if yes how many? __
D Remodel: ____ SF of affected area Is the area a conversion or change of use ? 0 Y O N
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? ____________ _
□solar: ___ KW, __ Modules, Mounted:0Roof 0 Ground, Tilt:O YO N, RMA:O YO N,
Battery:O Y O N, Panel Upgrade: O Y O N
D Reroof: _________________________________ _
0 Plumbing/Mechanical/Electrical Only: _E_le_c_tr_ic_a_l _O_n_ly ___________________ _
D Other: _________________________________ _
APPLICANT (PRIMARY CONTACT)
Name: Matthew Roper, Roper Electric Inc
Address: 1116 Sunview Place
City: Oceanside State: CA Zip: 92057
Phone: 760-681-71 08
Email: mroperelectric@gmail.com
DESIGN PROFESSIONAL
Name: _________________ _
Address: ________________ _
City: ________ State: ___ Zip: ___ _
Phone: ________________ _
Email: _________________ _
Architect State License: __________ _
PROPERTY OWNER
Name: Erika Streuer
Address: __________________ _
City: __________ State: ___ Zip: ____ _
Phone: 858-755-7163
Email: erikastreuer@cox.net
CONTRACTOR BUSINESS
Name: Roper Electric Inc., Matthew Roper
Address: 1116 Sunview Place
City: Oceanside state: CA Zip: _9_20_5_7 ___ _
Phone: 760-681-7108
Email: mroperelectric@gmail.com
State License: 1008473 Bus. License: BLOS001333-07-:
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.S by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
B-1 Page 1 of 2 Rev. 03/20
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
D I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued.
IZJ I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: Accredited Surety and Casualty Company Inc
Policy No. 1ATCA16002171-0 PGO Expiration Date: _8_/2_7_/2_0 _______ _
D Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONTRACTOR SIGNATURE: Matthew Roper □AGENT DATE: s112120 ----~------------------------------
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
D I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
D I am exempt under Section ________ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. Q YES O NO
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: □AGENT DATE: ______ _ ---------------------------
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _____________________ Lender's Address: ____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? Yes / No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes / No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes / No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time after
the work is commenced for a period of 180 days. CBC section 105.5.
APPLICANT SIGNATURE: _M_att_h_ew_Ro-p_e_r ___________________ DATE:s_11_2_12_0 ______ _
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 03/20
Building Permit Inspection History Finaled
{city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#80-33
Status: Closed -Finaled Expiration Date: 10/12/2021 Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519 IVR Number: 26623
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection
Date Start Date Status
09/23/2020 09/22/2020 BLDG-31 139086-2020 Partial Pass Tony Alvarado Reinspection
Underground/Conduit -
Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency September 22, 2020: Yes
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
compromised, to allow for new
underground electrical conduit to pass
beneath existing drain swale for new
future transformer.
4. V-ditch/drainage swale needs to be
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work.
5. Informed project manager Matthew
regarding replacement of existing building
drainage swale replacement.
10/19/2020 10/19/2020 BLDG-34 Rough 141226-2020 Partial Pass Tony Alvarado Reinspection
Electrical
Checklist Item COMMENTS Passed
BLDG-Building Deficiency October 19, 2020: Yes
1. Spoke to Erica -"SDGE planner",
requested Revised SDGE Electrical Meter
Release site plan layout of existing
transformer new SDGE switchgear/pool
station cabinet To reflect as-built site
conditions.
2. Exterior switchgear cabinet needs to be
weather tight, due to installation of cabinet
not sealed properly.
4. Spoke to contractor representative
Matthew and will provide better weather
tight cabinet insulation and protection, for
SDGE switchgear cabinet scope of work.
04/14/2021 04/14/2021 BLDG-31 154864-2021 Partial Pass Tony Alvarado Reinspection
Underground/Conduit -
Wiring
Wednesday, October 6, 2021
Inspection
Incomplete
Incomplete
Incomplete
Page 1 of 7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status: Closed -Finaled
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Scheduled
Date
Actual Inspection Type
Start Date
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
Wednesday, October 6, 2021
COMMENTS
September 22, 2020:
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
compromised, to allow for new
underground electrical conduit to pass
beneath existing drain swale for new
future transformer.
4. V-ditch/drainage swale needs to be
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work.
5. Informed project manager Matthew
regarding replacement of existing building
drainage swale replacement.
April 14, 2021:
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending***
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
Passed
Yes
Yes
Page 2 of7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
BLDG-34 Rough
Electrical
Checklist Item
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Inspection No. Inspection
Status
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Primary Inspector Reinspection Inspection
154866-2021 Partial Pass Tony Alvarado Reinspection Incomplete
COMMENTS Passed
BLDG-Building Deficiency October 19, 2020: Yes
Wednesday, October 6, 2021
BLDG-Building Deficiency
1. Spoke to Erica -"SDGE planner",
requested Revised SDGE Electrical Meter
Release site plan layout of existing
transformer new SDGE switchgear/pool
station cabinet To reflect as-built site
conditions.
2. Exterior switchgear cabinet needs to be
weather tight, due to installation of cabinet
not sealed properly.
4. Spoke to contractor representative
Matthew and will provide better weather
tight cabinet insulation and protection, for
SDGE switchgear cabinet scope of work.
April 14, 2021 :
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending***
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
BLDG-Final Inspection 154865-2021 Partial Pass Tony Alvarado
Yes
Reinspection Incomplete
Page 3 of7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
BLDG-Structural Final
Wednesday, October 6, 2021
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
COMMENTS
April 14, 2021: (partial pass).
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending***
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
Passed
Yes
Page 4of7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status:
Scheduled
Date
10/06/2021
Closed -Finaled
Actual Inspection Type
Start Date
BLDG-Electrical Final
10/06/2021 BLDG-Final Inspection
Wednesday, October 6, 2021
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
April 14, 2021: (Partial pass).
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending•••
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
168134-2021 Passed Tim Kersch
Yes
Complete
Page 5 of7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
BLDG-Structural Final
Wednesday, October 6, 2021
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
COMMENTS
April 14, 2021: (partial pass).
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending***
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
Passed
Yes
Page 6 of7
PERMIT INSPECTION HISTORY for (CBC2020-0188)
Permit Type: BLDG-Commercial
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
BLDG-Electrical Final
Wednesday, October 6, 2021
Application Date: 05/30/2020 Owner: TRUST GREENE STREUER FAMILY
Issue Date: 06/20/2020 Subdivision: CARLSBAD TCT#S0-33
Expiration Date: 10/12/2021
IVR Number: 26623
Address: 2077 LAS PALMAS DR
CARLSBAD, CA 92011-1519
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
April 14, 2021: (Partial pass).
(Switchgear ceiling drywall
patchwork-deficiency)
Rest of electrical work-Approved.
1. Underground electrical conduit for (3)
-6"inch pipes for future upgrade to existing
transformer and commercial building
switchgear upgrade.
2. approved only for underground conduit.
3. Existing 3 to 4 feet wide v-ditch/drainage
swale connected to existing building
running alongside building length has been
repaired and reconnected to existing
v-ditch, to allow for new underground
electrical conduit to pass beneath existing
drain swale for new future transformer
locations cabinet.
4. V-ditch/drainage swale has been
reconstructed and replaced back to original
condition. prior to final electrical sign-off
scope of work-approved.
5. ***pending•••
Informed project manager Matthew
regarding replacement of existing building
electrical switch gear/meter room,
regarding ceiling-drywall patch work
required prior to final sign-off in City of
Carlsbad computer tracking system.
6. ****Pending***
Face Time of small-minimal ceiling drywall
patchwork, drywall mud and tape work
completed in existing switchgear electrical
room ceiling area-(only), required.
Yes